P50 Agile P154 5 Configuration

2.3.8 Configuration menu

2.3.8.1 View / Edit settings


Password protected window for settings i.e.
CONFIGURATION
Restore Defaults, Active Settings, Copy From, Copy To, Setting Group 1
(Enabled/Disabled), Setting Group 2 (Enabled/Disabled), System Config
(Enabled/Disabled), Overcurrent (Enabled/Disabled), Neg Sequence
O/C (Enabled/Disabled), Broken Conductor (Enabled/Disabled), Earth
Fault 1 (Enabled/Disabled), Earth Fault 2 (Enabled/Disabled), Thermal
Overload (Enabled/Disabled), Cold Load Pickup (Enabled/Disabled),
Measuret Setup, UnderCurr Prot (Enabled/Disabled), CB Fail
(Enabled/Disabled) and Setting Values.

Editable setting
Restore Defaults
By using the (+ / ) or (- / ) key, can be set as No
No Operation Operation / All Settings / Setting Group 1 / Setting Group 2.

Editable setting
Active Settings
By using the (+ / ) or (- / ) key, can be set as Group 1
Group 1 / Group 2.

Editable setting
Copy From
By using the (+ / ) or (- / ) key, can be set as Group 1 /
Group 1 Group 2.

Editable setting
Copy To
By using the (+ / ) or (- / ) key, can be set as No Operation
No Operation / Group 1 / Group 2.

Editable setting
Setting Group 1
By using the (+ / ) or (- / ) key, can be Enabled or
Enabled Disabled.

Editable setting
Setting Group 2
By using the (+ / ) or (- / ) key, can be Enabled or
Disabled Disabled.

Editable setting
System Config
By using the (+ / ) or (- / ) key, can be
Disabled Enabled or Disabled.

P154/EN M/B 5-25


An evaluation version of novaPDF was used to create this PDF file.
Purchase a license to generate PDF files without this notice.
P50 Agile P154 5 Configuration

Editable setting
Overcurrent
By using the (+ / ) or (- / ) key, can be Enabled or
Enabled Disabled.

Editable setting
Neg Sequence O/C
By using the (+ / ) or (- / ) key, can be
Disabled Enabled or Disabled.

Editable setting
Broken Conductor
By using the (+ / ) or (- / ) key, can be Enabled
Disabled or Disabled.

Editable setting
Earth Fault 1
By using the (+ / ) or (- / ) key, can be Enabled or
Enabled Disabled.

Editable setting
Earth Fault 2
By using the (+ / ) or (- / ) key, can be Enabled or
Enabled Disabled.

Editable setting
Thermal Overload
By using the (+ / ) or (- / ) key, can be Enabled
Disabled or Disabled.

Editable setting
Cold Load Pickup
By using the (+ / ) or (- / ) key, can be Enabled or
Disabled Disabled.

Editable setting
Measuret setup
By using the (+ / ) or (- / ) key, can be set as
ABC ABC / RYB.

Editable setting
UnderCurr Prot
By using the (+ / ) or (- / ) key, can be
Disabled Enabled or Disabled.

P154/EN M/B 5-26


An evaluation version of novaPDF was used to create this PDF file.
Purchase a license to generate PDF files without this notice.
P50 Agile P154 5 Configuration

Editable setting
CB Fail
By using the (+ / ) or (- / ) key, can be Enabled or Disabled.
Disabled

Editable setting
Setting Values
By using the (+ / ) or (- / ) key, can be set as Primary
Secondary / Secondary.

2.3.9 Transformer Ratios menu

2.3.9.1 View / Edit settings


Password protected window for settings :
TRANS. RATIOS
Phase CT Primary, Phase CT Secondary, E/F CT Primary and E/F CT
Secondary.

Editable setting
Phase CT Primary
By using the (+ / ) or (- / ) key, can be set The
100 A setting range is from 1A to 30000A step 1A.

Editable setting
Phase CT Secy
By using the (+ / ) or (- / ) key, can be set as
1A 1A / 5A.

Editable setting
E/F CT Primary
By using the (+ / ) or (- / ) key, can be set The
100 A setting range is from 1A to 30000A step 1A.

Editable setting
E/F CT Secondary
By using the (+ / ) or (- / ) key, can be set as 1A /
1A 5A.

2.3.10 Record Control menu

2.3.10.1 View / Edit settings


Password protected window for settings :
RECORD CONTROL
Clear Events (Yes/No), Clear Faults (Yes/No), Clear Dist Recs (Yes/No),
Clear Maint (Yes/No), Thermal Reset (Yes/No).