Вы находитесь на странице: 1из 4

LOW VOLTAGE  &  HIGH VOLTAGE 

FCMA SOFT STARTER
FCMA  SOFT STARTER

Application Areas :-

 Water Supply.  Chemical  Mines.


 Sewage.  Fertilizer  Steel Plant.
 Irrigation.  Pharmaceuticals  Cement Plant
 Textile Industries.  Petrochemical  Aluminium Plant
 Air Conditioning  Oil Refineries  Copper Plant
 Chillers  Paper  Rolling Mill.
 Sugar Industry  Tyre & Rubber Industry.  Material Handling

Range – 50 to 15000 KW, Voltage – 380 V to 15 KV, 3Ph.

A Fresh Approach to Power & Energy
ELTECH ENGINEERING,
ENGINEERING, PUNE , INDIA
Features :-
 Low starting current.

 Amplitude
p control.

 Sinusoidal Waveform – No harmonics.

 Rugged magnetic design.

 Built in bypass for full run voltage.

 Can be designed for multi motor starting.

 Available with Line side or Neutral side models for HT Motors

 Can be supplied in Open Execution for panel builders.

 Non Electronic.

 Suitable for extreme weather conditions.

 Indoor and outdoor models.

 CNC fabricated enclosures with powder coating.


coating

Advantages :-
 User Friendly, Simple for Installation & operation.

 S ft Stepless
Soft, St l acceleration.
l ti

 Reduced inrush current & mechanical shock, which increases the Motor &
Equipment life.

 Capital cost saving in power systems.

 Starting of motors on limited Power.

 Starting of motors on Gensets.

 No maintenance required.

A Fresh Approach to Power & Energy
ELTECH ENGINEERING,
ENGINEERING, PUNE , INDIA
Operating Principle
FCMA type Magnetic Soft Starter offers series impedance in the motor
circuit Usually constructed as a coil around core of high permeability
circuit.
than that of air, increases the magnetic field there by increasing the
required starting impedance. Thus it reduces the starting current &
torque of the motor & ensures the smooth starting.
ZSS – Soft Starter Impedance.
ZM – Motor Impedance.
Impedance
ZT – Total Impedance.
ZSS + ZM = ZT VSS – Voltage across Soft Starter.
VSS + VM = Vn VM – Voltage to Motor.
Vn – Applied Voltage.

As motor speed increases due to counter emf feedback the starter


i
impedance
d d
decreases, so the
th voltage
lt d
drop across the
th Soft
S ft Starter.
St t Thi
This
results in incremental voltage & torque to the motor. As motor reaches to
full speed the built in bypass device closes to ensure the full running
voltage to the motor. The operation of bypass device can be done
through the set value of acceleration time, current or rated speed.

Typical Curves

2.5 7.0
A
6.0
2.0
A - Motor current p.u.DOL
R CURRENT (P.U.).

5.0 B - Motor torque p.u. DOL


B
1.5 C - Motor torque p.u. SS
RQUE (P.U.).

4.0
D
D - Motor current p.u SS
3.0
1.0
E - Load torque
TOR

MOTOR

C
20
2.0
0.5 E
1.0

0.0 0.0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
SPEED (P.U.).

A Fresh Approach to Power & Energy
ELTECH ENGINEERING,
ENGINEERING, PUNE , INDIA
LT Soft Starter HT Soft Starter

Products

 Medium and high voltage Soft Starters for  MCC Panels.


Panels
Sq. Cage Motors.  APFC panels.
 Low voltage Soft Starters for Sq. Cage Motors.  Load Banks for Generator Testing.
 Rotor Starters for Slipring Motors.
Data required Applicable Standards

Motor Details (Kw, Ifl ) Motor & load torque speed curve Medium and high voltage FCMA Soft
Driven equipment Motor & load GD2 Starters are designed and manufactured and
Supply voltage Motor current speed curve tested in line with relevant clauses of IEC/
Supply frequency Motor thermal withstand curve BS/ IS standards. The General standards
Starting Current limits Transformer / Genset capacity applicable are IEC34, BS4999, BS5000, IS325
Ambient conditions Voltage drop limits and IS5553 (Part 3).

ELTECH ENGINEERING. Ph. No. +91


+91-- 7588025047, 140

J-316, MIDC, Bhosari,


Bhosari, Pune – 411 026, INDIA. + 91
91-- 8805041023,
E-mail :-
:- eltech.enggs@gmail.com
eltech enggs@gmail com Web site : www.eltech
www eltech-
eltech-engineering.com
engineering com

A Fresh Approach to Power & Energy
ELTECH ENGINEERING,
ENGINEERING, PUNE , INDIA

Вам также может понравиться