DOCUMENT / DRAWING TRANSMITTAL


1 4
PROJECT : RPLC Deep Conversion Project Date : 22 08 2013
Day Mon Year
TO : HYUNDAI-WISON
VT. No. : TR-SIE-CON-0005
Attn : Woon Sun Park
DISCIPLINE : Main substation (U52) GIS 230 kV

C.C. : S. H. SUH / Project Director

Subject: (GIS 230 kV / Siemens)

S/N Document / Drawing No. Rev. Sht/Vol Description / Title Purpose Status

1 A 1 SIGNAL LIST A

Purpose A : For Approval


R : For Review
I : For Information
C : For Construction/For Fabrication/For Sub-ordering
AB : As-built

Review Result A : Approved


C : Reviewed without Comments
R : Approved with Comments
N : Not Acceptable

Note: Please return above mentioned documents with


Approval requested by lastest 30.08.2013 comments/approved by 30 08 20 3
Day Mon Year
Sender's Signature:

Eli Sal Pia Vsquez


* Internal Distribution :
EM PR SE PI MS MS CI EL CV AR HV MM MT PC Please acknowledge receipt by return of signed and dated
duplicate copy.
Receipt Acknowledgement
COVER SHEET
Total Sheet 1

Vendor's name : SIEMENS, S.A.

Company's name : PDVSA Petrleo, S.A.

Contractor's name : HYUNDAI-WISON

Project name : RPLC Deep Conversion

REFERENCE
3006-MR-EL-001-4600043465
CONTRACTOR PO No :.

Unit/Facility name : MAIN SUBSTATION (U52)


Equipment/Material
Protection Panels
name :

Item number :

Document title : SIGNAL LIST

RPLC Deep Conversion Project


ISSUE DATE: 22-Ago-2013
ISSUE PURPOSE : IFA
Below : CONTRACTOR to fill in
RESULT CODE : A, C, R, N ( )
NEXT STATUS : IFA, IFR, IFI, IFC, AB ( )
RESUBMISSION DATE : ( )
RESPONSIBLE DEPT./PERSON : ( )
RELATED DEPT./PERSON : ( )
REVIEW DATE : ( )
A: Approved; C: Reviewed without Comment; R: Reviewed with Comment; N: Not Acceptable

Approval or review hereunder shall not be construed to relieve Supplier


/Subcontractor of his responsibilities and liability under the Contract.
PROJECT NO.

CONTRACTO CONTRACTOR DOCUMENT NO. SERIAL REV.


R
Doc. No. A
08/08/
A 2013 YM RY MG Vendors
CONTRACTOR DOCUMENT NO. SERIAL REV.
own Doc. No.
Rev. Date PRP'D CHK'D APRV'D A
SIGNAL LIST 230 kV MAIN SUBSTATION RPLC DEEP CONVERSION
Cabinet Reference Description Scheme name Topology Name Hardware
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Manual Close BI:01
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A Busbar PT fault BI:02
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) 50BF end fault trip BI:03
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q51) Close BI:04
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q52) Close BI:05
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Close phase R BI:06
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Close phase S BI:07
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Close phase T BI:08
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Locked auto-reclosure BI:09
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\(Q0) Interlocking Lock BI:10
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Auto-reclosure BI:11
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP2 General start BI:12
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP2 Trip Phase R BI:13
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP2 Trip Phase S BI:14
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP2 Trip Phase T BI:15
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP2 Fail feeder PL2 BI:16
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status LEDs Reset command -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status Parameters change in course -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status Communications failure channel 1 -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status Communications failure channel 2 -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status Time sync. failure -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 Status LEDs reset -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 87L Fault detection in phase A -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 87L Fault detection in phase B -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 87L Fault detection in phase C -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 87L General trip -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 87L Trip in phases ABC -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 25/79 Locked reclosure -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 25/79 Reclosure in proccess -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 25/79 Reclosure command -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 25/79 Succesful reclosure -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 85 Tele protection Fault -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 85 Direct trip release -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 85 Direct trip receipt -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 85 Power swing -
=D04+R04 7SD5 LP1 F003 230kV\Line from PAL A\LP1 85 Power swing trip -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Manual close BI:01
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A Busbar PT fault BI:02
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A 50BF end fault trip BI:03
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q51) Close BI:04
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q52) Close BI:05
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Close phase R BI:06
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Close phase S BI:07
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Close phase T BI:08
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Locked auto-reclosure BI:09
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\(Q0) Interlocking Lock BI:10
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Auto-reclosure BI:11
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 General start BI:12
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Trip Phase R BI:13
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Trip Phase S BI:14
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Trip Phase T BI:15
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Fail feeder PL1 BI:16
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Spare BI:17
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Spare BI:18
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Spare BI:19
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Spare BI:20
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Spare BI:21
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:22
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:23
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:24
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:25
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:26
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Spare BI:27
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 50-51 Start Phase A -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 50-51 Start Phase B -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 50-51 Start Phase C -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 51 Start -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 51 Trip -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 50 Start -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50/51 50 Trip -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50N/51N 50N-51N Start -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50N/51N 50N Start -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50N/51N 51N Start -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50N/51N 50N Trip -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 50N/51N 51N Trip -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status LEDs Reset command -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Parameters change in course -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Communications failure channel 1 -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Communications failure channel 2 -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status Time sync. failure -
=D04+R04 7SJ85 LP2 F004 230kV\Line from PAL A\LP2 Status LEDs reset -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Manual Close BI:01
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B Busbar PT fault BI:02
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) 50BF end fault trip BI:03
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q51) Close BI:04
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q52) Close BI:05
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Close phase R BI:06
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Close phase S BI:07
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Close phase T BI:08
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Locked auto-reclosure BI:09
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\(Q0) Interlocking Lock BI:10
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Auto-reclosure BI:11
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP2 General start BI:12
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP2 Trip Phase R BI:13
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP2 Trip Phase S BI:14
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP2 Trip Phase T BI:15
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP2 Fail feeder PL2 BI:16
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status LEDs Reset command -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status Parameters change in course -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status Communications failure channel 1 -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status Communications failure channel 2 -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status Time sync. failure -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 Status LEDs reset -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 87L Fault detection in phase A -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 87L Fault detection in phase B -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 87L Fault detection in phase C -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 87L General trip -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 87L Trip in phases ABC -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 25/79 Locked reclosure -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 25/79 Reclosure in proccess -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 25/79 Reclosure command -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 25/79 Succesful reclosure -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 85 Tele protection Fault -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 85 Direct trip release -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 85 Direct trip receipt -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 85 Power swing -
=D08+R08 7SD5 LP1 F003 230kV\Line from PAL B\LP1 85 Power swing trip -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Manual close BI:01
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B Busbar PT fault BI:02
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B 50BF end fault trip BI:03
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q51) Close BI:04
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q52) Close BI:05
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Close phase R BI:06
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Close phase S BI:07
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Close phase T BI:08
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Locked auto-reclosure BI:09
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\(Q0) Interlocking Lock BI:10
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Auto-reclosure BI:11
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 General start BI:12
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Trip Phase R BI:13
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Trip Phase S BI:14
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Trip Phase T BI:15
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Fail feeder PL1 BI:16
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Spare BI:17
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Spare BI:18
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Spare BI:19
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Spare BI:20
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Spare BI:21
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:22
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:23
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:24
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:25
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:26
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Spare BI:27
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 50-51 Start Phase A -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 50-51 Start Phase B -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 50-51 Start Phase C -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 51 Start -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 51 Trip -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 50 Start -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50/51 50 Trip -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50N/51N 50N-51N Start -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50N/51N 50N Start -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50N/51N 51N Start -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50N/51N 50N Trip -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 50N/51N 51N Trip -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status LEDs Reset command -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Parameters change in course -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Communications failure channel 1 -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Communications failure channel 2 -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status Time sync. failure -
=D08+R08 7SJ85 LP2 F004 230kV\Line from PAL B\LP2 Status LEDs reset -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\(Q0) Manual close BI:01
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Busbar A PT fault BI:02
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Busbar B PT fault BI:03
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\(Q0) State BI:04/05
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Fail feeder -F006 BI:06
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Fail feeder -F016 BI:07
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:08
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:09
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:10
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:11
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:12
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:13
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:14
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler Spare BI:15
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 50-51 Start Phase A -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 50-51 Start Phase B -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 50-51 Start Phase C -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 51 Start -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 51 Trip -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 50 Start -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50/51 50 Trip -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50N/51N 50N-51N Start -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50N/51N 50N Start -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50N/51N 51N Start -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50N/51N 50N Trip -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 50N/51N 51N Trip -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status LEDs Reset command -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status Parameters change in course -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status Communications failure channel 1 -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status Communications failure channel 2 -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status Time sync. failure -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 Status LEDs reset -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 27/59 Undervoltage Phase A -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 27/59 Undervoltage Phase B -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 27/59 Undervoltage Phase C -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 27/59 Reclosure command -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 27/59 Sinchronism conditions -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 25/79 Angle difference exceeded -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 25/79 Frequency difference exceeded -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 25/79 Voltage difference exceeded -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP1 85 Power swing trip -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP2 27/59 Undervoltage trip Phase-Phase -
=D06+R06 7VK87 CP1 F003 230kV\Busbar coupler\LP2 27/59 Undervoltage trip Phase-Ground -
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F006 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F016 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F026 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F036 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F046 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Enabled -BI:01
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Locked -BI:02
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B\(Q0) Spare -BI:03
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status LEDs Reset Command
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status Parameters change in course
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status Communications failure channel 1
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status Communications failure channel 2
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status Time sync. failure
=D06+R06 7UT612 87B F056 230kV\Busbar coupler\Prot 87B Status LEDs reset
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Manual Close BI:01
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A Busbar PT fault BI:02
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) 50BF end fault trip BI:03
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q51) Close BI:04
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q52) Close BI:05
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Close phase R BI:06
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Close phase S BI:07
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Close phase T BI:08
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Spare BI:09
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\(Q0) Interlocking Lock BI:10
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:11
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 General start BI:12
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Trip Phase R BI:13
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Trip Phase S BI:14
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Trip Phase T BI:15
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Fail feeder PL2 BI:16
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Fail feeder Temperature monitoring BI:17
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 RTD Error unavailable BI:18
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:19
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:20
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:21
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:22
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:23
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:24
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:25
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:26
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Spare BI:27
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status LEDs Reset command -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status Parameters change in course -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status Communications failure channel 1 -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status Communications failure channel 2 -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status Time sync. failure -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 Status LEDs reset -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 87L Fault detection in phase A -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 87L Fault detection in phase B -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 87L Fault detection in phase C -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 87L General trip -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 87L Trip in phases ABC -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 85 Power swing -
=D05+R05 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-A\TP1 85 Power swing trip -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Manual close BI:01
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A Busbar PT fault BI:02
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A 50BF end fault trip BI:03
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q51) Close BI:04
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q52) Close BI:05
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Close phase R BI:06
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Close phase S BI:07
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Close phase T BI:08
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Locked auto-reclosure BI:09
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\(Q0) Interlocking Lock BI:10
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Auto-reclosure BI:11
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 General start BI:12
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Trip Phase R BI:13
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Trip Phase S BI:14
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Trip Phase T BI:15
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Fail feeder PL1 BI:16
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Spare BI:17
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Spare BI:18
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Spare BI:19
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Spare BI:20
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Spare BI:21
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:22
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:23
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:24
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:25
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:26
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Spare BI:27
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 50-51 Start Phase A -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 50-51 Start Phase B -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 50-51 Start Phase C -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 51 Start -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 51 Trip -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 50 Start -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50/51 50 Trip -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50N/51N 50N-51N Start -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50N/51N 50N Start -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50N/51N 51N Start -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50N/51N 50N Trip -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 50N/51N 51N Trip -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status LEDs Reset command -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Parameters change in course -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Communications failure channel 1 -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Communications failure channel 2 -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status Time sync. failure -
=D05+R05 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-A\TP2 Status LEDs reset -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Manual Close BI:01
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A Busbar PT fault BI:02
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) 50BF end fault trip BI:03
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q51) Close BI:04
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q52) Close BI:05
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Close phase R BI:06
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Close phase S BI:07
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Close phase T BI:08
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Spare BI:09
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\(Q0) Interlocking Lock BI:10
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:11
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 General start BI:12
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Trip Phase R BI:13
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Trip Phase S BI:14
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Trip Phase T BI:15
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Fail feeder PL2 BI:16
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Fail feeder Temperature monitoring BI:17
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 RTD Error unavailable BI:18
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:19
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:20
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:21
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:22
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:23
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:24
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:25
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:26
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Spare BI:27
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status LEDs Reset command -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status Parameters change in course -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status Communications failure channel 1 -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status Communications failure channel 2 -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status Time sync. failure -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 Status LEDs reset -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 87L Fault detection in phase A -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 87L Fault detection in phase B -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 87L Fault detection in phase C -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 87L General trip -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 87L Trip in phases ABC -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 85 Power swing -
=D03+R03 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-A\TP1 85 Power swing trip -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Manual close BI:01
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A Busbar PT fault BI:02
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A 50BF end fault trip BI:03
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q51) Close BI:04
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q52) Close BI:05
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Close phase R BI:06
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Close phase S BI:07
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Close phase T BI:08
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Locked auto-reclosure BI:09
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\(Q0) Interlocking Lock BI:10
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Auto-reclosure BI:11
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 General start BI:12
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Trip Phase R BI:13
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Trip Phase S BI:14
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Trip Phase T BI:15
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Fail feeder PL1 BI:16
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Spare BI:17
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Spare BI:18
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Spare BI:19
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Spare BI:20
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Spare BI:21
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:22
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:23
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:24
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:25
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:26
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Spare BI:27
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 50-51 Start Phase A -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 50-51 Start Phase B -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 50-51 Start Phase C -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 51 Start -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 51 Trip -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 50 Start -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50/51 50 Trip -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50N/51N 50N-51N Start -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50N/51N 50N Start -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50N/51N 51N Start -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50N/51N 50N Trip -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 50N/51N 51N Trip -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status LEDs Reset command -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Parameters change in course -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Communications failure channel 1 -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Communications failure channel 2 -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status Time sync. failure -
=D03+R03 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-A\TP2 Status LEDs reset -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Manual Close BI:01
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A Busbar PT fault BI:02
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) 50BF end fault trip BI:03
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q51) Close BI:04
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q52) Close BI:05
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Close phase R BI:06
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Close phase S BI:07
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Close phase T BI:08
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Spare BI:09
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\(Q0) Interlocking Lock BI:10
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:11
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 General start BI:12
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Trip Phase R BI:13
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Trip Phase S BI:14
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Trip Phase T BI:15
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Fail feeder PL2 BI:16
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Fail feeder Temperature monitoring BI:17
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 RTD Error unavailable BI:18
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:19
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:20
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:21
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:22
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:23
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:24
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:25
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:26
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Spare BI:27
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status LEDs Reset command -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status Parameters change in course -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status Communications failure channel 1 -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status Communications failure channel 2 -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status Time sync. failure -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 Status LEDs reset -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 87L Fault detection in phase A -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 87L Fault detection in phase B -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 87L Fault detection in phase C -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 87L General trip -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 87L Trip in phases ABC -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 85 Power swing -
=D02+R02 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-A\TP1 85 Power swing trip -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Manual close BI:01
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A Busbar PT fault BI:02
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A 50BF end fault trip BI:03
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q51) Close BI:04
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q52) Close BI:05
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Close phase R BI:06
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Close phase S BI:07
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Close phase T BI:08
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Locked auto-reclosure BI:09
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\(Q0) Interlocking Lock BI:10
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Auto-reclosure BI:11
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 General start BI:12
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Trip Phase R BI:13
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Trip Phase S BI:14
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Trip Phase T BI:15
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Fail feeder PL1 BI:16
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Spare BI:17
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Spare BI:18
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Spare BI:19
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Spare BI:20
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Spare BI:21
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:22
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:23
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:24
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:25
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:26
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Spare BI:27
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 50-51 Start Phase A -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 50-51 Start Phase B -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 50-51 Start Phase C -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 51 Start -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 51 Trip -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 50 Start -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50/51 50 Trip -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50N/51N 50N-51N Start -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50N/51N 50N Start -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50N/51N 51N Start -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50N/51N 50N Trip -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 50N/51N 51N Trip -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status LEDs Reset command -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Parameters change in course -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Communications failure channel 1 -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Communications failure channel 2 -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status Time sync. failure -
=D02+R02 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-A\TP2 Status LEDs reset -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Manual Close BI:01
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A Busbar PT fault BI:02
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) 50BF end fault trip BI:03
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q51) Close BI:04
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q52) Close BI:05
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Close phase R BI:06
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Close phase S BI:07
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Close phase T BI:08
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Spare BI:09
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\(Q0) Interlocking Lock BI:10
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:11
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 General start BI:12
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Trip Phase R BI:13
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Trip Phase S BI:14
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Trip Phase T BI:15
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Fail feeder PL2 BI:16
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Fail feeder Temperature monitoring BI:17
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 RTD Error unavailable BI:18
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:19
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:20
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:21
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:22
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:23
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:24
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:25
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:26
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Spare BI:27
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status LEDs Reset command -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status Parameters change in course -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status Communications failure channel 1 -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status Communications failure channel 2 -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status Time sync. failure -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 Status LEDs reset -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 87L Fault detection in phase A -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 87L Fault detection in phase B -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 87L Fault detection in phase C -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 87L General trip -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 87L Trip in phases ABC -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 85 Power swing -
=D01+R01 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-A\TP1 85 Power swing trip -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Manual close BI:01
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A Busbar PT fault BI:02
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A 50BF end fault trip BI:03
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q51) Close BI:04
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q52) Close BI:05
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Close phase R BI:06
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Close phase S BI:07
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Close phase T BI:08
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Locked auto-reclosure BI:09
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\(Q0) Interlocking Lock BI:10
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Auto-reclosure BI:11
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 General start BI:12
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Trip Phase R BI:13
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Trip Phase S BI:14
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Trip Phase T BI:15
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Fail feeder PL1 BI:16
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Spare BI:17
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Spare BI:18
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Spare BI:19
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Spare BI:20
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Spare BI:21
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:22
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:23
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:24
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:25
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:26
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Spare BI:27
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 50-51 Start Phase A -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 50-51 Start Phase B -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 50-51 Start Phase C -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 51 Start -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 51 Trip -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 50 Start -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50/51 50 Trip -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50N/51N 50N-51N Start -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50N/51N 50N Start -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50N/51N 51N Start -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50N/51N 50N Trip -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 50N/51N 51N Trip -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status LEDs Reset command -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Parameters change in course -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Communications failure channel 1 -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Communications failure channel 2 -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status Time sync. failure -
=D01+R01 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-A\TP2 Status LEDs reset -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Manual Close BI:01
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B Busbar PT fault BI:02
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) 50BF end fault trip BI:03
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q51) Close BI:04
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q52) Close BI:05
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Close phase R BI:06
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Close phase S BI:07
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Close phase T BI:08
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Spare BI:09
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\(Q0) Interlocking Lock BI:10
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:11
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 General start BI:12
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Trip Phase R BI:13
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Trip Phase S BI:14
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Trip Phase T BI:15
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Fail feeder PL2 BI:16
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Fail feeder Temperature monitoring BI:17
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 RTD Error unavailable BI:18
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:19
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:20
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:21
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:22
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:23
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:24
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:25
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:26
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Spare BI:27
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status LEDs Reset command -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status Parameters change in course -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status Communications failure channel 1 -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status Communications failure channel 2 -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status Time sync. failure -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 Status LEDs reset -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 87L Fault detection in phase A -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 87L Fault detection in phase B -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 87L Fault detection in phase C -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 87L General trip -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 87L Trip in phases ABC -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 85 Power swing -
=D07+R07 7SD87 TP1 F003 230kV\Transformer MS-XFR-601-B\TP1 85 Power swing trip -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Manual close BI:01
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B Busbar PT fault BI:02
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B 50BF end fault trip BI:03
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q51) Close BI:04
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q52) Close BI:05
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Close phase R BI:06
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Close phase S BI:07
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Close phase T BI:08
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Locked auto-reclosure BI:09
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\(Q0) Interlocking Lock BI:10
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Auto-reclosure BI:11
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 General start BI:12
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Trip Phase R BI:13
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Trip Phase S BI:14
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Trip Phase T BI:15
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Fail feeder PL1 BI:16
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Spare BI:17
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Spare BI:18
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Spare BI:19
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Spare BI:20
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Spare BI:21
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:22
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:23
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:24
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:25
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:26
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Spare BI:27
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 50-51 Start Phase A -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 50-51 Start Phase B -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 50-51 Start Phase C -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 51 Start -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 51 Trip -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 50 Start -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50/51 50 Trip -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50N/51N 50N-51N Start -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50N/51N 50N Start -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50N/51N 51N Start -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50N/51N 50N Trip -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 50N/51N 51N Trip -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status LEDs Reset command -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Parameters change in course -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Communications failure channel 1 -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Communications failure channel 2 -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status Time sync. failure -
=D07+R07 7SJ85 TP2 F004 230kV\Transformer MS-XFR-601-B\TP2 Status LEDs reset -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Manual Close BI:01
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B Busbar PT fault BI:02
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) 50BF end fault trip BI:03
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q51) Close BI:04
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q52) Close BI:05
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Close phase R BI:06
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Close phase S BI:07
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Close phase T BI:08
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Spare BI:09
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\(Q0) Interlocking Lock BI:10
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:11
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 General start BI:12
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Trip Phase R BI:13
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Trip Phase S BI:14
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Trip Phase T BI:15
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Fail feeder PL2 BI:16
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Fail feeder Temperature monitoring BI:17
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 RTD Error unavailable BI:18
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:19
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:20
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:21
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:22
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:23
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:24
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:25
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:26
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Spare BI:27
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status LEDs Reset command -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status Parameters change in course -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status Communications failure channel 1 -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status Communications failure channel 2 -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status Time sync. failure -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 Status LEDs reset -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 87L Fault detection in phase A -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 87L Fault detection in phase B -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 87L Fault detection in phase C -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 87L General trip -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 87L Trip in phases ABC -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 85 Power swing -
=D09+R09 7SD87 TP1 F003 230kV\Transformer MS-XFR-602-B\TP1 85 Power swing trip -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Manual close BI:01
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B Busbar PT fault BI:02
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B 50BF end fault trip BI:03
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q51) Close BI:04
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q52) Close BI:05
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Close phase R BI:06
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Close phase S BI:07
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Close phase T BI:08
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Locked auto-reclosure BI:09
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\(Q0) Interlocking Lock BI:10
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Auto-reclosure BI:11
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 General start BI:12
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Trip Phase R BI:13
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Trip Phase S BI:14
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Trip Phase T BI:15
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Fail feeder PL1 BI:16
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Spare BI:17
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Spare BI:18
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Spare BI:19
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Spare BI:20
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Spare BI:21
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:22
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:23
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:24
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:25
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:26
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Spare BI:27
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 50-51 Start Phase A -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 50-51 Start Phase B -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 50-51 Start Phase C -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 51 Start -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 51 Trip -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 50 Start -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50/51 50 Trip -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50N/51N 50N-51N Start -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50N/51N 50N Start -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50N/51N 51N Start -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50N/51N 50N Trip -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 50N/51N 51N Trip -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status LEDs Reset command -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Parameters change in course -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Communications failure channel 1 -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Communications failure channel 2 -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status Time sync. failure -
=D09+R09 7SJ85 TP2 F004 230kV\Transformer MS-XFR-602-B\TP2 Status LEDs reset -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Manual Close BI:01
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B Busbar PT fault BI:02
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) 50BF end fault trip BI:03
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q51) Close BI:04
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q52) Close BI:05
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Close phase R BI:06
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Close phase S BI:07
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Close phase T BI:08
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Spare BI:09
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\(Q0) Interlocking Lock BI:10
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:11
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 General start BI:12
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Trip Phase R BI:13
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Trip Phase S BI:14
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Trip Phase T BI:15
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Fail feeder PL2 BI:16
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Fail feeder Temperature monitoring BI:17
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 RTD Error unavailable BI:18
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:19
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:20
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:21
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:22
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:23
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:24
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:25
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:26
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Spare BI:27
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status LEDs Reset command -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status Parameters change in course -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status Communications failure channel 1 -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status Communications failure channel 2 -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status Time sync. failure -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 Status LEDs reset -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 87L Fault detection in phase A -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 87L Fault detection in phase B -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 87L Fault detection in phase C -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 87L General trip -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 87L Trip in phases ABC -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 85 Power swing -
=D10+R10 7SD87 TP1 F003 230kV\Transformer MS-XFR-603-B\TP1 85 Power swing trip -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Manual close BI:01
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B Busbar PT fault BI:02
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B 50BF end fault trip BI:03
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q51) Close BI:04
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q52) Close BI:05
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Close phase R BI:06
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Close phase S BI:07
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Close phase T BI:08
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Locked auto-reclosure BI:09
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\(Q0) Interlocking Lock BI:10
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Auto-reclosure BI:11
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 General start BI:12
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Trip Phase R BI:13
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Trip Phase S BI:14
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Trip Phase T BI:15
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Fail feeder PL1 BI:16
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Spare BI:17
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Spare BI:18
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Spare BI:19
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Spare BI:20
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Spare BI:21
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:22
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:23
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:24
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:25
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:26
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Spare BI:27
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 50-51 Start Phase A -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 50-51 Start Phase B -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 50-51 Start Phase C -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 51 Start -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 51 Trip -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 50 Start -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50/51 50 Trip -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50N/51N 50N-51N Start -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50N/51N 50N Start -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50N/51N 51N Start -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50N/51N 50N Trip -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 50N/51N 51N Trip -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status LEDs Reset command -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Parameters change in course -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Communications failure channel 1 -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Communications failure channel 2 -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status Time sync. failure -
=D10+R10 7SJ85 TP2 F004 230kV\Transformer MS-XFR-603-B\TP2 Status LEDs reset -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Manual Close BI:01
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B Busbar PT fault BI:02
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) 50BF end fault trip BI:03
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q51) Close BI:04
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q52) Close BI:05
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Close phase R BI:06
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Close phase S BI:07
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Close phase T BI:08
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Spare BI:09
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\(Q0) Interlocking Lock BI:10
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\LP1 Spare BI:11
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 General start BI:12
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Trip Phase R BI:13
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Trip Phase S BI:14
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Trip Phase T BI:15
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Fail feeder PL2 BI:16
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Fail feeder Temperature monitoring BI:17
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 RTD Error unavailable BI:18
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:19
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:20
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:21
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:22
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:23
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:24
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:25
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:26
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Spare BI:27
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status LEDs Reset command -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status Parameters change in course -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status Communications failure channel 1 -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status Communications failure channel 2 -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status Time sync. failure -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 Status LEDs reset -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 87L Fault detection in phase A -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 87L Fault detection in phase B -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 87L Fault detection in phase C -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 87L General trip -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 87L Trip in phases ABC -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 85 Power swing -
=D11+R11 7SD87 TP1 F003 230kV\Transformer MS-XFR-604-B\TP1 85 Power swing trip -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Manual close BI:01
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B Busbar PT fault BI:02
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B 50BF end fault trip BI:03
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q51) Close BI:04
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q52) Close BI:05
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Close phase R BI:06
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Close phase S BI:07
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Close phase T BI:08
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Locked auto-reclosure BI:09
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\(Q0) Interlocking Lock BI:10
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Auto-reclosure BI:11
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 General start BI:12
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Trip Phase R BI:13
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Trip Phase S BI:14
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Trip Phase T BI:15
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Fail feeder PL1 BI:16
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Spare BI:17
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Spare BI:18
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Spare BI:19
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Spare BI:20
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Spare BI:21
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:22
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:23
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:24
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:25
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:26
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Spare BI:27
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 50-51 Start Phase A -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 50-51 Start Phase B -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 50-51 Start Phase C -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 51 Start -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 51 Trip -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 50 Start -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50/51 50 Trip -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50N/51N 50N-51N Start -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50N/51N 50N Start -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50N/51N 51N Start -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50N/51N 50N Trip -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 50N/51N 51N Trip -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status LEDs Reset command -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Parameters change in course -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Communications failure channel 1 -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Communications failure channel 2 -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status Time sync. failure -
=D11+R11 7SJ85 TP2 F004 230kV\Transformer MS-XFR-604-B\TP2 Status LEDs reset -

ADVICE: Wired signals are noted with respective binary input