Вы находитесь на странице: 1из 12

Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.

2
SC-GCM-62 CM Issue 2 © Copyright 2005 Spirax-Sarco Limited

Module 7.2
Typical Self-acting Temperature
Control Valves and Systems

The Steam and Condensate Loop 7.2.1


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Typical Self-acting Temperature


Control Valves and Systems
Typical self-acting temperature control systems
The required temperature for the system in Figure 7.2.1 is adjusted at the sensor. It is the most
common type of self-acting temperature control configuration, and most other self-acting control
designs are derived from it.

Temperature Set temperature knob


control valve

Flow

Valve actuator Capillary Sensor

Fig. 7.2.1 Adjustment at sensor

Figure 7.2.2 illustrates a design which is adjusted at the actuator end of the system. It is worth
noting that this system is limited to 1" (DN25) temperature control valves. This configuration is
useful where the control valve position is more accessible than the sensor position.

Temperature control valve

Flow

Valve actuator Capillary

Sensor

Set temperature knob


Fig. 7.2.2 Adjustment at actuator

7.2.2 The Steam and Condensate Loop


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Figure 7.2.3 depicts a third configuration which is similar to the one in Figure 7.2.1 but where
the adjustment is located between the sensor and the temperature control valve actuation. This
type of system is referred to as remote adjustment, and is helpful when either the control valve
or the sensor, or both, are likely to be inaccessible once the control valve has been installed.
Temperature control valve

Flow

Valve actuator Capillary Sensor

Set temperature knob

Fig. 7.2.3 Remote adjustment

Capillaries
It should be noted that capillaries of 10 metres or more in length may slightly affect the accuracy
of the control. This is because a larger amount of capillary fluid is subjected to ambient
temperature. When the ambient temperature changes a lot, it can affect the temperature setting.
If long lengths of capillary are run outside, it is recommended they are lagged to minimise this effect.
Pockets
Pockets (sometimes called thermowells) can be fitted into pipework or vessels. These enable the
sensor to be removed easily from the controlled medium without the need to drain the system.
Pockets will tend to slow the response of the system and, where the heat load can change
quickly, should be filled with an appropriate conducting medium to increase the heat transfer to
the sensor.
Pockets fitted to systems which have relatively steady or slow changing load conditions do not
usually need a conducting medium. Pockets are available in mild steel, copper, brass or stainless
steel. Long pockets of up to 1 metre in length are available for special applications and in glass
for corrosive applications. However, these longer pockets are only suitable for use where the
adjustment head is not fitted at the sensor end.

The Steam and Condensate Loop 7.2.3


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Enhancements for self-acting temperature control


systems
Overheat protection by a high limit cut-out device
A separate overheat protection system, as shown in Figure 7.2.4, is available to comply with
local health and safety regulations or to prevent product spoilage. The purpose of the high limit
cut-out device is to shut off the flow of the heating medium in the pipe, thereby preventing
overheating of the process. It was originally developed to prevent overheating in domestic hot
water services (DHWS) which supply general purpose hot water users, such as hospitals, prisons
and schools. However, it is also used for industrial process applications.

Temperature
control valve
Storage
Calorifier
Flow

Adjustable
temperature
sensor

High limit Fail-safe


cut-out actuator
unit unit

Fig. 7.2.4 High limit cut-out unit with fail-safe control system

The system is driven by a self-acting control system, which releases a compressed spring in the
high limit cut-out unit and snaps the isolating valve shut if the pre-set high limit temperature is
exceeded.
The fail-safe actuator unit does not drive the control valve directly, but a shuttle mechanism in
the high limit cut-out unit instead. When the temperature is below the set point, the mechanism
lies dormant. A certain amount of shuttle travel is allowed for in either direction, to avoid spurious
activation of the system.
However, when the system temperature rises above the adjustable high limit temperature, the
actuator drives the shuttle, displacing the trigger, which then releases the spring in the high limit
cut-out unit. This causes the control valve to snap shut. Once the fault has been rectified, and
after the system has cooled below the set temperature, the high limit cut-out can be manually
reset, using a small lever. The system can also be connected to an alarm system via an optional
microswitch.
The high limit system also has a fail-safe facility. If the capillary is damaged and loses fluid, a
spring beyond the shuttle is released, pushing it the other way. This will also activate the cut-out
and shut the control valve.
The trigger temperature can be adjusted between 0°C and 100°C.

7.2.4 The Steam and Condensate Loop


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

The fail-safe actuator unit shown in Figure 7.2.5 is only suitable for use with a high limit cut-out
unit. The systems shown in Figures 7.2.1, 7.2.2 and 7.2.3 can also be used with the cut-out unit
but they will not fail-safe. Figure 7.2.5 shows the high limit cut-out unit attached to a separate
valve to the temperature control valve. This is preferable because the high limit valve remains
fully open during normal operation and is less likely to harbour dirt under the valve seat. The
high limit valve should be line size to reduce pressure drop in normal use, and should be fitted
upstream of the self-acting (or other) control valve and as close to it as possible.

Separator Temperature
control valve
Steam

Flow
High limit High limit
protection temperature
sensor
High limit Fail-
cut-out unit safe
actuator
unit

Normal
temperature
Condensate sensor
Hot water
storage calorifier

Return

Cold water
make-up

Condensate

Fig. 7.2.5 Typical arrangement showing a high limit cut-out on DHWS heat exchanger

For heating applications, the high limit valve must be fitted in series with the temperature control
valve, as shown in Figure 7.2.5. However, in cooling applications, the temperature control valve
and high limit valve will both be of the normally-open type and must be fitted in parallel with
each other, not in series.
The following valves can be used with the high limit system:
o Two-port valves, normally open for heating systems.
o Two-port valves, normally closed for cooling systems.
o Three-port valves.
Valves having a ball shaped plug cannot be used with the cut-out unit. This is because the closing
operation could drive the ball into the seat and damage the valve.
Also, a double seated valve should not be used with this system because it does not have tight
shut-off.

The Steam and Condensate Loop 7.2.5


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Typical self-acting 2-port temperature control valves

Reverse acting
higher capacity
valve

Normally
open Normally open
medium low capacity
capacity valve
valve

Reverse acting
medium capacity
valve

Bellows
balanced
valve

Double seated
Double reverse acting
seated valve
valve

Fig. 7.2.6 Typical self-acting 2-port temperature control valves

7.2.6 The Steam and Condensate Loop


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Self-acting temperature control ancillaries


Twin sensor adaptor
A twin sensor adaptor, Figure 7.2.7, allows one valve to be operated by a control system with the
option of having a manual isolation facility.
The adaptor can be used with both 2-port and 3-port control valves. The advantage offered by
the adaptor is that the cost of a separate valve is saved. However, it is not recommended that
temperature control and safeguard high limit protection be provided with a common valve, as
there is no protection against failure of the valve itself.
Manual actuator
A manual adaptor as shown in Figure 7.2.8, is designed to be used with 2-port and 3-port
control valves. It can also be used in conjunction with a twin sensor adaptor and a self-acting
temperature control system, allowing manual shutdown without interfering with the control
settings, as shown in Figure 7.2.7
Spacer
A spacer (Figure 7.2.9) enables the system to operate at higher temperatures. Each control valve
and temperature control system has its own limiting conditions. A spacer, when fitted between
the control system and any 2-port or 3-port control valve (except DN80 and DN100 3-port
valves), enables the system to operate at a maximum of 350°C, providing that the control valve
itself is able to tolerate such high temperatures.

Spacer

Twin Fig. 7.2.9


sensor Spacer
adaptor

Fig. 7.2.7
Twin sensor
adaptor

Fig. 7.2.8
Manual actuator

Manual
actuator

The Steam and Condensate Loop 7.2.7


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Typical environments and applications


Environments suitable for self-acting temperature controls:
o Any environment where the sophistication of electrical and pneumatic controls is not required.
Especially suited to dirty and hazardous areas.
o Areas remote from any power source.
o For the accurate control of storage or constant load applications, or for variable load applications
where high accuracy is not required.

Industries using self-acting temperature controls:


Foods
o Milling, heater battery temperature control (non-hazardous).
o Abattoirs - washing down etc.
o Manufacture of oils and fats - storage tank heating.

Industrial
o Metal plating - tank heating.
o Tank farms - heating.
o Refineries.
o Industrial washing.
o Steam and condensate systems.
o Laundries.

Heating, ventilation and air conditioning (HVAC)


o Domestic hot water and heating services in nursing homes, hospitals, leisure centres and
schools, prisons and in horticulture for frost protection.

The most commonly encountered applications for self-acting temperature controls:


Boiler houses
o Boiler feedwater conditioning or direct steam injection heating to boiler feedtank.
o Stand-by generator cooling systems.

Non-storage calorifiers
o 2-port temperature control and overheat protection, (steam or water).
o 3-port temperature control and overheat protection (water only).
o 2-port time / temperature control (steam only).

Storage calorifiers
o 2-port temperature or time / temperature control and overheat protection (steam or water).
o 3-port control and overheat protection (water only).

Injection (or bleed-in) systems


o 2-port or 3-port injection system.

7.2.8 The Steam and Condensate Loop


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Heating systems
o Basic mixing valve and compensating control.
o Zoned compensating controls.
o Basic compensator plus internal zone controls.
o Control of overhead radiant strip or radiant panels.

Warm air systems


o Heater battery control via room sensor, air-off sensor or return air sensor.
o Compensating control on air-input unit.
o Low limit and high limit control.
o Frost protection to a heater battery.

Fuel oil control


o Bulk tank heating coil control.
o Control of line heaters.
o Control of steam tracer lines.

Process control
o Acid pickling tank.
o Plating vat.
o Process liquor boiling tank.
o Brewing plant detergent tank.
o Drying equipment, for example, laundry cabinet or wool hank dryer, chemical plant drying
stove for powder and cake, tannery plant drying oven.
o Continuous or batch process reaction pan.
o Food industry jacketed pan.

Cooling applications
o Diesel engine cooling.
o Rotary vane compressor oil cooler control.
o Hydraulic and lubricating oil coolers.
o Cooling control on cold water to single-stage compressor.
o Closed circuit compressor cooling control.
o Air aftercooler control.
o Air cooler battery control.
o Jacketed vessel water cooling control.
o Degreaser cooling water control.

The Steam and Condensate Loop 7.2.9


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Special applications
o Control for reducing fireside corrosion and thermal stress in LTHW boilers.
o Hot water cylinder control.
o Temperature limiting.

Applications for the high limit safeguard system


o Preventing temperature overrun on hot water services, or heating calorifiers, in accordance
with many Health and Safety Regulations. Good examples include prisons, hospitals and schools.
An optional BMS / EMS interface to flag high temperature trip is available.

7.2.10 The Steam and Condensate Loop


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

Questions

1. Where is a self-acting temperature control system adjusted?


a| Locally to the control valve ¨
b| Locally to the sensor ¨
c| Remotely, at a point between the control valve and sensor ¨
d| Any of the above ¨

2. Why are sensor pockets sometimes used?


a| To protect the sensor from overheating ¨
b| To allow the sensor to be removed without draining the system ¨
c| To contain any leakage of liquid fill from the sensor ¨
d| To enable small sensors to fit into large diameter pipes ¨

3. How can fail-safe temperature protection be achieved?


a| By fitting two control valves in series ¨
b| By fitting a proprietary spring-loaded actuator and control valve ¨
c| By setting the control system at a lower temperature ¨
d| By fitting a cooling valve in parallel with the heating valve ¨

4. What does a proprietary fail-safe protection device do?


a| It protects the control valve from high operating temperatures ¨
b| It protects the steam system from overpressure ¨
c| It protects the water system from overtemperature ¨
d| It allows one valve to act as a control and high limit valve ¨

5. For what application is a self-acting temperature control system not suitable?


a| An application with slow changes in heat load ¨
b| An application in a hazardous area ¨
c| An application with fast and frequent changes in heat load ¨
d| A warm air system such as a heater battery control ¨

6. What is the purpose of a twin sensor adaptor?


a| To close the control valve under fault conditions ¨
b| To allow two control valves to be operated by one controller ¨
c| To allow one control valve to be operated by two controllers ¨
d| To allow both heating and cooling with one valve ¨

Answers
1: d, 2: b, 3: b, 4: c, 5: c, 6: c

The Steam and Condensate Loop 7.2.11


Block 7 Control Hardware: Self-acting Actuation Typical Self-acting Temperature Control Valves and Systems Module 7.2

7.2.12 The Steam and Condensate Loop

Вам также может понравиться