NO DESCRIPTION
X : NO
Perform usually inspection of valve body for any abnormalities (erosion/corrosion) on the
1
outside of the valve. Check the mounting bolts for any corrosion. Retighten if necessary.
Inspect Air Instrument connection / tubing, Tube fittings, Quick Exhaust and Cylinder’s
3 seals for leak. Use SNOOPY (Soap solvent) to confirm any leaking on them and repair or
replace as necessary.
Inspect the limit switches for micro switches and cable terminals condition.
4
Clean up/replace and retighten if necessary.
Inspect the Solenoid Valve and its wiring connection in junction box for loosing and
5
corrosion. Clean up and retighten as necessary, and record the Ohm Resistance (mm Ω).
Inspect instrument air supply Pressure Regulator for proper functionality to supplying
pressure as per Valve operating pressure.
6
Adjust pressure setting as necessary refer to Valve operating pressure and repair or
replace if it is worn out, inspect local Press Gauge. Replace if necessary.
Do stroke & loop tests. Observe and record for any jerk during travelling. Ensure that any
process/line related is dated or free from hazard during function test. Calibrate if need.
7
Activation from engineering work station can perform for individual control valve
performance test.
Check the full opening and closing position are within travel scales with the set
8 pressure of 0% and 100%
For Control Valve with positioner, check the positioner level is parallel with slide
9 rail at 50% open of valve. Adjust as per Manufacturer’s Instruction if necessary.
Check positioner operating pressure and ensure correct supply
10 Supply input signal of 0%, 25%, 50%, 75% and 100% of range. Record
corresponding % opening / closing.
The tolerance for valve w/ positioner shall be; linearity ± 1.030, hysteresis ±1.0%.
11
Ensure all control valves have been inspected and function tested and report to your
12
Supervisor if found any abnormal condition or function to be followed up.
Page 1 of 3
PM Checklist
√ : OK
NO DESCRIPTION X : NO
Remove any surface rust or corrosion that may inhibit valve operation and coat any exposed
1
parts with anti-rust compound
Using the Gas Leakage Detection device (ultrasonic test), check all external leak paths from
2
the valve, including flange joints, stem or gland seals and ancillary piping and connections.
√ : OK
NO DESCRIPTION X : NO
Function valve configuration locally (if process conditions permit). This should be repeated 3
1
times. Confirm correct and smooth valve operation
2 Ensure local indicator is showing correct position as per regulating requirements
Page 2 of 3
PM Checklist
Approval
Revision # Revised by Approved by Description
Date
Page 3 of 3