Академический Документы
Профессиональный Документы
Культура Документы
Earthing
Press release
TN TT IT
2
Insulation involves:
b separation by insulating materials
Risks linked
b separation by linear clearances in gases to the insulation fault
(e.g. in air) or by creepage distances along
insulators (e.g. to prevent flashover on electrical
switchgear). Whatever its cause, an insulation fault is a risk
Insulation is characterised by specific voltages to life property and the availability of electrical
which, in accordance with standards, apply power: all this comes under the heading
to new products and equipment: of dependability.
b insulation voltage (highest voltage on system)
b lightning impulse withstand voltage Risk of electric shock
(1.2/50 µs impulse wave)
b power frequency withstand voltage A person (or animal) subjected to an electrical
(2U + 1000 V/1 min). voltage, is electrified.
Example for an LV switchboard of the Prisma
type: The effects of alternating (15 to 1000 Hz)
b insulation voltage: 1000 V
current on the human body
b impulse voltage: 12 kV.
1A Cardiac arrest
When commissioning a new installation,
produced in accordance with standard working 75 mA Irreversible cardiac
practices with products manufactured as per fibrillation threshold
standards, the risk of an insulation fault is 30 mA Respiratory paralysis
extremely low. However, this risk increases threshold
with time. 10 mA Muscular contraction
This is because the installation is subjected (tetanisation)
to a variety of aggressions which are responsible
for insulation faults. Below are a few examples: 0.5 mA Very slight sensation
b during installation:
v mechanical deterioration of a cable insulator
Protection of persons against the dangerous
b during operation:
effects of electrical current takes top priority;
v dust with a varying degree of conductivity
the risk of electric shock must therefore be taken
v the thermal ageing of insulators due
into account before the rest.
to excessive temperature caused by:
- the climate
- too many cables in a duct Risk of fire
- an insufficiently ventilated cubicle Should this risk materialise, it can have serious
- harmonics consequences for persons and equipment. Many
- overcurrents… fires are caused by an excessive temperature rise
v the electrodynamic forces developed during at a specific time or an electrical arc generated
a short-circuit which may damage a cable by an insulation fault. The higher the fault
or reduce a clearance current, the greater the risk. This risk also
v switching and lightning surges depends on the degree of the fire or explosion risk
v 50 Hz voltage surges caused by MV earth faults on the premises.
and affecting LV equipment.
3 3
Moreover, if the fault current is high: system which is geographically spread out
b the damage, in the installation or the loads, with galvanic links.
can be serious and increase repair costs and time Finally, on de-energisation, the appearance
b the circulation of high fault currents in of overvoltages and/or electromagnetic radiation
the common mode (between the system phenomena can cause malfunctioning
and earth) can also disturb sensitive devices, or even deterioration of sensitive equipment.
particularly if they are part of a "low current"
A few reminders
Terminology
E95663
4
Example of a simplified earth leakage current (Id) calculation
E95665 RCD
IMD
1st fault:
2nd fault:
Tripping by RCD Tripping by overcurrent Tripping by overcurrent
protection device protection device
Function
T T This system sustains the "earth fault" ... stages of earth leakage protection in order
but limits the consequences by implementing to reduce breaking to the smallest part
residual current devices which detect the earth of the system.
fault before it becomes a short-circuit. This is b Note that RCDs are:
the principle of the TT "directly earthed neutral" v built into or added to the circuit-breaker and
systems which allow the addition of extra switch with the 0.5 to more than 100 A
outgoers by simply combining them Multi 9 range
with an RCD. v built into the circuit-breaker with the 100
to 630 A Vigi module
It is the safety champion! v built into the circuit-breaker with the insulation
monitoring module
b In this case, as for short-circuits, the only v with separate toroid with
contribution that can be made to availability is the 100 to 6300 A Vigirex devices which indicate
to enhance discrimination by installing several absence of auxiliary supply source without
5 5
E95664
Protection by residual Protection by overcurrent Protection by insulation
current devices (RCDs) protection devices monitoring devices (IMDs)
HV / LV
HV / LV HV / LV
RCD
IMD
1st fault
b RCCB (residual current cb) b fuse b surge limiter
b RCCB with overcurrent prot. b thermal magnetic circuit breaker b insulation monitoring device
b residual current relay b circuit breaker
with separate toroid with electronic trip unit
causing tripping (avoids resets), and also warn I T This system renders the fault inoffensive.
the user of the insulation drop without causing
It consists of attacking the cause rather than the
tripping, by means of an early warning contact
effect by limiting the fault current to a few mA.
which is activated at half of the displayed
In an IT unearthed neutral or impedant neutral
threshold.
system, as the fault is not dangerous, there is no
For example: set at 300 mA, it warns the user
need to trip and operation can continue.
at 150 mA.
It is the electrical power availability
TN When a fault occurs, this system causes champion!
tripping of the SCPD (short-circuit protective
device) to provide protection. b however, leaving an earth fault on such
This fault is similar to a short-circuit (very low a system would mean leaving a direct link
fault loop impedance) and is thus violent between the system and the earth, as before.
and destructive. The circuit-breaker therefore In this case, the appearance of a 2nd fault creates
trips on the 1st fault. a dangerous current which must cause tripping
b this is the principle of the TN systems with of the same kind as in the TT and TN system
exposed conductive parts connected to the earthing arrangements.
neutral earthing point and which do not require b for this reason, this type of unearthed neutral
additional protection devices such as RCDs system is only advantageous if real insulation
or IMDs. It is thus the installation economy faults are detected as soon as they appear by
champion! This principle quickly becomes costly the Vigilohm System range which automatically
in the event of modifications or extensions, and immediately detects faults on outgoers,
and is hard on installations due including transient faults (which users
to short-circuit effects on cables and loads, particularly dread).
as well as voltage drops which can disturb This is the function of the XM200 IMD with
computers, MN undervoltage releases, motors, … the XD301 detectors (1 outgoer) or XD312
b in order to limit the consequences of the fault detectors (12 outgoers) combined with closed
to the part of the system concerned, current, time A toroids or split OA toroids.
and energy discrimination methods must be b in order to meet the needs of sites with
implemented. the most exacting availability requirements,
b when the fault loop impedance is poorly Schneider Electric offers products designed to
controlled, it may be necessary to add additional measure resistance and capacitance outgoer by
protection of the residual current type. The NEC outgoer.
(National Electrical Code) requires earth-fault These products communicate this information
protection of TN-S systems by GFP (ground locally and via the supervision system, and make
fault protection) devices or low-sensitivity RCDs. it possible to implement preventive maintenance
Moreover, the use of medium-sensitivity RCDs so as never to be subjected
(300 mA) can also reduce the risk of fire to the earth fault.
by eliminating stray currents. These protection devices are: XM300C,
b an extensive choice of 1P/3P/4P circuit-breakers XD308C, XL308, XL316, and the local XAS,
provides a perfect solution from 1 to more than XL1200, XL1300, XTU300 interfaces according
6300 A with the following ranges: to the installation configuration.
v Multi 9
v Compact
v Masterpact.
6
Switchgear
E95667
Residual current Overcurrent Surge limiter
devices RCD
protection Insulation monitoring IMD
devices
0.5 to 125 A Cadew C surge limiter
0.5 to 125 A Multi 9 circuit breaker (HV/LV transformer)
Multi 9 system (or fuse)
Vigilohm/Vigilohm system
80 to 3200 A Insulation monitoring
100 to 630 A Compact circuit breaker device
Compact + Vigi 800 to 6300 A
Masterpact circ. breaker Vigilohm system
automatic fault locating
1 to 8000 A
Vigilohm system manual
Vigirex + toroids
fault locating
Prevention possible with: If the conditions for the protection of life Tripping by overcurrent protection devices
b Vigirex with option P are not satisfied, use a low-sensitivity RCD on second fault
b Compact NS with insulation monitoring module or earth protection on TN-S systems only
7 7
Overvoltage protection The TT, TN-S and IT system earthing
arrangements can thus satisfy all electromagnetic
Protection may be necessary in all system compatibility criteria. However, it should be
earthing arrangements. Choice of the right noted that the TN-S system generates more
protection must take site exposure and the type disturbances during the insulation fault,
and activity of the establishment into account. as the fault current is higher.
It is then necessary to determine the number On the other hand, the TN-C and TN-C-S
and quality of necessary equipotential zones system earthing arrangements are not
in order to implement the protection devices recommended, as in these systems a permanent
required (surge arresters, etc.) on the lines current due to load unbalance flows through
of the various incoming and outgoing electrical the PEN conductor, the exposed conductive parts
systems. and the cable shieldings. This permanent current
Remarks: creates disturbing voltage drops between the
b the IT system earthing arrangement more often exposed conductive parts of the sensitive
requires the use of surge arresters equipment connected to the PEN. The presence
b no system earthing arrangement completely of 3rd order multiple harmonics has considerably
does away with these measures amplified this current in modern installations.
b in the IT system earthing arrangement,
protection against overvoltages due to MV faults
must be provided by a surge limiter.
Protection against
electromagnetic
disturbances
Any system earthing arrangement can be chosen:
b for all differential mode disturbances
b for all disturbances (common or differential
mode) with a frequency greater than a MHz.
Summary
E95666
Protection of life
Protection of property:
b against fire
b protection of equipment (1)
8
Choice of system earthing arrangement
and conclusion
The common aim of the three system earthing Generally speaking:
arrangements internationally used and v continuity of supply and a maintenance
standardised by the IEC 60364 is maximum department: the solution is an IT system
dependability. v continuity of supply and no maintenance
As regards protection of persons, all 3 system department: there is no completely satisfactory
earthing arrangements are equivalent provided solution: prefer a TT system for which
that all installation and operating rules are discrimination on tripping is easier to implement
complied with. and which minimises damage compared with
Given the specific characteristics of each system a TN system.
earthing arrangement, it is impossible to make Extensions are easy (no calculations)
a choice without considering installation v continuity of supply is not essential and there is
and operating needs. a competent maintenance department:
This choice must be the result of joint prefer a TN-S system (rapid repairs and extension
deliberation between the user and the system according to rules)
designer (electrical consultants, contractor, …) v continuity of supply is not essential and there is
on: no maintenance department: prefer a TT system
b the installation characteristics v risk of fire: IT if there is a maintenance
b operating conditions and requirements. department, and use a 0.5 A RCD, or TT
It is pointless trying to operate an unearthed b take the special features of the system and loads
neutral system in part of an installation which, into account:
by its very nature, has a low insulation level v very extensive system or with a high leakage
(a few thousand ohms): old and extended current: prefer TN-S
installations, installations with external lines… v use of replacement or standby power supplies:
Likewise, it would be a contradiction in industry prefer TT
where continuity of supply and productivity v loads sensitive to high fault currents (motors):
are essential and fire risks high, to choose prefer TT or IT systems
a multiple earthed neutral system. v loads with low natural insulation (furnaces)
or with a large HF filter (large computers):
How to choose the right prefer a TN-S system
v supply of control and monitoring systems:
system earthing prefer an IT (continuity of supply) or TT system
(enhanced equipotentiality of communicating
arrangement devices).
b first and foremost, do not forget that all three
system earthing arrangements can exist side
by side in the same electrical installation. This is
Conclusion
a guarantee that the best solution for safety Using only one system earthing arrangement is
and availability needs will be found for every case. not always the best choice. In many cases it is
b you must then ensure that the choice thus preferable to implement several system
of system earthing arrangement is not earthing arrangements in the same installation.
recommended As a rule, a "radial" installation, with careful
or imposed by standards or legislation identification of priority loads and use of standby
(decrees, ministerial orders). sources or uninterruptible power supplies,
b you then need to dialogue with the user in is preferable to a tree-structured monolithic
order to identify his needs and means: installation.
v need for continuity of supply We hope this technical guide has furthered your
v whether or not there is a maintenance knowledge of system earthing arrangements
department and that it will enable you to optimise
v risk of fire. the dependability of your installations.
9 9
DBTP72ART/EN © 2003 - Schneider Electric - All rights reserved
DBTP72ART/EN 02-2003