PRUEBA DE NDICE DE POLARIZACIN (IP)

TRANSFORMADOR

FECHA 04/11/2017 PGINA 1

TEMP. AMBIENTE 22.7 C N DE TRABAJO

SUBESTACIN CHE SAN GABAN HUMEDAD 56.4 % Activo ID

POSICIN ESTADO DE PRUEBA

Ubicacin del Equipo CASA MAQUINA

DATOS DE PLACA

FABRICANTE VERBANO CLASE FASES 3


NO SERIE 16767 REFRIG. ACEITE RAZN Rutina
AO 1998 BIL kV PESO Kg
YNd5 MAT. DEVANADO Cu
VOL. ACEITE 11,500 Kg
TEMP. ACEITE 31.2 C
IMPEDANCIA %
CLIMA De Interior
TANQUE TIPO SELLADO

# POSICIN
Tensin (kV) MVA I NOM. TOMAS NEUTRO CAMBIADOR CAMBIADOR

PRIMARIO: 146 / 84.293 62.5 247.15 5 3 CTDM


SECUNDARIO: 13.8 62.5 2,614.81 1 3 OLTC
COMENTARIOS:

TENSIN DE PRUEBA: ALTABAJA & TIERRA 5 KVCD BAJAALTA & TIERRA 5 KVCD ALTA & BAJATIERRA 5 KVCD
TEMP. NCLEO/BOBINA: 32.4 C Introduzca TCF Manualmente: FACTOR CORR. TEMP A 20C,
SECOTCF 1.7816 LQUIDO 2.374
Usar Valor de Instrumento PI / DAR:
TRANSFORMADOR
Alta Baja & Tierra Baja Alta & Tierra Alta & Baja Tierra
MINUTOS LECTURA Lectura Corregida LECTURA Lectura Corregida LECTURA Lectura Corregida
(Mohms) (Mohms) (megaohmios) (Mohms) (megaohmios) (Mohms)

0.25 750.00 1,336.20 1,190.00 2,120.10 1,290.00 2,298.26


0.50 1,080.00 1,924.13 1,590.00 2,832.74 1,790.00 3,189.06
0.75 1,380.00 2,458.61 1,920.00 3,420.67 2,220.00 3,955.15
1.00 1,660.00 2,957.46 2,190.00 3,901.70 2,580.00 4,596.53
2.00 2,580.00 4,596.53 2,940.00 5,237.90 3,940.00 7,019.50
3.00 3,330.00 5,932.73 3,420.00 6,093.07 4,950.00 8,818.92
4.00 3,960.00 7,055.14 3,770.00 6,716.63 5,770.00 10,279.83
5.00 4,510.00 8,035.02 4,070.00 7,251.11 6,480.00 11,544.77
6.00 4,980.00 8,872.37 4,330.00 7,714.33 7,110.00 12,667.18
7.00 5,410.00 9,638.46 4,560.00 8,124.10 7,660.00 13,647.06
8.00 5,790.00 10,315.46 4,770.00 8,498.23 8,170.00 14,555.67
9.00 6,130.00 10,921.21 4,970.00 8,854.55 8,620.00 15,357.39
10.00 6,450.00 11,491.32 5,150.00 9,175.24 9,040.00 16,105.66
NDICE POLARIZACIN: 3.37 2.13 3.04
ABSORCIN DIELCTRICA: 1.54 1.37 1.44

CONDICIN NDICE NOTAS: CONDICIN Dar NOTAS:


AISLANTE DE POLARIZACIN (PI) Rangos PI de IEEE C57.152-2013 AISLANTE 60/30 Sec DAR ranges from
DANGEROUS < 1.0 CUESTIONABLE 1.0 - 1.25 A Stitch In Time (Megger, 2006)
Polarization Index should not be used to assess insulation
POBRE 1.0 a 1.1 in new power transformers (IEEE C57.152-2013) BUENO 1.4 a 1.6 These values must be considered
CUESTIONABLE 1.1 a 1.25 The polarization index for insulation liquid is always close to 1. Therefore, EXCELENTE > 1.6 tentative and relative - subject
the polarization index for transformers with low conductivity liquids to experience, over time
JUSTO 1.25 A 2.0
(e.g. new mineral oil) may be low in spite of good insulation condition.
BUENO > 2.0 (IEEE C57.152-2013)

EQUIPO DE PRUEBA USADO:


Megger MIT 1525 Insulation Resistance Testers PROBADO POR: M&P INGENIEROS S.A.C

COPYRIGHT 2002-2017 POWERDB, INC. www.powerdb.com 56600, Form Schema 2, REVISED 21/10/2014
PRUEBA DE NDICE DE POLARIZACIN (IP)
TRANSFORMADOR

PGINA 2

FECHA04/11/2017 TEMPERATURA 22.7 C HUMEDAD 56.4 % UBI. DEL EQUIPO CASA MAQUINA
72.9
SUBESTACINCHE SAN GABAN POSICIN

CURVA DE POLARIZACIN Alta Baja & Tierra : Cuadrado Rojo

CURVA DE POLARIZACIN Baja Alta & Tierra : Crculo Azul

CURVA DE POLARIZACIN Alta & Baja Tierra : Tringulo Verde

COMENTARIOS:
DEFICIENCIAS: