Power system studies for Relay

Coordination
AD220-705-G-04770-Rev-B

ANNEX 5.4.1.4 –711-ESWGR-1101 SETTING TABLE

GTP and AP and SP - LV SWGR relay setting table shall be


revised and updated in line with next page - HHI comments.
Delete ETAP comments
thermal trip setting shall be "rated current on cable feeder ampacity
in Amp" x 1.15(typical for UMC). and contactor withstand
"Rated current in Amp" shall use Efficiency capacity(typical all)
and Power Factor of load list.(typical for all
MCCB feeders including motor and power
feeders including UPS feeders also). motor feeder is only applicable.(typical
thermal protecton shall be performed by UMC. for UMC).
MCCB thermal protection shall be N/A(typical).

Over Current Relay Universal motor Controller CEM 11 Release


Therma Magnetic
DMT DMT l Trip
Rated RATED IDMT Setting (51) IDMT Setting (51G) Thermal (49) Jam Ground ELM Long Time Short Time Instant
seting(50) seting(50G)
C/T contact Cubicle Circ Circuit Circuit Breaker Protection
Sl NO Volt Tag From Tag to Bus Feeder discrepation Load CURRENT Load Type Trip in
Detail or Type No type Type Relay Trip = Ext. (Ie)
Kw IN AMP
% of Sec
Pick Multiple Trip CT4L Pri % of Delay Delay milli LT LT ST ST Inst
Pickup TMS Curve Pickup TMS Curve Delay Pickup Delay Trip Trip % of Ie Remark
up of Trip class current Trip Ie in sec in sec Amp pickup Band pickup Band pickup
unit Amp
unit factor AMP
setting
IEC IEC
Incomer from (0.8 800 E3V 1250AF 4P,
1 415 711-ETR-1101/A 711-ESWGR-1101 A 1067 Feeder 1250/1 N/A +A01 ACB_I RET620 0.9 0.55 NORMAL 0.1 0.31 NORMAL 3 0.27 D/A D/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
MVA) Tranformer (kVA) PR121/P LI
INVERSE INVERSE
IEC IEC
Incomer from (0.8 800 E3V 1250AF 4P,
2 415 711-ETR-1101/B 711-ESWGR-1101 B 1067 Feeder 1250/1 N/A +B01 ACB_I RET620 0.9 0.55 NORMAL 0.1 0.31 NORMAL 3 0.27 D/A D/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
MVA) Tranformer (kVA) PR121/P LI
INVERSE INVERSE
IEC IEC
711-ESWGR-1101 711-ESWGR-1101 800 E3V 1250AF 4P,
3 415 A/B Bus Coupler 1067 Feeder 1250/1 N/A +AB00 ACB_T REF620 0.9 0.55 NORMAL 0.1 0.31 NORMAL 3 0.27 D/A D/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Bus A Bus B (kVA) PR121/P LI
INVERSE INVERSE
IEC
E3V 800AF 4P, IE C DEF
4 415 711-ESWGR-1101 711-HVAC-1101 A 415V HVAC MCC 246.51 498.9904 Feeder 800/1 N/A +A02 ACB_F REF620 0.75 0.91 NORMAL 0.1 0.2 3.3 0.1 D/A D/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
PR121/P LI TIME
INVERSE
PEDESTAL CRANE - 711- XT2L 160 TMA
5 415 711-ESWGR-1101 711-JB-2122 A 22 50 Feeder N/A AF52 +A04JD01 4CF UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 8 10 1 50.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
CR-1101 R50
PRE MAGNETIZATION Contactor capacity needs to be
T5L 400 PR221DS-
6 415 711-ESWGR-1101 711-TR-1101/A A PANEL FOR 132/34.5kV 200 400 Feeder N/A AF305 +A03UD01 4CF UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A 10 125 400 3.2 200 3.9 20 0.1 13600 N/A N/A N/A N/A 8 reviewed for contactor making
LS/I In 400
TRANSFORMER (711- capacity and Cable installed ampacity
PRE MAGNETIZATION
Cable installed ampacity is less than
PANEL FOR 33/11.5kV XT4L 250 Ekip LS/I
7 415 711-ESWGR-1101 711-TR-1102/A A 100 250 Feeder N/A AF265 +A05UD01 4CF UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A 10 77.5 250 3.2 200 3.9 20 0.1 13600 N/A N/A N/A N/A 8 feeder rated current. Need to be
TRANSFORMER (711- In 250
reverified.
TR-1102/A)
33/11.5KV XT2L 160 TMD
8 415 711-ESWGR-1101 711-TR-1102/A A 9 20 Feeder N/A AF52 +A03LD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
TRANSFORMER - OLTC R20
132/34.5KV
XT2L 160 TMD
9 415 711-ESWGR-1101 711-TR-1101/A A TRANSFORMER - 9 20 Feeder N/A AF52 +A05QD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
R20
OLTC/FAN
132KV, 26MVAR
XT2L 160 TMD
10 415 711-ESWGR-1101 711-SR-1101/A A SHUNT REACTOR - 9 20 Feeder N/A AF52 +A03JD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
R20
OLTC
Cable installed ampacity is less than
110VDC UPS (CABINET XT4L 250 Ekip LS/I
11 415 711-ESWGR-1101 711-UPS-1102/B B 26.4 250 Feeder N/A AF265 +B06LD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A 10 1 250 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A 8 feeder rated current. Need to be
B) In 250
reverified.
IEC
E3V 800AF 4P, IE C DEF
12 415 711-ESWGR-1101 711-HVAC-1101 B 415V HVAC MCC 246.51 498.9904 Feeder 800/1 N/A +B02 ACB_F REF620 0.75 0.91 NORMAL 0.1 0.2 3.3 0.1 D/A D/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
PR121/P LI TIME
INVERSE
Contactor capacity needs to be
PRE MAGNETIZATION
reviewed for contactor making
PANEL FOR 132/34.5kV T5L 400 PR221DS-
13 415 711-ESWGR-1101 711-TR-1101/B B 200 400 Feeder N/A AF305 +B04UD01 4CF UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A 10 125 400 3.2 200 3.9 20 0.1 13600 N/A N/A N/A N/A 8 capacity and Cable installed ampacity
TRANSFORMERS (711- LS/I In 400
is less than feeder rated current. Need
TR-1101/B)
to be reverified.
PRE MAGNETIZATION
Cable installed ampacity is less than
PANEL FOR 33/11.5kV XT4L 250 Ekip LS/I
14 415 711-ESWGR-1101 711-TR-1102/B B 100 250 Feeder N/A AF265 +B06UD01 4CF UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 N/A 10 77.5 250 3.2 200 3.9 20 0.1 13600 N/A N/A N/A N/A 8 feeder rated current. Need to be
TRANSFORMER (711- In 250
reverified.
TR-1102/B)
33/11.5KV XT2L 160 TMD
15 415 711-ESWGR-1101 711-TR-1102/B B 9 20 Feeder N/A AF52 +B04LD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
TRANSFORMER - OLTC R20
132/34.5KV
XT2L 160 TMD
16 415 711-ESWGR-1101 711-TR-1101/B B TRANSFORMER - PRE 9 20 Feeder N/A AF52 +B06QD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
R20
MAG
132KV, 26MVAR
XT2L 160 TMD
17 415 711-ESWGR-1101 711-SR-1101/B B SHUNT REACTOR - 9 20 Feeder N/A AF52 +B04JD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 FIXED 10 1 20.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
R20
OLTC
110V DC UPS (CHANGE XT2L 160 TMA R
18 415 711-ESWGR-1101 486-ZZZ-1101 B 18.4 50 Feeder N/A AF52 +B05JD01 4F UMC 100.3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 100 8 10 1 50.0 -- 200 3.9 20 0.1 N/A N/A N/A N/A N/A N/A
OVER SWITCH) 50