Source- Electrical diagrams

changeover
systems
Presentation 2
Functions and characteristics 7
Dimensions 33

Remote-operated source-changeover systems


Compact NS100 to 1600 or Masterpact NW 56
Compact NS100 to 630 57
Compact NS630b to 1600 60
Masterpact NW 68
Source-changeover systems with automatic controllers
Compact NS100 to 1600 87
Masterpact NW 90

Order forms 91

55
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/1600 or
Masterpact NW devices
Electrical interlocking by the IVE unit
Recommended electrical control system

L1 L2

11 12 13 14 15 16

84 84
N
SDE"N" SDE"R"
(2) (2) IVE
81 81
R

1 2 3 4 5 6 7 8 9 10
ON OR FN FR

ordre de transfert sur


la source "remplacement" (1)

ordre de retour sur


la source "normal" (1)

CN 1 + CN 1 +

CN 2 CN 2

(1) : the normal and replacement source transfer orders must be interlocked electrically
(2) : operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE
auxiliary contacts are mounted in the circuit breakers.

Legends Note:
ON "Normal source opening order Diagram shown with circuits de-energised, circuit breakers
OR "Replacement source opening order open and relays in normal position.
FN "Normal source closing order
FR Replacement source closing order
L1 Normal source fault-trip signal
L2 Replacement source fault-trip signal
N Normal source auxiliary wiring connector
R Replacement source auxiliary wiring connector

56
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201177
Source-changeover system without automatic-control system
Without auxiliaries for emergency off
Local reset
NORMAL

11 12 13 14 15 16

N
IVE
R

1 2 3 4 5 6 7 8 9 10
22 24 82 84 B2 A2 A4 B4

QN
OF2 Voluntary remote reset
MT
trip unit
SDE
11 12 13 14 15 16

N
IVE
R
21 81 A1 L1

1 2 3 4 5 6 7 8 9 10

RN RR

REPLACEMENT

22 24 82 84 B2 A2 A4 B4
Automatic reset

QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
R

1 2 3 4 5 6 7 8 9 10

21 81 A1 L1

States permitted by mechanical interlocking system


Normal Replacement
0 0
(1) : Prefabricated wiring: cannot be modified 1 0
0 1
Legends
QN Normal source Compact NS equipped with motor mechanism Note:
QR Replacement source Compact NS equipped with motor mechanism Diagram shown with circuits de-energised, circuit breakers
SDE fault-trip indication contact open and relays in normal position.
IVE electrical interlocking and terminal block unit
MT motor mechanism
OF2 breaker ON/OFF indication contact
RN reset order for breaker QN
RR reset order for breaker QR

57
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201178
Source-changeover system without automatic-control system
With emergency off by MN release and automatic reset

NORMAL
CN1 . CN1 +

(2) CN2 . CN2

D1
F1

D1 22 24 82 84 B2 A2 A4 B4

QN
OF2
MT

trip unit
SDE

MN

BP

D4 21 81 A1 L1

KA3
KA3
D4

REPLACEMENT

D1

D1 22 24 82 84 B2 A2 A4 B4 Automatic reset

QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MN R

1 2 3 4 5 6 7 8 9 10

D4 21 81 A1 L1 KA3 KA3

D4

(1) : Prefabricated wiring supplied


(2) : Independent auxiliary source States permitted by mechanical interlocking system
Normal Replacement
Legends 0 0
QN Normal source Compact NS equipped with motor mechanism 1 0
QR "Replacement source Compact NS equipped with motor mechanism 0 1
MN undervoltage release
OF2 breaker ON/OFF indication contact Note:
SDE fault-trip indication contact After a fault trip, the breaker must be reset manually by
MT motor mechanism pressing its reset button.
IVE electrical interlocking and terminal block unit Diagram shown with circuits de-energised, circuit breakers
BP emergency off button with latching open and relays in normal position.
KA3 auxiliary relay
F1 auxiliary power supply circuit breaker

58
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201179
Source-changeover system without automatic-control system
With emergency off by MX release / automatic reset

NORMAL
CN3 . CN3 +
(2) CN4 . CN4

C1
F1

C1 22 24 82 84 B2 A2 A4 B4
opening
order

QN
OF2 KA1
MT KA1

trip unit
SDE

MX

CN5 . CN5 +
C2 21 81 A1 L1 (2) CN6 . CN6

C2 F2

opening
order

REPLACEMENT
KA2
KA2

C1

C1 22 24 82 84 B2 A2 A4 B4

Automatic reset
QR
OF2
(1)
MT N
trip unit
SDE IVE
(1)
MX R

1 2 3 4 5 6 7 8 9 10

KA1
C2 21 81 A1 L1
(3) KA2

C2

(1) : Prefabricated wiring supplied


(2) : This source can be:
the source present in the case of voltage monitoring
an independent source
In this case, the MX release must be protected.
(3) : The reset orders must be delayed by 0.3 seconds. States permitted by mechanical interlocking system
Normal Replacement
Legends 0 0
QN Normal source Compact NS equipped with motor mechanism 1 0
QR Replacement source Compact NS equipped with motor mechanism 0 1
SDE fault-trip indication contact
OF2 breaker ON/OFF indication contact Note:
MX shunt release After a fault trip, the breaker must be reset manually by
MT motor mechanism pressing its reset button.
IVE electrical interlocking and terminal block unit Diagram shown with circuits de-energised, circuit breakers
KA1 time-delayed auxiliary relays open and relays in normal position.
KA2 time-delayed auxiliary relays
F1 auxiliary power supply circuit breaker
F2 auxiliary power supply circuit breaker

59
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201180
Electrical interlocking with lockout after a fault

N R Auxiliary CN1 . CN1 +


Transfer to
power supply CN2 . CN2
replacement source
ON FR
F1

Transfer to normal OR FN

source

(1)
312
314

(1)
B4

A4

A2

82
84

12
14

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
OF1
QN
SDE1
OF1
QR
SDE1
Electrical
operation
Electrical
operation
A1

81

11

311

A1

81

11

311

(1)

(1)

(1) Not to be wired on fixed version

Legends States permitted by mechanical interlocking system


QN Normal source Compact NS630b to 1600 Normal Remplacement
QR Replacement source Compact NS NS630b to 1600
0 0
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact 1 0
CE1 connected-position indication contact (carriage switch) 0 1
F1 auxiliary power supply circuit breaker
ON Normal source opening order Note:
OR Replacement source opening order Diagram shown with circuit breakers in connected position,
FN Normal source closing order (0.25 second delay) open, charged, and ready to close.
FR Replacement source closing order (0.25 second delay) Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).

60
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201181
Electrical interlocking with lockout after a fault and emergency off by shunt release

Auxiliary CN1 . CN1 +


N R Transfer to power supply CN2 . CN2
replacement source
ON FR
F1

OR FN
Transfer to
normal source

KA3 KA3

(1)
C12

312
314

(1)
B4

A4

A2

82
84

12
14

C12

312
314
B4

A4

A2

82
84
12
14
CE1

CE1 BP
OF1
QN
SDE1
OF1
QR
Electrical SDE1
operation
MX Electrical
operation
MX
C11
A1

81

11

311

C11
A1

81

11

(1) 311

(1)

KA3

(1) Not to be wired on fixed version

Legends States permitted by mechanical interlocking system


QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600 Normal Replacement
OF... breaker ON/OFF indication contact 0 0
SDE1 fault-trip indication contact 1 0
CE1 connected-position indication contact (carriage switch) 0 1
F1 auxiliary power supply circuit breaker
MX shunt release Note:
BP emergency off button with latching Diagram shown with circuit breakers in connected position,
KA3 auxiliary relay open, charged, and ready to close.
ON Normal source opening order Auxiliary power supply = supply voltage of auxiliary relays
OR Replacement source opening order (KA...) = supply voltage of electrical auxiliaries (electrical
FN Normal source closing order (0.25 second delay) operation, MCH, MX, MN...).
FR Replacement source closing order (0.25 second delay)

61
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201182
Electrical interlocking with lockout after a fault and emergency off by undervoltage

Auxiliary CN1 . CN1 +


N R Transfer to
power supply CN2 . CN2
replacement source
ON FR
F1

OR FN
Transfer to
normal source

KA3 KA3

(1)

(1)
312
314
D2
B4

A4

A2

82
84

12
14

312
314
D2
B4

A4

A2

82
84
12
14
CE1

CE1 BP

QN OF1

SDE1
OF1
QR
SDE1
Electrical
operation
MN Electrical
operation
MN
D1
A1

81

11

311

D1
A1

81

11

311

(1)

(1)

KA3

(1) Not to be wired on fixed version

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR "Replacement source closing order (0.25 second delay)
States permitted by mechanical interlocking system
Wiring colour codes Normal Replacement
0 0
RD red
GN green 1 0
BK black 0 1
VT violet
YE yellow Note:
GY grey Diagram shown with circuit breakers in connected position,
WH white open, charged, and ready to close.
BN brown Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).

62
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201183
Electrical interlocking by IVE with lockout after a fault
CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R

BN

BK
WH

GN
RD
VT
(1)
312
314

1 2 3 4 5 6 7 8 9 10
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer to
replacement source

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
Transfer to normal
OF1 source
QN
SDE

QR OF1
Electrical
operation SDE
Electrical
operation
81
A1

11

311

(1)
GY

81
A1

11

311
YE

(1)
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)

Wiring colour codes


States permitted by mechanical interlocking system
RD red Normal Replacement
GN green
0 0
BK black
VT violet 1 0
YE yellow 0 1
GY grey
WH white Note:
BN brown Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).

63
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices

Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release

CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

KA3
F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R
BN

BK
WH

GN
RD
VT

(1)
C12

1 2 3 4 5 6 7 8 9 10
312
314
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer to
replacement source
C12

312
314
B4

A4

A2

82
84
12
14
CE1

CE1
Transfer to normal
OF1 source
QN
SDE
OF1
QR
Electrical
operation SDE KA3
MX Electrical
operation
MX
C11

81
A1

11

311

BP

(1)
C11

81
A1

11

311
GY

YE

(1)
KA3
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Lgende
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MX shunt release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay) States permitted by mechanical interlocking system
Normal Replacement
Wiring colour codes 0 0
RD red 1 0
GN green 0 1
BK black
Note:
VT violet
Diagram shown with circuit breakers in connected position,
YE yellow
open, charged, and ready to close.
GY grey
Auxiliary power supply = supply voltage of auxiliary relays
WH white
(KA...) = supply voltage of electrical auxiliaries (electrical
BN brown
operation, MCH, MX, MN...).

64
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201185
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
E59543

CN1 . CN1 +
N R Auxiliary
Alimentation
Auxilliary
power CN2 . CN2
powersupply
auxiliaire
supply
KA3
F1

(2)
N
BN

BK
WH

GN
RD
VT

IVE
(2)
R

BN

BK
WH

GN
RD
VT
(1)

1 2 3 4 5 6 7 8 9 10
312
314
D2
B4

A4

A2

12
14

ON OR FN FR
(1)
Transfer
Transfer to
Transfert vers
to
replacement source

312
314
le Remplacement
replacement source
D2
B4

A4

A2

82
84
12
14
CE1

CE1
Transfertto
Transfer vers
normal
OF1 le Normal
source
normal source
QN
SDE
OF1
QR
Electrical
operation SDE KA3
MN Electrical
operation
MN
81
A1

D1

11

311

BP

(1)
A1

D1

81

11

311
GY

YE

(1)
KA3
GY

YE

(1) Not to be wired on fixed version


(2) Prefabricated wiring supplied

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
MCH spring-charging motor
MX standard opening release
XF standard closing release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order States permitted by mechanical interlocking system
OR Replacement source opening order Normal Replacement
FN Normal source closing order (0.25 second delay) 0 0
FR Replacement source closing order (0.25 second delay) 1 0
0 1
Wiring colour codes
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (electrical
WH white operation, MCH, MX, MN...).
BN brown

65
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201186
Automatic-control system without IVE for permanent replacement source without lockout after a fault

N R Auxiliary CN1 . CN1 +


power supply CN2 . CN2

F1

KA2
S1
F3
OFF Auto N R

KM2
KM1
KA1 KM2 KM1 KA1 KA2

F2
(1)
312
314
B4

A4

A2

82
84
12
14

(1)

312
314
B4

A4

A2

82
84

12
CE1 14

KA1

CE1
OF1
QN
SDE

OF1
QR
Electrical SDE
operation

Electrical
operation
A1

81

11

311

(1)
A1

81

11

311

(1) Not to be wired on fixed version


(1) KM1 KM2

Legends States permitted by mechanical interlocking system


QN Normal source Compact NS630b to 1600 Normal Replacement
QR Replacement source Compact NS NS630b to 1600
0 0
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact 1 0
CE1 connected-position indication contact (carriage switch) 0 1
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity) Note:
S1 control switches Diagram shown with circuit breakers in connected position,
KA1 auxiliary relays - UN presence detection open, charged, and ready to close.
KA2 auxiliary relays - UR presence detection Auxiliary power supply = supply voltage of auxiliary relays
KM1 contactors with 0.25 second delay (for transfer to Replacement source) (KA...) = supply voltage of electrical auxiliaries (electrical
KM2 contactors with 0.25 second delay (for transfer to Normal source) operation, MCH, MX, MN...).

66
Electrical diagrams Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201187
Automatic-control system for replacement source generator set without lockout after a fault

N1 REPLACEMENT SOURCE

genset
G automatic-control genset startup order CN1 . CN1 +
system Auxiliary
power supply CN2 . CN2

genset genset
monitoring fault F1
KA3

genset genset
voltage voltage
monitoring fault

S1

OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2

F3 (1)
312
314
C2
B4

A2

82
84
12
14

KA1 KA3

F2 (1)
CE1

312
314
B4

A4

A2

82
84
12
14
OF1 CE1
QN
SDE1
OF1
QR
Electrical
operation SDE1
KA1
Electrical
operation
A1

81

11

311

(1)
A1

81

11

311

KM1 KM2

(1)

(1) Not to be wired on fixed version

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal source)
States permitted by mechanical interlocking system
Wiring colour codes Normal Replacement
0 0
RD red
GN green 1 0
BK black 0 1
VT violet
YE yellow Note:
GY grey Diagram shown with circuit breakers in connected position,
WH white open, charged, and ready to close.
BN brown Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (electrical
operation, MCH, MX, MN...).

67
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201139
Electrical interlocking with lockout after a fault

Auxiliary CN1 . CN1 +


power supply CN2 . CN2
N R Transfer to
replacement source
F1
ON FR

Transfer to OR FN

normal source

(1)
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

(1)

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311

(1)

(1) Not to be wired on fixed version

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay) States permitted by mechanical interlocking system
FR Replacement source closing order (0.25 second delay) Normal Replacement
0 0
1 0
0 1

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

68
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201140
Electrical interlocking with lockout after a fault and emergency off by shunt release

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source
F1
ON FR

Transfer to OR
KA3
normal source KA3

(1)
C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
(1)

C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1 BP

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MX XF MX2 MCH

CH
MX XF MX2
B1

C1

A1

251

C11

81

11

21

31

41

311

(1)
C11
B1

C1

A1

251

81

11

21

31

41

311
(1)

KA3

(1) Not to be wired on fixed version

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
MX2 shunt release
BP emergency off button with latching
KA3 time delay for genset startup order to avoid starting the genset for transient UN disturbances States permitted by mechanical interlocking system
S1 control switches Normal Replacement
ON Normal source opening order 0 0
OR Replacement source opening order 1 0
FN Normal source closing order (0.25 second delay) 0 1
FR Replacement source closing order (0.25 second delay)

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

69
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201141
Electrical interlocking with lockout after a fault and emergency off by undervoltage release

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R Transfer to
replacement source F1
ON FR

OR
Transfer to KA3 KA3
normal source

(1)
254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

(1)

254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
BP
OF1 OF2 OF3 OF4
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MX XF MN MCH

CH
MX XF MN
B1

C1

A1

251

D1

81

11

21

31

41

311

(1)
B1

C1

A1

251

D1

81

11

21

31

41

311

(1)

(1) Not to be wired on fixed version KA3

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
S1 control switches States permitted by mechanical interlocking system
KA3 auxiliary relay Normal Replacement
ON Normal source opening order 0 0
OR Replacement source opening order 1 0
FN Normal source closing order (0.25 second delay) 0 1
FR Replacement source closing order (0.25 second delay)

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

70
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201142
Electrical interlocking by IVE with lockout after a fault

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2
N R

F1

(3)
N
VT
WH

GN
RD
BK

IVE
(3)
R

VT
WH

GN
RD
BK
(2)
252
254

312
314

1 2 3 4 5 6 7 8 9 10
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2)
Transfer to
replacement source
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN "Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
ON Normal source opening order
OR Replacement source opening order States permitted by mechanical interlocking system
FN Normal source closing order (0.25 second delay) Normal Replacement
FR Replacement source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes 0 1
RD red
GN green
BK black
VT violet Note:
YE yellow Diagram shown with circuit breakers in connected position,
GY grey open, charged, and ready to close.
WH white Auxiliary power supply = supply voltage of auxiliary relays
BN brown (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

71
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201143
Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release

CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2

F1

KA3

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R
WH

GN
RD
BK
VT

(2)
C12
252
254

312
314

1 2 3 4 5 6 7 8 9 10
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2) Transfer to
replacement source
C12
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3

MCH
PF

CH
MX XF MX2 MCH

BP
CH
MX XF MX2
B1

C1

A1

251

C11

81

11

21

31

41

311

(1) (2)
C11
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

KA3

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order States permitted by mechanical interlocking system
FN Normal source closing order (0.25 second delay) Normal Replacement
FR Replacement source closing order (0.25 second delay) 0 0
1 0
Wiring colour codes 0 1
RD red
GN green
BK black Note:
VT violet Diagram shown with circuit breakers in connected position,
YE yellow open, charged, and ready to close.
GY grey Auxiliary power supply = supply voltage of auxiliary relays
WH white (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
BN brown MN...).

72
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51201144
Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release
CN1 . CN1 +
Auxiliary
N R power supply CN2 . CN2

F1

KA3

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R
WH

GN
RD
BK
VT
(2)
254
252

312
314

1 2 3 4 5 6 7 8 9 10
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

ON OR FN FR
(2) Transfer to
replacement source
254
252

312
314
C2

D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1
Transfer to
OF1 OF2 OF3 OF4 normal source
QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1 KA3

MCH
PF

CH
MX XF MN MCH

BP
CH
MX XF MN
B1

C1

A1

251

D1

81

11

21

31

41

311

(1) (2)
D1
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
GY

GY
BN

BN
YE

YE

KA3

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker
BP emergency off button with latching
S1 control switches
KA3 auxiliary relay States permitted by mechanical interlocking system
ON Normal source opening order Normal Replacement
OR Replacement source opening order 0 0
FN Normal source closing order (0.25 second delay) 1 0
FR Replacement source closing order (0.25 second delay)
0 1
Wiring colour codes
RD red
GN green Note:
BK black Diagram shown with circuit breakers in connected position,
VT violet open, charged, and ready to close.
YE yellow Auxiliary power supply = supply voltage of auxiliary relays
GY grey (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
WH white MN...).
BN brown

73
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156226
Automatic-control system without IVE for permanent replacement source without lockout after a fault

N R

CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

S1
KA2

OFF Auto N R
F3
KM2 KM1
KM2 KM1 KA1 KA2

KA1
(1)
F2
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

252 (1)
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH KA1
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311

(1)
KM1 KM2

(1) Not to be wired on fixed version

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection States permitted by mechanical interlocking system
KA2 auxiliary relays - UR presence detection Normal Replacement
KA3 auxiliary relays - generator set startup if UN absent 0 0
KM1 contactors with 0.25 second delay (for transfer to Replacement source) 1 0
KM2 contactors with 0.25 second delay (for transfer to Normal source) 0 1

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

74
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156227
Automatic-control system for replacement source generator set without lockout after a fault

N1
REPLACEMENT SOURCE

genset CN1 . CN1 +


G automatic-control genset startup order Auxiliary
system
power supply CN2 . CN2

genset genset
monitoring fault F1
KA3

genset genset
voltage voltage
monitoring fault

S1

OFF Auto N R
KM2 KM1
KM2 KM1 KA1 KA2
KA2
(1)
F3
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

(1)
KA1 KA3

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
F2
CE1

CE1

OF1 OF2 OF3 OF4


QN
SDE1

QR OF1 OF2 OF3 OF4


PF
SDE1

MCH KA1
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1)
B1

C1

A1

251

81

11

21

31

41

311

(1)
KM1 KM2

(1) Not to be wired on fixed version

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1 control switches
KA1 auxiliary relays - UN presence detection States permitted by mechanical interlocking system
KA2 auxiliary relays - UR presence detection Normal Replacement
KA3 auxiliary relays - generator set startup if UN absent 0 0
KM1 contactors with 0.25 second delay (for transfer to Replacement source) 1 0
KM2 contactors with 0.25 second delay (for transfer to Normal source) 0 1

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

75
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156904
Automatic-control system for permanent replacement source with lockout after a fault (with MN)
CN1 . CN1 +
N R Auxiliary
power supply CN2 . CN2

F1

KA1

S1

OFF R Auto N

KA1 KA1

KA3 KA2

11 12 13 14 15 16

(3)
N
WH

VT

BK
GN
RD

IVE
(3)
R
WH

VT

BK

GN
RD
(2)
254
252

312
314
D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

1 2 3 4 5 6 7 8 9 10
(2)
254
252

312
314
D2
B3

B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

KA2 KA3 KA2 KA3

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MN XF MCH

CH
MN XF
B1

D1

A1

251

81

11

21

31

41

311

(1) (2)
B1

D1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2 circuit breaker (high breaking capacity) Normal Replacement
S1 control switches 0 0
KA1 auxiliary relays 1 0
KA2 auxiliary relays
0 1
KA3 auxiliary relays
Wiring colour codes
RD red Note:
GN green Diagram shown with circuit breakers in connected position,
BK black open, charged, and ready to close.
VT violet Auxiliary power supply = supply voltage of auxiliary relays
YE yellow (KA...) = supply voltage of electrical auxiliaries (MCH, MX,
GY grey MN...).
WH white
BN brown

76
Electrical diagrams Remote-operated
source-changeover systems
2 Masterpact NW devices
Diagram no. 51156905
Automatic-control system for replacement source generator set with lockout after a fault (with MN)
N
CN1 . CN1 +
Auxiliary
KA1 power supply CN2 . CN2

REPLACEMENT SOURCE
F1

genset
G automatic-control genset startup order
system
S1

genset genset OFF R Auto N


monitoring fault KA2

genset genset KA1 KA1


voltage voltage
monitoring fault

KA3 KA2

11 12 13 14 15 16

(3)
N
WH

GN
RD
BK
VT

IVE
(3)
R
WH

GN
RD
BK
VT

(2)
254
252

312
314
D2
B3

B2

A2

82
84

12
14
22
24
32
34
42
44

1 2 3 4 5 6 7 8 9 10
(2)
254
252

312
314
D2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1
KA2 KA3 KA2 KA3

CE1

OF1 OF2 OF3 OF4


QN
SDE1
OF1 OF2 OF3 OF4
QR
PF
SDE1

MCH
PF

CH
MN XF MCH

CH
MN XF
B1

D1

A1

251

81

11

21

31

41

311

(1) (2)
B1

D1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2 circuit breaker (high breaking capacity) Normal Replacement
S1 control switches 0 0
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting the genset for transient UN disturbances 1 0
KA3 auxiliary relay 0 1
Wiring colour codes
RD red Note:
GN green Diagram shown with circuit breakers in connected position,
BK black open, charged, and ready to close.
VT violet
Auxiliary power supply = supply voltage of auxiliary relays
YE yellow
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
GY grey
WH white MN...).
BN brown

77
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906
2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault

N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

t1

t2
252
254

312
314
322

324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QN1
CE1 CE2

OF1 OF2 OF3 OF4


QN2
PF

MCH OF1 OF2 OF3 OF4


QR
PF

CH
MX XF MCH
PF

CH
MX XF
MCH
C1

A1

251

21
B1

321
11

31

41

CH
311

MX XF
C1

A1

251

21
B1

321
11

31

41

311

C1

A1

251

21
B1

321
11

31

41

311

Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2 order for transfer from N1 + N2to R
(QR closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
Normal 1 Normal 2 Replacement
0 0 0
1 1 0
0 0 1
1 0 0
0 1 0
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

78
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907
2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault

N1 N2 R CN1 . CN1 +
Auxiliary
power supply CN2 . CN2

F1

t1

t2
KA1

KA1
KA1
KA2
252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44

KA2
KA2
252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

252
254

312
314
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1

OF1 OF2 OF3 OF4


QN1
CE1
SDE1
OF1 OF2 OF3 OF4
QN2
PF
SDE1

QR MCH OF1 OF2 OF3 OF4


PF
SDE1
CH
MX XF MCH
PF

CH
MX XF MCH
251

11
C1

81

21
B1

A1

311
31

41

CH
MX XF
251
C1

81

21
B1

A1

311
31

41
11

251
C1

81

21
B1

A1

311
31

41
11

Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
S1 control switches
S2 source selection switches
t1 order for transfer from R to N1 + N2 States permitted by mechanical interlocking system
(QN1 and QN2 closing time delay = 0.25 sec. minimum) Normal 1 Normal 2 Replacement
t2 order for transfer from N1 + N2to R 0 0 0
(QR closing time delay = 0.25 sec. minimumm) 1 1 0
0 0 1
1 0 0
0 1 0

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

79
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908
2 Normal sources and 1 Replacement source: automatic-control system for generator set without
lockout after a fault (with MN)

N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2

genset
G automatic-control genset startup order
system
F1

genset genset
monitoring fault S1

OFF R Auto N
genset genset
voltage voltage
monitoring fault

F2
S2

F2
KA2
KA2 KA4 KA2 KA2 KA2 N1 N2
F2
KA1 KA1 KA4 KA4 N1+N2
KA3 KA3

F2 KA1

KA5 KA6

KA6

KA5
254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44

254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44

CE1 CE2

254
252

312
314
322
324
D2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QN1
CE1 CE2

OF1 OF2 OF3 OF4


QN2
PF

QR MCH OF1 OF2 OF3 OF4


PF

CH MN XF MCH
PF
CH MN XF MCH
321
D1

311
21
B1

A1

251

31

41
11

CH MN XF
251

321
D1

311
21
B1

A1

31

41
11

D1

311
21
B1

A1

321
251

31

41
11

Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker States permitted by mechanical interlocking system
F2/F3 circuit breaker (high breaking capacity) Normal 1 Normal 2 Replacement
S1 control switches 0 0 0
S2 source selection switches 1 1 0
KA1 auxiliary relay 0 0 1
KA2 auxiliary relays with 10 to 180 sec. time delay 1 0 0
KA3 auxiliary relays with 0.1 to 30 sec. time delay 0 1 0
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay Note:
KA6 auxiliary relays with 0.25 sec. time delay Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

80
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909
2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout
after a fault (with MN))

N1 N2
CN1 . CN1 +
REPLACEMENT SOURCE Auxiliary
power supply CN2 . CN2
genset
G automatic-control genset startup order
system
F1

genset genset
monitoring fault S1

genset genset OFF R Auto N


voltage voltage
monitoring fault

F2
S2

F2
KA2 KA2
KA2 N1 N2
KA4 KA2 KA2
F2
KA1 KA1 N1+N2
KA3 KA4 KA4 KA3

KA1
F2

KA5 KA7
KA6

KA6

KA8

KA7 KA8
KA7 KA8 KA5
254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

CE1 CE2 CE3

254
252

312
314
322
324
332
334
D2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2 CE3

OF1 OF2 OF3 OF4


QN1
CE1 CE2 CE3
SDE1
OF1 OF2 OF3 OF4
QN2
PF
SDE1
QR MCH OF1 OF2 OF3 OF4
PF
SDE1
CH MN XF MCH
PF

CH MN XF MCH
B1

D1

A1

251

81

11

21

31

41

311

321

331

CH MN XF
B1

D1

A1

251

81

11

21

31

41

311

321

331

B1

D1

A1

251

81

11

21

31

41

311

321

331

Legends
QN... Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
XF standard closing voltage release
MN undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact States permitted by mechanical interlocking system
F1 auxiliary power supply circuit breaker Normal 1 Normal 2 Replacement
F2/F3 circuit breaker (high breaking capacity) 0 0 0
S1 control switches 1 1 0
S2 source selection switches 0 0 1
KA1 auxiliary relay 1 0 0
KA2 auxiliary relays with 10 to 180 sec. time delay 0 1 0
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
Note:
KA5 auxiliary relays with 0.25 sec. time delay
Diagram shown with circuit breakers in connected position,
KA6 auxiliary relays with 0.25 sec. time delay
open, charge.
KA7 auxiliary relay
Auxiliary power supply = supply voltage of auxiliary relays
KA8 auxiliary relay
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

81
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910
3 sources with only 1 device closed: electrical interlocking without lockout after a fault

SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1

t1

t2

t3
252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2

QS2 OF1 OF2 OF3 OF4


PF

QS3 MCH OF1 OF2 OF3 OF4


PF

CH
MX XF MCH
PF

CH
MX XF MCH
251

321
C1

21
B1

A1

311
31

41
11

CH
MX XF
251

321
C1
B1

A1

21

311
31

41
11

251

321
C1
B1

A1

311
31

41
11

21

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2 order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3 order for transfer to Source 3 States permitted by mechanical interlocking system
(QS3 closing time delay = 0.25 sec. minimum) Source 1 Source 2 Source 3
0 0 0
1 0 0
0 1 0
0 0 1

Note:
Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

82
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911
3 sources with only 1 device closed: electrical interlocking with lockout after a fault

SOURCE 1
SOURCE 2
SOURCE 3 Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1

t1

t2

t3

KA1

KA2

KA1 KA1
252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44

KA3
KA2 KA2
252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3

252
254

312
314
322
324
C2
B3
B2

A2

82
84

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2
SDE1

QS2 OF1 OF2 OF3 OF4


PF
SDE1

QS3 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH MX XF MCH
PF

CH MX XF MCH
251

321
C1

81

21
B1

A1

311
31

41
11

CH MX XF
251

321
C1

81

21
B1

A1

311
31

41
11

251

321
C1

81

21
B1

A1

311
31

41
11

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2 order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
t3 order for transfer to Source 3 Source 1 Source 2 Source 3
(QS3 closing time delay = 0.25 sec. minimum) 0 0 0
KA1 auxiliary relays 1 0 0
KA2 auxiliary relays 0 1 0
KA3 auxiliary relays 0 0 1

Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

83
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912
2 sources and 1 coupling: electrical interlocking without lockout after a fault

SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1
COUPLING

t1

t2

t3

t4
252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2

OF1 OF2 OF3 OF4


QC
PF

QS2 MCH OF1 OF2 OF3 OF4


PF

CH MX XF MCH
PF

CH MX XF MCH
251

321
C1

21
B1

A1

311
31

41
11

CH MX XF
251

321
C1

21
B1

A1

311
31

41
11

251

321
C1

21
B1

A1

311
31

41
11

Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum) States permitted by mechanical interlocking system
t2 coupling order for Source 2 failure Source 1 Source 2 Coupling
(QC closing time delay = 0.25 sec. minimum) 0 0 0
t3 coupling order for Source 1 restored 1 1 0
(QS1 closing time delay = 0.25 sec. minimum)
1 0 1
t4 coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum) 0 1 1
1 0 0
0 1 0
0 0 1
Note:
Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

84
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913
2 sources and 1 coupling: electrical interlocking with lockout after a fault

SOURCE 1 SOURCE 2
Auxiliary CN1 . CN1 +
power supply CN2 . CN2

F1
COUPLING

t1

t2

t3

t4
KA1

KA2
KA1 KA1
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

KA3

KA2 KA2
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2
KA3 KA3

252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1
CE1 CE2
SDE1

QC OF1 OF2 OF3 OF4


PF
SDE1

QS2 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH
MX XF MCH
PF

CH MX XF MCH
251
C1

321
81

21
B1

A1

311
31

41
11

CH MX XF
251
C1

321
81

21
B1

A1

311
31

41
11

251
C1

321
81

21
B1

A1

311
31

41
11

Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH springs charged indication contact
F1 auxiliary power supply circuit breaker
t1 coupling order for Source 1 failure States permitted by mechanical interlocking system
(QC closing time delay = 0.25 sec. minimum) Source 1 Source 2 Coupling
t2 coupling order for Source 2 failure 0 0 0
(QC closing time delay = 0.25 sec. minimum) 1 1 0
t3 coupling order for Source 1 restored
1 0 1
(QS1 closing time delay = 0.25 sec. minimum)
t4 coupling order for Source 2 restored 0 1 1
(QS2 closing time delay = 0.25 sec. minimum) 1 0 0
KA1 auxiliary relays 0 1 0
KA2 auxiliary relays 0 0 1
KA3 auxiliary relays
Note:
Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

85
Electrical diagrams Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914
2 sources and 1 coupling: automatic-control system with lockout after a fault

SOURCE 1 SOURCE 2

S1

KA1 KA1 KA1 KA1

forced
KA1

OFF
auto
KA2 KA1

F3 KA2

KA3

KA3 S2
KA4
KA4

S1 + S2
S1 + C

S2 + C
F2

KA5 KA6
KA7
KA5
KA5

KA6
KA6
COUPLING

KA7 KA7

F2
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

F2
252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44

CE1 CE2

252
254

312
314
322
324
C2
B3
B2

A2

82
84
12
14
22
24
32
34
42
44
CE1 CE2

OF1 OF2 OF3 OF4


QS1 CE1 CE2
SDE1
OF1 OF2 OF3 OF4
QC
PF
SDE1

QS2 MCH OF1 OF2 OF3 OF4


PF
SDE1
CH MX XF MCH
PF

CH MX XF MCH
B1

C1

A1

251

81

11

21

31

41

311

321

CH MX XF
B1

C1

A1

251

81

11

21

31

41

311

321

B1

C1

A1

251

81

11

21

31

41

311

321

Legends
QS... Source Masterpact NW
QC Coupling Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
PF ready-to-close contact
CE... connected-position indication contact (carriage switch) States permitted by mechanical interlocking system
CH springs charged indication contact Source 1 Source 2 Coupling
F1 auxiliary power supply circuit breaker 0 0 0
F2/F3 circuit breaker (high breaking capacity) 1 1 0
S1 control switches 1 0 1
S2 source selection switches 0 1 1
KA1 auxiliary relays with 10 to 180 sec. time delay 1 0 0
KA2 auxiliary relays with 0.1 to 30 sec. time delay
0 1 0
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay 0 0 1
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay Note:
KA7 auxiliary relays with 0.25 sec. time delay Diagram shown with circuit breakers in connected position,
open, charge.
Auxiliary power supply = supply voltage of auxiliary relays
(KA...) = supply voltage of electrical auxiliaries (MCH, MX,
MN...).

86
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Source-changeover system with BA controller
Coupling
selector
N R N
R
auto stop
23 22

14 13 16 15 11 12 10 9 5 7 6 8
1 3 5 1 3 5

Q1 Q2

2 4 6 2 4 6 Transfer conditions

ACP 2 N O L 17 18 20 21 R E 25

24 N O L 9 10 R E 25
N R if contact closed

voluntary transfer order


(e.g. for energy management)

24 N O L R E 25
Terminals 20 and 21:
stop
additional control contact
N (not part of controller).
23 22

R auto
17 18 20

BA
21

11 12 13 14 15 16 10 9 8 7 6 5

11 12 13 14 15 16

N
IVE
R

1 2 3 4 5 6 7 8 9 10

remove jumpers
for NS630b/1600 and
Masterpact NT/NW

Legends Tests on Normal and Replacement


Q1 : circuit breaker supplying and protecting the automatic-control circuits for the Normal source voltages
source The single-phase check for UN and UR is
Q2: circuit breaker supplying and protecting the automatic-control circuits for the implemented across terminals 1 and 5 of
Replacement source
ACP: auxiliaries control plate
circuit breakers Q1 and Q2.
BA: automatic controller
IVE: electrical interlocking and terminal block unit
Note:
Diagram shown with circuits de-energised, circuit breakers
open and relays in normal position.

87
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Source-changeover system with UA controller
Load shedding and genset management

selector load shedding generator


order start-up order
N
N R R
auto stop
23 22 27 26 28 30 29 31

14 13 16 15 11 12 10 9 5 7 6 8

1 3 5 1 3 5

Q1 Q2
Contacts shown with normal supply healthy; normal
2 4 6 2 4 6
breaker in ON position.

ACP
Transfer conditions

24 N O L 9 10 R E 25
24 N O L 17 18 20 21 R E 25
A
B
C
01

/ voltage
N
voir tableau contrle de A=0 1 phase control if contact closed
N R
la tension "Normal" UN A=1 3 phases control
EJP / voluntary
B=0 N=off fault voluntary transfer
B=1 N=on generator
24 N O L R E 25 C=0 t6=20s t max
stop C=1 t6=180s start generator
N
23 22

R auto
Terminals 20 and 21:
additional control contact
(not part of controller).
UA
17 18 20

Tests on Normal and Replacement


source voltages
Normal source voltage UN test
21

11 12 13 14 15 16 10 9 8 7 6 5

ref. UA 29472 29472 29473


ref. UA150 29474 29474 29475
supply
voltage N/ . / /
220/240VAC 220/240VAC 380/415VAC
switch
50/60Hz 50/60Hz 50/60Hz
position
440V - 60Hz

A=0
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3
11 12 13 14 15 16
Q1 Q1 Q1
N
IVE
R
A=1 1L1 3L2 5L3 1L1 3L2 5L3
1 2 3 4 5 6 7 8 9 10
Q1 Q1
enlever
pour NS630b/1600 et Replacement source voltage UR test
Masterpact NW
The single-phase check for UR is
implemented across terminals 1 and 5 of
circuit breaker Q2.

Legends Note:
Q1 : circuit breaker supplying and protecting the automatic-control circuits for the Normal Diagram shown with circuits de-energised, circuit breakers
source open and relays in normal position.
Q2: circuit breaker supplying and protecting the automatic-control circuits for the
Replacement source
ACP: auxiliaries control plate
UA: automatic controller
IVE: electrical interlocking and terminal block unit

88
Electrical diagrams Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NW devices
Controller settings Using communication functions

boucle COM
COM loop

24 N O L 17 18 20 21 R E 25 2
4 6
8

A
1
10
24 N O L 17 18 20 21 R E 25 2
4 6
8
12 1
B 14
5 A 10
C + 0v 24v 3 7
B 14
5
12
01 1 9 C + 0v 24v 3 7

24v 0v + 15
13
11 01 1 9

N / voltage 24v 0v + 15
13
11

N/ voltage
A=0 1 phase control N R
BBus
A=1 3 phase control if contact closed A=0 1 phase control N R
BBus
A=1 3 phase control if contact closed
EJP / voluntary transfer
EJP / voluntary transfer
B=0 N=off fault voluntary transfer
B=1 N=on generator B=0 N=off fault voluntary transfert
B=1 N=on generator
C=0 t6=20s t max
C=1 t6=180s start generator C=0 t6=20s t max
C=1 t6=180s start generator

The address of the UA controller is set


using the two BBus dials.
Tests on Normal source voltage

A=0 single-phase test,


A=1 three-phase test.
Voluntary transfer (e.g. for energy management)
c action in the event of genset failure
B = 0 circuit breaker N opens,
B = 1 circuit breaker N remains closed.
c maximum permissible genset startup time (T6)
C = 0 T = 120 s,
C = 1 T = 180 s.
After this time has elapsed, the genset is consid-
ered to have failed.

89
Electrical diagram Source-changeover systems
with automatic controllers
2 Masterpact NW devices
Diagram no. 51156903
Electrical interlocking with lockout after a fault

source management
N 1IA038

(3)
N R N
BA/UA controller
WH

VT

BK
GN
RD

for 2 devices
(3) N 1IA036
R

RD
WH

VT

BK
GN
(2)
252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44

(2)

252
254

312
314
C2
B3

B2

A2

82
84
12
14
22
24
32
34
42
44
CE1

CE1

QN OF1 OF2 OF3 OF4

SDE1
QR OF1 OF2 OF3 OF4
PF
SDE1

MCH
PF

CH
MX XF MCH

CH
MX XF
B1

C1

A1

251

81

11

21

31

41

311

(1) (2)
B1

C1

A1

251

81

11

21

31

41

311
GY

BN

YE

(1) (2)
GY

BN

YE

(1) Not to be wired for the without lockout after a fault solution
(2) Not to be wired on fixed version
(3) Prefabricated wiring supplied

Legends
QN Normal source Masterpact NW
QR Replacement source Masterpact NW
MCH spring-charging motor
MX standard opening voltage release
XF standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH springs charged indication contact
IVE electrical interlocking and terminal block unit

Wiring colour codes


States permitted by mechanical interlocking system
RD red Normal Replacement
GN green
0 0
BK black
VT violet 1 0
YE yellow 0 1
GY grey
WH white Note:
BN brown Diagram shown with circuit breakers in connected position,
open, charged, and ready to close.