Tank no.

1203
Safety Margin 0.71%
Pumping time 5 Pumped Volume 25 0.71%
safety marging
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 15
Overfill Level Mtr 20
Tankline diameter mm 300

Maximum in M3 300 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6

Dual linked Single linked ATG/ESV-A ATG HHLA LS-HA


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A or LS-HH/ESV-A
LS-HH/ESV-A

System type and reaction times


Valve closure type Auto Auto Auto Auto Remote Remote
Detect / sound level 1 1 1 1 1 1
alarm
T1 LS-HH or linked 0 0 0 0
HHLA
Travel to 0 0 0 0 2 2
valve/initiate closure

Close Valve or stop 1 1 1 1 2 2


flow
Total T1 2 2 2 2 5 5

Valve closure type Remote Remote Remote Remote Remote Manual


Detect / sound level 1 1 1 1 N/A N/A
alarm
T2 Validate HHLA 0 7 0 7 N/A N/A
Travel to 2 2 2 2 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 2 N/A N/A


flow
Total T2 5 12 5 12 N/A N/A

Valve closure type Remote Remote N/A N/A N/A N/A


Detect / sound level 1 1 N/A N/A N/A N/A
alarm
T3 Validate HLA 7 7 N/A N/A N/A N/A
Travel to 2 2 N/A N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 N/A N/A N/A N/A


flow
Total T3 12 12 N/A N/A N/A N/A

Response time T1 Min 2 2 2 2 5 5


LS-HH - Overfill

Response time T2 Min 5 12 5 15 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 N/A N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3533 3533 3533 3533 3533 3533
Capacity
Max pipe flow limit m3/hr 1781.514 1781.514 1781.514 1781.514 1781.514 1781.514
at 7m/s
permitted tank m3/hr 300 300 300 300 300 300
inflow
Maximum rate of cm/min 2.8 2.8 2.8 2.8 2.8 2.8
liquid rise
Ltr/mm ltr 176.6 176.6 176.6 176.6 176.6 176.6

Alarm Set point


Overfill Level 19.858 19.858(metres above floor19.858
datum) 19.858 19.858 19.858
including safety
Margin
LS-HH 19.802 19.802 19.802 19.802 19.717 19.717
HHLA 19.660 19.462 19.660 19.377 N/A N/A
HLA 19.321 19.122 N/A N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.01% 99.01% 99.01% 99.01% 98.58% 98.58%
HHLA 98.30% 97.31% 98.30% 96.89% N/A N/A
HLA 96.60% 95.61% N/A N/A N/A N/A

Permitted fill 97.30% 96.31% 97.30% 95.89% 97.58% 97.58%


Altura
Overfill
pared tk a Altura Diferencia Distancia Altura de
Radio Altura parte Level Permitted Permitted Altura de Altura Longitud
Dimetro Radio Angulo Altura total Nivel de parte segura altura tablas Volumen pared a envolvent Longitud
Tanque cpula inferior including LS-HH HHLA HLA fill level fill level Ltr/mm envolvent boquilla REAL LS-
nominal nominal cpula pared tanque Overfill inferior llenado vs permitted restado boquilla e a cupula LS-HH
(cnico) boquilla CE safety % m e a LS-HH LS-HH HH
boquilla Tablas fill level LS-HH LS-HH
Margin
CE
1 18.288 9.144 12.192 12.192 0.500 11.692 11.22 12.097 12.052 11.875 11.697 94.94% 11.575 -0.36 262.68 -93.82 1.00 0.14 0.15 0.22 0.510 700

Alarma PC y disparo manual 700


Alarma sonora ( Parte inferior de boquilla camara espuma) 1.6
Cierre ESV-A por overfill 1.6
3
694
Tank no. TK-01 Nytro 11 GBX US
Safety Margin 0.78%
Pumping time 5
safety marging Pumped Volume 25.00 0.78%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 12.192
Tankline diameter mm 254 LINEA 10"

Maximum in M3 350 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-01

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3203 3203 3203 3203 3203 3203
Capacity
Max pipe flow limit m3/hr 1277.07 1277.07 1277.07 1277.07 1277.07 1277.07
at 7m/s
permitted tank m3/hr 350 350 350 350 350 350
inflow
Maximum rate of cm/min 2.2 2.2 2.2 2.2 2.2 2.2
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 12.097 12.097(metres above floor12.097
datum) 12.097 12.097 12.097
including safety
Margin
LS-HH 12.052 12.052 12.052 12.097 12.097 12.097
HHLA 11.941 11.786 11.875 12.097 N/A N/A
HLA 11.675 11.519 11.697 N/A N/A N/A
Filling Ratios
Overfill including 99.22% 99.22% 99.22% 99.22% 99.22% 99.22%
SM
LS-HH ( or LS-HA) 98.86% 98.86% 98.86% 99.22% 99.22% 99.22%
HHLA 97.94% 96.67% 97.40% 99.22% N/A N/A
HLA 95.76% 94.48% 95.94% N/A N/A N/A

Permitted fill 96.94% 93.48% 94.94% 98.22% 98.22% 98.22%


Calculation area - normally hidden
Manual Manual
Remote Remote
TK-01 TK-01 TK-01 TK-01 TK-01 TK-01
18.288 18.288 18.288 18.288 18.288 18.288
12.192 12.192 12.192 12.192 12.192 12.192
350 350 350 350 350 350
254 254 254 254 254 254
Tank no. TK-02 TOLUENO
Safety Margin 0.78%
Pumping time 5
safety marging Pumped Volume 25.00 0.78%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 12.192
Tankline diameter mm 254 LINEA 10"

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-02

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3203 3203 3203 3203 3203 3203
Capacity
Max pipe flow limit m3/hr 1277.07 1277.07 1277.07 1277.07 1277.07 1277.07
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 12.097 (metres above floor12.097
12.097 datum) 12.097 12.097 12.097
including safety
Margin
LS-HH 12.065 12.065 12.065 12.097 12.097 12.097
HHLA 11.986 11.875 11.938 12.097 N/A N/A
HLA 11.795 11.684 11.811 N/A N/A N/A
Filling Ratios
Overfill including 99.22% 99.22% 99.22% 99.22% 99.22% 99.22%
SM
LS-HH ( or LS-HA) 98.96% 98.96% 98.96% 99.22% 99.22% 99.22%
HHLA 98.31% 97.40% 97.92% 99.22% N/A N/A
HLA 96.75% 95.84% 96.88% N/A N/A N/A

Permitted fill 97.31% 94.84% 95.88% 98.22% 98.22% 98.22%


Tank no. TK-03 2 ETILHEXANOL
Safety Margin 0.78%
Pumping time 5
safety marging Pumped Volume 25.00 0.78%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 12.192
Tankline diameter mm 254 LINEA 10"

Maximum in M3 350 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-03

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3203 3203 3203 3203 3203 3203
Capacity
Max pipe flow limit m3/hr 1277.07 1277.07 1277.07 1277.07 1277.07 1277.07
at 7m/s
permitted tank m3/hr 350 350 350 350 350 350
inflow
Maximum rate of cm/min 2.2 2.2 2.2 2.2 2.2 2.2
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 12.097 (metres above floor12.097
12.097 datum) 12.097 12.097 12.097
including safety
Margin
LS-HH 12.052 12.052 12.052 12.097 12.097 12.097
HHLA 11.941 11.786 11.875 12.097 N/A N/A
HLA 11.675 11.519 11.697 N/A N/A N/A
Filling Ratios
Overfill including 99.22% 99.22% 99.22% 99.22% 99.22% 99.22%
SM
LS-HH ( or LS-HA) 98.86% 98.86% 98.86% 99.22% 99.22% 99.22%
HHLA 97.94% 96.67% 97.40% 99.22% N/A N/A
HLA 95.76% 94.48% 95.94% N/A N/A N/A

Permitted fill 96.94% 93.48% 94.94% 98.22% 98.22% 98.22%


Tank no. TK-04 Nytro 11 GBX US
Safety Margin 0.78%
Pumping time 5
safety marging Pumped Volume 25.00 0.78%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 12.192
Tankline diameter mm 254 LINEA 10"

Maximum in M3 350 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-04

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3203 3203 3203 3203 3203 3203
Capacity
Max pipe flow limit m3/hr 1277.07 1277.07 1277.07 1277.07 1277.07 1277.07
at 7m/s
permitted tank m3/hr 350 350 350 350 350 350
inflow
Maximum rate of cm/min 2.2 2.2 2.2 2.2 2.2 2.2
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 12.097 (metres above floor12.097
12.097 datum) 12.097 12.097 12.097
including safety
Margin
LS-HH 12.052 12.052 12.052 12.097 12.097 12.097
HHLA 11.941 11.786 11.875 12.097 N/A N/A
HLA 11.675 11.519 11.697 N/A N/A N/A
Filling Ratios
Overfill including 99.22% 99.22% 99.22% 99.22% 99.22% 99.22%
SM
LS-HH ( or LS-HA) 98.86% 98.86% 98.86% 99.22% 99.22% 99.22%
HHLA 97.94% 96.67% 97.40% 99.22% N/A N/A
HLA 95.76% 94.48% 95.94% N/A N/A N/A

Permitted fill 96.94% 93.48% 94.94% 98.22% 98.22% 98.22%


Tank no. TK-05 MEG
Safety Margin 0.78%
Pumping time 5
safety marging Pumped Volume 25.00 0.78%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 12.192
Tankline diameter mm 203 LINEA 8"

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-05

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3203 3203 3203 3203 3203 3203
Capacity
Max pipe flow limit m3/hr 815.72 815.72 815.72 815.72 815.72 815.72
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 12.097 (metres above floor12.097
12.097 datum) 12.097 12.097 12.097
including safety
Margin
LS-HH 12.065 12.065 12.065 12.097 12.097 12.097
HHLA 11.986 11.875 11.938 12.097 N/A N/A
HLA 11.795 11.684 11.811 N/A N/A N/A
Filling Ratios
Overfill including 99.22% 99.22% 99.22% 99.22% 99.22% 99.22%
SM
LS-HH ( or LS-HA) 98.96% 98.96% 98.96% 99.22% 99.22% 99.22%
HHLA 98.31% 97.40% 97.92% 99.22% N/A N/A
HLA 96.75% 95.84% 96.88% N/A N/A N/A

Permitted fill 97.31% 94.84% 95.88% 98.22% 98.22% 98.22%


Tank no. 7 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-7

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 8d MEG
Safety Margin 2.63%
Pumping time 5
safety marging Pumped Volume 25.00 2.63%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 9.500
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-8D

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 949 949 949 949 949 949
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 5.9 5.9 5.9 5.9 5.9 5.9
liquid rise
Ltr/mm ltr 70.9 70.9 70.9 70.9 70.9 70.9

Alarm Set point


Overfill Level 13.041 (metres above floor13.041
13.041 datum) 13.041 13.041 13.041
including safety
Margin
LS-HH 12.924 12.924 12.924 13.041 13.041 13.041
HHLA 12.630 12.218 12.453 13.041 N/A N/A
HLA 11.924 11.513 11.983 N/A N/A N/A
Filling Ratios
Overfill including 97.37% 97.37% 97.37% 97.37% 97.37% 97.37%
SM
LS-HH ( or LS-HA) 96.49% 96.49% 96.49% 97.37% 97.37% 97.37%
HHLA 94.29% 91.22% 92.98% 97.37% N/A N/A
HLA 89.03% 85.96% 89.47% N/A N/A N/A

Permitted fill 93.29% 84.96% 88.47% 96.37% 96.37% 96.37%


Tank no. 10 MEG
Safety Margin 0.70%
Pumping time 5
safety marging Pumped Volume 25.00 0.70%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.55
Tankline diameter mm 152

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-10

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3559 3559 3559 3559 3559 3559
Capacity
Max pipe flow limit m3/hr 457.33 457.33 457.33 457.33 457.33 457.33
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.455 (metres above floor13.455
13.455 datum) 13.455 13.455 13.455
including safety
Margin
LS-HH 13.423 13.423 13.423 13.455 13.455 13.455
HHLA 13.344 13.233 13.296 13.455 N/A N/A
HLA 13.153 13.042 13.169 N/A N/A N/A
Filling Ratios
Overfill including 99.30% 99.30% 99.30% 99.30% 99.30% 99.30%
SM
LS-HH ( or LS-HA) 99.06% 99.06% 99.06% 99.30% 99.30% 99.30%
HHLA 98.48% 97.66% 98.13% 99.30% N/A N/A
HLA 97.07% 96.25% 97.19% N/A N/A N/A

Permitted fill 97.48% 95.25% 96.19% 98.30% 98.30% 98.30%


Tank no. 32 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-32

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 35 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-7

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 36 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-36

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 41 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-41

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 50 AC 2500
Safety Margin 1.02%
Pumping time 5
safety marging Pumped Volume 25.00 1.02%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 13.567
Overfill Level Mtr 16.927
Tankline diameter mm 150

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-50

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 2447 2447 2447 2447 2447 2447
Capacity
Max pipe flow limit m3/hr 445.38 445.38 445.38 445.38 445.38 445.38
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 2.9 2.9 2.9 2.9 2.9 2.9
liquid rise
Ltr/mm ltr 144.6 144.6 144.6 144.6 144.6 144.6

Alarm Set point


Overfill Level 16.754 (metres above floor16.754
16.754 datum) 16.754 16.754 16.754
including safety
Margin
LS-HH 16.696 16.696 16.696 16.754 16.754 16.754
HHLA 16.552 16.351 16.466 16.754 N/A N/A
HLA 16.206 16.005 16.235 N/A N/A N/A
Filling Ratios
Overfill including 98.98% 98.98% 98.98% 98.98% 98.98% 98.98%
SM
LS-HH ( or LS-HA) 98.64% 98.64% 98.64% 98.98% 98.98% 98.98%
HHLA 97.79% 96.59% 97.28% 98.98% N/A N/A
HLA 95.74% 94.55% 95.91% N/A N/A N/A

Permitted fill 96.79% 93.55% 94.91% 97.98% 97.98% 97.98%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%


Tank no. 42 MEG
Safety Margin 0.71%
Pumping time 5
safety marging Pumped Volume 25.00 0.71%
Expansion Factor 1.00% This is the % below HHLA to prevent nuisance alarms
from expansion
Diameter Mtr 18.288
Overfill Level Mtr 13.394
Tankline diameter mm 250

Maximum in M3 250 OK- Pumping rate below 7 m/s & acceptable


pumping rate

Over Fill Type


Figure 1 Figure 2 TK-42

Dual linked Single linked Single linked


ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A ATG & LS-HH & ESV-A
LOCAL TIMES
System type and reaction times
Valve closure type Auto Auto Auto
Detect / sound level 1 1 1
alarm
LS-HH or linked 0 0 0
T1 HHLA
Travel to 0 0 0
valve/initiate closure

Close Valve or stop 1 1 1


flow
Total T1 2 2 2 0 0 0

Valve closure type Remote Manual Manual


Detect / sound level 1 1 1 N/A
alarm
Validate HHLA 0 7 2 N/A N/A
T2 Travel to 2 2 3 N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A


flow
Total T2 5 12 8 0 N/A N/A

Valve closure type Remote Manual Remote N/A N/A N/A


Detect / sound level 1 1 1 N/A N/A N/A
alarm
Validate HLA 7 5 2 N/A N/A N/A
T3 Travel to 2 4 3 N/A N/A N/A
valve/initiate closure

Close Valve or stop 2 2 2 N/A N/A N/A


flow
Total T3 12 12 8 N/A N/A N/A

Response time T1 Min 2 2 2 0 0 0


LS-HH - Overfill

Response time T2 Min 5 12 8 N/A N/A


HHLA - LS-HH
Response time T3 Min 12 12 8 N/A N/A N/A
HLA - HHLA
Calculated Cells
Tank Rated M3 3518 3518 3518 3518 3518 3518
Capacity
Max pipe flow limit m3/hr 1237.16 1237.16 1237.16 1237.16 1237.16 1237.16
at 7m/s
permitted tank m3/hr 250 250 250 250 250 250
inflow
Maximum rate of cm/min 1.6 1.6 1.6 1.6 1.6 1.6
liquid rise
Ltr/mm ltr 262.7 262.7 262.7 262.7 262.7 262.7

Alarm Set point


Overfill Level 13.299 (metres above floor13.299
13.299 datum) 13.299 13.299 13.299
including safety
Margin
LS-HH 13.267 13.267 13.267 13.299 13.299 13.299
HHLA 13.188 13.077 13.140 13.299 N/A N/A
HLA 12.997 12.886 13.013 N/A N/A N/A
Filling Ratios
Overfill including 99.29% 99.29% 99.29% 99.29% 99.29% 99.29%
SM
LS-HH ( or LS-HA) 99.05% 99.05% 99.05% 99.29% 99.29% 99.29%
HHLA 98.46% 97.63% 98.11% 99.29% N/A N/A
HLA 97.04% 96.21% 97.16% N/A N/A N/A

Permitted fill 97.46% 95.21% 96.16% 98.29% 98.29% 98.29%