SPECIFICATION IDENTIFICATION

CALORIMETRIC FLOW
DOCUMENT 2016052-DI05-500
DETECTOR PAGES 1 OF 1
DATA SHEET REV. BY CHK APPR. DATE
A PMF AGB PAR Mar-2017
0 PMF AGB PAR Ago-2017
1 PMF AGB PAR Sep-2017
INGENIERA DE DETALLE DE EQUIPOS Y PROCESO EC PROJECT
PROJECT
PARA EL PROYECTO MAQUI - ECOLAB EQ PROJECT 2016052-EC

1 TAG NO. FE/FT-501 FE/FT-512


2 SERVICE Discharge Pump P-501A/B Discharge Pump P-052/053
3 GENERAL P&ID 2016052-PID-501 2016052-PID-512_1
4 INFORMATION
5
6
7 FLUID Soft Water Hot Water
8 LINE 6"-SW-5A-0-5110 4"-HWS-4F-3AA-6219
9 TEMPERATURE MIN / NORM / MAX, C 10 20 65 20 60 80
10 PRESSUR MIN / NORM / MAX, barg 0,1 3,5 5,0 0,1 4,0 6,0
PROCESS DATA
11 FLOW MIN / NORM / MAX, m3/h 10 60 75 10 45 50
12 OPER. SPECIFIC GRAVITY 1,0 @ 25 C 1,0 @ 25 C
13 OPER. VISCOSITY, cP 1,0 cP 1,0 cP
14
15 TYPE Insertion Insertion
16 DISPLAY / BLIND Blind Blind
17 SERVICE Soft Water Hot Water
18 FLOW DIRECTION Perpendicular to sensor Perpendicular to sensor
19 WETTED PARTS MATERIAL SS SS
20 ELECTRIC CONNECTION By vendor By vendor
21 PROCESS CONNECTION 1/2" NPT 1/2" NPT
22 MAX. PRESSURE, kg/cm2g 5.0 barg 6.0 barg
23 FLOW RANGE, m3/h 5 - 75 m3/h 5 - 50 m3/h
DESIGN DATA
24 SETTING - -
25 ELECTRICAL CLASSIFICATION General Purpose General Purpose
26 OUTPUT SIGNAL 4 - 20 mA 4 - 20 mA
27 POWER SUPPLY 24 VDC 24 VDC
28 INSERTION LENGTH For 6" PIPE SS For 4" PIPE CS
29 TIME RESPONSE, seconds - -
30 PROTECTION IP 65 / NEMA 4X IP 65 / NEMA 4X
31 INSTALLATION Outdoor Outdoor
32 FUNCTION LED (STATUS)
33
34 MANUFACTURER
PURCHASE
35 MODEL & MFR NUMBER
INFORMATION
36
37

NOTES:
1.- Vendor shall include all accesories to install and operate instrument.
2.- Vendor shall include nameplate with TAG number.
3.- Vendor shall include quality certificates and technical documentation.

Basado en formato ISA S20.41a