Sizing the Generator

Three Phase Power


Power Generator Formulas

www.dieselserviceandsupply.com
Amperage of 3 Ph Generators
Amperage (120/208 3-Ph, 80% PF)

KW x 1000
E x PF x 1.73

30 KW Generator = 30,000 = 104


AMPS
208 x .8 x 1.73
Amperage of 3 Ph Generators
80% Power Factor

www.dieselserviceandsupply.com
Amperage of 1 Ph Generators
Amperage (120V- 1-Ph, 80% PF)

KW x 1000
E x PF

30 KW Generator = 30,000 = 312


AMPS
120 x .8
Compare 3 PH to 1 PH

Both Generators produce the


same amount of total POWER –
WATTS – but in completely
different methods of delivery.
Example
Assume:
•Charger is set
at 30 amps.
•Lab Loads will
be 15 amps
•Total expected
amp draw – 45
amps
•Everything here
is single phase.
Example
• We need to supply 45 amps to the Inverter /
Battery / Lab Load system from a generator.
• We would probably select a minimum 15 KW
three phase generator, producing 52 amps (per
phase).
• (single phase generators over 5 kw are often
hard to find.)
• Most often the difference between three phase
and single phase is not considered.
The result:
Other likely Scenarios
• For expediency, a ministry purchases a
trainload of 30KW, 3PH generators.
– Good discount
– 30 KW sounds plenty big enough
– Not sure of the application (single phase,
three phase, 240V, inverter, no inverter???
• Result: Much more fuel is burned, or
health services are not provided because
fuel can not be afforded.
Discussion Topics

• Suggested Solutions?

• What does unbalancing do to a generator?

• Questions for Generator representative?