Вы находитесь на странице: 1из 44

Spotlight On

Fire-Alarm Controlled
Door Hardware

Gerry Atkin, AHC


Doors do more than just open & close...
they provide safety, security, and
accessibility.
Codes
NFPA 80 Fire Rated Doors
and Windows

NFPA 101 Life Safety

Barrier Free NBC / OBC


Ontarians with
Disabilities Act 2006
NFPA 80 2007 Edition
Fire Door Inspection
Requirements
NFPA 80 (2007) NEW SECTION

5.2 - Inspection

5.2.1 Fire door assemblies shall be inspected


and tested not less that annually, and a written
report shall be signed and kept for inspection by
the AHJ
A basic electric circuit has 4
components.
1-Power Supply

2-Switch 3-Conductor

4-Load
2 1
4
3
Power Supplies
Power Supplies
Power Supplies
Hardware for Fire Doors
Problem
Fire doors must close with closer
Cross corridor doors are fire rated
Owner wants doors to be held open
Solutions

wall or floor magnet with closer


electro-magnetic hold-open closer
battery-operated detector holder with closer
non-detector holders must be wired into the
fire alarm system
stairwells - all doors must close
simultaneously
Acceptable Ways to Hold Open a
Fire Door
wall or floor magnet with closer
Acceptable Ways to Hold Open a
Fire Door
Closing Device
Fire-rated openings require a
closing device to ensure the
door is kept closed
fire rated, non-petroleum, hydraulic
fluid may be required

Fire-rated openings can be held


open only with listed closing
devices, provided they:
Release upon signal from alarm system
Integral to closer / fail safe door holder
Acceptable Ways to Hold Open a
Fire Door
Electro-Magnetic Hold-Open Closer
Single Point Hold-Open (SE)
Multi-Point Hold-Open (ME)
Un-Acceptable Ways to Hold Open
a Fire Door
Problem
Fire doors must close with closer
Owner wants doors to be held open

Other locations may include:


Theatre exit doors
Storage room doors
Shipping / Receiving areas
Elevator Lobbies
Office Suite entry
Problem
Fire doors must have positive latching
Owner wants free access during fire

Buildings over a certain number of floors


must provide re-entry every 5th floor
allowing access to second stairwell. Office
buildings pose additional security issues.
Solutions

Electrically controlled access from stair side


Must be fail un-locked
Controlled by security system
Un-locked by the fire alarm system
Solutions

Electric Locks
Electrically controlled trim
Two options:
Electrically LOCKED
Electrically UN-LOCKED
Solutions

Electric exit device trim


Electrically controlled trim
Two options:
Electrically LOCKED
Electrically UN-LOCKED
Fail Safe vs. Fail Secure

Fail Safe - When power fails, the door is


un-locked or un-latched

Fail Secure - When power fails, the door


remains locked or secure
Electric Strikes
Replaces standard strike
for lockset or exit
device.
Keeper secures and
releases latchbolt.
Problem
Fire doors must have positive latching
Owner wants a push-pull operation

In certain locations such as theatres and


banquet halls exit doors make a lot of
noise and would function better if they
could just be PUSH and PULL
Solutions
Electric exit device with
latch retraction
Electrically controlled
latch
Two options:
EL - Solenoid
QEL Motorized
EL devices can be used to hold the latches retracted on
fire doors if they are connected to the fire alarm system.
EL devices can be used to hold the latches retracted on
fire doors if they are connected to the fire alarm system.
LIFE SAFETY
Problem
Exit door are required due to occupancy loads
Owner does not want people to use exits

In certain locations such as art galleries or


public libraries require several exits but
they are for emergency only... Or there
are security requirements that need
authorized egress
Delayed Egress Locks
Designed to delay egress to prevent theft.
Must allow egress for life safety.
Typically a delayed egress exit device
(Chexit) or magnetic lock with delayed
egress controller.
Delayed Egress Exits
15-second delay(30 seconds IF approved by AHJ)
30-second relock per BOCA, manual relock per NFPA 101
No delay when fire alarm sounds or upon loss of power
Audible local alarm
Signage - Push until alarm sounds. Door can be opened in 15
seconds.
One delay maximum per means of egress.
Not allowed in all occupancies.
Controlled Egress Doors
Sensor on egress side to unlock when approached by an
occupant
Unlocked by loss of power to sensor or lock.
Manual release device (push button) on egress side with
signage. Remains unlocked for 30 seconds min.
Unlocked by fire alarm or sprinkler system until system is
reset.
Prohibited on entrance doors in Use Groups A, B, E, or M
while open to the public.
Solutions

Exit device with delay egress


Electric Latch Retraction
Electric Dogging (push-pull function)
Electrically Operated Trim
Exit Alarm or Request to Exit
Delay Exit (where codes permit)
Controlled Egress Doors
(restricted egress)
Controlled Exit Doors
Problem
Doors are card access with inter-lock
Must be fail locked (ingress) and fail safe egress

Bio-Hazard, Forensic Lab, Drug-Labs etc.,


Bank sorting centers, Museums or Art
galleries may have doors that can only be
opened one at time creating inter-lock
doors or man-traps
Solutions
Electro-magnetic Locks
Mag-Locks can be used (where codes permit) to
control ingress and/or egress, or to enable
a inter-locks doors
Solutions
Mag-Locks for inter-locking doors
Controlled Egress Doors
Used to control and monitor ingress &
egress.
Must also provide life safety.
Typically an electro-magnetic lock and card
reader or keypad.
Electromagnetic Locks
Always Fail
safe
Direct Hold
(surface
mounted)
Shear Locks
(concealed)
Questions & Answers

Вам также может понравиться