Вы находитесь на странице: 1из 1

SPECIFICATION AND DEVIATION MATERIAL PAINTING

A) Requirement for rusted area 3000 Sq. Meter (Approx)


The rusted portion in various area in STG Building & Coal bunker, LSBM bunkers and its structures need to be thoroughly clean by using power tools such as buffing
wheels and others before apply the primer coat.

Jotun Painting specification


DEVIATION by GTE KPC Standard Specification KPC - C-11
( GTE using specification system 1) Shall be using System 9
Application : APPLICATION :
CARBON STEEL SERVICE TEMPERATURE CARBON STEEL
NO Description of spec DFT (Micron) Jotun Painting specification LESS THAN 100 DEG C INSULATED AND NON INSULATED
EXAMPLES: SERVICE TEMPERATURE 100 DEG C - 400 DEG C.
OFFSHORE ATMOSPHERIC ZONE EXAMPLES: POWER STATION EXHAUSIST ETC.
ONSHORE
GENERAL
MARINE JETTIES TOPSIDES
DFT (Micron) Product Description

1 Primer Zinc Rich Epoxy 75 Barrier Zep BARRIER ZEP, GREY 75 Product Code no V
(Thinner No 17 +/- 10%) (Thinner No 17 +/- 10%) INORGANIC ZINC SILICATE

JOTAMASTIC 87 JOTAMASTIC 90, ALUMINIUM Product Code no VI


2 2nd Coat- High Build Epoxy 150 40 HIGH TEMP SELF CURING
Thinner No.17 (+/-10%) Thinner No.17 (+/-10%)
ZINC FREE INORGANIC COAT

Product Code VI
3 3rd Coat- Gloss 2 pack Recoatable (Acrylic Topcoat) 50 HARDTOP AS HARDTOP AX, 40 HIGH TEMP SELF CURING
Thinner No. 10 (+/- 10%) Thinner No. 10 (+/- 10%)
ZINC FREE INORGANIC COAT

B) Requirement for Final Coat painting:


Other than rusted area, surface to be cleaned thoroughly with water Jet/ Compressed air/ cloth before apply the final coat
painting. Paint for final coat shall be used Gloss 2 Pack Recoatable (Acrylic Topcoat) with filim thickness of 50 Micron

Area To be covered for Final coating: KPC Standard Specification KPC - C-11
Shall be using System 9

Sr. No Area DFT (Micron) Quantity in Sq. Meter Jotun Painting specification DFT (Micron) Product Description
DEVIATION by GTE

1 Coal Bunker structure & Coal Bunker and Its various platforms 50 12000 (Approx) HARDTOP AX, Thinner No. 10 (+/- 10%) 150
Refer to KPC-C-11 System 14
Product Code II high Build Epoxy

2 STG Building structure 50 15000 (Approx) HARDTOP AX, Thinner No. 10 (+/- 10%) 40
Refer to KPC-C-11 System 9
Product Code VI Zink Free Inorganic Coat
3 LSBM Bed material bunker and its structures 50 3000 (Approx) HARDTOP AX, Thinner No. 10 (+/- 10%) 150 Refer to KPC-C-11 System 14
Product Code II high Build Epoxy

4 Ash Pipe Rack, Plant pipe rack & Air Receivers 50 3000 ( Approx) HARDTOP AX, Thinner No. 10 (+/- 10%) 40
Refer to KPC-C-11 System 9
Product Code VI Zink Free Inorganic Coat
Total 33,000 Sq. Meters