S&C Circuit-Switchers Mark V Pre-insertion Inductors

Outdoor Transmission (34.5 kV through 230 kV)

Effective overvoltage control for capacitor bank switching


applications

Pre-insertion inductors mounted on 138-kV Vertical-Break Style Mark V Circuit-Switcher.

S&C Mark V Circuit-Switchers are available with a variety Limiting phase-to-phase switching-surge overvol-
of optional pre-insertion inductors for use in single-bank tages produced at remote transformers as a result
and multiple-bank (back-to-back) capacitor switching of energizing a capacitor bank . . . a phenomenon which
applications. Pre-insertion inductors are more effective can lead to decreased transformer life, or even trans-
than controlled-closing schemes and pre-insertion resis- former failure, because of the high voltage-stress con-
tors for: centrations which are imposed across the transformer
Limiting inrush current and overvoltage at the windings, and,
capacitor bank busand thus induced transient volt- Limiting overvoltages on long open-ended lines.
age disturbances in substation low-voltage control cir- Such overvoltages can cause nuisance operation of
cuits that can cause spurious signals, insulation surge arresters.
puncture, and component damage,
CONTINUED v

May 10, 2010 S&C Electric Company Photo Sheet 711-757


S&C Circuit-Switchers Mark V

Pre-insertion Inductors Construction


Pre-insertion inductors are especially suited for limiting Each pre-insertion inductor is comprised of two or more
transient overvoltages which, through voltage manica- close-coupled layers of stainless-steel or aluminum con-
tion, can result in nuisance tripping of adjustable-speed ductor wound, along with a resin-impregnated lament-
drives and other sensitive electronic devices. Voltage mag- berglass roving, to form a hollow glass-reinforced tube.
nication can occur where power-factor correction capac- An integral counter-wound stainless-steel damping wind-
itors and/or voltage control capacitors are applied on the ing is also provided to limit the voltage across the Circuit-
utility distribution system or on a utility customers low- Switcher interrupter during opening in capacitor bank
voltage bus, and is caused by a near-resonant condition applications. A layer of roving separates the layers of con-
between the switched capacitor bus and the capacitances ductor and other layers of roving are added for mechanical
at lower voltages. strength and stability. The outer roving is nished with a
For complete application information on S&C Pre- coat of a silicone-alkyd paint for all-weather durability.
insertion Inductors refer to S&C Data Bulletin 711-95 or the
nearest S&C Sales Ofce.