Вы находитесь на странице: 1из 4

Document kind Document identity Revision

Technical description 3GZF500930-245 C


Owner organization Document type Date of revision (yyyy-mm-dd) Status Page(s)

PG IEC LV MOTORS Variant code description 2013-05-20 Valid 1(4)


Department Prepared by Approved by Security level

MLA900 Tom Eklf Patrik Norrgrd Internal

Variant code: 450


Heating element 100 - 120V.
56 63 71 80 90 100 112 132 160 180 200 225 250 280 315 355 400 450
M3BP x x x x x x x x x x x x x x x x
M3AA x x x x x x x x x x x x x
M2BA x x x x x x x x x x x x x x
M2AA x x x x x x x x x x x x x
x = Available, s = Standard feature

This code includes heating element(s). Heating elements are used to heat the coils of the stator winding when the
motor is not running to prevent moisture from condensing on the surface of the stator coils. When the stator coils
are kept just a few degrees warmer than the stator frame, will moisture from the air condensate on the surface of
the stator frame instead of on the coils. Difference in temperature inside and outside the motor will also cause
over-pressure that keep humidity outside.

Variant code execution

The motor can be equipped with heating elements either at one and or at both ends depending on the motor size.
Please refer to product catalogues for more information about power of heating resistors and amount of heaters.

Position of the heating element

The heating element is tied around the end-coil, see figure 1.

Figure 1. Heating element

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Copyright 2007 ABB
Variant code description Valid 3GZF500930-245 C
2013-05-20 2(4)

Table of Power and Amps for the heaters used / frame sizes.

M3BP M2BA M3AA M2AA


Frame size W W W W
Power A Power A Power A Power A
Current 220V Current 220V Current 220V Current 220V

56
63 8 0,04 8 0,04 8 0,04 8 0,04
71 8 0,04 8 0,04 8 0,04 8 0,04
80 8 0,04 8 0,04 8 0,04 8 0,04
90 25 0,11 25 0,11 25 0,11 25 0,11
100 25 0,11 25 0,11 25 0,11 25 0,11
112 25 0,11 25 0,11 25 0,11 25 0,11
132 25 0,11 25 0,11 25 0,11 25 0,11
160 25 0,11 25 0,11 25 0,11 25 0,11
180 50 0,23 25 0,11 50 0,23 25 0,11
200 50 0,23 50 0,23 50 0,23 50 0,23
225 50 0,23 50 0,23 50 0,23 50 0,23
250 50 0,23 50 0,23 50 0,23 50 0,23
280 60 0,27 60 0,27
315 2x60 0,54 2x60 0,54
355 2x60 0,54 2x60 0,54
400 2x60 0,54
450 2x100 0,91

NOTE !

If nothing else is specified the heaters are wired to a terminal block in the main terminal box, a separate auxiliary
terminal box for the heaters connections can be ordered using VC418, VC447 or VC568.

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Copyright 2006 ABB
Variant code description Valid 3GZF500930-245 C
2013-05-20 3(4)

Connection point and connection diagram M3BP

M3BP 71-132 M3BP 160-250

Connection diagram of motor with


two heating resistors
M3BP 280-450

Connection point and connection diagram M3AA

M3AA 71-132 M3AA 160 M3AA 180-280

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Copyright 2006 ABB
Variant code description Valid 3GZF500930-245 C
2013-05-20 4(4)

Connection point and connection diagram M2BA

M2BA 71-132 M2BA 160-250

Connection diagram of motor


with two heating resistors

M2BA 280-355

Connection point and connection diagram M2AA

M2AA 71-132 M2AA 160-180 M2AA 200-250

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Copyright 2006 ABB