F871- C11 /C21 BI - P12-3A-10-32-P057 DTA- 09461- REV- A- STATUS- I

S. No Point of Origination of signals Signals Binary Input at F871 (87T-1) Event list LED Remarks

Insert Test Plug in S871.A / S871.B Test Block in C11 RP BI-1 (F871) Low Diff1Test SPN ON LED 13 ON
1 Tx. Diff. Relay Test Block in Test Mode
Remove Test Plug From S871.A / S871.B Test Block in C11 RP BI-1 (F871) High Diff1Test SPN OFF LED 13 OFF

CB Close command from C11.LCC BI-1 (F871) High CB ManClose SPN ON


2 CB Closing order NA
NORMALISE BI-1 (F871) Low CB ManClose SPN OFF

Switch OFF MCB F111 in C11 RP BI-5 (F871) Low TDBIDCSFl SPN ON LED 14 ON
3 Group-A MTR/Tx. Diff. Main-1 BI DC Supply Fail
Switch ON MCB F111 in C11 RP BI-5 (F871) High TDBIDCSFl SPN OFF LED 14 OFF

F511- C11 /C21 BI - P12-3A-10-32-P057 DTA- 09461- REV- A- STATUS- I


S.
Point of Origination of signals Signals Binary Input at F511 (50/51) Event list LED Remarks
No

Insert Test Plug in S511 Test Block in C11 RP BI-1 (F511) Low OCTest SPN ON
1 O/C & E/F Relay Test block in Test Mode NA
Remove Test Plug From S511 Test Block in C11 RP BI-1 (F511) High OCTest SPN OFF

Simulate Tap raise or Lower at 132/11kV 40MVA Tx. BI-2 (F511) High TpChPrg SPN ON
2 Tap change in Progress NA
Normalise Tap raise or Lower at 132/11kV 40MVA Tx. BI-2 (F511) Low TpChPrg SPN OFF

Switch OFF MCB F121 in C11 RP BI-7 (F511) Low TD2BIDCSFl SPN ON
Group-B MTR/Main-2 Diff/ O/C & E/F Relay BI DC Supply
3 NA
Fail
Switch ON MCB F121 in C11 RP BI-7 (F511) High TD2BIDCSFl SPN OFF

M1-F871- C10 /C20/C50/C60 BI - P12-3A-10-32-P022 DTA- 06312- REV- A- STATUS- I


S. No Point of Orgination of signals Signals Binary Input at F871 Protn Relay Event list LED Remarks

Apply Temp Short at (F8710.6D3,6D4) Test Block service position BI-1 (F871) High >Intertrip 3POL ON LED 6 ON
at BB RP2
1 BF Stage-2 trip/BB Protn.
Remove Temp Short at (F8710.6D3,6D4) Test Block service
BI-1 (F871) Low >Intertrip 3POL OFF LED 6 OFF
position at BB RP2

Close CB C100 BI-2 (F871) High CB Close SPN ON


2 CB C100(Q01) close NA
Open CB C100 BI-2 (F871) Low CB Close SPN OFF

Give Manual Close Command for CB C100 From LCC / BCU BI-3 (F871) High >Manual Close ON
CB C100 (Q01) closing order from
3 NA
LCC/BCU to initiate SOTF
Release Close Command for CB C100 From LCC / BCU BI-3 (F871) Low >Manual Close OFF

Switch OFF VT MCB F711 in C10 LCC and VT BOX MCB VT MCB Trip/Off
BI-4 (F871) High FAIL:Feeder VT ON LED 11 ON
F11/F12/F13 OFF
4 (Dist. protn. block)
Switch ON VT MCB F711 in C10 LCC and VT BOX MCB
BI-4 (F871) Low FAIL:Feeder VT OFF LED 11 OFF
F11/F12/F13 ON VT Core-1 MCB Trip/Off

Insert test block S871 at C10 RP BI-5 (F871) High Main1 Test SPN ON
5 Diff. protn. Main-1 relay test block NA
Remove test block S871 at C10 RP BI-5 (F871) Low Main1 Test SPN ON

Switch OFF F111 in C10 RP Group-A Master trip relay/ BI-8 (F871) Low BI1DC Fail SPN ON

6 NA
Fdr. diff. Main-1 relay BI DC
Switch ON F111 in C10 RP BI-8 (F871) High BI1DC Fail SPN OFF
supply fail
M1-F511- C12/C22 BI - P12-3A-10-32-P037 DTA- 03688- REV- 0- STATUS- A
S. No Point of Origination of signals Signals Binary Input at F511 (51) Event list LED Remarks

Simulate BCU A201 unhealthy at C12 LCC BI-1 (F511) High BCUUnh SPN ON
1 BCU Unhealthy NA
Normalise BCU A201 unhealthy at C12 LCC BI-1 (F511) Low BCUUnh SPN OFF

Switch OFF F133 at C12 LCC BI-2 (F511) High BCUDCMCBTr SPN ON
2 BCU DC 1/2 MCB trip/off NA
Switch ON F133 at C12 LCC BI-2 (F511) Low BCUDCMCBTr SPN OFF

Insert Test Plug in S511 Test Block in C12 RP BI-4 (F511) Low OCTest SPN ON
3 Remove Test Plug From S511 Test Block in C12 O/C Relay Test block in Test Mode NA
BI-4 (F511) High OCTest SPN OFF
RP

Switch OFF MCB F140 in C12 RP BI-5 (F511) High MBDCMCBTr SPN ON C12
4 Main I/c Bcu Dc MCB Trip/off
Switch ON MCB F140 in C12 RP BI-5 (F511) Low MBDCMCBTr SPN OFF C12

Switch OFF MCB F150 in C12 RP BI-8 (F511) High MBIAIDCMTr SPN ON C12
5 Main I/c Bcu BI/ALARM MCB Trip/off
Switch ON MCB F150 in C12 RP BI-8 (F511) Low MBDCMCBTr SPN OFF C12

Switch OFF MCB F111 in C12 RP BI-7 (F511) Low Gr ARBIDCF1 SPN ON LED 7 ON
6 Group-A MTR / O/C Relay BI DC Supply Fail
Switch ON MCB F111 in C12 RP BI-7 (F511) High Gr ARBIDCF1 SPN OFF LED 7 OFF

M1-F511- C13/C23 BI - P12-3A-10-32-P037 DTA- 03688- REV- 0- STATUS- A

S. No Point of Origination of signals Signals Binary Input at F511 (51) Event list LED Remarks

Simulate BCU A201 unhealthy at C13 LCC BI-1 (F511) Low BCUUnh SPN ON
1 BCU Unhealthy NA
Normalise BCU A201 unhealthy at C13 LCC BI-1 (F511) High BCUUnh SPN OFF

Switch OFF F133 at C13 LCC BI-2 (F511) Low BCUDCMTr SPN ON
2 BCU DC 1/2 MCB trip/off NA
Switch ON F133 at C13 LCC BI-2 (F511) High BCUDCMTr SPN OFF

Insert Test Plug in S511 Test Block in C13 RP BI-4 (F511) Low OC Test SPN ON
O/C Relay Test block in
3 NA
Test Mode
Remove Test Plug From S511 Test Block in C13 RP BI-4 (F511) High OC Test SPN OFF

Switch OFF MCB F111 in C13 RP BI-7 (F511) Low Gr ARBIDCF1 SPN ON LED 7 ON
Group-A MTR / O/C Relay
4
BI DC Supply Fail
Switch ON MCB F111 in C13 RP BI-7 (F511) High Gr ARBIDCF1 SPN OFF LED 7 OFF