Вы находитесь на странице: 1из 14

_______________________

Last Name, First


CHE426: Problem set #9
1. A circulating chilled-water system is used to cool an oil stream from 90 to 70oF in a tube-
in-shell heat exchanger. The temperature of the chilled water entering the process heat
exchanger is maintained constant at 50oF by pumping the chilled water through a cooler
located upstream of the process heat exchanger.
The design chilled-water for normal conditions is 1000 gpm, with chilled water
leaving the process heat exchanger at 60oF. Chilled-water pressure drop through the process
heat exchanger is 15 psi at 1000 gpm. Chilled-water pressure drop through the refrigerated
cooler is 15 psi at 1000 gpm. The heat exchanger area of the process heat exchanger is 1143
ft2.
The temperature transmitter on the process oil stream leaving the heat exchanger has
a range of 50-150oF. The range of the orifice-differential pressure flow transmitter on the
chilled water is 0-1500 gpm. All instrumentation is electronic (4 to 20 mA). Assume the
chilled-water pump is centrifugal with a flat pump curve (total pressure drop across the
system is constant).
1) Assuming linear trim determine Cv for the chilled-water control valve that is 25
percent open at the 1000 gpm design rate and has a maximum flow of 1500 gpm.
2) Determine values of the signals from the temperature transmitter, temperature
controller, and chilled-water flow transmitter when the chilled-water flow is 1000
gpm.
3) Determine the pressure drop over the chilled-water valve when it is wide open.
4) Determine the pressure drop and fraction open of the chilled-water control valve
when the chilled-water flow rate is reduced to 500 gpm. Determine the chilled-water
flow transmitter output at this rate.

Elevation 20' Tank at atmospheric


pressure

Elevation 15' Circulating chilled water

Hot oil
Refrigerant 90oF
FT
o
50 F Heat
Elevation 0' Cooler exchanger

Cooled oil
70oF
TT TC
Solution

1) Determine Cv for the chilled-water control valve

Cv = 605.5 gpm/psi0.5

PT = 73.64 psi

2) Determine values of the signals from the temperature transmitter, temperature


controller, and chilled-water flow transmitter

Temperature transmitter

PMT = 7.2 mA

Temperature controller

CO = 12 mA

Flow transmitter
PMF = 11.11 mA

3) Determine the pressure drop over the chilled-water valve when it is wide open

Pv = 6.14 psi

4) Determine the pressure drop and fraction open of the chilled-water control valve
when the chilled-water flow rate is reduced to 500 gpm. Determine the chilled-water
flow transmitter output at this rate.

Pv = 66.14 psi

PMF = 5.78 mA
2. Consider the two-tank, interacting liquid-level system shown below and its block diagram.
The data for the system are: A1 = 1 ft2, A2 = 0.5 ft2, R1 = 0.5 ft/cfm, R2 = 2 ft/cfm, and R3 = 1
ft/cfm.
m1 m2

c1
c2
R1 R2

A1 R3 A2

M1 + C1
G11(s)
+
G21(s)

G12(s)
+
M2 + C2
G22(s)

The transfer functions G11, G21, G12, and G22 are given as:

s5 4
G11 = G12 =
( s  1)( s  7) ( s  1)( s  7)

4 s3
G21 = G22 =
( s  1)( s  7) ( s  1)( s  7)

Use Simulink to obtain the response of c1 and c2 for (a) M1 = 1/s, M2 = 0, and (b) M1 = 0, M2
= 1/s.
Solution

Figure E-1 Simulink model for the two-tank system.


Figure E-2 Response for step change in tank 1, M1 = 1/s, M2 = 0

Figure E-3 Response for step change in tank 2, M1 = 0, M2 = 1/s


3.1 A tank is heated by steam condensing inside a coil. A PID controller is used to control the
temperature in the tank by manipulating the steam valve position. Derive the complete block
diagram and the closed-loop transfer function from the following design data.

Process. The feed has a density  of 68.0 lb/ft3 and a heat capacity cp of 0.80 Btu/lboF. The
volume V of liquid in the reactor is maintained constant at 120 ft3. The coil consists of 205 ft
of 4-in. schedule 40 steel pipe that weighs 10.8 lb/ft and has a heat capacity of 0.12 Btu/lboF
and an outside diameter of 4.5 in. The overall heat transfer coefficient U, based on the
outside are of the coil, has been estimated as 2.1 Btu/minft2oF. The saturated steam is
available at 30 psia; it can be assumed that its latent heat of condensation  is constant at 966
Btu/lb. It can also be assumed that the inlet temperature Ti is constant.

Design Conditions. The feed flow F at design condition is 15 ft3/min, and its temperature Ti
is 100oF. The contents of the tank must be maintained at a temperature T of 150oF. Possible
disturbances are changes in feed rate and temperature.

Temperature Sensor and Transmitter. The temperature sensor has a calibrated range of
100 to 200oF and a time constant T of 0.75 min.

Control Valve. The control valve is to be designed for 100% overcapacity, and pressure drop
variation can be neglected. The valve is an equal percentage valve with a rangeability
parameter  of 50, f(x) = x-1 = 50x-1. The actuator has a time constant v of 0.20 min.

a) Determine the parameters listed in the following table

Parameters for stirred tank heater.


A 241.5 ft2  4.93 min
CM 265.7 Btu/oF c 0.524 min
KF  2.06 F/(ft /min)
o 3 Kw o
1.905 F/(lb/min)
o o
Ks 0.383 F/ F KT 1.0 %TO/ oF
Kv 1.652 (lb/min)/ %CO v 0.20 min
T 0.75 min
b) Use simulink to simulate the temperature response to a step change in both set point
and flow rate with a PID controller for two reset rates of 0.5 min-1 and 1.0 min-1, Kc =
2, and D = 1 min.

Solution

b)
255
4. A liquid stream enters tank 1 at a volumetric flow rate F in cfm and contains reactant A at
a concentration of C0 [mol A/ft3]. Reactant A decomposes in the tanks according to the
irreversible chemical reaction

AB

The reaction is first order with reaction rate constant k1 and k2 for tank 1 and tank 2
respectively. The reaction is to be carried out in a series of two continuous stirred-tank
reactors. The tanks are maintained at different temperatures with tank 2 at a higher
temperature. We will neglect any changes in physical properties due to chemical reaction.

The purpose of the control system is to maintain C2, the concentration of A leaving tank 2 at
some desired value in spite of variations in the inlet concentration C0. This will be
accomplished by adding a stream of pure A to tank 1 through a control valve using a
proportional controller. A portion of the liquid leaving tank 2 is continuously withdrawn
through a sample line at a rate of 0.1 cfm. The sample line has a length of 50 ft and the cross-
sectional area of the line is 0.001 ft2.

Controller
Pure A

F, C0 F+m/A (Set point )

Composition
V, T1 V, T2 measuring
C1, k1 C2, k2 element
Sample stream
Product stream

Heating coil

Data: MwA = 100, A = 0.8 lbmol/ft3, C0s = 0.1 lbmol/ft3, F = 100 cfm, ms = 1.0 lbmol/min, k1
= 1/6 min-1, k2 = 2/3 min-1, V = 300 ft3,  = V/F = 3 min.
1 mA
Kv = cfm/psi, Km = 400 , KT = 0.75 psi/mA, d = 0.5 min
6 lbmol/ft 3

a) Use simulink to obtain the response to a unit step change in both the set point and the
inlet concentration C0 for Kc = 2.
b) Find the value of Kc at which the system will have a sustained oscillation.

Solution
Response with Kc = 2
Response with Kc = 7.75
5.2 For the control system shown, determine the ISE, ITAE, and IAE for a unit-step load
disturbance. Let the controller be a PID controller with Kc = 6, I = 4, and D = 4.
load

+
+  Controller +
Gc 1/(10s2 + 11s + 1)
Set point - Controlled
variable
Error

Measured variable exp(-s)

Solution -----------------------------------------------------------------------------------------
6.2 Determine the Z-N and the C-C settings for the PI control system shown below.

Solution

The format of the PID controller block from Simulink is Gc,Simulink(s) = K + I/s + Ds. Without
integral and derivative actions, I = 0 and D = 0.

Figure E-1 Simulink model to determine Ku and Pu.

A sustained oscillation is obtained when Ku = 1.6. From Figure E-2, the ultimate period Pu =
2.8.

Figure E-2 Closed loop response to change in set point


Kc = 0.72

I = 2.33

Kc = 0.5333

I = 0.7347

7.1 The formula for the flow of saturated steam through a control valve is

msteam (lb/h) = 2.1Cvf(x) P12  P22

In this equation, P1 is upstream pressure (psia) and P2 is downstream pressure (psia). The
temperature of the steam-cooled reactor shown below is 285oF. The heat that must be
transferred from the reactor into the steam generation system is 25×106 Btu/h. The overall
heat transfer coefficient for the cooling coils is 300 Btu/hft2oF. The steam discharges into a
25-psia steam header. The enthalpy difference between saturated steam and liquid condensate
is 1000 Btu/lb. The vapor pressure of water can be approximated by

T(oF) = 195 + 1.8P (psia)

To steam
Reactor header

Steam
drum
Cooling Condensate
Feed coils

Product

For questions (1) and (2) the drum pressure is 40 psia.


a) Calculate the area of the cooling coils.

b) Calculate the Cv for the steam valve, assuming that the valve is half open at the design
conditions: f(x) = 0.5.

c) If Cv = 700 lb/hpsia, and the temperature of the drum at the maximum heat removal
(Qmax) of the system is 257.1oF, determine Qmax in Btu/h

Solution

a) Calculate the area of the cooling coils 4630 ft2


b) Calculate the Cv for the steam valve, assuming that the valve is half open at the
design conditions: f(x) = 0.5.

Cv = 762 lb/hpsia

c) If Cv = 700 lb/hpsia, and the temperature of the drum at the maximum heat removal
(Qmax) of the system is 257.1oF, determine Qmax in Btu/h

Qmax = 34.95×106 Btu/h

8. Consider the following control system with U(s) = 5/s, Kc = 4 and D = 2.

a) Determine C(t = 1.25)

C(t = 1.25) = 0.5559

b) Determine the offset.

C(∞)  R(∞) = 1.25

9. Consider the following control system

R(s) + C(s)
Kc 1/(8s + 1)2
- +

1/(1 + s)
Calculate the ultimate gain.

Kcu = 20.2500
10. Consider a tank in which a solution (w1, x1) containing 10 weight % salt is blended with a
concentrated solution (w2, x2) containing 42 weight % salt, to produce 100 lb/h of a solution
(w, x) containing 20 weight % salt at design conditions.

SP SP
m1
AC FC

w1, x1 V AT FT
m2

x w

w2, x2

a) Determine the open loop steady state gain on the mass percent of salt in the product stream
for an increase of 2.0 lb/h in w2

Kx2 = 0.2155 % salt/(lb/h)

b) Determine the closed loop steady state gain on the mass percent of salt in the product
stream for an increase of 2.0 lb/h in w2 (and w1 is reduced by 2.0 lb/h).

Kx2,closed = 0.32 % salt/(lb/h)

References

1. Process Modeling, Simulation, and Control for Chemical Engineers by Luyben


2. D.R. Coughanowr and S. LeBlanc, Process Systems Analysis and Control, McGraw-
Hill, 3nd edition, 2008.

Вам также может понравиться