Академический Документы
Профессиональный Документы
Культура Документы
CLASS 2
STATUS CODE : A = Issued for comments B = Issued for approval C = Approved D = As Built
TABLE OF CONTENTS
3. INTRINSICALLY SAFE HEAT DETECTOR DT1101A-EX & SMOKE DETECTOR DO1101A-EX 102
8. RESISTOR 125
5 / 125
Model IR2100
Warranty Statement
General Monitors warrants the Model IR2100 to be free from defects in workmanship
or material under normal use and service within two (2) years from the date of
shipment. General Monitors will repair or replace without charge any such defective
equipment found to be defective during the warranty period. Full determination of the
nature of, and responsibility for, defective equipment will be made by General
Monitors personnel. Defective or damaged equipment must be shipped prepaid to
General Monitors plant or representative from which shipment was made. In all cases
this warranty is limited to the cost of the equipment supplied by General Monitors. The
customer will assume all liability for the misuse of this equipment by its employees or
other personnel.
All warranties are contingent upon proper use in the application for which the product
was intended and do not cover products which have been modified or repaired without
General Monitors approval, or which have been subjected to neglect, accident,
improper installation or application, or on which the original identification marks have
been removed or altered. Except for the express warranty stated above, General
Monitors disclaims all warranties with regard to the products sold, including all implied
warranties of merchantability and fitness and the express warranty stated herein are
in lieu of all obligations or liabilities on the part of General Monitors for damages
including, but not limited to, consequential damages arising out of/or in connection
with the use or performance of the product.
Warnings
The Model IR2100 Point IR Detector contains components which can be damaged by
static electricity. Special care must be taken when wiring the system to ensure that
only the connection points are touched.
The Zero Switch must be supplied from apparatus which provides protection against
short circuit currents of up to 4000A.
Note on Methane EU Gas: Users should be aware that these instruments may have
100% LEL of 4.4% by Volume. Methane Calibration level is
2.2% by Volume. See Section 2.4 for Unit part#s
ii
6 / 125
Model IR2100
A Technical Construction File No. GM 97003 and Competent Body Report No. 4473/1L6/1
and
b) Conforms with the protection requirements of IEC 1010-1: 1990 + Amd 1:1992 +Amd 2: 1995
relating to safety by the application of:
A Technical Construction File No. GM 97003 and Competent Body Certificate No. 4146/1198/9684
issued by:
ERA Technology Ltd. Cleeve Road, Leatherhead Surrey KT22 7SA, England. Tel: +44 1372 367000
This declaration shall cease to be valid if modifications are made to the equipment without our approval.
It is ensured through internal measures and our ISO9001: 2000 certifications, that series production
units conform at all times to the requirements of these current EC Directives and relevant standards.
II 2 G Demko 01.ATEX.130840
Model: IR2100
Denis Connolly
General Manager European Operations
The signatory acts on behalf of company management, and with full power of attorney
iii
7 / 125
Model IR2100
Table of Contents
Page
Warranty Statement ................................................................................................... ii
Warnings ................................................................................................... ii
Table of Contents .................................................................................................. iv
Table of Figures ................................................................................................... v
8 / 125
Model IR2100
Table of Figures
Figure 1 Model IR2100 Picture...........................................................................................1
Figure 8 EExe Duct Mount Junction Box and IR2100 Assembly ...................................... 17
9 / 125
Model IR2100
1.0 Introduction
1.1 General Description
The Model IR2100 Infrared Point Detector is a microprocessor based hydrocarbon gas
detector. The General Monitors Model IR2100 is calibrated at the factory and needs no
routine field calibration. The sensitivity of the Model IR2100 can be checked by applying a
test film when the unit is placed in the Calibration Check mode. It is also relatively
maintenance free, requiring only a periodic cleaning of the windows to assure dependable
performance.
The Model IR2100 Infrared Point Detector continuously monitors combustible gases below
the Lower Explosion Level (LEL) range* and provides a 4 to 20mA analogue signal
proportional to the 0-100% LEL concentration it detects along with a digital RS485 output,
allowing unit to be addressable via Modbus Protocol.
Sensor data and status information for the Model IR2100 can be transmitted to a variety of
General Monitors readout units.
The Model IR2100 Infrared Point Detector operates from a nominal + 24VDC CE marked
supply which must be supplied by the customer.
The Model IR2100 may be mounted in a stand alone Junction Box, or Junction Box to
ducting via Duct Mounting Plate. A Zero Switch maybe fitted into this Junction Box. The
IR2100 may also be connected to the following:
Field Mounted Display TA102A S4100E
* - or in Methane % by volume range, in which case all references to 0 to 100% LEL should
be read as 0 to 100% by volume.
Figure 1
10 / 125
Model IR2100
This is a partial list of features and benefits for the Model IR2100 Infrared Point Detector:
1.3 Applications
This is a partial list of applications suitable for the Model IR2100 Infrared Point Detector:
11 / 125
Model IR2100
2.0 Specifications
2.1 System Specifications
Readout Module: TA102A Single Channel, Zero Two Series, Rev E S/W and up.
Malfunctions Monitored
Re-calibration Error
EPROM Checksum Error
Optics Failure/Blockage
Low Supply Voltage
EEPROM Checksum Error
Heater Failure
Time to Re-Zero unit
Open Analogue Output Loop
Reference or Active Lamp Failure
Response Time
With 100% LEL* Methane Applied
T50 7 seconds & T90 10 seconds
* - also read as 0 to 100% by volume
Approvals
CSA (Class 1, Division I, Groups B, C & D),
CSA Certified to C22.2 No. 152-M1984*
ATEX (EExd IIB + H2 T5) & CE Marking
12 / 125
Model IR2100
Electrical Classification:
Class I, Division 1, Groups B, C and D
EExd, IIB+H2 T5
Power:
24 VDC @ 0.4 amp (nominal)
20 to 36 VDC range
NOTE: PSU noise and ripple voltage 1V pk/pk max.
Customer supplied PSU must meet requirements
IEC 1010-1 limiting current to 8A under Fault
conditions, in order to comply with CE Marking
requirements.
Power - The maximum distance between the IR2100 and the Power Source varies
according to the wire size. (10 ohm loop resistance at 24 VDC)
Analogue Output Signal - The maximum total distance between the IR2100 and a device
with a 300 ohm input impedance varies according to the wire size.
13 / 125
Model IR2100
EMC Protection:
Complies with EN50082/2:1995) 10V/m max.
Note: Compliance with EMC Directive 89/336/EEC is only valid for environments
corresponding with the test standards EN50081-1:1992 and EN50082-2:1995
14 / 125
Model IR2100
Most gases absorb infrared radiation in specific wavelengths or bands that are
characteristic of the chemical structure of molecules in the gas. All hydrocarbon gases
absorb infrared radiation, but to differing degrees. Gases, to be infrared active, must have
an electric dipole moment.
The Model IR2100 is based on measuring absorption of infrared radiation passing through
a volume of gas. Absorption of the radiation follows the Beer-Lambert Law, which states
the transmittance T of radiation through an absorbing medium decreases exponentially by
the product of the extinction coefficient A, the concentration C and the path length L :
T = exp (-ACL)
The Model IR2100 uses a single beam,dual source, single detector measurement
absorption method. One source is optimised to a wavelength where absorption of a
specific gas (or gases) occurs (the active wavelength). The reference source is optimised
to a wavelength that is adjacent to the active wavelength but not absorbed by the gas (or
gases). By comparing the signals from these two sources the concentration of the gas can
be measured using the differential absorption technique.
This method of gas detection comes under what is commonly known as the non-dispersive
infrared (NDIR) absorption principle. The reference wavelength is chosen suitable to
compensate for any interference that can otherwise occur from atmospheric variation (e.g.
humidity, dust, snow, fog, steam, temperature, etc.).
The Model IR2100 operates from a customer supplied, CE Marked nominal +24VDC
(nominal) input, which is fed to an on board power-supply that produces all of the
necessary voltages within the unit.
The microprocessor generates output information and feeds it to the digital to analogue
converter to produce a 4 to 20 milliampere (mA) signal that is
proportional to the 0 to 100% LEL concentration of gas at the sensor. The microprocessor
program also monitors other conditions such as the supply voltage and the optical path
integrity.
The Model IR2100 also provides a two-wire RS485 addressable communications link
conforming to the Modbus Protocol that is used to monitor the IR2100s status and settings
in order to simplify installation and maintenance and can be used to monitor the units
status, or change the detection gas requirements.
The Model IR2100 can be configured to simulate a Wheat stone bridge output instead of
the 4-20 mA signal, which enables the unit to be retrofitted to an existing General
Monitors smart sensor. Contact the Factory for details.
15 / 125
Model IR2100
4.0 Installation
4.1 Receipt of Equipment
Each Model IR2100 is completely tested by the factory, however, a complete system
checkout is suggested upon initial installation and start-up to ensure system integrity.
Note: The Model IR2100 is factory set against the particular gas ordered by the Customer.
Where no gas is specified, Methane (CH4) is the factory standard. The unit may be
changed to detect another gas via RS485 comms link or by returning to General Monitors
Representative or the Factory.The gasses the unit can be changed to are:
Methane, Propane, Ethane, Hexane, n-Butane, Pentane and Methane 100% Volume.
NOTE: The indications shown in the table for cross sensitivity to other gasses is only a
guide as General Monitors recommends the unit should be calibrated for the specific gas.
Calibration Gas %LEL Methane Propane Ethane Hexane n-Butane Pentane % Vol CH4
methane 50 LEL 50 99 188 40 88 72 317
propane 50 LEL 25 50 94 20 44 36 159
There are no standard rules for detector placement, since the optimum detector location
varies with the application. The customer must evaluate conditions at the facility to make
this determination. If practical, the Model IR2100 Infrared Point Detector should be easily
accessible for occasional integrity checks. The unit should be mounted horizontally so that
dirt and dust do not build up on the windows. Although the Model IR2100 Infrared Point
Detector is RFI resistant, it should not be mounted close to radio transmitters or similar
equipment.
16 / 125
Model IR2100
The Model is not affected by typical environmental poisons (but see note below) and is
suitable for use in an O2 deficient area.
The baffle design also ensures that gas readings are immune to air velocity, wind etc.
Note: Acetic acid will cause damage to metal components, metal hardware, ceramics ICs
etc. If damage results from the use of a sealant that outgases acetic acid (RTV silicone),
the normal two year warranty will be void.
The Model IR2100 should be mounted horizontally (see Figure 3) to reduce the likelihood
of dirt and dust build-up on the windows. For optimum performance, the splashguards
should be located on the top and bottom as shown in Figure 3. Apply the supplied thread
lubricant/sealant to all conduit entries before use to prevent binding.
To make the power and analogue connections to the Model IR2100 Infrared Point
Detector, see below:
WIRING CHART
WIRE COLOR SIGNAL
BLACK COM (0 Volts)
GREEN FG (Earth Terminal)
RED +24V
WHITE 4-20mA
BLUE CBUSS+
WHT/BLU CBUSS-
BROWN CAL
Figure 2
The Model IR2100 Infrared Point Detector operates on nominal power of 24VDC which
must be provided by the customer, and shall be CE marked, meeting safety requirements
of IEC 10101-1. Since the Model IR2100 Infrared Point Detector is designed to
continuously monitor for leaks of hydrocarbon gas, a power switch is not included to
prevent accidental system shut down.
NOTE: Power should remain disconnected until all other wiring connections are
made.
The maximum distance between the Model IR2100 and the power source is specified in
the Appendix (see Section 2.3)
Power Connections
To connect the +24VDC to the Model IR2100 use the red lead from the IR2100 and
connect to the +24VDC source. Connect the black lead from the IR2100 to the power
supply Common. Refer to the manual of the power source being used, for more detailed
instructions. This customer supplied power supply must comply with IEC 1010-1 for CE
Marking compliance.
17 / 125
Model IR2100
NOTE: If the Model IR2100 is being used with a +24V power supply and an industrial
analogue to digital (A/D) converter, then the negative supply (Common) of all three must
be connected.
Figure 3
An internal diode protects the system in the event of inadvertent supply reversal.
4- 20mA Output
A 4 to 20mA output signal is provided by the Model IR2100 and can be sent to a General
Monitors read-out/relay display module or any industrial device that can accept a 4 to
20mA signal, for computer based multi-point monitoring. The Analogue
Output connection provides a signal for use in displaying current LEL readings, special
operation or fault conditions. The maximum distance between the Model IR2100 and the
device connected to the Analogue Output Signal is specified in the Appendix.
Connect the white lead from the IR2100, to the signal in terminal of the input unit (display
module)
Connect the black lead from the IR2100, to the device Common. The Common connection
serves both the Analogue Signal and the Power connections.
The Green lead from the IR2100 can be connected to Earth stud, (or Safety Earth) on
Junction Box, which is in turn connected to cable armour.
To connect the RS485 output, the blue lead from the IR2100 is connected to the RS485
BUSS+ terminal and the blue/white lead is connected to the RS485 BUSS-terminal on the
customers RS485 capable device.
18 / 125
Model IR2100
The interconnecting cables must have an overall screen and armour. Cables to BS5308
Part 2 or equivalent are suitable. Note that the terms screen and shield are equivalent for
the purpose of this manual. The cable armour must be terminated in a suitable cable gland
at the detector to ensure a positive electrical connection. The Green wire from Model
IR2100 should be connected to Earth stud on continuity plate of GM housing or to internal
Earthing point if using a non-GM Junction Box.
General Monitors do not recommend the use of cable shoes or crimps on any junction box
or housing wiring terminals. Poor crimping can cause bad connection when unit
experiences temperature variations. We therefore would recommend the following:
The cable armour must be connected to safety earth in the safe area.
The cable screen (drain wire) must be connected to an instrument earth in the safe
area.
The power supply OV return must be connected to an instrument earth in the safe
area.
The interconnecting cables should be segregated from power and other noisy
cables. Avoid proximity to cables associated with radio transmitters, welders, switch
mode power supplies, inverters, battery chargers, ignition systems, generators, high
power switching process equipment. Avoid running instrument cable trenches close
to lightning conductor earthing pits.
Complete all cable insulation testing before connecting the cable at either end.
10
19 / 125
Model IR2100
Figure 4
WARNING
Under no circumstances should equipment be connected or disconnected when
under power. This is contrary to hazardous area regulations and may lead to
serious damage to the equipment. Equipment damaged in this manner is not
covered under warranty.
Before applying power to the system for the first time, all wiring connections should be
checked for correctness. Upon initial power-up or after a fault condition has been
corrected, the unit will enter a start-up mode for 120 seconds before returning to normal
operation (Analogue output will be 0 mA).
After power is applied, the Model IR2100 should be allowed to stabilize for approximately
60 minutes while the unit attains its proper operating temperature.
After stabilization, it is recommended that the Model IR2100 be zeroed, per the procedure
in Section 5.1 (step 1 only). A gas check should then be performed to ensure that the unit
is operating properly. Use the General Monitors Gas Check Kit (P/N 31468) to perform this
check. If the unit does not respond properly, calibrate per the procedure in Section 4.1
(steps 1-4).
a) When connecting the Model IR2100 to a safety system, the +24V (Red) wire should be
the last wire connected and first wire disconnected when removing unit to protect the
system from shorting.
B) If the analogue (4-20 mA) output is not used, then the white signal wire must be
connected to ground to prevent a fault condition.
Note: Where customer requires unit to detect a different gas from that which unit has been
factory calibrated to, then the IR2100 must be re-calibrated by General Monitors personnel
or authorised representatives.
11
20 / 125
Model IR2100
5.0 Operation
5.1 Zeroing of IR2100
The Model IR2100 also provides a lead for the connection of a +24VDC powered EExd
approved magnetic switch. This switch is available in 316 Stainless Steel with an M20
thread. The switch can be fitted to a General Monitors supplied Junction Box.
Special conditions for safe use of General Monitors Ex. Approved Zero Switch
The Zero Switch, where used, must be mounted in a suitably certified enclosure or
enclosure wall, and its flying leads terminated at Ex e terminals, also within a
suitably certified enclosure.
The electrical supply to the Zero Switch must not exceed the following values:
The Zero Switch must be supplied from apparatus which provides protection against short
circuit currents of up to 4000A.
The Brown lead from the IR2100 is connected to the powered side of the switch so that
Brown lead is grounded when switch is activated via magnet.
1. Apply the General Monitors magnet, which was included with the unit, to the Magnetic
switch Assembly for approximately three seconds. The LED in the switch will light to
show proper placement. Remove the magnet and the LED will flash on for one second
and off for one second to indicate that the unit is attaining a zero value.
2. When the unit has finished zeroing, the LED will turn on and flash off quickly once per
second for 30 seconds. If a complete gas check is required, apply the magnet and the
unit will enter gas check mode (if the magnet is not applied, the unit will return to
normal operation). The LED will flash off quickly once every half second while the unit
is waiting for gas to be applied.
3. Apply 50% LEL* calibration gas. When the unit is seeing gas, the LED will flash on for
a half second every one and one-half seconds.
4. Once gas check has been completed, the LED will turn on and flash off once every
second. Remove the gas and the unit will return to normal operation once the gas has
fallen below 5% LEL.
* or 50% and 5% by volume for those units specifically designed for monitoring 0 to
100% by volume.
Note on Methane EU Gas: Users should be aware that these instruments may have
100% LEL of 4.4% by Volume. Methane Calibration level is
2.2% by Volume. See Section 2.4 for Unit part#s
12
21 / 125
Model IR2100
Figure 5
5.2 Maintenance
Although the Model IR2100 is calibrated at the factory and fails-to-safe, periodic cleaning
and integrity tests are required to ensure proper operation. The windows should be
cleaned by gently wiping them with a soft, clean cloth, which has a cleaning solution (P/N
10272-1) applied. Integrity checks can be performed using the General Monitors Gas
Check Kit (P/N 31468).
General Monitors recommends that a maintenance logbook be kept for each unit in
operation. Since maintenance requirements will vary with each installation, this
maintenance record will help to develop an efficient schedule for periodic maintenance.
NOTE: Gassing into the screened splashguard will not provide a stable or accurate
reading.
Warning - Do not clean the windows while the unit is zeroing or in recalibration mode.
The unit must be re-zeroed after the windows have been cleaned.
If an optical fault still occurs after cleaning and re-zeroing is complete, the unit must be
returned to the factory for service. The reverse is also the case.
13
22 / 125
Model IR2100
5.3 Communications
The Model IR2100 has built-in serial communications in the form of a half- duplex RS- 485
digital serial interface designed to conform with EIA-485 specifications.
The format is in binary data transferred at 9600 baud with 1 start bit, 8 data bits, 1 stop bit
and no parity.
General Monitors has available a Windows-based program that allows the user to
configure the IR2100 for use in their facility. The customer must provide access to the RS-
485 bus by way of a PLC or other controlling device (bus master) with communications
software programmed to provide the following information to the Model IR2100.
The bus master sends a command message to the Model IR2100, which is comprised of
5 bytes of data in the following for mat. The first byte is the address of the slave device
(IR2100). The second byte is the Command Word (see page 18). The third byte is the
Command Data. The last two bytes are a 16-bit checksum calculated by performing a 16-
bit addition of the first three bytes of the message and placing the result in the check sum
bytes.
A 1" in the most significant bit of the Command Word (byte 2), tells the Model IR2100 to
change its settings to those given in the Command Data (byte 3).
A 0" in the most significant bit of the Command Word (byte 2), tells the Model IR2100 to
return its current settings. In this case the Command Data (byte 3) will be all 0s.
The Model IR2100 then responds by sending back a 5-byte message in the following
format. The first byte is the address of the Model IR2100. The second byte is an echo of
the Command Word sent by the bus master. The third byte is
the data requested by the Command Word. The last two bytes are the 16- bit check sum.
NOTE: Users not using RS485 bus on installed IR2100s cannot change detection gas
without returning unit to GM Factory or local Representative.
14
23 / 125
Model IR2100
6.0 Appendix A
6.1 Engineering Documentation
Figure 6
15
24 / 125
Model IR2100
Figure 7
16
25 / 125
Model IR2100
Figure 8
17
26 / 125
Model IR2100
To order spare parts and/or accessories, please contact your nearest General Monitors
Representative or General Monitors directly and give the following information:
1 Part Number
2 Description
3 Quantity
Manual, MANIR2100
Accessories:
Junction Box - Housing used to accommodate field wiring terminals and zero switch.
ATEX (P/N 31421-4)
Flow Block (P/N 31420-1) - Used to connect the IR2100 to a gas sampling system.
Splashguard Fitted as standard. Has facility to connect remote gas supply for testing
indoors.
Version with CAL cell for calibration in outside also available P/N 31467-1
Gas Check Kit (P/N 31468-Specify Gas) Gas bottle with regulator and cup.
Gas Check Chamber (P/N 31428-1) Used when checking the IR2100s response to a
Liquid.
18
27 / 125
Modbus Communications
Safety Warning
Installation and maintenance must be carried out by suitably skilled and competent
personnel only.
Note: The Modbus protocol applies only to factory shipments of product from the end of
July 1998. Please contact GM factory for confirmation.
28 / 125
Modbus Communications
ii
29 / 125
Modbus Communications
Modbus RTU
Serial Communications Protocol for IR2100 Methane & IR2100
Ethylene Series
1.0 Modbus
Modbus on the IR2100 enables the operator to get gas and status information and also
remotely zero or gas check the unit.
The Baud rate is a selectable setting via the Modbus Communications Interface. The
selectable baud rates are 9600, 4800 or 2400 bits per second. (Factory default is 9600).
The Data Format is a selectable setting via the Modbus Communications Interface. The
selectable data formats are as follows:
2.3 Default
The unit is shipped with the following default baud rate and data format. The baud rate is
9600 baud. The format is 8 Data bits, no parity and 1 stop bit (8-N-1).
If you are unsure of the settings, the default settings can be recovered using the following
procedures:
2. While holding the magnet over the zero switch turn the power back on.
2a If you do not have the zero switch installed, ground the brown wire, and hold.
3. Continue to hold the magnet over the switch (or ground the brown wire) for 10
seconds.
4. The baud rate will now be 9600, and the data format will be 8-N-1.
30 / 125
Modbus Communications
* Note: Address 0 is reserved for broadcast mode and will not be supported at this
time.
* Note: Address 0 is reserved for broadcast mode and will not be supported at this
time.
31 / 125
Modbus Communications
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time.
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time.
Function Code 03, (Read Holding Registers) will be used to read status from the slave
unit. Function Code 06, (Preset Single Register) will be used to write a command to the
slave unit.
32 / 125
Modbus Communications
In a normal communications query and response, the master device sends a query and
the unit receives the query without a communications error and handles it normally within
the master devices allowable timeout. The unit then returns a normal response to the
master. Abnormal communications produce one of four possible events.
1. If the unit does not receive the query due to a communications error, then no
response is returned and the master device will eventually process a timeout
condition for the query.
2. If the unit receives the query, but detects a communication error (CRC, etc.), then no
response is returned and the master device will eventually process a timeout
condition for the query.
3. If the unit receives the query without a communications error, but cannot process the
response to the master within the masters timeout setting, then no response is
returned and the master device will eventually process a timeout condition from the
query. In order to prevent this condition from occurring the maximum
response time for the unit is 200 milliseconds. Therefore the Masters Timeout
Setting should be set to 200 milliseconds or greater.
4. If the unit receives the query without a communications error, but cannot process it
due to reading or writing to a non-existent command register, then the unit will return
an exception response message informing the master of the error.
The exception response message (ref. No. 4 above) has two fields that differentiate it
from a normal response:
* Note: Address 0 is reserved for broadcast mode and will not be supported at this time
33 / 125
Modbus Communications
02 Illegal Data Address The data address received in the query is not an
allowable address.
03 Illegal Data Value A value contained in the query data field is not an
allowable value.
04 Slave Device Failure An unrecoverable error occurred while the unit was
attempting to perform the requested action.
34 / 125
Modbus Communications
Gas Type of Gas Unit is sensing Value Dec Read/Write 0003 40004
Type Unit Identifies the unit in Decimal Value Read 0004 40005
Software Rev. Indicates the Software Rev. ASCII 2-Char Read 0005 40006
LED Disable Disables the LED Function Value Read/Write 0007 40008
Sol On/Off Turns the Solenoid On or Off Value Read/Write 0008 40009
Total Receive
Errors Total # of Receive Errors Value 8-Bit Read 0020 40033
Number of
Register Errors Total # of Register Errors Value 8-Bit Read 0024 40037
35 / 125
Modbus Communications
Overrun Errors Total # of Overrun Errors Value 8-Bit Read 0027 40040
Framing Errors Total # of f Framing Errors Value 8-Bit Read 0029 40042
Clear Comm
Errors Clear all Comm Errors Bit 1-Bit Write 002D 40046
36 / 125
Modbus Communications
When in zero mode (Bit-3) and a calibrate command is given, the unit will return an
Exception Code 06 (Device Busy) until it is ready to go to the calibrate mode (Bit-4).
37 / 125
Modbus Communications
Exception: If the gas is not a 0 to 8, the Exception Code 03 (Illegal Data Value) is
returned.
Exception: If the EEPROM cannot store the Gas type, an Exception Code 04 (Slave
device failure) is returned.
Methane 0 Read/Write
Propane 1 Read/Write
Butane 2 Read/Write
Hexane 3 Read/Write
100% by Volume 4 Read/Write
TBD 5 Read/Write
Ethane 6 Read/Write
Pentane 7 Read/Write
Other 8 Read/Write
38 / 125
Modbus Communications
Exception: If a value other than 0 or 1 is used, then the Exception Code 01 (Illegal
Function) is returned. If an EEPROM error occurs, then the Exception
Code 04 (Slave Device Failure) is returned.
A write command turns the solenoid output On or Off. A read returns the status of the
solenoid output; if the LED is not disabled, a value of 30 will be returned.
On 10 Read/Write
Off 20 Read/Write
Normal Operation 30 Read
Exception: If the EEPROM write fails, and Exception Code 04 (Slave Device
Failure) is returned.
NOTE: By activating the magnetic switch input during power-up (10 seconds), the
Address will default to 1.
10
39 / 125
Modbus Communications
9600 02 Read/Write
4800 01 Read/Write
2400 00 Read/Write
This function is indicated on the Low Data Byte and the High Data Byte is not used.
Exception: If the baud rate is not in range, an illegal data value (03) is returned.
Note: By activating the magnetic switch during power-up (10 seconds), the Baud Rate
will default to 9600.
This function is indicated on the Low Data Byte and the High Data Byte is not used.
NOTE: By activating the magnetic switch during power-up (10 seconds), the Data Format
will default to 8-N-1.
Exception: If the baud rate is not in range, an illegal data value (03) is returned.
11
40 / 125
Modbus Communications
12
41 / 125
Model IR2100
Customer Support
UNITED STATES
UNITED KINGDOM
Heather Close Phone: +44-1625-619-583
Lyme Green Business Park Fax: +44-1625-619-098
Macclesfield, Cheshire, Email: info@generalmonitors.co.uk
United Kingdom, SK11 0LR
IRELAND
Ballybrit Business Park Phone: +353-91-751175
Galway, Republic of Ireland Fax: +353-91-751317
Email: info@gmil.ie
SINGAPORE
No. 2 Kallang Pudding Rd. Phone: +656-748-3488
#09-16 Mactech Building Fax: +656-748-1911
Singapore 349307 Email: genmon@gmpacifica.com.sg
MIDDLE EAST
LOB12, #G20 Phone: +971-4-8815751
P.O. Box 61209 Fax: +971-4-8817927
Jebel Ali, Dubai Email: gmme@emirates.net.ae
United Arab Emirates
13
42 / 125
Model IR2100
Client
If you have answered NO to any of the above, please provide further details overleaf. Thank you.
14
43 / 125
PT NISCONI
45 / 125
Model IR5000
Table of Contents
Table of Contents ................................................................................................ i
Table of Figures .............................................................................................. iv
Table of Tables ............................................................................................... v
E C Declaration of Conformity in accordance with EC & ATEX Directives ......... vi
i
46 / 125
Model IR5000
ii
47 / 125
Model IR5000
iii
48 / 125
Model IR5000
Table of Figures
Figure 1 Indoor Gas Cloud.......................................................................................xii
Figure 2 Outdoor Gas Cloud....................................................................................xii
Figure 3 LNG Storage Tank Application .................................................................xiv
Figure 4 System Mounting Hardware .....................................................................xiv
Figure 5 Terminal Block Operation Diagram ...........................................................xv
Figure 6 Wire Strip Length Diagram .......................................................................xvi
Figure 7 Relay Contact Protection for AC / DC Loads........................................... xvii
Figure 8 Source Terminal Block Location ............................................................xix
Figure 9 European Union Source Terminal Block Location..................................xx
Figure 10 Receiver Terminal Block Location ..........................................................xx
Figure 11 European Union Receiver Terminal Block Location..............................xxi
Figure 12 European Union IR5000 Junction Boxes..................................................xxi
Figure 13 IR5000 Receiver / Source Unit ................................................................... 1
Figure 14 Indoor Gas Cloud........................................................................................ 4
Figure 15 Outdoor Gas Cloud..................................................................................... 4
Figure 16 LNG Storage Tank Application ................................................................... 7
Figure 17 System Mounting Hardware ....................................................................... 7
Figure 18 Terminal Block Operation ........................................................................... 8
Figure 19 Wire Strip Length Diagram ......................................................................... 9
Figure 20 Relay Contact Protection for AC / DC Loads............................................ 10
Figure 21 Source Terminal Block Location ............................................................ 12
Figure 22 European Union Source Terminal Block Location................................. 13
Figure 23 IR Receiver Terminal Block Location ....................................................... 13
Figure 24 European Union IR Receiver Terminal Block Location ............................ 14
Figure 25 European Union IR5000 Junction Boxes.................................................. 14
Figure 26 Outline Drawing, Source........................................................................... 27
Figure 27 Outline Drawing, Receiver ........................................................................ 28
Figure 28 Junction Box Assembly of IR50000 Receiver & Source European Units. 29
Figure 29 IR5000 Block Diagram.............................................................................. 30
Figure 30 Grounding Connections ............................................................................ 31
Figure 31 Mounting Bracket Assembly ..................................................................... 31
Figure 32 Aperture Plate ........................................................................................... 32
iv
49 / 125
Model IR5000
Table of Tables
Table 1 Example Readings of Methane Gas Clouds 0-5000 ppmmeter range .............xiii
Table 2 Example Readings of Methane Gas Clouds 0-5 LELmeter range....................xiii
Table 3 Example Readings of Methane Gas Clouds 0-5000 ppmmeter range ............... 5
Table 4 Example Readings of Methane Gas Clouds 0-5 LELmeter range...................... 5
Table 5 PPM & LEL Faults ..............................................................................................21
Table 6 Recommended Cable Lengths Receiver Unit (+24VDC)...................................26
Table 7 Recommended Cable Lengths Source Unit (+24VDC) .....................................26
Table 8 Recommended Cable Lengths Analog Output ..................................................26
v
50 / 125
Model IR5000
A Technical Construction File No. GM 97002 and Competent Body Report No. 4473/1K5
and
b) Conforms with the protection requirements of IEC 1010-1: 1990 + Amd 1:1992 +Amd 2: 1995
relating to safety by the application of:
A Technical Construction File No. GM 97002 and Competent Body Certificate No. 4146/1093/9367
issued by:
ERA Technology Ltd. Cleeve Road, Leatherhead Surrey KT22 7SA, England. Tel: +44 1372 367000
This declaration shall cease to be valid if modifications are made to the equipment without our
approval.
It is ensured through internal measures and our ISO9001: 1994 certifications, that series production
units conform at all times to the requirements of these current EC Directives and relevant standards.
General Monitors Ireland Ltd. in order to comply with ATEX, will provide this Instruction Manual in a
European Language required to operate the product upon request. Should this be necessary,
General Monitors Ireland Ltd. should be notified of this request to allow adequate time to process the
request.
II 2 G Sira02ATEX1172
Model: IR5000
Denis Connolly
General Manager European Operations
The signatory acts on behalf of company management, and with full power of attorney
vi
51 / 125
Model IR5000
1.0 Warranty
General Monitors warrants the Model IR5000 to be free from defects in workmanship
or material under normal use and service within two (2) years from the date of
shipment. General Monitors will repair or replace without charge any such defective
equipment found to be defective during the warranty period. General Monitors
personnel will make full determination of the nature of, and responsibility for
defective equipment. Defective or damaged equipment must be shipped prepaid to
General Monitors plant or representative from which shipment was made. In all
cases, this warranty is limited to the cost of the equipment supplied by General
Monitors. The customer will assume all liability for the misuse of this equipment by its
employees or other personnel.
NOTE - The Model IR5000 Infrared Open Path System is easy to install; however,
this manual should be read and understood before attempting to operate the system.
As with other Infrared devices, the Model IR5000 does NOT detect Hydrogen gas.
All warranties are contingent upon proper use in the application for which the product
was intended and do not cover products which have been modified or repaired
without General Monitors approval or which have been subjected to neglect,
accident, improper installation or application, or on which the original identification
marks have been removed or altered. Except for the express warranty stated above,
General Monitors disclaims all warranties with regard to the products sold, including
all implied warranties of merchantability and fitness and the express warranty stated
herein are in lieu of all obligations or liabilities on the part of General Monitors for
damages including, but not limited to, consequential damages arising out of/or in
connection with the use or performance of the product.
1.1 Warning
The Model IR5000 Open Path System contains components which can be damaged
by static electricity. Special care must be taken when wiring the system to ensure
that only the connection points are touched.
The IR5000 is manufactured from stainless steel or Aluminium with nitrile rubber
seals and glass windows. The performance of these materials with respect to attack
by aggressive substances that may be present in the hazardous area should be
considered before installation.
vii
52 / 125
Model IR5000
The safety products you have purchased should be handled carefully and installed,
calibrated and maintained in accordance with the respective product instruction
manual. Remember, these products are for your safety.
Power supplies
Control modules
Field detection devices
Signaling / output devices
Accessories connected to field and signaling devices
After the initial application of power (and any factory specified warm-up period) to the
safety system, verify that all signal outputs, to and from devices and modules, are
within the manufacturers specifications. Initial calibration / calibration checking /
testing should be performed per the manufacturers recommendations and
instructions.
Proper system operation should be verified by performing a full, functional test of all
component devices of the safety system, ensuring that the proper levels of alarming
occur.
viii
53 / 125
Model IR5000
Verify wiring, terminal connections and stability of mounting for all integral safety
equipment including, but not limited to:
Power supplies
Control modules
Field detection devices
Signaling / output devices
Accessories connected to field and signaling devices
Proper system operation should be verified by performing a full, functional test of all
component devices of the safety system, ensuring that the proper levels of alarming
occur.
ix
54 / 125
Model IR5000
Quick-Start Guide
Shipping container contents should be carefully removed and checked against the
packing list. If any damage has occurred or there is any discrepancy in the order,
please notify General Monitors as soon as possible.
All correspondence with General Monitors must specify the equipment part number
and serial number.
Each unit is tested by the factory, however, a complete system check-out is suggested
upon initial installation to ensure system integrity.
The line of sight between the Source and Receiver Units should be free from:
Items that may block the beam (i.e. a parked truck or moveable machinery).
Interruptions caused by frequent human or animal crossings.
The units should be reasonably protected (i.e. covered by a hood if temperatures
exceed the specifications in Section 8.7.2).
The units are RFI resistant, but should not be mounted too close to radio transmitters
or similar equipment.
Mount the Receiver unit so that direct sunlight does not enter the front window.
Locate the units away from concentrated sources of heat.
Mount away from sources of excessive vibration and away from high voltage/high
current power lines.
If the path length is less than 15 meters (<50 feet), an aperture plate is required.
x
55 / 125
Model IR5000
Quick-Start Guide
This method of detection comes under what is commonly known as the non-dispersive
infrared (NDIR) absorption principle.
xi
56 / 125
Model IR5000
Quick-Start Guide
No Wind
xii
57 / 125
Model IR5000
Quick-Start Guide
2.4 System
2.4.1 Gas cloud measurements
Example readings of Methane gas clouds by the standard Model IR5000 are:
In normal operation the microprocessor program constantly monitors the two infrared
wavelengths and performs mathematical operations on this information in conjunction
with values obtained during the factory calibration process.
The microprocessor derives output information and feeds it to the digital to analog
converter to produce two 4 to 20 milliampere (mA) signals that are proportional to the
0 to 5000 ppmmeters and 0 to 5 LELmeters* concentration of gas at the sensor. The
microprocessor program also monitors other conditions such as the supply voltage,
the optical path integrity (beam block) and automatic gain control.
xiii
58 / 125
Model IR5000
Quick-Start Guide
Possible installation:
LNG Storage Tanks
xiv
59 / 125
Model IR5000
Quick-Start Guide
The customer must connect a section of flex conduit to the Source and the Receiver
units to allow movement of the units during alignment (see Figures 8 through 11).
General Monitors requires the use of a drain loop or conduit seal in the conduit to
prevent moisture from entering the unit housing.
CAUTION - Acetic Acid will cause damage to metal components, metal hardware,
ceramic ICs, etc. If damage results from the use of a sealant that outgases Acetic
Acid (RTV) the two-year warranty will be void.
NOTE - Contact with printed circuit board (PCB) components should be avoided to
pre-vent damage by static electricity.
xv
60 / 125
Model IR5000
Quick-Start Guide
The Receiver and Source common must be connected to the chassis. This is
accomplished by connecting the power supply common to earth-ground and
connecting the earth-ground to the chassis. To ground the Receiver and Source
chassis, the earth-ground wire must be connected to the inside or outside chassis
grounding screw (see Figure 8).
Source:
TB1-1 Common
TB1-2 +24 VDC
Receiver:
TB4-6 Common
TB4-5 +24 VDC
The maximum distance between the Model IR5000 and the power source is specified
in the Appendix (see Section 8.8.3).
(Two) 4 to 20mA output signals are provided by the Model IR5000 and can be sent to
any industrial device that can accept a 4 to 20mA signal for computer based multi-
point monitoring. The Analog Output Signals provide for a control room or other
location to display indications of operation and alarm conditions. See Section 8.7 for
the maximum distance between the Model IR5000 and the device connected to the
Analog Output Signal.
NOTE - If either Analog Output is not being used, it must be jumpered to the common
terminal.
xvi
61 / 125
Model IR5000
Quick-Start Guide
Receiver:
TB4-4 LELmeters Common
TB4-3 LELmeters Current Output
TB4-2 ppmmeters Common
TB4-1 ppmmeters Current Output
Receiver:
TB3-3 External Reset Switch
TB4-6 Switch Common
The Model IR5000 provides external Reset Switch terminations to allow remote
resetting of the alarms. Connect each end of a normally open SPST momentary switch
to the above terminals. To reset a latched relay, simply press and release the switch.
Before making connections to these relay contacts, see Figures 8 through 11.
xvii
62 / 125
Model IR5000
Quick-Start Guide
2.9.2 The terminal connections for the LELmeters-Warn (A2) Relay Contacts
Receiver:
TB1-5 WARN Common
Before making connections to these relay contacts, see Figures 8 through 11.
2.9.3 The terminal connections for the ppmmeters-Alarm (A1) Relay Contacts
Receiver:
TB2-2 ALARM Common
Before making connections to these relay contacts, see Figures 8 through 11.
Receiver:
TB2-5 FAULT Common
TB2-4 FAULT Normally Open Contact
TB2-6 FAULT Normally Closed Contact
Before making connections to these relay contacts, see Figures 8 through 11.
NOTE - The FAULT Relay is energized and non-latching in normal operation. There
are no software selectable options that are associated with the FAULT Relay.
xviii
63 / 125
Model IR5000
Quick-Start Guide
5 to 6 meters None
9 meters Pos 1, Pos 4
12 meters Pos 1, Pos 2 Aperture
19 meters Pos 1 Plate
xix
64 / 125
Model IR5000
Quick-Start Guide
COM
+ 24
LAMP
POWER
1 2 3 4
SUPPLY 1 2 3 4 5 6 7 8
J1
OPEN
24 VDC
RELAY RESET
DeEn En TB1
POWER SUPPLY
0-5 LEL 0-5 LEL
(BLK)
FAULT
FAULT
TB2
ANALOG
ANALOG
xx
65 / 125
Model IR5000
Quick-Start Guide
0 - 5000 PPM
xxi
66 / 125
Model IR5000
Quick-Start Guide
The IR5000 contains a heater circuit to remove condensation from the windows. The
unit should be allowed to stabilize for approximately two hours before continuing with
the setup mode.
2.10.3 Alignment
To ensure optimal performance of the Model IR5000, the final alignment code must be
between 87 and 99. To align the Source and Receiver Units, use the following
guidelines:
1. Turn the Source units lamp to full power and perform a rough alignment by sight
until a maximum number is displayed on the Receiver. Tighten the horizontal and
vertical adjustment screws on each unit. Set the Source units brightness as
specified in Section 2.9.5.
2. Loosen the Source units horizontal adjustment screw and move the unit from side
to side until a maximum value is displayed on the Receiver unit. Tighten the
horizontal adjustment screw and loosen the vertical adjustment screw. Move the unit
up and down to obtain a maximum value on the display. Tighten the vertical
adjustment screw.
3. Adjust the Receiver unit from side to side and then up and down to obtain a
maximum display value, tightening the adjustment screws after each adjustment.
4. If a flashing 99 is displayed after alignment, reduce the Source lamp brightness. If
a value lower than 87 is displayed after alignment, increase the Source lamp
brightness (see Section 2.9.5).
5. Re-align the Receiver unit to obtain a maximum display value.
Repeat steps 4 and 5 each time the Source lamp brightness is changed.
If the unit is displaying a number less than 87 or a flashing 99, the IR5000 will not
exit the alignment/adjustment mode.
DO NOT intentionally misalign the Model IR5000 to get below a flashing 99. Turn
down the source lamp brightness. It is important to obtain the highest alignment
number possible within the allowed range. Alignment at high temperatures may result
in alignment numbers at the low-end of the alignment range. Alignment at low
temperatures may result in high alignment numbers.
xxii
67 / 125
Model IR5000
Quick-Start Guide
Once a number within the 87 to 99 range is attained, tighten the Source and
Receivers rear covers and verify that the alignment number has not changed. Apply
the magnet until a flashing CP is displayed (Calibration in Progress Mode). Remove
the magnet and the unit will set the zero value. After approximately 2 minutes, the
unit will return to normal operation.
Ensure that there is no significant amount of background gas when the unit is setting
the zero value, as this will alter the Model IR5000s performance. If there is normally
gas present, try setting-up the IR5000 on a breezy day, as this will dissipate the gas. If
the unit cannot set a zero value, an F8 fault code will appear. The above procedure
should then be repeated. If the unit fails to align properly, check the line of sight
carefully, then contact your GMI representative or the factory direct.
NOTE - The instrument is now ready to operate! Please consult the manual for more
information on the instruments many features.
NOTE - If you have any problems in the setup or testing of the detector, please refer to
the Troubleshooting Section, or call the factory direct.
xxiii
68 / 125
Model IR5000
3.0 Introduction
3.1 General Description
The Model IR5000 Infrared Open Path System is a microprocessor-based hydrocarbon
gas detector (Figure 13). The system consists of an IR Source unit and a Receiver unit
that may be placed from 5-100 meters (approx. 15-300 feet) apart. The General Monitors
Model IR5000 is calibrated at the factory and needs no further calibration. The sensitivity
of the Model IR5000 can be checked by placing a Test Gas Filter in front of the Receiver
unit. It is also relatively maintenance free, requiring only a periodic cleaning of the
windows to assure dependable performance.
The Model IR5000 Infrared Open Path System continuously monitors hydrocarbon gases
in both the 0 to 5000 ppmmeter and 0 to 5 LELmeter range*. It provides two 4 to 20mA
analog signals proportional to each of the above ranges, in addition to a digital display
and an A3 (LELmeters-Alarm), A2 (LELmeters-Warn), A1 (ppmmeters-Warn) and
FAULT relay contacts.
The Model IR5000 Infrared Open Path System is easily aligned using the digital display
and adjustable mounting arms, therefore not requiring any bulky setup equipment (e.g.
Digital Volt Meters, Alignment Scopes, etc).
Sensor data and status information from the Model IR5000 can be transmitted up to 9000
feet to any industrial analog to digital (A/D) converter for use in multipoint computer-based
monitoring.
The Model IR5000 Infrared Open Path System operates from an unregulated +24 volt DC
power supply which must be supplied by the customer.
* The Model IR5000 Heavy Hydrocarbon unit (Propane) displays 0 to 2000 ppmmeter
and 0 to 1 LELmeter ranges.
Receiver Source
1
69 / 125
Model IR5000
3.3 Applications
This is a partial list of applications suitable for the Model IR5000 Infrared Open Path
System:
2
70 / 125
Model IR5000
The reference wavelength is chosen to compensate for interferences that can otherwise
occur from atmospheric variation (e.g. humidity, rain, dust, snow, fog, steam, temperature,
etc.).
NOTE - Extremely dense fog, steam or interruption of the beam by an object or person
may cause the system to enter into a temporary beam blocked condition until the line-of-
sight clears. This condition is signaled by 1.5mA output level so as to discriminate it from
an Instrument true Fault. If preferred, the menu allows a level of 0mA (Fault) to be
selected.
This method of detection comes under what is commonly known as the non-dispersive
infrared (NDIR) absorption principle.
3
71 / 125
Model IR5000
No Wind
4
72 / 125
Model IR5000
4.1.5 System
Gas cloud measurements
Example readings of Methane gas clouds by the standard Model IR5000 are:
In normal operation, the microprocessor program constantly monitors the two infrared
wavelengths and performs mathematical operations on this information in conjunction
with values obtained during the factory calibration process.
The microprocessor derives output information and feeds it to the digital to analog
converter to produce two 4 to 20 milliampere (mA) signals that are proportional to the 0 to
5000 ppmmeters and 0 to 5 LELmeters* concentration of gas at the sensor. The
microprocessor program also monitors other conditions such as the supply voltage, the
optical path integrity (beam block) and automatic gain control.
5
73 / 125
Model IR5000
5.0 Installation
5.1 Receipt of Equipment
All equipment shipped by General Monitors is pre-packed in shock absorbing containers
which provide protection against physical damage (original containers should be kept for
future shipping or storage needs).
Shipping container contents should be carefully removed and checked against the
packing list. If any damage has occurred or there is any discrepancy in the order, please
notify General Monitors as soon as possible.
All correspondence with General Monitors must specify the equipment part number and
serial number.
Each unit is tested by the factory, however, a complete system check-out is suggested
upon initial installation to ensure system integrity.
6
74 / 125
Model IR5000
After the mounting location has been established, mount the support arms. Apply Lithium
grease on both taper joints before attaching the unit to the support arm. Add the supplied
bolt and washer, do not tighten until unit is fully adjusted. If the bolt has been tightened
and further adjustment is necessary, loosen the bolt two turns and tap the bolt head to
release taper (see Figures 17 and 32).
Possible installation:
7
75 / 125
Model IR5000
The customer must connect a section of flex conduit to the Source and the Receiver units
to allow movement of the units during alignment (see Figures 26 and 27).
General Monitors requires the use of a drain loop or conduit seal in the conduit to prevent
moisture from entering the unit housing.
CAUTION - Acetic Acid will cause damage to metal components, metal hardware,
ceramic ICs, etc. If damage results from the use of a sealant that outgases Acetic Acid
(RTV) the two-year warranty will be void.
NOTE - Contact with printed circuit board (PCB) components should be avoided to
prevent damage by static electricity.
8
76 / 125
Model IR5000
The terminal block is designed to accept 16 AWG to 22 AWG stranded or solid-wire (14
AWG wire can be used if it is carefully inserted). Each wire should be stripped as shown
in Figure 19.
Primary DC voltage power must be provided by the customer. Since the Model IR5000
Infrared Open Path System is designed to continuously monitor for leaks of combustible
gas, a power switch is not included to prevent accidental system shutdown. Power must
remain disconnected until all other wiring connections are made.
The Receiver and Source common must be connected to the chassis. This is
accomplished by connecting the power supply common to earth-ground and connecting
the earth-ground to the chassis. To ground the Receiver and Source chassis, the earth-
ground wire must be connected to the inside or outside chassis grounding screw.
Source:
TB1-1 Common
TB1-2 +24 VDC
Receiver:
TB4-6 Common
TB4-5 +24 VDC
The maximum distance between the Model IR5000 and the power source is specified in
the Appendix (see Section 8.8.3).
(Two) 4 to 20mA output signals are provided by the Model IR5000 and can be sent to any
industrial device that can accept a 4 to 20mA signal for computer based multi-point
monitoring. The Analogue Output Signals provide for a control room or other location to
display indications of operation and alarm conditions. See Section 8.8.3 for the maximum
distance between the Model IR5000 and the device connected to the Analogue Output
Signal.
NOTE - If either Analogue Output is not being used, it must be jumpered to the common
terminal.
9
77 / 125
Model IR5000
Receiver:
TB4-4 LELmeters Common
TB4-3 LELmeters Current Output
TB4-2 ppmmeters Common
TB4-1 ppmmeters Current Output
Receiver:
TB3-3 External Reset Switch
TB4-6 Switch Common
The Model IR5000 provides external Reset Switch terminations to allow remote resetting
of the alarms. Connect each end of a normally open SPST momentary switch to the
above terminals. To reset a latched relay, simply press and release the switch.
Receiver:
TB1-2 ALARM Common
10
78 / 125
Model IR5000
5.5.2.2 The terminal connections for the LELmeters-Warn (A2) Relay Contacts
Receiver:
TB1-5 WARN Common
Before making connections to these relay contacts, see Figures 21 through 24.
5.5.2.3 The terminal connections for the ppmmeters-Alarm (A1) Relay Contacts
Receiver:
TB2-2 ALARM Common
Before making connections to these relay contacts, see Figures 21 through 24.
5.5.2.4 The terminal connections for the ppmmeters-Alarm (A1) Relay Contacts
Receiver:
TB2-2 ALARM Common
Before making connections to these relay contacts, see Figures 21 through 24.
11
79 / 125
Model IR5000
Receiver:
TB2-5 FAULT Common
TB2-4 FAULT Normally Open Contact
TB2-6 FAULT Normally Closed Contact
Before making connections to these relay contacts, see Figures 21 through 24.
NOTE - The FAULT Relay is energized and non-latching in normal operation. There are
no software selectable options that are associated with the FAULT Relay.
5 to 6 meters None
9 meters Pos 1, Pos 4
12 meters Pos 1, Pos 2 Aperture
19 meters Pos 1 Plate
12
80 / 125
Model IR5000
COM
+ 24
LAMP
POWER
1 2 3 4
SUPPLY 1 2 3 4 5 6 7 8
J1
OPEN
24 VDC
RELAY RESET
DeEn En TB1
POWER SUPPLY
0-5 LEL 0-5 LEL
(BLK)
FAULT
FAULT
TB2
ANALOG
ANALOG
13
81 / 125
Model IR5000
0 - 5000 PPM
14
82 / 125
Model IR5000
The IR5000 contains a heater circuit to remove condensation from the windows. The unit
should be allowed to stabilize for approximately two hours before continuing with the
setup mode.
5.6.3 Alignment
To ensure optimal performance of the Model IR5000, the final alignment code must be
between 87 and 99. To align the Source and Receiver Units, use the following
guidelines:
1. Turn the Source units lamp to full power and perform a rough alignment by sight until a
maximum number is displayed on the Receiver. Tighten the horizontal and vertical
adjustment screws on each unit. Set the Source units brightness as specified in
Section 5.5.3.
2. Loosen the Source units horizontal adjustment screw and move the unit from side to
side until a maximum value is displayed on the Receiver unit. Tighten the horizontal
adjustment screw and loosen the vertical adjustment screw. Move the unit up and down
to obtain a maximum value on the display. Tighten the vertical adjustment screw.
3. Adjust the Receiver unit from side to side and then up and down to obtain a maximum
display value, tightening the adjustment screws after each adjustment.
4. If a flashing 99 is displayed after alignment, reduce the Source lamp brightness. If a
value lower than 87 is displayed after alignment, increase the Source lamp brightness
(see Section 5.5.3).
5. Re-align the Receiver unit to obtain a maximum display value.
Repeat steps 4 and 5 each time the Source lamp brightness is changed.
If the unit is displaying a number less than 87 or a flashing 99, the IR5000 will not exit
the alignment/adjustment mode.
DO NOT intentionally misalign the Model IR5000 to get below a flashing 99. Turn down
the source lamp brightness. It is important to obtain the highest alignment number
possible within the allowed range. Alignment at high temperatures may result in alignment
numbers at the low-end of the alignment range. Alignment at low temperatures may result
in high alignment numbers.
Once a number within the 87 to 99 range is attained, tighten the Source and
Receivers rear covers and verify that the alignment number has not changed. Apply the
magnet until a flashing CP is displayed (Calibration in Progress Mode). Remove the
magnet and the unit will set the zero value. After approximately 2 minutes, the unit will
return to normal operation.
15
83 / 125
Model IR5000
Ensure that there is no significant amount of background gas when the unit is setting the
zero value, as this will alter the Model IR5000s performance. If there is normally gas
present, try setting-up the IR5000 on a breezy day, as this will dissipate the gas. If the
unit cannot set a zero value, an F8 fault code will appear. The above procedure should
then be repeated. If the unit fails to align properly, check the line of sight carefully, then
contact your General Monitors representative or the factory direct.
The Heavy Hydrocarbon version of the Model IR5000 Open Path System will perform
accurately and reliably for propane gas detection applications in extreme industrial
environments. However, there are certain conditions, which one needs to account for,
when designing the gas detection system. Users are cautioned that under the following
two situations the Heavy Hydrocarbon IR5000 could give a beam block indication rather
than a gas reading or alarm:
5.7.2 A rapid and massive buildup of a high concentration propane gas cloud
For example, a propane gas cloud greater than 18 LEL-meter very rapidly and completely
placed in the gas path can indicate beam block instead of a gas reading.
The ppmmeter range of the IR5000 Heavy Hydrocarbon Open Path Monitor should be
used as a warning that there is a gas-leak. This may allow action to take place before a
leak reaches a hazardous level, while the LELmeter range should be used for action
taken for a high gas alarm.
Please review our Technical bulletin on this subject for further details.
16
84 / 125
Model IR5000
6.0 Operation
6.1 Output Options
The Model IR5000 allows the user to configure the units outputs via a magnetically
sensitive reed switch. To activate the reed switch, place the magnet supplied with the
Model IR5000 over the General Monitors logo on the label of the Receiver unit for
approximately five seconds. Remove the magnet when the flashing bars appear. The
display will cycle between the options until the magnet is re-applied, thereby accepting
the current option. These options are:
- - - Test Gas Mode
SE - Setup Mode
AJ - Alignment/Adjustment Mode
Fi - Finish, return to normal operation
This mode allows the user to check the IR5000s response to gas cells without activating
the relays. After verifying the response (see Section 5.6), remove the gas, the unit will
return to normal operation If the gas is not removed after 5 minutes, the unit will revert to
fault condition. If left in this mode for 5 minutes, the unit will return to normal operation
automatically.
This mode allows the user to change various attributes concerning the analog and relay
outputs. Following is the order in which the options are displayed (to change, apply
magnet when the desired option is showing):
Display - Description
bb - Beam Block
5 to 60 - Seconds before analog output changes.
0, 1.5 2.0mA - Analog output value during beam block.
0 to 60 - Minutes before entering optical fault.
Fi - Exits the current option and goes on to next.
17
85 / 125
Model IR5000
Fi - Exits the Setup Mode, saves the current settings and returns to normal operation.
18
86 / 125
Model IR5000
bb - Apply magnet when this code is showing to alter the options for Beam Block
5 to 60 - Select how many seconds before sending beam block fault ____________
0, 1.5 or 2.0 - Select analog output value during beam block fault ____________
0 to 60 - Select minutes of beam block before sending optical fault ____________
Fi - Exits Beam Block setup.
01 - Apply magnet when this code is showing to alter the options for Analog Output #1
on or oFf - Select whether 0-5000 (0-2000) ppmmeters range is available _____________
0 or 1.5 - Select analog output level for Test Gas Mode ____________
Fi - Exits Analog Output #1 setup.
02 - Apply magnet when this code is showing to alter the options for Analog Output #2
0 or 1.5 - Select analog output level for Test Gas Mode ____________
Fi - Exits Analog Output #2 setup.
A1 - Apply magnet when this code is showing to alter the options for Alarm Relay #1
En or dE - Select whether relay is Energized or De-energized ____________
LA or nL - Select whether relay is Latching or Non-latching ____________
2000 to 4500 (800 to 1800) - Select where relay alarm level is set
(in ppmmeters) ____________
Fi - Exits Warn Relay #1 setup.
A2 - Apply magnet when this code is showing to alter the options for Warn Relay #2
En or dE - Select whether relay is Energized or De-energized ____________
LA or nL - Select whether relay is Latching or Non-latching ____________
0.5 (0.1) to A3 level - Select where relay alarm level is set (in LELmeters) _____________
Fi - Exits Warn Relay #2 setup.
A3 - Apply magnet when this code is showing to alter the options for Alarm Relay #3
En or dE - Select whether relay is Energized or De-energized ____________
LA or nL - Select whether relay is Latching or Non-latching ____________
A2 level to 4.5 (0.8) - Select where relay alarm level is set (in LELmeters) _____________
Fi - Saves changes and exits Setup Mode.
Fi - Apply magnet when this code is showing to save changes and exit Setup Mode.
NOTE - Values in parentheses are for the Heavy Hydrocarbon (Propane) unit.
19
87 / 125
Model IR5000
This mode allows the user to re-align the Model IR5000 and set a new zero value. This
mode is covered in Section 5.6 (Applying Power).
6.5 Fi Finish
Apply the magnet when Fi is showing and the unit will exit the Options Mode, save any
changes that were made and return to normal operation. This is the only way changes
made in setup mode will be saved.
6.6 Maintenance
After the Model IR5000 has been initially aligned, very little must be done to maintain the
unit. Although calibration is not required, response should be tested from time to time
using the Test Gas Filters designed for the IR5000 (see Section 5.6 for details).
If the Model IR5000 is operated under dusty or dirty conditions, the windows should be
cleaned periodically. This is accomplished by gently wiping them with a soft, clean cloth,
which has had a commercial window cleaning solution applied. The cleaning should be
done in test mode to prevent false alarms.
NOTE - The IR5000 will see alcohol and other cleaning solvents.
SU Start-Up - This is displayed immediately after power is applied and lasts for
approximately two minutes.
SF Re-Start from an optical Fault - This is displayed when an optical Fault condition
has been corrected.
Other codes that can appear on the display are Fault codes, which are listed on the
following page.
20
88 / 125
Model IR5000
A LEL negative drift is an IR5000 source or receiver problem. It is unsafe to use the
IR5000 in this condition. A LEL negative drift causes both currents go to zero and the fault
relay to de-energize. The LEL negative drift may occur when the system is first installed
and not yet zeroed.
Negative drift on the PPM range is not a dangerous condition as with a LEL negative drift.
The PPM negative drift does not put the IR5000 into a total fault. It will however return the
PPM current to zero.
6.9 Troubleshooting
If equipment or qualified personnel required to troubleshoot are not available, it is
recommended that the defective unit be returned to General Monitors for repair.
CAUTION - General Monitors warranty will be voided if damage results from repair
attempts other than routine replacement of recommended spare parts. Repairs performed
by persons other than General Monitors authorized personnel may void the warranty.
Please read the warranty statement carefully (see inside front page). A defective IR5000
Infrared Open Path System should be returned to the factory for repair even if the
warranty has expired. A complete written description of the problem should be included
with all returned equipment.
The Model IR5000 Infrared Open Path System will indicate a fault code number on the
two-digit display as an aid to troubleshooting. The following list identifies the Fault codes,
gives a description of the Fault and indicates the corrective action that should be taken:
Multiple Faults will result in alternating fault codes being displayed. All faults have a 10-
second delay before activating, unless otherwise noted.
F1* The Receiver Unit is seeing less than optimum infrared from the Source Unit. The
units windows should be cleaned and optical path checked for blockage.
F2 Motor stalled. Timing error will try to restart the motor for up to five minutes.
The unit must be sent in for repair.
F3 The infrared source is too dim. The units optical path should be checked for
blockage and/or windows cleaned. If this continues, the unit should be returned
for repair. Activates Fault relay after user defined Beam Block time-out period.
F4 This code is displayed if there is excess infraredenergy being received by the
Receiver Unit. This may occur if there is a bright IR source in line with the detector
window.
21
89 / 125
Model IR5000
F5 This code is displayed when there is a sudden large change in the infrared energy
being received by the detector. This will occur during the cleaning of the optics, or if
any obstruction is placed in the optical path.
NOTE - Heavy Hydrocarbon IR5000: If the unit attains a ppm warn level, then goes into
an F5 fault within 2 seconds, the unit will activate the LEL alarm relay and Analog Output
will go to 20.0mA as this situation is indicative of a catastrophic Propane leak.
F6* The unit is receiving a low line voltage. This will be displayed if the Receiver
unit is being supplied with less than 18VDC.
F7 Internal system failure. The unit must be returned for repair.
F8 The unit failed to acquire a zero during alignment/adjustment mode or is
responding to a loss of background gas. Recalibrate unit.
F9* Open current loop. One or both of the Analog Outputs are open. These must be
jumpered, if not being used.
* - During the F1, F6 and F9 faults, the unit will attempt to output an alarm if gas is
present.
22
90 / 125
Model IR5000
Area Phone/Fax/Email
UNITED STATES
UNITED KINGDOM
Heather Close Phone: +44-1625-619583
Lyme Green Business Park Fax: +44-1625-619098
Macclesfield, Cheshire, Email: info@generalmonitors.co.uk
United Kingdom, SK11 0LR
IRELAND
Ballybrit Business Park Phone: +353-91-751175
Galway, Republic of Ireland Fax: +353-91-751317
Email: info@gmil.ie
SINGAPORE
No. 2 Kallang Pudding Rd. Phone: +65-6748-3488
#09-16 Mactech Building Fax: +65-6748-1911
Singapore 349307 Email: genmon@gmpacifica.com.sg
MIDDLE EAST
LOB12, #G20 Phone: +971-4-8815751
P.O. Box 61209 Fax: +971-4-8817927
Jebel Ali, Dubai Email: gmme@emirates.net.ae
United Arab Emirates
23
91 / 125
Model IR5000
8.0 Appendix
8.1 Specifications
8.1.1 System Specifications
Sensor Type
Infrared Absorption Type
8.2 Warranty
Two Years
8.4.1 Linearity
+10% over full-scale
@ 25C & 0% Blockage
8.6 Approvals
CSA & ATEX approved, CE Marked.
24
92 / 125
Model IR5000
Weight 9 lbs. 4 kg
Source Unit:
Length 12 inches 305 mm
Weight 10 lbs 5 kg
Electrical Classification
CSA = Class I, Division 1, Groups C and D
ATEX = EEx d IIB T4 Ta = -40C TO +60C
EEx de IIB T4 Ta = -40C TO +60C
8.8 Power
24 VDC @ 30 Watts (nominal) - Source
24 VDC @ 25 Watts (nominal) - Receiver
20 to 32 VDC range (maximum)
Range 0-22 mA
Malfunction 0 mA**
Beam Block 1.5 mA (std)
User selectable
Test Gas 1.5 mA (std)
User selectable
0 to 5000* ppmmeters 4-20 mA (01)
Proportional over full scale
0 to 5* LELmeters 4-20 mA (02)
Proportional over full scale
Overrange 20-22 mA
25
93 / 125
Model IR5000
26
94 / 125
Model IR5000
27
95 / 125
Model IR5000
28
96 / 125
Model IR5000
Figure 28 Junction Box Assembly of IR50000 Receiver & Source European Units
29
97 / 125
Model IR5000
30
98 / 125
Model IR5000
31
99 / 125
Model IR5000
32
100 / 125
Model IR5000
Part Number
Description
Quantity
NOTE - 31080-1 and 31080-2 are the upgrades of 30878-1 and 30878-2; respectively.
30878-1 and 30878-2 are still available for older units.
8.10.3 Accessories
30880-1 Aperture Plate: Used on the Source Unit for 5-20 Meter installations (see
Figure 32)
33
101 / 125
PT NISCONI
1. Brief overview
OptoRex DO1101Ex
ThermoRex DT1101Ex / DT1102Ex
1.1. Characteristics
1.2. Design
2. Technical data
3. Principle of operation
4. Environmental influences
4.1. Influence of the ambient temperature
4.2. Other influencing variables
5. Application
5.1. Compatibility
5.2. Alignment functions
5.3. Application
5.4. Installation
6. Commissioning
7. Maintenance
7.1. Functional check
7.2. Overhaul
7.3. On-site measurement with the DZ1194 detector test set
103 / 125
1. Brief overview
OptoRex DO1101Ex ThermoRex DT1101Ex / DT1102Ex
Dimensions Dimensions
115 115
47 . . . 70 47 . . . 70
54,5
51
With base DB1101 With base DB1101
1.1. Characteristics
For applications in explosion-hazard areas of zones For applications in explosion-hazard areas of zones
1 and 2 1 and 2
Balanced response behavior and wide range of ap- Heat detectors to meet the highest requirements
plications DT1101Ex Category 1 heat detector with wide ap-
High reliability and stability through new, high-qual- plication range (up to +50C)
ity optoelectronic sensor system and fully automat- DT1102Ex Heat detector for high ambient tempera-
ic manufacturing and inspection processes tures (up to +70C)
Response behaviour immune to deceptive phenom-
ena with rapid and slow increase in temperature
through:
Intelligently designed differential characteristics
Precise maximum temperature alarm activation with
quality thermosensor
High degree of reliability and long-term stability
High resistance to:
Electromagnetic interference (EMI) intelligently designed
circuit
Soiling, temperature fluctuations, humidity and corrosion
achieved through custom developed, protective circuit board
coating
Together with detection line coupler and shunt Zener barrier,
compatible with Cerberus control units with collective signal
evaluation
Manufactured in state-of-the-art SMD technology
Bayonet fitting for connection to base simplifies detector re-
placement
Comprehensive range of detector base accessories for spe-
cial applications
Data and design subject to change without notice / Supply subject to availability
e1485a 06.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 1
104 / 125
1.2. Design
Data and design subject to change without notice / Supply subject to availability
2 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 06.96 e1485a
105 / 125
2. Technical data
Normal ambient conditions, if nothing else is specified:
Temperature Ta DO1101Ex = 20C (293K) DT1101Ex/DT1102Ex = 25C (298K)
Air pressure p = 1000hPa (750 Torr)
Parameters Symbol Unit DO1101Ex DT1101Ex DT1102Ex Conditions
Operating voltage Ub VDC 17 . . . . . . 24 16 . . . . . . 24 16 . . . . . . 24
(quiescent condition)
Max. permissible voltage Umax VDC max. 27 max. 27 max. 27
Starting current Ie A max. 160 max. 100 max. 100 max. 25s after switch-on
Operating current Ib A max. 100 max. 100 max. 100 for DT1101Ex Ta=25...50C
(quiescent condition) for DT1102Ex Ta=25...70C
Alarm voltage
at IA = 1 ... 10mA UA V 5 .....10 5 .....10 5 10
.....
at IA = 1...60mA UA V 5 .....12 5 .....12 5 12
.....
Max. alarm current, pulsed IA mA max. 100 max. 100 max. 100 must be limited externally
f0.5Hz, Duty Cycle 50%
Reset voltage UR V 2 ...... 6 2 ......6 2 ......6
Reset current IR A 20 .....500 40 500
..... 40 500
.....
* not Ex conditional
(Alarm release DT1101Ex 54C
DT1102Ex 74C)
Data and design subject to change without notice / Supply subject to availability
e1485a 06.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 3
106 / 125
3. Principle of operation
OptoRex DO1101Ex ThermoRex DT1101Ex / DT1102Ex
The OptoRex DO1101Ex is based on the principle that The ThermoRex DT1101/DT1102 measures the ambient
smoke scatters light. An infrared LED (IRED) transmits temperature with the NTC thermistor Rm in the tip of the
brief, intensive light pulses into the scattering chamber. sensor and measures the temperature in the detector
The receiving element is screened off from direct IR light housing with the NTC thermistor Rg. Rapid temperature
incidence and reflections. Smoke entering the chamber changes bring about a faster change of resistance with
scatters the light so that some of it reaches the receiver thermistor Rm than with thermistor Rg. This causes a posi-
whose signal is evaluated by the electronics. After three tive voltage shift at point P. As soon as this voltage ex-
positively evaluated pulses an alarm is transmitted to the ceeds a fixed threshold value, the threshold value detec-
control unit. tor 3 activates multivibrator 4 and an alarm is given. If,
Time base 2 in the integrated circuit 1 controls the logic due to a very slow increase in temperature, the resistance
unit 3 and produces pulses for controlling the IRED light values Rm and Rg fall to the same extent, upon reaching a
source 5 via the amplifier 4 . If the detector is not contam- maximum temperature determined by resistors 1 and 2
inated and the air is clean, no signal is available at the re- an alarm is given. At the same time resistor 2 accelerates
ceiver 6 . response for fast changes in temperature.
If the air contains smoke, the receiver sees a signal that is The weak current IB flows in non-alarm condition. As soon
transmitted via the amplifier 7 to the discriminator 9 . Inte- as the multivibrator 4 becomes conductive, the response
grated in the amplifier is a multiple coincidence circuit that indicator alarm current IA flows. At the same time the re-
generates the difference between a light and a dark mea- sponse indicator 6 built into the detector is activated via
surement which has the effect that no interference signals the driver stage 5 . One external response indicator 7
and only smoke induced signals are amplified and may be connected. The multivibrator remains in self-hold
transmitted. In circuit 8 a stable reference voltage Uaref is condition until the control unit is reset by briefly interrupt-
produced which in discriminator 9 forms the alarm ing the operating voltage, whereupon it reverts to its origi-
threshold. The detector sensitivity is set with the trimming nal state. The intrinsically safe detector circuit is isolated
resistor 10 . The signal voltage Usig at the output of the re- from the line circuit by protective diodes 8 .
ceiving amplifier can only be factory-measured with the
aid of special measuring equipment. The alarm threshold
Uaref is used for measuring the alarm stroke U3A on site
with the detector measuring instrument DZ1194.
The logic unit 3 evaluates the pulses of discriminator 9
and after the third pulse activates the alarm stage 11 inte-
grated in ASIC. Also activated in the event of an alarm are
the internal response indicator 12 and an external re-
sponse indicator 13 if available. The alarm stage 11 is self-
holding and is restored to the initial condition only when re-
set by the system control unit (through brief interruption of
the operating voltage). The intrinsically safe detector cir-
cuit is isolated from the line circuit by protective diodes 14 .
4
B
D
+ B
D
+
F F
2
12 13
1
6 7
ASIC 3
5 6 7 9
Operating voltage
Operating voltage
E MB
Rm
3 4
11
8 2 UB UB
P
E
Rg
1 IA
10
14 5 8
C IB C
Usig Uaref
A A
Shunt Zener Shunt Zener
Detector diode barrier Detector diode barrier
U3A Base Base
Data and design subject to change without notice / Supply subject to availability
4 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 06.96 e1485a
107 / 125
4. Environmental influences
[%/m]
5
4
DO1101A-Ex
3
0
10 0 10 20 30 40 50 60 [C]
Ambient temperature
Data and design subject to change without notice / Supply subject to availability
e1485a 06.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 5
108 / 125
5. Application
5.1. Compatibility
Control units: Compatible with all Cerberus control
units with collective signal evaluation to-
gether with input/output module DC1192
and shunt Zener barrier
Bases: DB1101
5.3. Application
OptoRex DO1101Ex ThermoRex DT1101Ex / DT1102Ex
The OptoRex DO1101Ex is suitable for applications in ex- The ThermoRex DT1101Ex/DT1102Ex is suitable for ap-
plosion-hazard areas of zones 1 and 2. Due to its EN 54 plications in explosion-hazard areas of zones 0, 1 and 2.
compliance, the OptoRex DO1101Ex can be used as a The ThermoRex DT1101Ex can be used up to a tempera-
universal smoke detector. ture of 50C and the DT1102Ex up to a temperature of
70C. The DT1101Ex/DT1102Ex are especially suitable for
monitoring rooms and installations in which in the event of
fire, a rapid increase in temperature is to be expected, or
where other types of detector cannot be used because
work processes cause smoke, dust, exhaust gases etc.
The recommended monitoring areas, distances between detectors
etc. can be found in the national guidelines, the Cerberus Guide-
lines for Planning and Application (CRP), Fire Detection in Explo-
sion-hazard Areas, document e1204, or the Security Guide.
5.4. Installation
Bases are connected together by twisted twin wire. Shielded cable
is only required for special applications, e.g. in the case of powerful
high frequency fields or special national guidelines.
For detailed information, see Fire Detection in Explosion-hazard
Areas, document e1204.
Input/output
EOL22(Ex)
module DC1192
Detection line, SB3 Ex Ex Ex
control unit sided
max. 15 DO1011Ex
Supply 24VDC max. 25 DT1011/02Ex
End-of-line device
Shunt Zener diode barrier Equipotential bonding
Data and design subject to change without notice / Supply subject to availability
6 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 06.96 e1485a
109 / 125
6. Commissioning
To prevent unnecessary soiling during the construction phase,
the detectors should be inserted into the bases just before the
system is put into service.
For detailed information, see Fire Detection in Explosion-hazard
Areas, document e1204.
7. Maintenance
7.2. Overhaul
All detectors should be jointly replaced and factory overhauled in in-
tervals of 2 to 8 years, depending on the environmental conditions
and the severity of contamination.
Data and design subject to change without notice / Supply subject to availability
e1485a 06.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 7
110 / 125
Terms
Data and design subject to change without notice / Supply subject to availability
8 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1996 06.96 e1485a
111 / 125
Sockel fr kollek-
DB1101A tive Brandmelder DB1101A Embase pour d- Base for collec-
tecteurs dincendie DB1101A tive Fire Detec-
DS11 collectifs DS11 tors DS11
Ansprechindikator
Melder Indicateur daction
Dtecteur Response indicator
Detector min. 2cm
50cm
1 2
1 Platzbedarf 1 Encombrement 1 Space requirements
Fr Service- und Revisionsarbeiten muss Une fois mont, lembase doit tre parfai- For maintenance purposes the installed
der montierte Melder gut zugnglich sein. tement accessible pour les travaux de rvi- base must be easily accessible. Ensure
Melder mssen mit dem Melderaustau- sion et pour le service. Les dtecteurs doi- that it is possible to extract the detector us-
scher senkrecht von unten herausgenom- vent pouvoir tre retirs avec lchangeur ing exchanger or to test from a point di-
men und geprft werden knnen. Der de dtecteur ou vrifis verticalement et rectly below the base. The base must
Sockel muss seitlich min. 20mm Spiel- par le bas. Respecter au minimum 20mm have at least 20mm clearance on all sides.
raum haben. dloignement par rapport aux obstacles.
Montage bei Unterputz-Leitungsverle- Montage lorsque les cbles sont poss Installation with concealed wiring
gung sous crpi
Sockel
Embase DB1101A
Base
60...70mm
Schrauben
Vis max. 4mm
Screws
Data and design subject to change without notice / Supply subject to availability
x1336b 08.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1995 486 446 1
112 / 125
Aufputz-Montage in trockener Montage sur crpi dans environne- Surface mounting for dry
Umgebung ment sec application
Sockelzusatz verwenden
Gewnschte Leitungseinfhrung
Utiliser auxiliaire dembase ausbrechen
Use base attachment
Sockel
Embase DB1101A
Base
Sockelzusatz, feucht
Sockel
Embase DB1101A
Base
Data and design subject to change without notice / Supply subject to availability
2 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1995 08.96 x1336b
113 / 125
Anschluss Raccordement Connection
Draht einschieben
Insrer le fil Zum Einschieben des Leiters, Fe-
Insert wire derklemme mit Schraubenzieher
Nr. 0 (Klingenbreite max. 3,5mm)
Pro Klemme darf max. 1 Leiter entlasten
0,22,5mm2 angeschlossen werden Pour insrer le conducteur, dga-
1 conducteur de 0,22,5mm2 au max. ger la borne ressort avec un
peut tre raccord sur une borne tournevis no. 0 (largeur de la tige
Max. one conductor of 0.22.5mm2 in 3,5mm au max.)
each terminal In order to insert the wire, open
spring terminal with a screwdriver
no. 0 (blade width max. 3.5mm)
Markierung Ansprechindikator
113
4,3
Melderkennzeichnungsschild
21
47
70
Montageschablone
Gabarit de perage
Drilling template
Meldermarkierung
Marquage du dtecteur
Detector marking
DBZ1193A-AA (Art. Nr. 500 982)
Data and design subject to change without notice / Supply subject to availability
x1336b 08.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1995 3
114 / 125
Anschluss Meldelinie fr Melder mit Raccordement ligne de dtection pour Connection detection line for detec-
kollektiver Adresse dtecteurs avec adresse collective tors with collective address
Linieneinschub
Tiroir de ligne
Zone module +
Achtung! Polaritt beachten!
Attention! Considrer la polarit! Zusatzklemme DBZ1190-AA/AB
Important! Observe polarity! Borne additionnelle
Auxiliary terminal
+ + +
DJ1192 DJ1192 DJ1191
DJ1191 DJ1191 DJ1192
Externe Ansprechindikatoren (DJ1191/ Indicateurs daction externes (DJ1191/ External response indicators (DJ1191/
DJ1192, DJ1193). Bei Ansteuerung von DJ1192, DJ1193). Lors de lasservisse- DJ1192, DJ1193). When activated by
mehr als einem Melder: Plus nur mit ei- ment de plus dun dtecteur: ne relier le more than one detector, connect positive
nem Sockel verbinden. plus quavec une seule embase. only from one base.
Max. 2 externe Ansprechindikatoren pro 2 indicateurs daction externes au max. Max. 2 external response indicators per
Sockel. par embase. base.
Linienabschluss (zentralenspezi- Aprs vrification de la ligne, placer Connect end-of-line unit (depending
fisch) jeweils nach Ausprfen der Lei- llment de fin de ligne (spcifique on control unit) in the last base after
tung in den letzten Sockel einsetzen lquipement de contrle et de signa- line has been checked
lisation) dans la dernire embase
Zusatzklemmen Melderschutzkorb
Bornes additionnelles Corbeille protectrice
Auxiliary terminals Protective cage
1 2 2 1
Querschnitt
Section Ausbrechen und Schutzkorb festschrauben
Pos Type Cross-section Ebrcher et serrer le corbeille protectrice
Break out and fasten the protective cage
1 Zusatzklemme DBZ1190-AA 0.28 ... 0.5mm2 467 708 DBZ1194 (Art. Nr. 467 711)
Borne additionnelle
2 Auxiliary terminal DBZ1190-AB 1.0 ... 2.5mm2 494 234
Data and design subject to change without notice / Supply subject to availability
4 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1995 08.96 x1336b
115 / 125
PT NISCONI
3,2
37
32
62
Fr die Leitungseinfhrungen nach Be- Selon besoin, on percera dans le chs- 1 hole (7.5mm max.) may be drilled in
darf 1 Loch max. 7,5mm in die Trzar- sis de porte 1 trou max. 7,5mm pour the door frame as required for cable
ge bohren lintroduction des lignes entry
Weisse Abdeckung entfernen (ausra- Retirer (dcliqueter) le couvercle blanc Remove white cover plate (unlatching
sten) Fixer sur le chssis de porte la plaque de action)
Grundplatte/Leuchtelement mit 2 base avec llment lumineux au moyen Mount the base plate/lamp on the door
Schrauben max. 3mm auf Trzarge de 2 vis max 3mm frame with 2 screws (3mm max.)
befestigen Raccorder selon schma de raccorde- Connect up as described under connec-
Anschluss gemss Anschluss-Schema ment tion diagram
Weisse Abdeckung wieder aufsetzen Remettre en place (encliqueter) le cou- Replace white cover plate
und einrasten vercle blanc
DJ1192Ex Aufputz DJ1192Ex saillant DJ1192Ex surface mounted
60
25
85
56
4,1
56
Weisse Abdeckung entfernen (schwar- Retirer le couvercle blanc (en pressant Remove white cover plate by pressing
zen Nocken drcken) sur lergot noir) black lugs
Grundplatte mit 2...4 Schrauben max. Fixer la plaque de base sur la paroi ou la Mount the base plate on the wall or a re-
4mm auf Wand oder UP-Dosen mon- bote encastrer au moyen de 2...4 vis cess box with 2...4 screws (4mm
tieren max. 4mm max.)
Fr die Befestigung auf Dosen mit Eloigner llment lumineux pour la fixa- Remove the lamp before mounting on
60mm Lochdistanz das Leuchtelement tion sur des botes dont les trous se trou- recess boxes with holes spaced at
entfernen vent 60mm lun de lautre 60mm
Anschluss gemss Anschluss-Schema Raccorder selon schma de raccordem. Connect up as described under connec-
Weisse Abdeckung wieder einhngen Raccrocher et encliqueter le couvercle tion diagram
und einrasten blanc Replace white cover plate
Data and design subject to change without notice / Supply subject to availability
x1240a 09.96 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1994 485 900 1
117 / 125
Zusatzrahmen AI330 zu DJ1192Ex Cadre supplmentaire AI330 pour AI330 adapter frame for DJ1192Ex
DJ1192Ex
16
85
Der Zusatzrahmen wird mit 2 Schrau- Fixer le cadre supplmentaire sur la pa- Mount the adapter frame on the wall or
ben max. 4mm auf die Wand oder Do- roi ou la bote au moyen de 2 vis max. box with 2 screws (4mm max.). The
se montiert. Je nach Dose kann die 4mm. La distance entre les vis peut tre distance between mounting holes can
Schraubendistanz beliebig gewhlt choisie conformment la bote be chosen as required according to the
werden Fixer lindicateur daction sur le cadre box used
Der Ansprechindikator wird seinerseits supplmentaire au moyen de 2 vis Mount the response indicator on the
mit 2 Holz- oder Blechschrauben bois ou vis Parker max. 3mm, lon- adapter frame with 2 wood or metal
3mm , max. 16mm lang, auf dem Zu- gueur max. 16mm screws (3mm max., 16mm long)
satzrahmen befestigt
Steckanschlsse fr einen Leiter Bornes sans vis pour un conducteur de Plug-in connection for one lead
0,25...1,5mm2 bzw. 0,6...1,3mm 0,25...1,5mm2, soit 0,6...1,3mm 0.25...1.5mm2 or 0.6...1.3mm
Anschlussdrhte ca. 7...8mm abisolie- Dnuder les conducteurs sur une lon- Insulate leads approx. 7...8mm
ren gueur denv. 7...8mm Insert wired in terminals
Drhte in die Klemmen einstecken Pousser les fils dans les bornes In order to be able to connect smaller
Um dnnere Drhte einstecken zu kn- Ouvrir les bornes pour pouvoir engager wire, or release wires already con-
nen oder bereits eingeklemmte Drhte des fils plus minces ou dgager des fils nected, open the terminals by inserting
zu lsen, die Klemmen durch Drcken coincs. Engager et pousser cet effet and pushing a screwdriver in the termi-
mit einem Schraubenzieher dans les fentes un tournevis de nal slots (screwdriver blade
0,35...0,6mm, DIN 5264, ffnen 0,35...0,6mm selon DIN 5264 0.35...0.6mm, DIN 5264)
DJ1191Ex
DJ1192Ex
+ +
Ex Ex Ex Ex
Melder Dtecteurs Detectors
Data and design subject to change without notice / Supply subject to availability
2 Copyright by CERBERUS AG, CH-8708 Mnnedorf / Switzerland, 1994 09.96 x1240a
118 / 125
PT NISCONI
MTL5061 FIRE/SMOKE
DETECTOR INTERFACE To earth
leakage
two-channel, loop-powered detector
Ch 2 Fire detectors 6 7
+
5
I 8
6 to
I Ch 2
4 9 35V dc
The MTL5061 is a loop-powered two-channel interface for use with
+
To earth leakage detector 3 10
conventional fire and smoke detectors located in hazardous areas. In +
2
I 11
6 to
I Ch 1
operation, the triggering of a detector causes a corresponding change 1 12 + 35V dc
Ch 1 Fire detectors
in the safe-area circuit. The unit has reverse input polarity protection,
while non-fail earth fault detection on either line can be provided by
connecting an earth leakage detector to terminals 3 or 6.
SPECIFICATION
See also common specification
Terminal Function
Number of channels 1 Output ve (channel 1)
Two 2 Output +ve (channel 1)
Location of detectors 3 Earth leakage detection (channel 1)
Zone 0, IIC, T46 hazardous area if suitably certified 4 Output ve (channel 2)
Div. 1, Group A hazardous location 5 Output +ve (channel 2)
Current range 6 Earth leakage detection (channel 2)
1 to 40mA, nominal 8 Input ve (channel 2)
Integral input polarity protection 9 Input +ve (channel 2)
Input circuit protected against reverse polarity 11 Input ve (channel 1)
No-fail earth fault protection (optional) 12 Input +ve (channel 1)
Enabled by connecting terminals 3 and 6 to the MTL4220 earth
leakage detector. If a fault on either line of each channel is
proclaimed: unit continues working.
Note: 1. The earth leakage detector introduces a 100A, 1Hz
ripple to the field circuit.
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997
June 2004
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
120 / 125
PT NISCONI
I- INSTALLATION
1- Unscrew the fout screws (pull-handle for removing the two screws - Wrench Allen n5)
3- Screw the base plate on the wall with stainless steel screws.
You have to do a serious fixation supporting the own weight of the pull-handle and the tractive
effort given for unlock it.
TO UNLATCH ALARM
1- If an alarm must be sent from a call point, just pull the handle to-wards you, till the handle be
locked down.
Now the electrical circuit is on.
TO LATCH ALARM
III-INSPECTION-MAINTENANCE
ONCE A MONTH
Unlatch all the pull-handle (one after one) of the protected area and verify that :
a) The Handle Well Lock Down
b) The Electrical Signal Neaded Is Present
c) When Turning Back The Key, Handle Come Back Up In The Housing.
d) The Plug Will Be Well Tight.(No Enter Of Humidity)
TWICE A YEAR
Remove the hood and verify that no dust or insect are inside the instrument.
ATTACHEMENT
7. NPT ADAPTERS
Manufacturer : RCN
Material : Nickel plated brass
Certification : EExd / EExe
Protection : IP66
Size model : M20x1.5 to 1/2 NPT
Size model : M3/4 NPT to 1/2 NPT
8. RESISTOR
Manufacturer : NEOHM
Category : Carbon film
Type : 0.5 W
Resistance : 6.8 k & 2.2 k
Maximum voltage : 350V
Resistance tolerance : 5%
Operating temperature : -55 to 155C