CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA 1

FREE GREEN
GROUND SUBJECT TO DAMAGE FROM
WIND SEISMIC WINTER ICE SHIELD www.FreeGreen.com
SNOW FLOOD
SPEED DESIGN DESIGN UNDERLAY 348 MEDFORD ST. SUITE 1
LOAD HAZARD CHARLESTOWN, MA 02129
(MPH) CATEGORY TEMP REQUIRED
(LB) WEATHERING FROST LINE TERMITE DECAY
DEPTH © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

NOTES:

1 THE CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA WILL


VARY BY REGION FOR ANY PROJECT. FOR THIS REASON,
FREEGREEN INC. CANNOT COMPLETE THIS TABLE UNTIL WE
KNOW WHERE THE PROJECT SITE IS LOCATED. ONCE YOU
HAVE A SITE LOCATION, PLEASE INQUIRE INTO OUR DESIGN
SERVICES AT Design@FreeGreen.com

www.FreeGreen.com
BUILDING CODE COMPLIANCE HOUSE AREAS
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129 - Attention CA, OR, WA, and NV residents: Our house plans do not meet Earthquake Seismic/Wind
code requirements. CONDITIONED UN-CONDITIONED
- Attention GA, SC, and NC Coastal residents: Plans may have to be engineered to meet local
Hurricane/Wind codes. CRAWL SPACE: - GARAGE: 577 SF
- Attention AL, AZ, CO, CT, DE, FL, ID, LA, MD, MA, MN, NV, NH, NJ, NY, OH, PN, UT, and VA SUB LEVEL: - BASEMENT: 1613 SF
residents: Plans may have to be engineered to meet local building codes. Please call your local
building department before placing order.
ENTRY LEVEL: 1862 SF ATTIC: 1569 SF
UPPER LEVEL: 2417 SF DECK/PATIO: 256 SF
Some cities and states now require that a licensed architect or engineer review and "seal" a blueprint,
or officially approve it, prior to construction. Prior to application for a building permit or the start of
actual construction, we strongly advise that you consult your local building official who can tell you if
TOTAL: 4279 SF TOTAL: 4015 SF

© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED. such a review is required.


THE ABOVE AREA CALCULATIONS ARE BASED ON THE METHOD LAID OUT IN
ANSI STANDARD Z765

RESIDENCE FOR: BUILDER: ENGINEER: ARCHITECT:


SITE ADDRESS: ADDRESS: ADDRESS: ADDRESS:

PHONE:
E-MAIL:
PHONE:
E-MAIL:
PHONE:
E-MAIL:
PHONE:
E-MAIL:
ARCHITECTURAL
A-00-0 PRODUCT SPECIFICATIONS
A-00-1 GENERAL NOTES
A-00-2 LEED-H RATING SYSTEM CHECKLIST
A-00-3 NAHB GREEN BUILDING STANDARD
A-01-1 ELEVATIONS FRONT
A-01-2 ELEVATIONS RIGHT
A-01-3 ELEVATION REAR
A-01-4 ELEVATION LEFT
A-02-1 ENTRY LEVEL FLOOR PLAN REVISION SCHEDULE:
No. Description Date
A-02-2 UPPER LEVEL FLOOR PLAN
A-03-1 BUILDING SECTIONS
A-04-1 DETAILS 1
A-04-2 DETAILS 2
A-04-3 DETAILS 3
A-04-4 DETAILS 4
A-05-1 FOUNDATION PLAN
A-05-2 ENTRY LEVEL FLOOR FRAMING PLAN
A-05-3 UPPER LEVEL FLOOR FRAMING PLAN
A-05-4 ATTIC FLOOR FRAMING PLAN
A-05-5 ROOF FRAMING PLAN
A-06-1 WINDOW SHADING DETAILS
PROJECT NAME:

NE COLONIAL
ELECTRICAL COVER PAGE
E-01-1 SUB LEVEL ELECTRICAL PLAN PROJECT NUMBER: 10-002
E-01-2 ENTRY LEVEL ELECTRICAL PLAN DATE: Issue Date

E-01-3 UPPER LEVEL ELECTRICAL PLAN DRAWN BY: MY

9/24/2009 10:33:43 AM
CHECKED BY: BU, SH

CVR
SCALE
1. BUILDING MATERIALS 2. DOORS & WINDOWS 3. HVAC 4. FINISHES 5. KITCHEN & BATH 6. LIGHTING & ELECTRONICS 7. APPLIANCES
1-1 2-1 3-1 4-1 5-1 6-1 7-1
GE Appliances
imagination at work
FREE GREEN

CLOTHS WASHER
CEILING FIXTURE
BATHROOM FAN
ENTRY DOOR
Sterritt Lumber Co. Fine Custom Cabinetry for Kitchen and Bath GE - 4.0 Cu. Ft. 26-Cycle King-Size Washer

CABINET
LUMBER

Environmentaly Responsible Paints

PAINT
Sterritt Lumber is a family owned and operated Crystal Cabinets is a manufacturer of fine This washer features HydroMotion technology www.FreeGreen.com
lumber yard serving the Great Boston Area AFM safecoat is the leading provider of custom cabinetry for your kitchen, bathroom that gently removes soils from garments to 348 MEDFORD ST. SUITE 1
and New England. Founded in 1841, Sterritt environmentally responsible, sustainable and and every room in your home. Celebrating 60 limit the wear and tear on your clothes. T CHARLESTOWN, MA 02129
lumber has developed into a full service lumber non-polluting paints, stains, wood finishes, years as a family-owned custom cabinet he HydroHeater feature increases the wash
yard, serving homeowners, building, and manufacturer, we offer a selection of door temperatures to reduce bacteria for a © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
sealers and related green building products.
architects and offering a wide range of products. styles, woods and designer finishes. thorough clean.
NOTES:
1-2 2-2 3-2 4-2 5-2 6-2 7-2
GE Appliances OTHER KOHLER PRODUCTS IN THIS DESIGN:
imagination at work KITCHEN:

CLOTHS DRYER
HANGING LAMP
GARAGE DOOR

COUNTERTOP
CENTRAL AC
Bio Composite Countertops GE - 7.0 Cu. Ft. Super Capacity Gas Dryer
SHEATHING

- Vinatta small Faucet 7.5 K-691-BN


- Undertone Small Sink K-3164

STAIN
EcoTop is one of the newest innovations from This front-load gas dryer features a stylish - HiRise™ wall-mount kitchen pot filler K-7322-4-BS
award-winning green product creator, Joel round door to add a contemporary touch to
Klippert. As a bio-composite surface material your laundry room. It is equipped with dual BAR:
for countertops, tabletops, floors and walls, thermistors and Sensor Dry Plus technology
EcoTop adds practical style in both residential to maintain a consistent amount of heat for - Wellspring® beverage faucet K-6666-CP
and commercial settings. thorough drying.
POWDER ROOM:
1-3 2-3 3-3 4-3 5-3 6-3 7-3
GE Appliances - Cimarron® pedestal lavatory with 8" centers K-2362-8-0
imagination at work - Archer Lavatory Faucet with lever handles K-11076-4-CP
ENGINEERED WOOD

STANDING LAMP
Made from 100% recycled glass and cement to Monogram® 48"Professional Gas Cooktop

COUNTERTOP
MASTER BATH:
STEEL DOOR

create a high performance, green concrete material.

COOKTOP
FURNACE
PolyWhey™ wood finishes

SEALANT
Authentic Professional appearance with - Bancroft® undercounter lavatory K-2319-0
premium-grade, 304 stainless steel with - Purist® wall-mount non-diverter bath spout, 35 D K-14426-CP
Vermont Natural Coatings’ PolyWhey™ wood
smoothly finished edges and large electronic - Purist® bath-, wall-mount high-flow bath valve trim K-T14429-3-CP
finishes enhance the innate beauty of wood
and preserve it with a durable shield that is control knobs. Sealed, dual-flame stacked - Purist faucet with cross handles K-14406-3-CP
burners deliver a full spectrum of heat settings, - Purist Cross Valves x3 K-T14490-3-CP
environmentally safe for those who work with it Made from a composite material that is made from from an ultra-low 140° F simmer to an intense - Purist Thermostatic Valve Trim K-T14488-3-CP
and for those who live with it. 100% post-consumer recycled standard office paper. 18,000 BTUs - WaterTile® 54-nozzle bodyspray K-8002-CP
- Purist Handheld K-978-CP
1-4 2-4 3-4 4-4 5-4 6-4 7-4 - Stillness® adjustable wall-mount bracket K-975-CP
GE Appliances - Pinstripe Door, Right hand Open K-705722-L-SHP
imagination at work
BATH 2
INTERIOR DOOR

WALL FIXTURE

DISH WASHER
COUNTERTOP
FSC Clear Rift & Quarter Swan Oak CaesarStone Quartz Surfaces GE Profile Spacemaker Series
HARDWARE

FLOORING
- Caxton® undercounter lavatory K-2209-0
Comprised of 93% natural quartz, Caesar Fullly Integrated Dishwasher with 7 Wash - Fairfax Widespread Lavatory Faucet K-12265-4-CP

HRV
Allegheny Mountain Hardwood Flooring is
part of Hickman Woods, a family business Stone Quartz Surfaces and Countertops offer Cycles Including SpeedWash/Air-Dry Cycles, - Fairfax Shower and Bath K-T12007-4-CP
whose commitment to sustainable forestry the ultimate combination of form and function. Delay Start, Stainless Steel Tub, Electronic
began before the popularity of “green” and With its stain, scratch, and heat-resistant Controls and ADA Compliant: Requires LAUNDRY ROOM:
before Forest Stewardship Council (FSC) properties, CaesarStone is the ideal choice Custom Panel and Handle.
certification even existed. for care-free countertops. - Sterling by Kohler Utility Sink 995-U-0
- Forté® single-control kitchen sink faucet K-10416-G
1-5 2-5 3-5 4-5 5-5 6-5 7-5

RECESSED FIXTURE
SPECIALTY DOOR

THERMOSTAT

WALL COVER

MICROWAVE
Undertone® undercounter kitchen sink
ROOFING

SINK
Mix and match to suit your needs. Undertone
single-basin sinks give you the design flexibility
you need with the professional look of stainless
steel. Chose one or select two or more
depending on your space consideration
and stylistic preferences.

1-6 2-6 3-6 4-6 5-6 6-6 7-6


GE Appliances
imagination at work

OUTDOOR LIGHTING
DOOR HARDWARE

WATER HEATER

REFRIGERATOR
Monogram Built-In Side by Side Refrigerators
SIDING & TRIM

Residential Security Products Vinnata kitchen sink faucet, Brushed Nickel

PANELING

FAUCET
Monogram's Built-In Side by Side Refrigerators
For over 85 years Schlage has provided MasterClean sprayface Resists hard water are available in widths of 36", 42" and 48".
homeowners with innovative quality security buildup. With the touch of a button, Vinnata Models are available with or without exterior
products. Today, Schlage offers home security pull-down spray faucets provide either an ice and water dispensers. Make a statement
solutions from a wide selection of mechanical aerated stream or a powerful spray. The with a Monogram stainless steel model or
and electronic security locks and accessories high-arch spout is elegantly designed to reach install custom door panels to seamlessly
in touch with modern lifestyles. over the tallest pots. integrate the unit with your custom cabinetry.

1-7 2-7 3-7 4-7 5-7


victoria albert 6-7 7-7
GE Appliances
contemporary, classic & spa baths imagination at work
Spray Polyerethene Foam Insulation

HOME AUDIO
York
INSULATION

WALL OVEN
MONOGRAM 30" Professional Electronic
WINDOWS

CARPET

Convection DOUBLE OVEN


BOILER

Icynene's array of insulation products are Triad Speakers and Home Audio Solutions

TUB
The freestanding York features a deep,
designed to let you have greater control over double-ended bathing well supported by an The General Electric ZET2PMSS Stainless
the indoor environment and are suitable for elegant pedestal base. Triad offers the most complete array of Steel Double Oven is a self-clean oven, with
are suitable for steel- or wood- framed applications-based custom speaker solutions, a capacity of 4.4 cubic feet.
residential or commercial construction. Victoria & Albert is a global brand with a world designed for specific usage, and without
wide reputation for creating beautiful baths. compromise. Made in America.

1-8 2-8 3-8 4-8 5-8 6-8 7-8


WATER PROTECTION

HOME AUTOMATION
WINDOW SHADING

SLIDE IN RANGE
SHOWERHEAD
Home Slicker® Plus Typar® Geothermal Heating and Cooling Systems Purist® 1.75 gpm showerhead Lighting Controls
HEAT PUMP

Home Slicker® Plus Typar® is a cost-effective, WaterFurnace manufactures and sells more
TILE

Conservation without compromise. This PulseWorx is a lighting control system utilizing


labor and material saving, moisture eliminating geothermal systems for homes than anyone showerhead is a true performance only existing wiring. Their patented UPB
rainscreen combined with a water resistive else in the business. They offer a wide variety showerhead for the green-build market. technology streamlines the installation process
barrier. of residential geothermal products. Their The showerhead provides LEED compliance and keeps your costs in control. This flexible
dealers and installers are the most highly with 30% reduction in water consumption and scalable system is backed by an industry
trained in the industry. without sacrificing shower performance. leading Money Back Guarantee.

1-9 2-9 3-9 4-9 5-9 6-9 7-9


GE Appliances PROJECT NAME:
imagination at work
RADIANT FLOORING

NE COLONIAL

SOLAR PANELS

RANGE HOOD
Tropical Hardwood Deck Products Radiant Floor Heating Persuade two-piece elongated toilet with
SKY LIGHTS

GE Monogram® 48" Stainless Steel


DECKING

Dual Flush Technology Professional Hood


TOILET
TRIM

Offers over 50 individual items for decks, A warm welcome every time … WarmlyYours
porches and interior/exterior trim. Blue Star makes comfort easy with a selection of Offers a contemporary design highlighted by 1200 CFM Vertical Exhaust with Dual Blowers,
products exceed all recognized industry premium home heating products, including the skirted trapway. This compact elongated
standards for strength, durability, pest and
rot resistance.
radiant floor heating for tile, carpet, and wood
at competitive prices. Fast and free quotes
model features Dual Flush technology, which
includes a 1.6 gpf and also an eco-friendly,
3 Halogen Lamps with 4 Lighting Levels,
Infrared Warming Lamps, Utensil Racks and PRODUCT
Removable Grease Trays
are available. 0.8-gallon flush option.
SPECIFICATIONS
1-10 2-10 3-10 4-10 5-10 6-10 7-10 PROJECT NUMBER: 10-002
DATE: Issue Date
FIREPLACE OR STOVE
BASEMENT WINDOWS

GARBAGE DISPOSAL
LIGHTING DESIGNER
KITCHEN DESIGNER

DRAWN BY: Author


COMPOSITE

Evolution Excel®

9/24/2009 10:33:18 AM
CHECKED BY: Checker
STONE

Kitchen Views Wolfers Lighting Designers


The Evolution Excel® features the best of
Kitchen Views offers exceptional customer service with talented
designers, exquisite showrooms, and quality products specializing in
quality cabinetry, decorative hardware and countertops our
showrooms offer a range of styles from traditional to contemporary.
When planning lighting for redesigns, renovations and new homes.
Wolfers state-of-the-art lighting solutions and technical expertise will
help bring your project to a higher level by making sure lighting is
integrated and installed the right way, on time and on budget.
InSinkErator's grinding and SoundSeal Plus™
noise-reduction technologies, handling more
volume and more types of food waste while
making 60% less noise than standard
A-00-0
disposers. SCALE
GENERAL REQUIREMENTS: ROUGH CARPENTRY: THERMAL & MOISTURE PROTECTION: ELECTRICAL:
1. Owner / Client Responsibilities: Reference is made throughout these General Notes to 1. Framing: 1. Foundations: 1. Scope: FREE GREEN
responsibilities and standards of care to be fulfilled by those providing services in the development and A. Blocking and Bridging: A. Provide adequate drainage away from walls & foundations. A. Supply all labor, transportation, materials, etc, for installation of complete electrical
construction of this project. Owner / Client shall be responsible for adherence to those requirements by the (1) Stud Walls: Per applicable building code. Full height walls shall have continuous B. Seal all plumbing, electrical and other penetrations of walls and floors and seal joints. system to operate according to the best practices of the trade and including but not
Owner, Builder, Developer, General Contractor, Subcontractors and other professional Consultants not studs from bottom to top plate. C. Slope final grade away from foundation. limited to: Fixtures, appliances, wiring, switches, outlets, television jacks, services,
retained by the Designer. (2) Ceiling Joists: Per applicable building code. Use solid bridging. D. Provide capillary break at all concrete slabs (poly not req. if <20” rainfall; gravel not req. grounds, temporary power, junction boxes, conduit, sub - panels, etc. All work, materials, www.FreeGreen.com
348 MEDFORD ST. SUITE 1
(3) Backing: Provide solid backing at all pendant or surface - mounted electrical for free draining soils = IRC Group 1. etc, to comply with all requirements of all legally constituted authorities having jurisdiction CHARLESTOWN, MA 02129
2. Builder's Set: The scope of this set of plans is to provide a “builder's set” of construction fixtures, rails, grab bars, bath accessories, etc. E. Exterior surface of below grade walls damp proofed or water proofed. including all County and State ordinances. Furnish and install electrical work complete
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
documents and general notes hereinafter referred to as “plans”. After formal review and approval B. Fire stopping: Per applicable building code. F. Slope garage floor towards main vehicle entry. and operable. Verify all material and installation requirements and limitations at fire and
by a licensed engineer and or architect, this set of plans is sufficient to obtain a building permit; C. Stud Walls: Per applicable building code. All studs to have full bearing on plate. All studs G. Foundation cont. footing drain with stone covered with filter fabric, drained to daylight. sound assemblies. NOTES:
however, all materials and methods of construction necessary to complete the project are not to be at 16” O.C. unless noted otherwise. Studs to be sized per requirements of code. H. Basement foundation walls use porous backfill material. B. Provide rubberized asphaltic membrane materials at all penetrations of the water-
necessarily described. The plans delineate and describe only locations, dimensions, types of D. Use continuous, full height studs in accordance with the highest standard of construction I. Provide cont. crushed stone under footings. resistive membrane at exterior walls.
materials and general methods of assembling or fastening. The FreeGreen Specification book and framing practices. J. Provide rigid insulation as specified directly under slab.
received with this plan set specifies the particular products or materials recommended for this E. All angled walls to be at 45 degrees unless noted otherwise 2. Walls: 2. Installation:
home design. The implementation of these plans requires an Owner/ Client/ Contractor thoroughly F. Built up roofs, waterproof balcony decks and exterior horizontal areas are to be framed A. Install windows, doors, exterior cladding, flashings & sealants as detailed in this A. Electrical system installed according to latest version of N.E.C or local code, whichever
knowledgeable with the applicable building codes and methods of construction specific to this with slope to ensure water drainage without ponding. drawing set. is more stringent.
product type and type of construction. G. Provide crickets as indicated and as necessary for proper water drainage and to redirect B. All deck ledgers must be pressure treated material. B. Provide separate circuits each for dishwasher, garbage disposal, refrigerator, washer,
channeled or run off water away from vertical surfaces. C. All penetrations that pass through exterior cladding into structure must be fully sealed. dryer, F.A.U. and microwave oven.
3. Building Maintenance: The exposed materials used in the construction of this project will H. Provide blocking where required to provide uniform surface where flush joists and beams D. Install materials with proper detailing to control degradation from moisture. C. Switched outlets shall be ½ hot.
deteriorate as the completed project ages unless properly and routinely maintained. Owner / are different depths. 3. Roofs: D. Bathroom and Kitchen fans: Install local exhaust systems in all
Client shall provide or cause the development of a plan to keep these exposed materials I. Use mitered joints at fascia splices. A. Ice flashing over sheathing at eaves (except climates CZ1-4). bathrooms and in the kitchen to meet the requirements of section 5 of
protected and maintained. J. Unless otherwise noted, all dimensions to exterior walls are given from inside or outside B. Metal drip edge at all exposed roof decking. ASHRAE Standard 62.2-2007. Design and install fan ducts to meet the
face of rough framing. All dimensions to interior partitions are given from centerline of C. Bituminous membrane at all eaves, valleys & penetrations (not req. if <20” rainfall). requirements of section 7 of ASHRAE Standard 62.2-2007.Exhaust air to
4. Codes: All construction shall comply with the most stringent requirements of all current applicable rough framing. D. Step flashing at all roof/wall intersections & terminated with “kickout” flashing. outdoors and also use ENERGY STAR labeled bathroom exhaust fans.
city, county, state and federal laws, rules, codes, ordinances and regulations. If the General K. Align bottom of all adjacent window and door headers, unless noted otherwise on framing E. Installed system for diverting roof water from house. (e.g. gutters). E. For every bathroom exhaust fan, install an occupancy sensor or an
Contractor or any Subcontractor performs any work in conflict with the above mentioned laws, plan. F. No. 30 roof felt underlayment minimum. automatic humidistat controller or an automatic timer to operate the fan
rules, codes, ordinances and regulations, then the contractor in violation shall bear all costs of 2. Trusses: G. Reduce ice dams: No non-airtight recessed light fixtures in insulated ceilings. for a timed interval after occupant leaves the room or a continuously
repair arising out of the non - conforming work. A. The General Contractor shall have City/ County approved truss plans on the job site prior H. Roof insulation as specified in this drawing set. operating exhaust fan.
to foundation inspection. The Truss Manufacturer shall submit calculations, shop 4. Wet Rooms: F. All fixtures, outlets, receptacles etc., penetrating fire assemblies shall be rated and
5. Permits: The general building permit and plan check shall be secured and paid for by Owner drawings, details, bridging and erection bracing signed by a registered Engineer to the A. Install drains or drain pans to capture leaks under water heaters or use tankless installed to meet the requirements of the building code. Outlet boxes on opposite sides of
/Client. All others permits shall be secured and paid for by the Subcontractor directly responsible. Building Department and Structural Engineer, for their review prior to fabrication. water heaters. fire assembly walls shall be separated by a horizontal distance of at least 24”.
B. Truss manufactures shall provide members of adequate bearing area in such a width to B. Properly install washer and water heater drain pans. G. All equipment installed outdoors and exposed to weather shall be weatherproof.
6. Insurance: The General Contractor and every Subcontractor performing work or providing insure against over - stressing of supporting timber, multiple joists, girders and plates or C. Use highly durable materials in wet areas. H. Provide ground fault circuit interrupters, G.F.C.I., at all baths, garages, out-door and wet
services and/ or materials for the work are required to purchase and maintain in force “All Risk” provide bearing plates and details to do same. D. Install no carpet in kitchens, bathrooms, spa areas, or within 3” of exterior door. area outlets. All branch circuits that supply 125 - volt single - phase, 15 and 20 ampere
Builders Insurance prior to commencement of the work and/ or furnishing labor, services and C. The General Contractor shall coordinate with the Truss Manufacturer, Framing, Electrical, E. Use nonpaper-faced backer board on walls in tub, shower and spa areas. receptacle outlets installed in dwelling unit bedrooms shall be protected by an arc - fault
materials. Each “All Risk” policy shall be in an amount sufficient to cover the replacement value Plumbing and Mechanical Contractors at fire protected areas to maintain required fire 5. Air Infiltration: circuit interrupter(s).
of the work being performed and/ or the labor, services and materials being supplied by the protection without penetrations unless allowed by code and local jurisdiction. A. Install “IC” airtight rated recessed lights in insulated ceilings. I. Each conductor of every system shall be permanently tagged in compliance with O.S.H.A
General Contractor, Subcontractors, Designer, and all professional Consultants. B. Complete air barrier between attic and conditioned space & all penetrations sealed. J. The complete electrical system shall be grounded in accordance with the presently
C. Air filter housings must be airtight to prevent bypass or leakage. adopted edition of the N.E.C., Art. #250. Proper ground requires #4 copper wire, 20' - 0”
7. Insurance: Owner/ Client shall cause the General Contractor and every Subcontractor performing D. Air seal ventilation ductwork. long, embedded into concrete and provide bond to gas or water line.
work or providing services and / or materials for the work to purchase and maintain General FINISH CARPENTRY: 6. Interstitial Condensation: K. Use only competent and skilled personnel and perform all work, including aesthetic as
Liability Insurance. A. Clothes dryers vented outdoors. well as electrical and mechanical aspects to standards consistent with the best practices
1. Scope: B. Insulate all cold water pipes and avoid plumbing in exterior walls. of the trade.
8. Named Products: The Designer makes no guarantee for products identified by trade name or A. Furnish and install all finish carpentry complete, including trim, door frames, paneling and C. >1 Perm finish on inside of exterior walls. L. No alterations to the structural frame, diaphragms, connections or shear panels shall be
manufacturer. shelving. (only req. in hot/humid & mixed/humid climates) made without approval from the Structural Engineer.
B. Installation of finish hardware, bath accessories, cabinet pulls, etc. 7. Heat Loss:
9. Scope: The General Contractor and Subcontractors shall furnish all labor, equipment, and material 2. Workmanship: A. Insulate all ventilation exhaust ductwork (min R-8) outside of the insulated envelope.
indicated on the plans and reasonably inferred or required by the applicable codes. A. All joints shall be tight and true and securely fastened. Corners shall be neatly mitered, B. R-5 slab edge insulation break at foundation wall intersection & R-10 slab edge
insulation outward of any walk-out slab edge.
10. Substitution: Substitutions of specific materials or products listed on the FreeGreen Specification B.
butted, or coped, with nails set and surfaces free of tool marks.
Wood work shall be accurately scribed to fit adjoining surfaces. C. Install insulation wind baffles at attic eave bays.
PLUMBING:
Sheet shall not be made without written authorization by Owner/ Client. The General Contractor C. All work shall be machined or hand sanded, sharp edges and splinters removed, and 8. Ultraviolet Radiation:
and any Subcontractor shall not make the structural substitutions or changes without prior written A. Install materials with proper detailing to control degradation from sun. 1.Scope:
completely prepared for finish. A. Supply all labor, transportation, materials, etc. for installation of complete plumbing
authorization from the structural engineer. D. Full length continuous boards shall be used wherever applicable or specifically noted. 9. Other:
A. Minimum 25-year expected lifetime roof warranty. system to operate according to the best practices of the trade and including but not limited
3. Fitting and Hanging Doors: to: fixtures, hot and cold water piping, exhaust flues, combustion air, gas piping, log
11. Changes: Any addition, deletion, or change in the scope of the work described by the plans A. Each door shall be accurately cut, trimmed, and fitted to its respective frame and B. Define “proper refrigerant charge” to be within 10% of manufacturer recommendations.
shall be by written change order only. Any approval from the building official for a change in the C. Mechanical equipment must be accessible for service, including AC condensate drain lighters, drains, soil and vent piping, hot water heaters, pipe insulation, meters, valves,
hardware with due allowance for painter's finishes. vaults, etc. All materials, work, etc. to comply with all requirements of all legally
work shall be the responsibility of the General Contractor. B. Clearance at the lock and hanging stiles and at the top shall not exceed 1/8”. Clearance pan & trap. REVISION SCHEDULE:
D. Use rigid duct or other methods to keep fan back-pressure below 0.2” for EOV systems. constituted public authorities having jurisdiction including all county and state
at the bottom shall be adjusted for finish floor covering. ordinances. Furnish and install plumbing work complete and operable,
No. Description Date
12. Intention: The General Contractor shall ensure that all labor, materials, equipment and C. Lock stile edges shall be beveled.
transportation shall be included in the work for complete execution of the project. The Designer including trenching and backfilling. Verify all
D. Door shall operate freely, but not loosely, without sticking or binding, without hinge bound material and installation requirements and limitations at fire and sound assemblies.
shall not be responsible for the means and methods of construction. conditions, and with all hardware properly adjusted and functioning. B. Provide rubberized asphaltic membrane materials at all penetrations of the water -
13. Review of Drawings: The General Contractor and all Subcontractors shall review the full content
4. Materials:
A. Door frames: Frames shall be set plumb and true, rigidly secured, and protected during
HEATING, VENTILATION & AIR CONDITIONING: resistive membrane at exterior walls.
of the plans for discrepancies and omissions prior to commencement of work. The General C. Protect pipes from freezing. Place all water lines and waste lines within “conditioned”
the course of construction. 1.Scope: space and where approved thermal insulation is between “line” and unheated area.
Contractor and all Subcontractors shall be responsible for any work not in conformance with the B. Door Stops and Casing: Size and profile as selected by Owner/ Client. A. Supply all labor, transportation, material, etc., for installation of a complete heating and air 2.Installation:
plans or in conflict with any code. C. Exterior Trim: Refer to drawings for exterior trim material & sizes. For wood, medium conditioning system to operate according to all applicable standards and best practices of A. Roughing-in shall be completed, tested and inspected as required by code before closing
dencity overlay (MDO) or fiber cement, all cut sides/faces/edges must be primed and the trade including, but not limited to: mechanical units, ducts, registers, catwalks, grilles, -in with other work.
14. Use of the Drawings: Dimensions take precedence over scaled measurements. Details and painted. If specific product brand is specified on drawings, see manufacturers
sections on the drawings are shown at specific locations and are intended to show general boots, vent pipes, dampers, combustion air, fans, ventilators, refrigerant, etc. All B. Openings in pipes, drains, and fittings shall be kept covered during construction.
specifications and installation instructions. materials, work, etc., to comply with all requirements of all legally constituted public C. Provide solid backing for securing fixtures. All fixtures to be set level.
requirements throughout. Details noted “typical” imply all like conditions treated similarly, unless D. Interior Trim:
noted otherwise. The architectural details shown are intended to further illustrate the visual design authorities having jurisdiction including all county and state ordinances. Furnish and install D. Provide cleanouts at ends of all lines and where required by codes.
(1) Interior Rails: Clear material, finished to match casework. all equipment complete and operable. Verify all material and installation requirements E. Copper tubing shall be fully sweated to fittings.
concept and the minimum recommended weather protection for this project. Building code (2) Window Trim: 1x clear wood to match casework or as noted in drawings (verify
requirements, structural considerations, trade association manuals and publications and product and limitations at fire and sound assemblies. F. Black iron and galvanized steel pipe joints shall be made with approved pipe thread
with Owner/Client). B. Provide rubberized asphaltic membrane materials at all penetrations of the water - compound.
manufacturer's written instructions shall also be considered in order to complete the construction (3) Base Boards: As noted in drawings or approved by Owner/Client.
of the details, and in some cases may supercede the details. resistive membrane at exterior walls. G. Provide shut- off valves at each fixture.
2. Installation: H. Provide condensate line at each F.A.U location. Provide primary & secondary condensate
15. Approved Drawings: The General Contractor shall be responsible for coordinating the work A. Provide required clearances for duct work and to combustibles. line to an approved drainage receptacle at attic F.A.U locations. Install condensate line for
B. Provide a permanent electric outlet and switched light fixture wherever equipment is each piece of condensating HVAC equipment per manufactureres specifications.
between the different Subcontractors and requiring all Subcontractors to use the most current
building department approved set of plans.
INSULATION: installed. I. Provide cold water line to refrigerator space in recessed box or in cabinet immediately
C. No alterations to the structural frame, diaphragms, connections or shear panels shall be adjacent to refrigerator space.
1. Installation: made without prior written approval from the Structural Engineer. J. Isolate all piping from structure with fiber padding and at all penetrations with elastic
16. Cutting and Patching: All Subcontractors shall do their own cutting, fitting, patching, etc. to make A. Thermal Insulation: Install insulation between joists, below all roof surfaces, and areas
the several parts come together properly and fit it to receive the work of other trades. D. No equipment located in garages. caulking or sound isolators.
including any vertical wall areas separating living spaces from unconditioned space and E. All combustion equipment shall be directly vented with an outdoor combustion air supply. K. All vents to lead to outside air, where possible, locate all roof vents to rear side or ridges.
between studs at all exterior walls. Insulation shall be securely installed and tightly fitted F. All penetrations of fire assemblies shall meet the requirements of the building code and Vents to terminate a minimum of 3'-0” from windows.
17. Clean up: All trades shall, at all times, keep the premises free from accumulation of waste without compressing the normal Loft thickness. Provide insulation stops/ baffles as PROJECT NAME:
materials or rubbish caused by their work. Subcontractors shall remove all rubbish, tools, Section 7D. L. All horizontal A.B.S. piping shall be hung with approved hangers at 4' -0” on center
required to prevent obstruction of vents. G. All HVAC equipment shall be approved prior to installation per nationally recognized minimum and spaced to permit expansion and contraction without hitting adjoining pipe.
scaffolding and surplus materials and leave the job in a broom - clean condition. All fixtures,
equipment, glazing, floors, etc., shall be left clean and ready for occupancy upon completion of
B. Sound insulation: Install insulation between studs, securely and tightly fitted at walls as standards and evidenced by listing and label of an approved agency. Vertical piping shall be supported at 8'-0” on center with wrought steel “U” straps securely NE COLONIAL
indicated on drawings. H. Combustion air from outside shall be supplied to all fuel burning appliances. fastened to building frame.
the project. C. Plumbing insulation: All domestic hot water piping shall have R-4 insulation. Insulation I. Install air filters with a minimum efficiency reporting value (MERV) ≥ 10 and ensure that M. Provide air chambers at lavatory, dishwasher and clothes washer water connections. Set
shall be properly installed on all piping elbows to adequately insulate the 90 degree bend. air handlers can maintain adequate pressure and air flow. Air filter housings must be air vertically as close to fixture as possible.
18. Storage of Materials: The General Contractor and Subcontractors shall be responsible for storing D. The General Contractor and Subcontractors shall be responsible for storing the materials tight to prevent bypass or leakage. N. Provide ¾” tee for irrigation at main shut-off.
GENERAL NOTES
the materials on the site according to material suppliers' or manufacturers' instructions. The on the site according to material supplier's or manufacturers' instructions. The materials
materials shall be kept secure and protected from moisture, pests, and vandals. Any loss arising J. All fixed appliances are required to be securely fastened in place. Provide seismic bracing O. Provide water heater with pressure/ temperature relief valve and pan and drain line piped
shall be kept secure and protected from moisture. or anchor unit to platform where appropriate. to the exterior of the buildings.
out of materials stored at the site shall be the responsibility of the General Contractor or 2. Materials:
Subcontractor who stored the damaged or lost materials. K. Install centralized HVAC system equipped with additional controls to operate in P. All combustion equipment shall be directly vented. PROJECT NUMBER: 10-002
A. At a minimum, all insulation specified for this house meets or exceeds the R-value dehumidification mode. Q. No alterations to the structural frame, diaphragms, connections or shear panels shall be DATE:
requirements listed in Chapter 4 of the 2004 International Energy Conservation Code and Issue Date
L. Condenser pad or compressor from ground must not be less than 3” above grade. made without prior written approval from the structural Engineer.
also the Grade II specifications set by the National Home Energy Rating Standards. DRAWN BY: MY
M. The General Contractor and Subcontractors shall be responsible for storing the materials R. Provide non- removable backflow device on all exterior hose bibs.

9/24/2009 10:33:18 AM
B. A pre-drywall thermal bypass inspection must be performed by a qualified rater. on the site according to material supplier's or manufacturers' instructions. The materials S. A 12” minimum access panel to bathtub trap connection is required. CHECKED BY: BU, SH
shall be kept secure and protected from moisture. T. Provide pressure regulator for water service where pressure exceeds 80 psi
U.

V.
Provide drain pan under washer with drain in laundry room and shut off valve if washer is
located above living space.
Provide solid metal pipe for dryer vent to exterior. Do not install screen on dryer vent.
A-00-1
SCALE
Provide energy efficient dryer vent (with floating shuttle).
IV. TOTAL: I. II. III. IV. I. II. III. IV. I. II. III. IV.
III. CREDIT ATTEMPTED: (YES/NO)
II.
I.
ESTIMATED POINTS ELIGIBLE BY THIS DESIGN:
MAX POINTS AVAILABLE: (P = PREREQUISITE)
ID 3: INNOVATIVE OR REGIONAL DESIGN
Intent. Minimize the environmental impact of the home by incorporating additional
WE 2: IRRIGATION SYSTEM
Intent. Minimize outdoor demand for water through water-efficient irrigation.
MR 2: ENVIRONMENTALLY PREFERABLE PRODUCTS
Intent. Increased demand for environmentally preferable products and products or
FREE GREEN
green design and construction measures that have tangible and demonstrable building components that are extracted, processed, and manufactured within the
benefits beyond those in the LEED for Homes Rating System. (pg. 145) 2.1 High-Efficiency Irrigation System (OR WE 2.3) 3 region.
(pg. 146) 2.2 Third-Party Inspection (OR WE 2.3) 1 www.FreeGreen.com
(pg. 45) 3.1 Innovation #1 1 (pg. 247) 2.1 FSC-Certified Tropical Wood (P)
(pg. 146) 2.3 Reduce Overall Irrigation Demand by at Least 45% 4 348 MEDFORD ST. SUITE 1
(pg. 45) 3.2 Innovation #2 1 (pg. 247) 2.2 Environmentally Preferable Products 8 CHARLESTOWN, MA 02129
WE 3: INDOOR WATER USE
(pg. 45) 3.3 Innovation #3 1 MR 3: WASTE MANAGEMENT © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
(pg. 45) 3.4 Innovation #4 1 Intent. Minimize outdoor demand for water through water-efficient irrigation.
Intent. Reduce waste generated to a level below the industry norm.
(pg. 159) 3.1 High-Efficiency Fixtures and Fittings 3 What is the LEED for Homes Green Building Rating System?
LOCATION AND LINKAGES (LL) (pg. 261) 3.1 Construction Waste Management Planning (P)
(pg. 159) 3.2 Very High-Efficiency Fixtures and Fittings 6 LEED for Homes is a national, voluntary certification system, developed by
LL 1: LEED FOR NEIGHBORHOOD DEVELOPMENT (pg. 261) 3.2 Construction Waste Reduction 3 national experts and experienced builders, that promotes the design and
construction of high-performance green homes and encourages the adoption
Intent. Minimize the environmental impact of land development practices by building ENERGY & ATMOSPHERE (EA) INDOOR ENVIRONMENTAL QUALITY (EQ) of sustainable practices by the homebuilding industry.
homes in LEED for Neighborhood Development certified developments. EA 1: OPTIMIZE ENERGY PERFORMANCE
IQ 1: ENERGY STAR WITH INDOOR AIR PACKAGE The LEED for Homes Rating System is part of the suite of nationally
(pg. 51) 1 LEED for Neighborhood Development 10 recognized LEED Green Building Rating Systems administered by USGBC.
(OR LL 2-6) Intent. Improve the overall energy performance of a home by meeting or exceeding
Intent. Improve the overall quality of a home's indoor environment by installing an Like all LEED Rating Systems, it is the market's leadership system, targeting
LL 2: SITE SELECTION the performance of an ENERGY STAR labeled home. the top 25% of home building practices in terms of environmental responsibility.
approved bundle of air quality measures. LEED provides industry resources and tools on how to "green" any new home.
Intent. Avoid development on environmentally sensitive sites. (pg. 169) 1.1 Performance of ENERGY STAR for Homes (OR EA 2-11) (P)
(pg. 273) 1.1 ENERGY STAR with Indoor Air Package (OR IQ 2-10) 13 With LEED, homebuilders can differentiate their structures as meeting the
(pg. 169) 1.2 Exceptional Energy Performance (OR EA 2-11) 34
I. II. III. IV. (pg. 55) 2 Site Selection 2 IQ 2: COMBUSTION VENTING highest performance measures, and homebuyers can readily identify high-
EA 2: INSULATION quality green homes. LEED provides national consistency in defining the
LL 3: PREFERRED LOCATIONS features of a green home, enables builders anywhere in the country to obtain
Intent. Minimize the leakage of combustion gases into the occupied space of the
CREDIT CATEGORIES & CERTIFICATION LEVELS Intent. Encourage the building of LEED homes near or within existing communities.
Intent. Design and install insulation to minimize heat transfer and thermal bridging.
home.
a green rating on their homes, and assures homebuyers of the quality of their
purchases, all based on a recognized national brand.
LEED certification is based on 18 prerequisites and 67 credits. The prerequisites are basic performance standards: they (pg. 179) 2.1 Basic Insulation (OR EA 1, 7.1, 7.2) (P) (P)
are mandatory for every project, and no points are awarded for meeting them. To achieve certification, builders earn credit (pg. 59) 3.1 Edge Development 1 (pg. 277) 2.1 Basic Combustion Venting Measures (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) (P) (P)
points by exceeding the minimum standards of the prerequisites. In total, 136 credit points are available. (pg. 179) 2.2 Enhanced Insulation (OR EA 1, 7.1, 7.2) 2 How to use the LEED for Homes Green Building Rating System Checklist:
(pg. 59) 3.2 Infill (OR LL 3.1) 2 (pg. 277) 2.2 Enhanced Combustion Venting Measures (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 2
EA 3: AIR INFILTRATION If you plan to have your project LEED certified, this page will provide you with a
Prerequisites and points are classified in eight credit categories: (pg. 59) 3.3 Previously Developed 1 IQ 3: MOISTURE CONTROL
brief but clear outline of the program's mandatory and credit requirements.
LL 4: INFRASTRUCTURE Intent. Minimize energy consumption caused by uncontrolled air leakage into and
1. Innovation & Design (ID) Process. Intent. Control indoor moisture levels to provide comfort, reduce the risk of mold, and
Special design methods, unique regional credits, measures not currently addressed in the Rating System, and exemplary out of conditioned spaces. Please visit www.usgbc.org/LEED/homes for complete participation
performance levels. Intent. Encourage the building of LEED homes in developments that are served increase the durability of the home. requirements, credit descriptions and to purchase the most current edition of
2. Location & Linkages (LL). by or are near existing infrastructure (i.e., sewers and water supply). (pg. 185) 3.1 Reduced Envelope Leakage (OR EA 1, 7.1, 7.2) (P) the LEED for Homes Reference Guide as show on the upper left hand corner
The placement of homes in socially and environmentally responsible ways in relation to the larger community. (pg. 285) 3.1 Moisture Load Control (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1 1 of this page.
(pg. 185) 3.2 Greatly Reduced Envelope Leakage (OR EA 1, 7.1, 7.2) 2
3. Sustainable Sites (SS). (pg. 65) 4 Existing Infrastructure 1 IQ 4: OUTDOOR AIR VENTILATION If you choose not to have your project certified but would like to incorporate
The use of the entire property so as to minimize the project's impact on the site. (pg. 185) 3.3 Minimal Envelope Leakage (OR EA 3.2) (OR EA 1, 7.1, 7.2) 3 3
LL 5: COMMUNITY RESOURCES / TRANSIT green practices, products and materials, use this sheet as a guide to select
4. Water Efficiency (WE). Intent. Reduce occupant exposure to indoor pollutants by ventilating with outdoor air. the green features you would like to include.
Water conservation practices, both indoor and outdoor. EA 4: WINDOWS
5. Energy & Atmosphere (EA). Intent. Encourage the building of LEED homes in development patterns that allow (pg. 289) 4.1 Basic Outdoor Air Ventilation (P) (P) FreeGreen Inc. has made an effort to include many green building practices,
Energy efficiency, particularly in the building envelope and heating and cooling design.
for walking, biking, or public transit (thereby minimizing dependency on personal Intent. Maximize the energy performance of windows. (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2)
products and materials right into this free home plan set. If followed as
6. Materials & Resources (MR).
automobiles and their associated environmental impacts. (pg. 289) 4.2 Enhanced Outdoor Air Ventilation 2 2 presented, this home design is already eligible for a variety of points under
Efficient utilization of materials, selection of environmentally preferable materials, and minimization of waste during (pg. 189) 4.1 Good Windows (OR EA 1, 7.1, 7.2) (P) (P)
construction. (pg. 289) 4.3 Third-Party Performance Testing (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1 LEED for Homes Green Building Rating System. This page also identifies
7. Indoor Environmental Quality (EQ). (pg. 69) 5.1 Basic Community Resources / Transit 1 (pg. 189) 4.2 Enhanced Windows (OR EA 1, 7.1, 7.2) 2 these achievable points for your convenience. SEE COLUMN "II."
Improvement of indoor air quality by reducing the creation of and exposure to pollutants. IQ 5: LOCAL EXHAUST
8. Awareness & Education (AE). (pg. 69) 5.2 Extensive Community Resources / Transit (OR LL 5.1, 5.3) 2 (pg. 189) 4.3 Exceptional Windows (OR EA 4.2) (OR EA 1, 7.1, 7.2) 3
The education of homeowner, tenant, or multifamily building manager about the operations and maintenance of the (pg. 69) 5.3 Outstanding Community Resources / Transit (OR LL 5.1, 5.2) 3 EA 5: HEATING AND COOLING DISTRIBUTION SYSTEM Intent. Reduce moisture and exposure to indoor pollutants in kitchen and bathrooms.
green features of a LEED Home.
LL 6: ACCESS TO OPEN SPACE Intent. Minimize energy consumption due to thermal bridges and/or leaks in the (pg. 299) 5.1 Basic Local Exhaust (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) (P) (P)
CERTIFICATION LEVELS
Intent. Provide open space to encourage walking, physical activity, and time spent heating and cooling distribution system. (pg. 299) 5.2 Enhanced Local Exhaust 1 1
The LEED for Homes Rating System works by requiring a minimum level of performance through prerequisites and
rewarding improved performance in each of the above categories. The level of performance is indicated by four performance outdoors. (pg. 195) 5.1 Reduced Distribution Losses (OR EA 1, 7.1, 7.2) (P) (P) (pg. 299) 5.3 Third-Party Performance Testing 1
tiers. See (Table 1). IQ 6: DISTRIBUTION OF SPACE HEATING AND COOLING
(pg. 75) 6 Access to Open Space 1 (pg. 195) 5.2 Greatly Reduced Distribution Losses (OR EA 1, 7.1, 7.2) 2 2
Table 1
LEED for Homes Certification Levels (pg. 195) 5.3 Minimal Distribution Losses (OR EA 5.2) (OR EA 1, 7.1, 7.2) 3 Intent. Provide appropriate distribution of space heating and cooling in the home to
Required Points
SUSTAINABLE SITES (SS) EA 6: SPACE HEATING AND COOLING EQUIPMENT improve thermal comfort and energy performance.
Certified 45-59 SS 1: SITE STEWARDSHIP
Intent. Reduce energy consumption associated with the heating and cooling system. (pg. 305) 6.1 Room by Room Load Calculations (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) (P)
Silver 60-74 Intent. Minimize the environmental damage to the building lot during the construction (pg. 305) 6.2 Return Air Flow or Room by Room Controls (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1
Gold 75-89 process. (pg. 201) 6.1 Good HVAC Design and Installation (OR EA 1, 7.1, 7.2) (P)
(pg. 305) 6.3 Third-Party Performance Testing (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 2
(pg. 201) 6.2 High-Efficiency HVAC (OR EA 1, 7.1, 7.2) 2 2
Platinum 90-136 (pg. 81) 1.1 Erosion Controls During Construction (P) IQ 7: AIR FILTERING
(pg. 201) 6.3 Very High-Efficiency HVAC (OR EA 6.2) (OR EA 1, 7.1, 7.2) 4
Total available points 136 (pg. 81) 1.2 Minimize Disturbed Area of Site 1
EA 7: WATER HEATING Intent. Reduce particulate matter from the air supply system.
HOME SIZE ADJUSTMENT SS 2: LANDSCAPING
Intent. Reduce energy consumption associated with the domestic hot water system, (pg. 311) 7.1 Good Filters (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) (P) (P)
The adjustments in (Table 2) below compensate for the overarching effects of home size on consumption by adjusting the Intent. Design landscape features to avoid invasive species and minimize demand for
award level point thresholds based on home size. For further explanation see pages 8-11 in the LEED H Reference Guide. including improving the efficiency of both the hot water system design and the layout (pg. 311) 7.2 Better Filters 1 1
water and synthetic chemicals.
Table 2
of the fixtures in the home. (pg. 311) 7.3 Best Filters (OR IQ 7.2) 2
Threshold Adjustment Certification Levels (pg. 89) 2.1 No Invasive Plants (P)
(pg. 207) 7.1 Efficient Hot Water Distribution 2 2 IQ 8: CONTAMINANT CONTROL
Required Points (pg. 89) 2.2 Basic Landscape Design (OR SS 2.5) 2
(pg. 208) 7.2 Pipe Insulation 1 1 Intent. Reduce occupants' and construction workers' exposure to indoor airborne
Certified 55-69 (pg. 89) 2.3 Limit Conventional Turf (OR SS 2.5) 3
(pg. 208) 7.3 Efficient Domestic Hot Water (DHW) Equipment (OR EA 1, 7.1, 7.2) 3 3 contaminant through source control and removal.
Silver 70-84 (pg. 89) 2.4 Drought-Tolerant Plants (OR SS 2.5) 2
EA 8: LIGHTING
Gold 85-99 (pg. 90) 2.5 Reduce Overall Irrigation Demand by at Least 20% 6 (pg. 315) 8.1 Indoor Contaminant Control during Const. (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1
Platinum 100-146 SS 3: LOCAL HEAT ISLAND EFFECTS Intent. Reduce energy consumption associated with interior and exterior lighting. (pg. 315) 8.2 Indoor Contaminant Control 2
Total available points 136 (pg. 213) 8.1 ENERGY STAR Lights (OR EA 1, 7.1, 7.2) (P) (P) (pg. 315) 8.3 Preoccupancy Flush (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1
Intent. Design landscape features to reduce local heat island effects.
HOW TO PARTICIPATE IN LEED FOR HOMES (pg. 213) 8.2 Improved Lighting (OR EA 1, 7.1, 7.2) 1.5 1.5 IQ 9: RADON PROTECTION
(pg. 111) 3 Reduce Local Heat Island Effects 1
There are five basic steps for a builder to follow in participating in LEED for Homes: (pg. 213) 8.3 Advanced Lighting Package (OR EA 8.2) (OR EA 1, 7.1, 7.2) 3 Intent. Reduce occupant exposure to radon gas and other soil gas contaminants.
1. Contact a LEED for Homes Provider and register the project with USGBC.
SS 4: SURFACE WATER MANAGEMENT
EA 9: APPLIANCES (P)
2. Identify a project team (pg. 323) 9.1 Radon-Resistant Const. in High Risk Areas (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) (P)
3. Build the home to the stated goals. Build onsite HERS and green rating tasks. Intent. Design site features to minimize erosion and runoff from the home site.
Intent. Reduce appliance energy consumption. (pg. 323) 9.2 Radon-Resistant Const. in Mod. Risk Areas (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1
4. Achieve certification as a LEED home.
5. Post-certification and marketing support. (pg. 115) 4.1 Permeable Lot 4
(pg. 217) 9.1 High-Efficiency Appliances (OR EA 1, 7.1, 7.2) 2 IQ 10: GARAGE POLLUTANT PROTECTION
(pg. 115) 4.2 Permanent Erosion Controls 1
For full participation requirements or to purchase the LEED H Reference Guide, please visit www.usgbc.org/LEED/homes I. II. III. IV. (pg. 217) 9.2 Water-Efficient Cloths Washer (OR EA 1, 7.1, 7.2) 1 Intent. Reduce occupant exposure to indoor pollutants originating from an adjacent
(pg. 115) 4.3 Management of Runoff from Roof 2
EA 10: RENEWABLE ENERGY garage.
INNOVATION AND DESIGN PROCESS (ID) SS 5: NONTOXIC PEST CONTROL
(pg. 327) 10.1 No HVAC in Garage (P) (P)
Intent. Reduce consumption of nonrenewable energy sources by encouraging the (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2)
ID 1: INTEGRATED PROJECT PLANNING Intent. Design home features to minimize the need for poisons for control of installation and operation of renewable electric generation systems. (pg. 327) 10.2 Minimize Pollutants from Garage (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 2 2
insects, rodents, and other pests.
Intent. Maximize opportunities for integrated, cost-effective adoption of green design (pg. 221) 10 Renewable Energy System (OR EA 1, 7.1, 7.2) 10 (pg. 327) 10.3 Exhaust Fan in Garage (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 1
and construction strategies. (pg. 125) 5 Pest Control Alternatives 2 (pg. 327) 10.4 Detached or No Garage (OR IQ 10.2, 10.3) (OR IQ 1, 4.2, 5.2, 5.3, 7.2/7.3, 8.2) 3
EA 11: RESIDENTIAL REFRIGERANT MANAGEMENT PROJECT NAME:
SS 6: COMPACT DEVELOPMENT
(pg. 31) 1.1 Preliminary Rating (P) Intent. Select and test air-conditioning refrigerant to ensure performance and AWARENESS & EDUCATION (AE)
(pg. 31) 1.2 Integrated Project Team 1 1 Intent. Make use of compact development patterns to conserve land and promote minimum contributions to ozone depletion and global warming. AE 1: EDUCATION OF HOMEOWNER OR TENANT
NE COLONIAL
community livability, transportation efficiency, and walkability.
(pg. 31) 1.3 Professional Credentialed with Respect to LEED for Homes 1 1 (pg. 227) 11.1 Refrigerant Charge Test (P)
(pg. 129) 6.1 Moderate Density 2 Intent. Maintain the performance of the home by educating the occupants (i.e., the
(pg. 31) 1.4 Design Charrette 1 1 (pg. 227) 11.2 Appropriate HVAC Refrigerants 1
(pg. 31) 1.5 Building Orientation for Solar Design 1 (pg. 129) 6.2 High Density (OR SS 6.1, 6.3) 3
homeowner or tenant) about the operations and maintenance of the home's LEED
features and equipment.
LEED-H RATING
(pg. 129) 6.3 Very High Density 4 MATERIAL & RESOURCES (MR)
ID 2: DURABILITY MANAGEMENT PROCESS (OR SS 6.1, 6.2)
MR 1: MATERIAL-EFFICIENT FRAMING (pg. 335) 1.1 Basic Operations Training (P) SYSTEM CHECKLIST
Intent. Promote durability and high performance of the building enclosure and its WATER EFFICIENCY (WE) (pg. 336) 1.1 Enhanced Training 1 PROJECT NUMBER: 10-002
components and systems through appropriate design, materials selection, and WE 1: WATER REUSE Intent. Optimize the use of framing materials.
AE 2: EDUCATION OF BUILDING MANAGER DATE: Issue Date
construction practices.
Intent. Use municipal recycled water or offset central water supply through the (pg. 235) 1.1 Framing Order Waste Factor Limit (P) DRAWN BY:
Intent. Maintain the performance of the home by educating the building manager MY
(pg. 37) 2.1 Durability Planning (P) (pg. 235) 1

9/24/2009 10:33:20 AM
capture and controlled reuse of rainwater and/or graywater. 1.2 Detailed Framing Documents (OR MR 1.5)
about the operations and maintenance of the home's LEED features and equipment. CHECKED BY: BU, SH
(pg. 37) 2.2 Durability Management (P) (pg. 235) 1.3 Detailed Cut List and Lumber Order (OR MR 1.5) 1
(pg. 135) 1.1 Rainwater Harvesting System (OR WE 1.3) 4
(pg. 339) 2 Education of Building Manager 1
(pg. 37) 2.3 Third-Party Durability Management Verification 3
(pg. 135) 1.2 Graywater Reuse System
(pg. 135) 1.3 Use of Municipal Recycled Water System
(OR WE 1.3) 1
3
(pg. 235)
(pg. 235)
1.4
1.5
Framing Efficiencies
Off-Site Fabrication
(OR MR 1.5) 3
4
A-00-2
TOTAL ESTIMATED POINTS ELIGIBLE BY THIS DESIGN: 24.5 SCALE
IV. TOTAL: I. II. III. IV. I. II. III. IV. I. II. III. IV.
III. CREDIT ATTEMPTED: (YES/NO)
(pg. 27) 15 (M) (pg. 54) 29
II.
I.
ESTIMATED POINTS ELIGIBLE BY THIS DESIGN:
MAX POINTS AVAILABLE: (M = MANDATORY REQUIREMENT PRESENT)
403 SITE DESIGN
403.0 Intent. The project is designed to avoid detrimental environmental impacts, (pg. 28)
601.1 Conditioned floor area.
601.2 Material usage. 9 (pg. 56)
704.2 Lighting and appliances.
704.3 Renewable energy and solar heating and cooling. (Max points vary) FREE GREEN
minimize any unavoidable impacts, and mitigate for those impacts that do occure. (pg. 28) 601.3 Building dimensions and layouts. 13 (pg. 59) 704.4 Ducts. 52
The project is designed to minimize environmental impacts and to protect, restore, (pg. 28) 601.4 Framing and structural plans. 4 (pg. 60) 704.5 HVAC design and installation. 9 1
and enhance the natural features and environmental quality of the site.
(pg. 28) 601.5 Prefabricated components. 38 (pg. 60) 704.6 Installation and performance verification. 43 www.FreeGreen.com
348 MEDFORD ST. SUITE 1
(pg. 16) 403.1 Natural resources. 18 (pg. 28) 601.6 Stacked stories. 8 4 705 INNOVATIVE PRACTICES CHARLESTOWN, MA 02129
(pg. 16) 403.2 Building orientation. 6 (pg. 28) 601.7 Site-applied finishing materials. 12 2 (pg. 62) 705.1 Energy consumption control. 7 © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
(pg. 16) 403.3 Slope disturbance. (Points awarded only if there are developable steep slopes in the project area) 28 (pg. 29) 601.8 Foundations. 3 (pg. 62) 705.2 Renewable energy service plan. 7
(pg. 16) 403.4 Soil disturbance and erosion. 12 (pg. 29) 601.9 Above grade wall systems. 4 What is the NAHB National Green Building Standard?
800 WATER EFFICIENCY
(pg. 16) 403.5 Storm water management. 21 602 ENHANCED DURABILITY AND REDUCED MAINTENANCE In 2007 the National Association of Home Builders (NAHB) and the
801 INDOOR AND OUTDOOR WATER USE International Code Council (ICC) partnered to form to establish a much-
(pg. 17) 403.6 Landscape plan. 54 602.0 Intent. Design and construction practices are implemented that enhance the needed and nationally-recognizable standard definition of what is meant by
(pg. 17) 403.7 Wildlife habitat. 5 durability of materials and reduce in-service maintenance. 801.0 Intent. Measures that reduce indoor and outdoor water usage are "Green Building."
implemented.
(pg. 18) 403.8 Operations and maintenance plan. 5 (pg. 29) 602.1 Exterior doors. 5 3 A consensus committee was formed to develop this standard in compliance

6 (pg. 63) 801.1 Indoor hot water usage. (Max points vary) 6 with the requirements of the American National Standards Institute (ANSI).
(pg. 18) 403.9 Existing buildings. (pg. 29) 602.2 Roof overhangs. 4 The resulting ANSI approved ICC-700-2008 National Green Building
(pg. 18) 403.10 Existing and recycled materials. 1 (pg. 64) 801.2 Water-conserving appliance. 14 Standard defines green building for single and multifamily homes, residential
(pg. 30) 602.3 Foundation drainage. (M) 4 M remodeling projects and site development projects while still allowing for the
(pg. 18) 403.11 Environmentally sensitive areas. 6 (pg. 64) 801.3 Food waste disposers. 1 flexibility required for regionally-appropriate best green practices.
(pg. 30) 602.4 Drip edge. 3 3
(pg. 18) 403.12 Density. 10 (pg. 65) 801.4 Showerheads. 5
I. II. III. IV. (pg. 30) 602.5 Roof water discharge. 4 4 Similar to the NAHB Model Green Homebuilding Guidelines, a builder,
(pg. 18) 403.13 Mixed-use development. 6 (pg. 65) 801.5 Faucets. 8 remodeler or developer must incorporate a minimum number of features
(pg. 30) 602.6 Finished grade. (M) M in the following areas: energy, water, and resource efficiency, lot and site
(pg. 66) 801.6 Water closets and urinals. (M) 28
300 COMPLIANCE METHOD 404 SITE DEVELOPMENT AND CONSTRUCTION (pg. 30) 602.7 Termite barrier. 4 development, indoor environmental quality, and home owner education.
The more points accrued, the higher the score.
(pg. 66) 801.7 Irrigation systems. 19
301 - GENERAL 404.0 Intent. Environmental impact during construction is avoided to the extent (pg. 31) 602.8 Termite-resistant materials. 6
(pg. 67) 801.8 Rainwater collection and distribution. 8 The Standard, however, includes more mandatory items and suggests
possible; impacts that do occure are minimized, and any significant impacts are (pg. 31) 602.9 Water-resistive barrier. (M) M that higher thresholds be met in several categories. A new threshold -
301.1 Environmental performance levels. The building, project, site, and or development's environmental performance
level shall consist of all mandatory requirements, plus points assessed using the point system specified within this Chapter. mitigated. (pg. 67) 801.9 Water filters. 1 "Emerald" - was added to denote the highest achievement in residential
(pg. 31) 602.10 Ice barrier. (M) green construction.
The level of performance shall be in accordance with Table 302, 303 or 305.5 as acceptable. 802 INNOVATIVE PRACTICES
(pg. 18) 404.1 On-site supervision and coordination. 4 (pg. 31) 602.11 Foundation waterproofing. 4 4
301.2 Awarding of points. Points shall be awarded as follows: (pg. 68) 802.1 Gray water. (Max points vary)
(1) The maximum number of points that can be awarded for each practice is noted with that practice.
(pg. 18) 404.2 Trees and vegetation. 12 (pg. 31) 602.12 Flashing. 6 6 How to use the NAHB National Green Building Standard Checklist:
(pg. 68) 802.2 Composting or waterless toilets and/or urinals. (M) 24
(2) Points allocation for multi-unit buildings shall be as prescribed in section 304. (pg. 19) 404.3 Soil disturbance and erosion. 31 (pg. 32) 602.13 Roof surfaces. 3
(3) The Adopting Entity shall allow new products and practices to be added where deemed to meet the intent of this (pg. 68) 802.3 Automatic shutoff water devices. 2 If you plan to have your project certified by the NAHB National Green Building
Standard. Points assigned for any new product or practice shall be determined by the Adopting Entity. (pg. 19) 404.4 Wildlife habitat. 19 (pg. 32) 602.14 Recycling. 6 Standard, this page will provide you with a brief but clear outline of the
program's mandatory and credit requirements. Additional clarifying text can
302 - GREEN SUBDIVISIONS
405 INNOVATIVE PRACTICES 603 REUSED OR SALVAGED MATERIALS 900 INDOOR ENVIRONMENTAL QUALITY be found in the full National Green Building Standard. This checklist is a
worksheet only and is not a substitute for online scoring at
405.0 Intent. Innovative site design, preparation, and development practices are 603.0 Intent. Practices that reuse or modify existing structures, salvages materials 901 POLLUTANT SOURCE CONTROL NAHBGreen.org which. Scoring through NAHBGreen.org is required for
302.1 Site design and development. The threshold points required for the environmental performance levels to qualify a new
or existing subdivision as green under this Standard shall be in accordance with Table 302 and based on points in Chapter 4. used to enhance environmental performance. Waivers or variances from local for other uses, or use salvaged materials in the building's construction are 901.0 Intent. Pollutant sources are controlled.
home certification in the NAHBGreen program.
development regulations are obtained, and innovative zoning practices are used to implemented. To purchase the National Green Building Standard or for more information
Table 302
implement such practices, as applicable. (pg. 69) 901.1 Space and water heating options. 25 10 visit www.BuilderBooks.com.
(pg. 32) 603.1 Reused of existing building. 12
Threshold Point Ratings for Site Design and Development
(pg. 19) 405.1 Driveways and parking areas. 5 (pg. 70) 901.2 Fireplaces and fuel-buring appliances. (M) 7
(pg. 32) 603.2 Salvaged materials. 3 If you choose not to have your project certified but would like to incorporate
Performance Level Points (pg. 71) 901.3 Garages. (M) 10 4 green practices, products and materials, use this sheet as a guide to select
Green Subdivision Category (pg. 20) 405.2 Street widths. 6 (pg. 32) 603.3 Scrap materials. 4 the green features you would like to include.
One Two Three Four
Star Stars Stars Stars (pg. 20) 405.3 Cluster development. 10 (pg. 71) 901.4 Wood materials. (M) 10
604 RECYCLED-CONTENT BUILDING MATERIALS FreeGreen Inc. has made an effort to include many green building practices,
400 Site Design and Development 79 104 134 175 (pg. 20) 405.4 Zoning. 18 (pg. 72) 901.5 Carpets. (M) 10 products and materials right into this free home plan set. If followed as
(pg. 32) 604.1 Recycled content. 9
(pg. 20) 405.5 Wetlands. 7 (pg. 72) 901.6 Hard-surface flooring. 6 presented, this home design is already eligible for a variety of points under
303 - GREEN BUILDINGS 605 RECYCLED CONSTRUCTION WASTE NAHB National Green Building Standard Rating System. This page also
(pg. 20) 405.6 Mass transit. 6 (pg. 72) 901.7 Wall coverings. 4 identifies these achievable points for your convenience.
303.1 Green buildings. The threshold points required for the environmental performance levels for a green building shall be 605.0 Intent. Waste generated during construction is recycled. All waste classified (pg. 73) 901.8 Architectural coatings. 13 SEE COLUMN "II."
in accordance with Table 303. To qualify for one of these performance levels, all of the following shall be satisfied: 500 LOT DESIGN, PREPARATION, AND DEVELOPMENT as hazardous shall be properly handled and disposed.
(pg. 73) 901.9 Adhesives and sealants. 10
(1) The threshold number of points, in accordance with Table 303, shall be achieved as prescribed in Categories 1 through 6. (pg. 33) 605.1 Construction waste management plan. 6
The lowest level achieved in any category shall determine the overall performance level achieved for the building. 500.0 Intent. This section applies to lot development for the eventual construction of (pg. 74) 901.10 Cabinets. 5
(2) In addition to the threshold number of points in each category, all mandatory provisions of each category shall be residential buildings, multi-unit buildings, or additions thereto that contain dwelling units. (pg. 33) 605.2 On-site recycling. 7 (pg. 74) 901.11 Insulation. 5
implemented. The buildings on the lot earn their own performance level by complying with the
(3) In addition to Section 701, either Section 702 (Performance Path) or Section 703 (Prescriptive Path) shall be used to (pg. 33) 605.1 Recycled construction materials. 6 (pg. 74) 901.12 Carbon monoxide (CO) alarms. 3 3
establish the threshold performance level under Category 3 (Energy Efficiency). provisions of Section 303, 304, or 305.5, as applicable.
(4) In addition to the threshold number of points prescribed in Categories 1 through 6, the additional points prescribed in
606 RENEWABLE MATERIALS (pg. 75) 901.13 Building entrance pollutants control. 1
Category 7 shall be achieved from any of the categories. Where deemed appropriate by the Adopting Entity, additional 501 LOT SELECTION (pg. 75) 1
points from Category 7 may be assigned to another category (or categories) to increase the threshold points required for that
606.0 Intent. Building materials derived from renewable resources are used. 901.14 Non-smoking areas.
category (or categories). Points shall not be reduced by the Adopting Entity in any of six other categories.
(pg. 21) 501.1 Lot. 9 902 POLLUTANT CONTROL
(pg. 33) 606.1 Biobased products. 8
Table 303 (pg. 21) 501.2 Mass Transportation. 9
Threshold Point Ratings for Green Buildings (pg. 34) 606.2 Wood-based products. 7 902.0 Intent. Pollutants generated in the building are controlled
502 PROJECT TEAM, MISSION STATEMENT, AND GOALS
Performance Level Points (1) (2) (1) In addition to the threshold number (pg. 34) 606.3 Manufacturing energy. 6 (pg. 75) 902.1 Spot ventilation. (M) 31 12
Green Building Category (pg. 21) 502.1 Project team, mission statement, and goals. 4
Bronze Silver Gold Emerald
of points in each category, all mandatory
607 RESOURCE-EFFICIENT MATERIALS (pg. 76) 902.2 Building ventilation systems. 28 15 NOTE: Points available for renovations and
provisions of each category shall be 503 LOT DESIGN
implemented. (pg. 77) 902.3 Radon control. (M) 15 M additions as specified in the NAHB Green Building
Lot Design, Preparation, and (pg. 34) 607.1 Resource-efficient materials. 9 6
1 500
Development
39 66 93 119 (2) For dwelling units greater than 4,000 503.0 Intent. The lot is designed to avoid detrimental environmental impacts first, Standard are not listed on this sheet. For a
608 INDIGENOUS MATERIALS (pg. 77) 902.4 HVAC system protection. 3
square feet (372 square meter), the
minimize any unavoidable impacts, and mitigate for those impacts that do occure. description of points available for renovations and
2 600 Resource Efficiency 45 79 113 146 number of points in Category 7 5
(pg. 34) 608.1 Indigenous materials. 10 (pg. 77) 902.5 Central vacuum system. additions as specified in the NAHB Green Building
3 700 Energy Efficiency 30 60 100 120 (Additional Points from any category) The project is designed to minimize environmental impacts and to protect, restore,
shall be increased in accordance with and enhance the natural features and environmental quality of the lot. 609 LIFE CYCLE ANALYSIS (pg. 78) 902.6 Living space contaminants. 8 Standard please purchace the full standard at
4 800 Water Efficiency 14 26 41 60 Section 601.1. The "Total Points" shall
903 MOISTURE MANAGEMENT: VAPOR, RAINWATER, PLUMBING, HVAC www.BuilderBooks.com.
be increased by the same number of (pg. 22) 503.1 Natural resources. 24 (pg. 35) 609.1 Life cycle analysis. 15
5 900 Indoor Environmental Quality 36 65 100 140 points.
Operation, Maintenance and (pg. 22) 503.2 Slope disturbance. (Points awarded only if there are developable steep slopes in the project area) 24 610 INNOVATIVE PRACTICES 903.0 Intent. Moisture and moisture effects are controlled
6 1000 8 10 11 12
Building Owner Education
(pg. 23) 503.3 Soil disturbance and erosion. 15 (pg. 35) 610.1 Manufacturer's environmental management system concepts. 10 (pg. 78) 903.1 Tile backing materials. (M)
Additional Points from any
category
52 102 102 102 (pg. 23) 503.4 Storm water management. 20 700 ENERGY EFFICIENCY (pg. 78) 903.2 Capillary breaks. (M) 3 3
Total Points: 224 408 560 699 (pg. 23) 503.5 Landscape plan. 34 701 MINIMUM ENERGY EFFICIENCY REQUIREMENTS (pg. 79) 903.3 Crawlspaces. (M) 16
(pg. 24) 503.6 Wildlife habitat. 4 (pg. 39) 701.1 Mandatory requirements. (pg. 79) 903.4 Moisture control measures. (M) 10
304 - GREEN BUILDINGS
(pg. 24) 503.7 Mixed-use development. 6 (pg. 39) 701.1.1 Minimum Performance Path requirements. (pg. 80) 903.5 Plumbing. 9 2
304.1 Green Multi-Unit Buildings. For multi-unit buildings, points for the green building practices that apply to multiple units (pg. 24) 6 (M) 2
shall be credited once for the entire building. Where points are credited, practices shall be implemented in all units, as
503.8 Environmentally sensitive areas. (pg. 39) 701.1.2 Minimum Prescriptive Path requirements. (pg. 81) 903.6 Duct insulation.
applicable. Where apllication of a prescribed practice allows for a different nuber of points for different units in a multi-unit (pg. 24) 503.9 Density. 10 (pg. 39) 701.1.3 Alternative bronze level compliance. (pg. 81) 903.7 Relative humidity. 8
building, the fewer number of points shall be awarded. I. II. III. IV.
504 LOT CONSTRUCTION (pg. 39) 701.2 Emerald level points. 904 INNOVATIVE PRACTICES
400 SITE DESIGN AND DEVELOPMENT 504.0 Intent. Environmental impact during construction is avoided to the extent (pg. 39) 701.1.3 Adopting Entity review. (pg. 81) 904.1 Humidity monitoring system. 2
possible; impacts that do occure are minimized, and any significant impacts are (pg. 40) 701.4 Mandatory practices. (pg. 81) 904.2 Kitchen exhaust. 2
400.0 Intent. This section applies to land development for the eventual construction of mitigated.
buildings or additions thereto that contain dwelling units. The rating earned under (pg. 40) 701.4.1 HVAC systems. (M) M 1000 OPERATION, MAINTENANCE, & BLDG OWNER EDUCATION
Section 303 based on practices herein, applies only to the site as defined in Chapter 2. (pg. 25) 504.1 On-site supervision and coordination. 4 (pg. 40) 701.4.2 Duct systems. (M) M 1001 BUILDING OWNERS' MANUAL FOR ONE AND TWO-FAMILY DWELLINGS PROJECT NAME:
The buildings on the site earn their own performance level by complying with the (pg. 25) 504.2 Trees and vegetation. 11 (pg. 41) 701.4.3 Insulation and air sealing. (M) M
provisions of Section 303, 304, or 305.5, as applicable. (pg. 25) 504.3 Soil disturbance and erosion. 34 1001.0 Intent. Information on the building's use, maintenance, and green
M
401 SITE SELECTION 505 INNOVATIVE PRACTICES
(pg. 43) 701.4.4 Fenestration.
702 PERFORMANCE PATH
(M)
components is provided. NE COLONIAL
(pg. 83) 1001.1 Building owner's manual. (M) 10
401.0 Intent. The site is selected to minimize environmental impact by one or 505.0 Intent. Innovative lot design, preparation and development practices are (pg. 43) 702.1 Point allocation. (M)
more of the following: used to enhance environmental performance. Waivers of variances from local 1002 TRAINING OF BUILDING OWNERS ON OPERATION & MAINTENANCE FOR
development regulations are obtained, and innovative zoning practices are used to
(pg. 43) 702.2 Energy cost performance level. 120
ONE & TWO-FAMILY DWELLINGS AND MULIT-UNIT BUILDINGS NAHB GREEN
(pg. 15) 401.1 Infill Site. 4 703 PRESCRIPTIVE PATH
(pg. 84) 1002.1 Training of building owners. 6
implement such practices.
(pg. 15) 401.2 Greyfield/brownfield site. 5 (pg. 44) 703.1 Building envelope. (Max points vary)
1003 CONSTRUCTION, OPERATION, & MAINTENANCE MANUALS & TRAINING
BUILDING STANDARD
402 PROJECT TEAM, MISSION STATEMENT, AND GOALS (pg. 26) 505.1 Driveways and parking areas. 4 (pg. 46) 703.2 Insulation and air sealing. 15 3 PROJECT NUMBER: 10-002
FOR MULTI-UNIT BUILDINGS
(pg. 26) 505.2 Heat island mitigation. 4 (pg. 48) 703.3 Fenestration. 12
402.0 Intent. The site is designed and constructed by a team of qualified 1003.0 Intent. Manuals are provided to the responsible parties (owner, management, DATE: Issue Date
professionals trained in green development issues. 600 RESOURCE EFFICIENCY (pg. 49) 703.4 HVAC equipment efficiency. (Max points vary) tenant, and/or maintenance team) regarding the construction, operation, and DRAWN BY: MY
maintenance of the building...

9/24/2009 10:33:21 AM
(pg. 52) 703.5 Water heating design, equipment, and installation. (Max points vary) CHECKED BY: BU, SH
(pg. 15) 402.1 Team. 4 601 QUALITY OF CONSTRUCTION MATERIALS AND WASTE
704 ADDITIONAL PRACTICES (pg. 85) 1003.1 Building construction manual. (M) 4
(pg. 15) 402.2 Training. 3 601.0 Intent. Design and construction practices that minimize the environmental
(pg. 15) 402.3 Project checklist. (M) 3 impact of the building materials are incorporated, environmentally efficient building
systems and materials are incorporated, and waste generated during construction is
704.1 Application of additional practice points. Points from Section 704 can be
added to points earned in Section 702 (Performance Path), Section 703 (Prescriptive
(pg. 85) 1003.2 Operations manual.
(pg. 86) 1003.3 Maintenance manual.
(M) 5
(M) 4.5
A-00-3
reduced. Path), or Section 701.1.3 (alternative bronze level compliance). TOTAL ESTIMATED POINTS ELIGIBLE BY THIS DESIGN: 91 SCALE
WINDOW SCHEDULE
No. MANUFACTURER MODEL NUMBER UNIT TYPE SPECIAL UNIT WIDTH UNIT HEIGHT ROUGH WIDTH ROUGH HEIGHT QUANTITY
FREE GREEN
1 ANDERSON CIR20 CIRCLE - FIXED 1' - 7 3/4" 1' - 7 3/4" 2' - 0 5/8" 2' - 0 5/8" 1
2 ANDERSON, 400 SERIES WOODWRIGHT WDH210-46 DOUBLE HUNG 2' - 11 5/8" 4' - 8 7/8" 3' - 0 1/8" 4' - 9 3/8" 12
3 ANDERSON, 400 SERIES WOODWRIGHT WDH210-410 DOUBLE HUNG 2' - 11 5/8" 5' - 0 7/8" 3' - 0 1/8" 5' - 1 3/8" 2 www.FreeGreen.com
348 MEDFORD ST. SUITE 1
4 ANDERSON, 400 SERIES WOODWRIGHT WDH210-410 DOUBLE HUNG MULLED UNIT 2' - 11 5/8" 5' - 0 7/8" 3' - 0 1/8" 6' - 1 3/8" 3 CHARLESTOWN, MA 02129
5 ANDERSON, 400 SERIES WOODWRIGHT WDH38-310 DOUBLE HUNG TEMPERED 3' - 9 5/8" 4' - 0 7/8" 3' - 10 1/8" 4' - 1 3/8" 1 © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
6 ANDERSON, 400 SERIES WOODWRIGHT WDH210-510 DOUBLE HUNG MULLED UNIT 2' - 11 5/8" 6' - 0 7/8" 3' - 0 1/8" 7' - 1 3/8" 4
7 ANDERSON, 400 SERIES WOODWRIGHT WDH210-310 DOUBLE HUNG 2' - 11 5/8" 4' - 0 7/8" 3' - 0 1/8" 4' - 1 3/8" 5 NOTES:

8 ANDERSON, 400 SERIES WOODWRIGHT WDH26-32 DOUBLE HUNG 2' - 7 5/8" 3' - 4 7/8" 2' - 8 1/8" 3' - 5 3/8" 3 EGRESS = WINDOW WITH MINIMUM NET CLEAR OPENING OF 5.7
9 ANDERSON, 400 SERIES WOODWRIGHT WDH20-410 DOUBLE HUNG MULLED UNIT 2' - 1 5/8" 5' - 0 7/8" 9' - 3 1/2" 5' - 1 3/8" 2 SQUARE FEET (24"Hx20"W MIN) WINDOW SILL HEIGHT
NOT MORE THAN 44" ABOVE FLOOR.
10 ANDERSON, 400 SERIES WOODWRIGHT WDH20-310 DOUBLE HUNG 2' - 1 5/8" 4' - 0 7/8" 2' - 2 1/8" 4' - 1 3/8" 2
11 ANDERSON, 400 SERIES WOODWRIGHT WDH18-46 DOUBLE HUNG MULLED UNIT 1' - 9 5/8" 4' - 8 7/8" 7' - 7 1/2" 4' - 9 3/8" 2 1 DEPTH OF SPRAY FOAM INSULATION TO MEET 2006 IECC
12 ANDERSON, 400 SERIES WOODWRIGHT WDH18-46 DOUBLE HUNG MULLED UNIT 1' - 9 5/8" 4' - 8 7/8" 1' - 10 1/8" 5' - 9 3/8" 2 REQUIREMENT FOR THE PROJECTS CLIMATE ZONE.
15 ANDERSON, 400 SERIES WOODWRIGHT WPW310-46 FIXED MULLED UNIT 3' - 11 5/16" 4' - 8 7/8" 7' - 7 1/2" 4' - 9 3/8" 1 2 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
16 ANDERSON, 400 SERIES WOODWRIGHT WPW410-410 FIXED MULLED UNIT 4' - 11 5/16" 5' - 0 7/8" 9' - 3 1/2" 5' - 1 3/8" 1 PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
17 ANDERSON, 400 SERIES WOODWRIGHT WPW20-310 (CUSTOM) FIXED, TEMPERED 2' - 1 5/8" 4' - 0 7/8" 2' - 2 1/8" 4' - 1 3/8" 1 HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.
18 ANDERSON, 400 SERIES WOODWRIGHT WTR210-10 TRANSOM MULLED UNIT 2' - 11 5/8" 1' - 0" 3' - 0 1/8" 6' - 1 3/8" 3
19 ANDERSON, 400 SERIES WOODWRIGHT WTR210-10 TRANSOM MULLED UNIT 2' - 11 5/8" 1' - 0" 3' - 0 1/8" 7' - 1 3/8" 4
20 ANDERSON, 400 SERIES WOODWRIGHT WTR18-10 TRANSOM MULLED UNIT 1' - 9 5/8" 1' - 0" 1' - 10 1/8" 5' - 9 3/8" 2

3
A-04-1
T.O. RIDGE RAFTER EL = +/- 31'-10 3/8" V.I.F.

12 12
9 9 ASPHALT SHINGLE ROOFING
ROOF CONSTRUCTION: (TOP DOWN)
- ASPHALT SHINGLES
- ROOFING PAPER (30LB FELT OR EQUIVALENT) EXTERIOR TRIM PROFILES: CLEAR CEDAR OR FIBER CEMENT
3
- 5/8" SHEATHING WINDOWS & DOORS - 1x4 + HEAD CROWN MOLDING (AT FRONT ONLY)
A-04-1 - 2x10 RAFTERS @ 24" O/C W/ SPRAY FOAM INSULATION (UNVENTED) 1 OUTSIDE CORNERS - 1x8 + CROWN MOLDING CAP
2
- 1x3 STRAPPING @ 16" O/C INSIDE CORNERS - 1x1
T.O. RIDGE RAFTER EL = +/- 25'-10 3/8" V.I.F. - 1/2" GYPSUM BOARD (REQ FOR THERMAL BARRIER)
A-04-1 12 12 ROOF FASCIA - 1/2"x8 @ EAVE, 1/2"x10 @ RAKE
BAND BOARD LOWER - 1x8 W/ 2x2 CANTED TOP COURSE
9 9
BAND BOARD UPPER - 1x8
+/- 6' - 8 3/8" V.I.F.

GABLE FRIEZE - 1x4


MASONRY CHIMNEY SOFFIT FRIEZE - 1x6 + CROWN MOLDING
& FIRE PLACE PANELING - 4'x8'x3/4" MDO (ALL SIDES PAINTED & SEALED)
SOFFIT - 1x4 T&G
1

3' - 2"
T.O. ATTIC SUB FLOOR EL = 19'-2" 2
B.O. FLOOR FRAMING EL A-04-2
+/- 31' - 10 3/8" V.I.F.

1' - 0"

CLAP BOARD SIDING REVISION SCHEDULE:


EXT WALL CONSTRUCTION: (OUTSIDE to IN) 3
B.O. WINDOW HEADER

No. Description Date

B.O. WINDOW HEADER


5/16" FIBER CEMENT CLAP BOARD SIDING - 5
A-04-2
9' - 1"

CORRUGATED SPACER MESH - A-04-2


8' - 1"

BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE - 5


7' - 0"

W/ MIN 6" OVERLAP AT HORZ JOINTS -

6' - 6"
2 2 11 15 11 2 2
A-04-2
1/2" SHEATHING - 2
2x6 STUD WALL W/ SPRAY FOAM INSULATION -
1/2" GYPSUM BOARD W/ VAPOR -
SEMI-PERMEABLE LATEX PAINT -
12 12
T.O. UPPER LEVEL SUB FLOOR EL = 10'-1" 6 6
B.O. FLOOR FRAMING EL
1' - 0"

1/2" COVER BOARDS OVER BEAM


18 1
A-04-4 GARAGE WALL CONSTRUCTION: (OUTSIDE to IN)
B.O. WINDOW HEADER

- 5/16" FIBER CEMENT CLAP BOARD SIDING


DECORATIVE COLUMN CAP OVER 6x6 PT POST
10' - 1"

- CORRUGATED SPACER MESH


ON GALV STEEL POST ANCHOR TYP
9' - 1"

2 - BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE


16 - W/ MIN 6" OVERLAP AT HORZ JOINTS
7' - 0"

A-04-4 - 1/2" SHEATHING


4 3 3 9 9 - 2x6 STUD WALL (UNINSULATED)
1 2 - 5/8" TYPE "X" GYPSUM BOARD W/ VAPOR
GARAGE DOOR GARAGE DOOR SEMI-PERMEABLE LATEX PAINT
A-04-3 A-04-3 8-0x7-0 8-0x7-0

T.O. ENTRY LEVEL SUB FLOOR EL = 0'-0"


B.O. FLOOR FRAMING EL 2 2
1' - 0"

T.O. FOUNDATION WALL


3"
9' - 3"

MDO PAINTED & SEALED 3 4 PROJECT NAME:


8' - 0"

6 6
ALL SIDES
A-04-4 A-04-4
GROUND SLOPES AWAY FROM A-04-2 A-04-3 GROUND SLOPES AWAY FROM
WALL @ 5% OR 6" PER 10' WALL @ 5% OR 6" PER 10' NE COLONIAL
STEP CONC FOOTING BELOW FROST DEPTH
T.O. CONCRETE FOOTING EL = (-) 9'-3"
ELEVATION FRONT
PROJECT NUMBER: 10-002
DATE: Issue Date
FRONT ELEVATION DRAWN BY: MY
1
1/4" = 1'-0"

9/24/2009 10:33:23 AM
CHECKED BY: BU, SH

A-01-1
SCALE 1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

NOTES:

EGRESS = WINDOW WITH MINIMUM NET CLEAR OPENING OF 5.7


SQUARE FEET (24"Hx20"W MIN) WINDOW SILL HEIGHT
NOT MORE THAN 44" ABOVE FLOOR.

1 DEPTH OF SPRAY FOAM INSULATION TO MEET 2006 IECC


REQUIREMENT FOR THE PROJECTS CLIMATE ZONE.
2 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.

3
12 12
A-04-1
10 10 T.O. RIDGE RAFTER EL = +/- 31'-10 3/8" V.I.F.

EXTERIOR TRIM PROFILES: CLEAR CEDAR OR FIBER CEMENT


WINDOWS & DOORS - 1x4 + HEAD CROWN MOLDING (AT FRONT ONLY) 3
OUTSIDE CORNERS - 1x8 + CROWN MOLDING CAP
INSIDE CORNERS - 1x1 A-04-1
ROOF FASCIA - 1/2"x8 @ EAVE, 1/2"x10 @ RAKE
BAND BOARD LOWER - 1x8 W/ 2x2 CANTED TOP COURSE T.O. RIDGE RAFTER EL = +/- 25'-10 3/8" V.I.F.
BAND BOARD UPPER - 1x8
GABLE FRIEZE - 1x4 2
SOFFIT FRIEZE - 1x6 + CROWN MOLDING

+/- 6' - 8 3/8" V.I.F.


PANELING - 4'x8'x3/4" MDO (ALL SIDES PAINTED & SEALED) A-04-2
SOFFIT - 1x4 T&G

T.O. ATTIC SUB FLOOR EL = 19'-2"


B.O. FLOOR FRAMING EL

+/- 31' - 10 3/8" V.I.F.


1' - 0"
ASPHALT SHINGLE ROOFING CLAP BOARD SIDING
ROOF CONSTRUCTION: (TOP DOWN)
ASPHALT SHINGLES - EXT WALL CONSTRUCTION: (OUTSIDE to IN)
ROOFING PAPER (30LB FELT OR EQUIVALENT) - - 5/16" FIBER CEMENT CLAP BOARD SIDING

9' - 1"
5/8" SHEATHING - - CORRUGATED SPACER MESH

8' - 1"
1 2x10 RAFTERS @ 24" O/C W/ SPRAY FOAM INSULATION (UNVENTED) - - BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE
1x3 STRAPPING @ 16" O/C -
2 2 W/ MIN 6" OVERLAP AT HORZ JOINTS
1/2" GYPSUM BOARD (REQ FOR THERMAL BARRIER) - - 1/2" SHEATHING
- 2x6 STUD WALL W/ SPRAY FOAM INSULATION 1
12 - 1/2" GYPSUM BOARD W/ VAPOR
6 SEMI-PERMEABLE LATEX PAINT
T.O. UPPER LEVEL SUB FLOOR EL = 10'-1"
B.O. FLOOR FRAMING EL

1' - 0"
REVISION SCHEDULE:

10' - 1"
No. Description Date

9' - 1"
7
7

T.O. ENTRY LEVEL SUB FLOOR EL = 0'-0"


2 B.O. FLOOR FRAMING EL

1' - 0"
T.O. FOUNDATION WALL

3"

9' - 3"
6 6
4

8' - 0"
A-04-2 A-04-3
GROUND SLOPES AWAY FROM A-04-4 GROUND SLOPES AWAY FROM
WALL @ 5% OR 6" PER 10' WALL @ 5% OR 6" PER 10'

T.O. CONCRETE FOOTING EL = (-) 9'-3"

RIGHT ELEVATION
1
1/4" = 1'-0"
PROJECT NAME:

NE COLONIAL

ELEVATION RIGHT
PROJECT NUMBER: 10-002
DATE: Issue Date
DRAWN BY: MY

9/24/2009 10:33:24 AM
CHECKED BY: BU, SH

A-01-2
SCALE 1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

NOTES:

EGRESS = WINDOW WITH MINIMUM NET CLEAR OPENING OF 5.7


SQUARE FEET (24"Hx20"W MIN) WINDOW SILL HEIGHT
NOT MORE THAN 44" ABOVE FLOOR.

1 DEPTH OF SPRAY FOAM INSULATION TO MEET 2006 IECC


REQUIREMENT FOR THE PROJECTS CLIMATE ZONE.
2 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
3 MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
A-04-1 HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.

T.O. RIDGE RAFTER EL = +/- 31'-10 3/8" V.I.F.

ASPHALT SHINGLE ROOFING


EXTERIOR TRIM PROFILES: CLEAR CEDAR OR FIBER CEMENT ROOF CONSTRUCTION: (TOP DOWN)
WINDOWS & DOORS - 1x4 + HEAD CROWN MOLDING (AT FRONT ONLY) ASPHALT SHINGLES - 3
OUTSIDE CORNERS - 1x8 + CROWN MOLDING CAP ROOFING PAPER (30LB FELT OR EQUIVALENT) -
INSIDE CORNERS - 1x1 5/8" SHEATHING - A-04-1
ROOF FASCIA - 1/2"x8 @ EAVE, 1/2"x10 @ RAKE 1 2x10 RAFTERS @ 24" O/C W/ SPRAY FOAM INSULATION (UNVENTED) -
BAND BOARD LOWER - 1x8 W/ 2x2 CANTED TOP COURSE 1x3 STRAPPING @ 16" O/C - T.O. RIDGE RAFTER EL = +/- 25'-10 3/8" V.I.F.
BAND BOARD UPPER - 1x8 1/2" GYPSUM BOARD (REQ FOR THERMAL BARRIER) -
GABLE FRIEZE - 1x4

+/- 6' - 8 3/8" V.I.F.


SOFFIT FRIEZE - 1x6 + CROWN MOLDING
PANELING - 4'x8'x3/4" MDO (ALL SIDES PAINTED & SEALED) MASONRY CHIMNEY
SOFFIT - 1x4 T&G & FIRE PLACE
1
A-04-1

T.O. ATTIC SUB FLOOR EL = 19'-2"


B.O. FLOOR FRAMING EL

+/- 31' - 10 3/8" V.I.F.


1' - 0"
5

B.O. WINDOW HEADER


A-04-2

9' - 1"
17

8' - 1"
5 10 10

7' - 0"
2

T.O. UPPER LEVEL SUB FLOOR EL = 10'-1"

2 B.O. FLOOR FRAMING EL

1' - 0"
A-04-2
19 19 19 18 18

B.O. WINDOW HEADER


GARAGE WALL CONSTRUCTION: (OUTSIDE to IN) 3
5/16" FIBER CEMENT CLAP BOARD SIDING -

10' - 1"
CORRUGATED SPACER MESH - A-04-2

9' - 1"
BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE - 8 8 8 REVISION SCHEDULE:

8' - 0"
W/ MIN 6" OVERLAP AT HORZ JOINTS - 7 7
No. Description Date
1/2" SHEATHING - 4 4
2x6 STUD WALL (UNINSULATED) -
5/8" TYPE "X" GYPSUM BOARD W/ VAPOR - 1 6 6 6
SEMI-PERMEABLE LATEX PAINT A-04-3

T.O. ENTRY LEVEL SUB FLOOR EL = 0'-0"


B.O. FLOOR FRAMING EL

1' - 0"
2
T.O. FOUNDATION WALL

3"
CLAP BOARD SIDING
EXT WALL CONSTRUCTION: (OUTSIDE to IN)

9' - 3"
- 5/16" FIBER CEMENT CLAP BOARD SIDING 6 6

8' - 0"
4
- CORRUGATED SPACER MESH
GROUND SLOPES AWAY FROM A-04-4 - BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE A-04-3 A-04-2 GROUND SLOPES AWAY FROM
WALL @ 5% OR 6" PER 10' W/ MIN 6" OVERLAP AT HORZ JOINTS WALL @ 5% OR 6" PER 10'
- 1/2" SHEATHING
- 2x6 STUD WALL W/ SPRAY FOAM INSULATION 1
STEP CONC FOOTING BELOW FROST DEPTH - 1/2" GYPSUM BOARD W/ VAPOR
SEMI-PERMEABLE LATEX PAINT T.O. CONCRETE FOOTING EL = (-) 9'-3"

REAR ELEVATION
1
1/4" = 1'-0"
PROJECT NAME:

NE COLONIAL

ELEVATION REAR
PROJECT NUMBER: 10-002
DATE: Issue Date
DRAWN BY: Author

9/24/2009 10:33:25 AM
CHECKED BY: Checker

A-01-3
SCALE 1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

NOTES:

EGRESS = WINDOW WITH MINIMUM NET CLEAR OPENING OF 5.7


SQUARE FEET (24"Hx20"W MIN) WINDOW SILL HEIGHT
NOT MORE THAN 44" ABOVE FLOOR.

1 DEPTH OF SPRAY FOAM INSULATION TO MEET 2006 IECC


REQUIREMENT FOR THE PROJECTS CLIMATE ZONE.
2 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
3
HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.
12 12
A-04-1
T.O. RIDGE RAFTER EL = +/- 31'-10 3/8" V.I.F. 10 10

EXTERIOR TRIM PROFILES: CLEAR CEDAR OR FIBER CEMENT


3
WINDOWS & DOORS - 1x4 + HEAD CROWN MOLDING (AT FRONT ONLY)
MASONRY CHIMNEY 2 A-04-1 OUTSIDE CORNERS - 1x8 + CROWN MOLDING CAP
& FIRE PLACE A-04-1 INSIDE CORNERS - 1x1
T.O. RIDGE RAFTER EL = +/- 25'-10 3/8" V.I.F. ROOF FASCIA - 1/2"x8 @ EAVE, 1/2"x10 @ RAKE
BAND BOARD LOWER - 1x8 W/ 2x2 CANTED TOP COURSE

B.O. WINDOW HEADER


BAND BOARD UPPER - 1x8
12 12 GABLE FRIEZE - 1x4
+/- 6' - 8 3/8" V.I.F.

SOFFIT FRIEZE - 1x6 + CROWN MOLDING


10 10
7 PANELING - 4'x8'x3/4" MDO (ALL SIDES PAINTED & SEALED)

7' - 0"
SOFFIT - 1x4 T&G

T.O. ATTIC SUB FLOOR EL = 19'-2"


B.O. FLOOR FRAMING EL
+/- 31' - 10 3/8" V.I.F.

1' - 0"

3 ASPHALT SHINGLE ROOFING


ROOF CONSTRUCTION: (TOP DOWN)

B.O. WINDOW HEADER


A-04-2 - ASPHALT SHINGLES
- ROOFING PAPER (30LB FELT OR EQUIVALENT)
9' - 1"

- 5/8" SHEATHING
8' - 1"

5
- 2x10 RAFTERS @ 24" O/C W/ SPRAY FOAM INSULATION (UNVENTED) 1

7' - 0"
2 2 2 2
A-04-2 - 1x3 STRAPPING @ 16" O/C
- 1/2" GYPSUM BOARD (REQ FOR THERMAL BARRIER)
12 12
6 4 12
2
T.O. UPPER LEVEL SUB FLOOR EL = 10'-1" 6
A-04-2
B.O. FLOOR FRAMING EL
1' - 0"

19 20 20

B.O. WINDOW HEADER


1/2" COVER BOARDS OVER BEAM
MDO PAINTED & SEALED ALL SIDES
10' - 1"

REVISION SCHEDULE:
9' - 1"

DECORATIVE COLUMN CAP OVER 6x6 PT POST


No. Description Date

8' - 0"
ON GALV STEEL POST ANCHOR TYP
12 12
6

2
T.O. ENTRY LEVEL SUB FLOOR EL = 0'-0"
B.O. FLOOR FRAMING EL
1' - 0"

T.O. FOUNDATION WALL


3"

CLAP BOARD SIDING


EXT WALL CONSTRUCTION: (OUTSIDE to IN)
9' - 3"

- 5/16" FIBER CEMENT CLAP BOARD SIDING


8' - 0"

6 - CORRUGATED SPACER MESH 6


GROUND SLOPES AWAY FROM A-04-2 - BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE GROUND SLOPES AWAY FROM
W/ MIN 6" OVERLAP AT HORZ JOINTS A-04-3
WALL @ 5% OR 6" PER 10' WALL @ 5% OR 6" PER 10'
- 1/2" SHEATHING
- 2x6 STUD WALL W/ SPRAY FOAM INSULATION 1
- 1/2" GYPSUM BOARD W/ VAPOR
SEMI-PERMEABLE LATEX PAINT
T.O. CONCRETE FOOTING EL = (-) 9'-3"

LEFT ELEVATION
1
1/4" = 1'-0"

PROJECT NAME:

NE COLONIAL

ELEVATION LEFT
PROJECT NUMBER: 10-002
DATE: Issue Date
DRAWN BY: Author

9/24/2009 10:33:26 AM
CHECKED BY: Checker

A-01-4
SCALE 1/4" = 1'-0"
1 A-01-3
A-03-1

Rear1

73' - 7"
FREE GREEN
2' - 3" 19' - 6" 12' - 11" 33' - 11" 5' - 0"
3" 3" 3" 3" WALL LEGEND www.FreeGreen.com
2' - 8" 3' - 0 1/8" 8' - 10" 3' - 0 1/8" 3' - 0 1/8" 3' - 0 1/8" 3' - 0 1/8" 2' - 9" 2' - 8 1/8" 2' - 8 1/8" 2' - 8 1/8" 7' - 10" 3' - 0 1/8" 4' - 11 7/8" 3' - 0 1/8" 3' - 9 1/2" 348 MEDFORD ST. SUITE 1
2x4 OR 2x6 STUD WALL CHARLESTOWN, MA 02129
R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. R.O. W/ INSULATION
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
2x4 OR 2x6 STUD WALL
1' - 11 3/4" 1' - 8 5/16" 1' - 8 5/16"
UN-INSULATED
NOTES:
LOAD BEARING
PARTITION D = COMBINATION SMOKE & CARBON MONOXIDE DETECTORS:
DETECTORS SHALL BE INSTALLED OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF
NOTE: BEDROOMS AND ON EACH STORY OF THE DWELLING
INCLUDING BASEMENTS. ALL DETECTORS SHALL BE
DIMENSIONS TO EXTERIOR WALLS CONNECTED TO A SOUNDING DEVICE OR OTHER
PROPOSED LOCATION OF REFERENCE FACE OF STUD. DETECTORS TO PROVIDE AN ALARM AUDIBLE IN ALL
PRE-FAB CONC BULKHEAD SLEEPING AREAS. ALL DETECTORS SHALL BE APPROVED
V.I.F. ALL DIMENSIONS & R.O. DIMENSIONS TO INTERIOR AND LISTED AND SHALL BE INSTALLED IN ACCORDANCE
PARTITIONS REFERENCE CENTER WITH MANUFACTURER'S INSTRUCTIONS.
OF 2x4 OR 2x6 STUD.
8 15/16"

8 11/16"
19 19 19 1 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
6 6 6 MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
1
PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.
3' - 0 1/8"

FLOOR TO FLOOR HEIGHTS WILL VARY BASED ON DEPTH OF


4' - 0"

4' - 0"
2' - 7"
2

R.O.
BEAM AS REQ (ABOVE)
R.O.

18 18 FLOOR FRAMING AS DETERMINED BY STRUCTURAL


1' - 10"

19 6
8 8 8 6x6 POST 7 7 ENGINEER. STAIR RISERS MUST NOT EXCEED 7 3/4", STAIR
4 4 4x6 POST TREADS MUST NOT BE LESS THAN 10" AS PER IRC 2006.
3 WALL MOUNT STAIR RAIL. MAX PROJECTION MUST NOT

8 3/8"
DINING NOOK
3"

EXCEED 4 1/2" FROM FACE OF FINISH WALL AS PER IRC 2006.


CASEWORK CASEWORK DECORATIVE COLUMN
4x6 POST D 4 PROVIDE ACCESS HATCH INTO ATTIC SPACE.
1' - 10 1/8"

BATH 1 CAP OVER 6x6 PT


5' - 0"

5' - 2 3/4"
19' - 4 1/4" POST ON GALV STEEL
R.O.

20 12 5 VENT AS PER MANUFACTURERS SPECIFICATIONS.


POST ANCHOR TYP
HALF HEIGHT PARTITION
4' - 0" 6 DECKING OVER PT 2x8 JOISTS @ 16" O/C. SOFFIT MATERIAL AT
20" RAISED HEARTH

2-6x7-0
KITCHEN UNDERSIDE OF COVERED PORCH TO BE 1x4 T&G CLEAR

4' - 0"
W/ WALL CAP TRIM OFFICE CEDAR.
DECORATIVE FAUX COLUMN
1' - 3 7/8"

60" CASED OPENING


MASONRY CHIMNEY 16' - 1 3/4"
BEAM AS REQ ABOVE

48" COOKTOP
& FIRE PLACE

15' - 2"
BENCH
2' - 0"
TOP OF SUB FLR
6' - 0"

EL = 0'-0" 5 REAR PORCH


2-6x7-0
1' - 3 7/8"

1' - 0"
1 6

9' - 5 3/4"
MUD ROOM
DECORATIVE FAUX COLUMN STORAGE
36" CASED
HALF HEIGHT PARTITION BEAM AS REQ (ABOVE) OPENING
1' - 10 1/8"

HEADER AS REQ
FAMILY ROOM W/ WALL CAP TRIM
(ABOVE)
R.O.
5' - 0"

20 12

3-0x7-0
STEEL
4x6 POST 4x6 POST 36" CASED 30" WALL
DESK / OFFICE OVEN 48" REF 6x6 POST
DBL 2-6x7-0 FRENCH POCKET OPENING 4x6 POST

3' - 0"
COAT 48" CASED OPENING
1' - 10"

3' - 10 3/4"
4 4x6 POST

MIN 36"

Right
HEADER AS REQ CLOSET 2-6x7-0 TOP OF SLAB HIGH POINT
3 R UP
44' - 0"

44' - 0"
4
A-01-4
1 18 (ABOVE) GLASS EL = (-) 1'-7" A-01-2
142DN 1
Left

6' - 7 1/2"
2-6x7-0

5-0x7-0

COOLER

3' - 0 1/8"
WINE

R.O.
WET BAR PANTRY CONCRETE OR WOOD FRAMED 1 7
BEAM AS REQ PLATFORM UP TO ENTRY LEVEL
(ABOVE) WALL MOUNTED 3
HAND RAIL
OPEN TO
3 GARAGE
ABOVE BUILDER TO APPLY 5/8" TYPE "X" GYPSUM
LIVING ROOM 48" CASED OPENING TO WALL & CLG. THROUGHOUT. TIGHTLY
16' - 0"

8 REVISION SCHEDULE:
SEAL SHARED SURFACES BETWEEN No. Description Date
GARAGE & CONDITIONED SPACES.

SLAB ON GRADE SLOPE 2"


TOWARDS GARAGE DOOR
A-04-4
PAINT GARAGE WALLS & CEILING.

60" CASED OPENING


LINE OF
FLOOR & BEAM 4x6 POST WEATHER STRIP ALL DOORS LEADING 4x6 POST
ABOVE FROM GARAGE CONDITIONED SPACES.

12' - 9 3/4"

24' - 10"
16 R UP
2 ENTRY FOYER D BEAM ABOVE AS REQ
36" CASED
LALLY COLUMN
14' - 4 3/4" OPENING 3' - 10 1/4" 8' - 7 1/4" 7' - 4 1/2" 5' - 3 1/4"

4x6 POST 4x6 POST

15' - 1 3/4"
2' - 4 1/2"

3 3
BEAM AS REQ
(ABOVE)
FRONT PORCH
6' - 0"

3' - 0 1/8"
BEAM AS REQ

R.O.
(ABOVE) 1 6 LINE OF 7
OVERHANG ABOVE
DINING ROOM 4x6 POST
GARAGE DOOR GARAGE DOOR

3' - 0"
8-0x7-0 8-0x7-0
2' - 0"

2' - 0"
BEAM AS REQ
(ABOVE)

9 16 9
4x6 POST BEAM ABOVE (AS REQ) 4x6 POST
DECORATIVE COLUMN
CAP OVER 6x6 PT
POST ON GALV STEEL TOP OF SLAB LOW POINT
POST ANCHOR TYP CONC APRON AS REQ
EL = (-) 1'-9"
PER SITE GRADE

PROJECT NAME:

NE COLONIAL

ENTRY LEVEL FLOOR


9 15/16"
1' - 2" R.O.
3' - 0 1/8" 2' - 6" 3' - 0 1/8" 4' - 0" 3' - 0 1/8" 5' - 4 7/8" 5' - 7" 3' - 5 7/8" 1' - 0 1/4"
OVERALL R.O.
9' - 3 1/2" 1' - 0 5/16" 2' - 7 1/2" 8' - 4 1/2" 2' - 0" 8' - 4 1/2" 2' - 7 1/2" PLAN
R.O. R.O. R.O. R.O. R.O. PROJECT NUMBER: 10-002
2' - 3" 5' - 0" 27' - 0" 2' - 0" 11' - 4" 2' - 0" 24' - 0"
DATE: Issue Date
73' - 7" DRAWN BY: MY

9/24/2009 10:33:26 AM
CHECKED BY: BU, SH
1Front

ENTRY LEVEL FLOOR PLAN


A-01-1 A-02-1
1 SCALE 1/4" = 1'-0"
1/4" = 1'-0"
1 A-01-3
A-03-1

47' - 9 1/2"
Rear1 FREE GREEN
2' - 8" 3' - 0 1/8" 10' - 4 13/16" 2' - 2 1/8" 7' - 10 7/8" 2' - 2 1/8" 6' - 9 5/8" 3' - 10 1/8" 3' - 2 3/16" 2' - 2 1/8" 3' - 5 7/16"
www.FreeGreen.com
R.O. R.O. R.O. R.O. R.O.
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
WALL LEGEND © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
2x4 OR 2x6 STUD WALL
W/ INSULATION NOTES:

2x4 OR 2x6 STUD WALL D = COMBINATION SMOKE & CARBON MONOXIDE DETECTORS:
UN-INSULATED DETECTORS SHALL BE INSTALLED OUTSIDE EACH
SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF
LOAD BEARING BEDROOMS AND ON EACH STORY OF THE DWELLING
PARTITION INCLUDING BASEMENTS. ALL DETECTORS SHALL BE
CONNECTED TO A SOUNDING DEVICE OR OTHER
NOTE: DETECTORS TO PROVIDE AN ALARM AUDIBLE IN ALL
SLEEPING AREAS. ALL DETECTORS SHALL BE APPROVED
DIMENSIONS TO EXTERIOR WALLS AND LISTED AND SHALL BE INSTALLED IN ACCORDANCE
REFERENCE FACE OF STUD. WITH MANUFACTURER'S INSTRUCTIONS.

DIMENSIONS TO INTERIOR 1 MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.


PARTITIONS REFERENCE CENTER PORCHES, BALCONIES OR RAISED FLOOR SURFACES
OF 2x4 OR 2x6 STUD. LOCATED MORE THAN 30" ABOVE THE FLOOR OR GRADE
BELOW SHALL HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.
2 FLOOR TO FLOOR HEIGHTS WILL VARY BASED ON DEPTH OF
FLOOR FRAMING AS DETERMINED BY STRUCTURAL
TEMPERED ENGINEER. STAIR RISERS MUST NOT EXCEED 7 3/4", STAIR
1' - 3"

TREADS MUST NOT BE LESS THAN 10" AS PER IRC 2006.


18
24 18
4 10 10 8 5 8 8 17
3 PROVIDE ACCESS HATCH INTO ATTIC SPACE.
4 DRIP PAN AND FLOOR DRAIN UNDER WASHER IN LAUNDRY
EGRESS TEMPERED AREA. VENT DRYER THROUGH ADJACENT EXT WALL OR UP

2-6x6-8 POCKET
DRYER SOAKING TUB GLASS SHOWER ENCLOSURE THROUGH ROOF.
3' - 0 1/8"

14' - 6 1/4" 7' - 0 1/2"


R.O.

12
2 2-6x6-8
3' - 5 1/2" 3' - 5 1/2"
LAUNDRY
4 WASHER

12' - 4 7/16"
KING BED

11' - 4 1/4"

2' - 8"
MASONRY CHIMNEY
& FIRE PLACE BATH 2 MASTER 7' - 10 3/4"
7' - 5 3/4"

BATH
16' - 0"

BED 2

5' - 11 1/2"
3' - 5 1/2" 7' - 0 1/2" WALK IN
CLOSET

3' - 9 1/2"
D TABLE
OR

2-6x6-8

2-6x6-8

2-6x6-8
SHELF
3' - 0 1/8"

2-6x6-8 POCKET
3' - 11 1/2"
R.O.

2-6x6-8

3' - 0 1/8"
4x6 POST
7

EGRESS
12
2 BEAM AS REQ (ABOVE)

R.O.
2-6x6-8
HEADER AS REQ (ABOVE) 2-6x6-8
A-04-4
36" MIN HALF HEIGHT PARTITION D HEADER AS REQ (ABOVE)
2
4x6 POST W/ WALL CAP TRIM KING BED
5-8x6-8 2-6x6-8 POCKET

2' - 9 1/2"
2' - 10 3/4"

1' - 3"

18' - 1"
18
4 7' - 3 7/8" LINEN

Right
16 R DN 2 CLOSET
1 A-01-2

DBL 2-0x6-8
2' - 5 1/2"

A-01-4 1
Left

WALK IN
MASTER SUITE
38' - 0"

38' - 0"
5-8x6-8

3' - 0 1/8"
CLOSET

R.O.

40' - 0"
3' - 0 1/8"

2
R.O.

OPEN TO
KING BED BELOW 6' - 4 1/4" 10' - 4 1/2" 6' - 4 1/4"

2-6x6-8
D
REVISION SCHEDULE:
16' - 0"

2-6x6-8
13' - 3 3/4"

No. Description Date


5' - 10"

BED 1 1
OPEN RAILS BED 3
5-0x6-8

14' - 4 3/4" 12' - 5 1/2" 4' - 9" 7' - 10 3/4"


1' - 3" 3' - 0 1/8"

16' - 9 7/8"
R.O.

2
2' - 4 1/2"
2-6x6-8
D
EGRESS 3
KING BED
SITTING RM

13' - 4 1/4"
2' - 0"

2 2

11 15 11 4x6 POST
BEAM AS REQ
4' - 0"

(ABOVE)

EGRESS

2' - 0"
2 2 EGRESS

PROJECT NAME:

NE COLONIAL

UPPER LEVEL
2' - 0 1/4" 3' - 0 1/8"

2' - 6" 3' - 0 1/8" 4' - 0" 3' - 0 1/8" 2' - 7"
OVERALL R.O.
7' - 7 1/2" 2' - 3" 2' - 6" 3' - 0 1/8" 4' - 9 1/4" 3' - 0 1/8" 2' - 6" 10' - 0 7/16" R.O. 10' - 5 15/16" FLOOR PLAN
R.O. R.O. PROJECT NUMBER: 10-002
5' - 0" 14' - 6 1/2" 12' - 5 1/2" 15' - 9 1/2" 23' - 6 1/2"
DATE: Issue Date
71' - 4" DRAWN BY: MY

9/24/2009 10:33:27 AM
CHECKED BY: BU, SH
1Front

A-01-1 A-02-2
UPPER LEVEL FLOOR PLAN SCALE 1/4" = 1'-0"
1
1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

NOTES:

1 DEPTH OF SPRAY FOAM INSULATION TO MEET 2006 IECC


REQUIREMENT FOR THE PROJECTS CLIMATE ZONE.
2 STEPS OR RAMP TO GRADE AS REQ PER SITE CONDITIONS.
MINIMUM 3'-0" LANDING REQUIRED AT ALL ENTRY WAYS.
PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
MORE THAN 30" ABOVE THE FLOOR OR GRADE BELOW SHALL
HAVE GUARDS NOT LESS THAN 36" IN HEIGHT.
3 FLOOR TO FLOOR HEIGHTS WILL VARY BASED ON DEPTH OF
FLOOR FRAMING AS DETERMINED BY STRUCTURAL
ENGINEER. STAIR RISERS MUST NOT EXCEED 7 3/4", STAIR
TREADS MUST NOT BE LESS THAN 10" AS PER IRC 2006.
4 WALL MOUNT STAIR RAIL. MAX PROJECTION MUST NOT
EXCEED 4 1/2" FROM FACE OF FINISH WALL AS PER IRC 2006.
12 12
5 DECKING OVER PT 2x8 JOISTS @ 16" O/C. SOFFIT MATERIAL AT
T.O. RIDGE RAFTER EL = +/- 31'-10 3/8" V.I.F. 10 10 UNDERSIDE OF COVERED PORCH TO BE 1x4 T&G CLEAR
CEDAR.

T.O. RIDGE RAFTER EL = +/- 25'-10 3/8" V.I.F.

PROVIDE 2x6 COLLAR


TIES IN UPPER THIRD
+/- 6' - 8 3/8" V.I.F.

PORTION OF ROOF GABLE

1/2" GYPSUM REQ IN OCCUPIED ATTIC 3/4" T&G SHEATHING


AS THERMAL BARRIER FOR SPRAY OVER 11 1/4" FLOOR TRUSSES
FOAM INSULATION IN RAFTERS @ 16" O/C (OR AS REQ)
T.O. ATTIC SUB FLOOR EL = 19'-2"
B.O. FLOOR FRAMING EL
+/- 31' - 10 3/8" V.I.F.

1' - 0"

ASPHALT SHINGLE ROOFING


16' - 0" 11' - 1" 6' - 11"
ROOF CONSTRUCTION: (TOP DOWN)
- ASPHALT SHINGLES
9' - 1"

HALF HEIGHT PARTITION OPEN RAILS AROUND - ROOFING PAPER (30LB FELT OR EQUIVALENT)
8' - 1"

3/4" T&G SHEATHING 2 - 5/8" SHEATHING


BALCONY & ON STAIR
OVER 11 1/4" FLOOR TRUSSES MIN 36" HIGH - 2x10 RAFTERS @ 24" O/C W/ SPRAY FOAM INSULATION (UNVENTED) 1
@ 16" O/C (OR AS REQ) - 1x3 STRAPPING @ 16" O/C
- 1/2" GYPSUM BOARD (REQ FOR THERMAL BARRIER)

3' - 0"

MIN
T.O. UPPER LEVEL SUB FLOOR EL = 10'-1"
B.O. FLOOR FRAMING EL

3' - 9 3/8"
1' - 0"

PROVIDE INSULATION CLAP BOARD SIDING


IN FLOOR CAVITY ABOVE
8'-6 1/2" OUTSIDE AIR EXT WALL CONSTRUCTION: (OUTSIDE to IN)
REVISION SCHEDULE:
10' - 1"

- 5/16" FIBER CEMENT CLAP BOARD SIDING


No. Description Date
9' - 1"

- CORRUGATED SPACER MESH


- BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE

6' - 3 5/8"
W/ MIN 6" OVERLAP AT HORZ JOINTS
- 1/2" SHEATHING
3/4" T&G SHEATHING - 2x6 STUD WALL W/ SPRAY FOAM INSULATION 1
OVER 11 1/4" FLOOR TRUSSES - 1/2" GYPSUM BOARD W/ VAPOR
@ 16" O/C (OR AS REQ) 16 R UP 2 5 SEMI-PERMEABLE LATEX PAINT
T.O. ENTRY LEVEL SUB FLOOR EL = 0'-0" 3

2' - 6 9/16"
B.O. FLOOR FRAMING EL
1' - 0"

T.O. FOUNDATION WALL 20' - 0" 10' - 4 1/2" 5' - 7 1/2"


3"
9' - 3"

GROUND SLOPES AWAY FROM 4 6'-9 1/2" GROUND SLOPES AWAY FROM

6' - 4 7/16"
8' - 0"

WALL @ 5% OR 6" PER 10' WALL @ 5% OR 6" PER 10'

CONC FOUNDATION WALL AS REQ CONC FOUNDATION WALL AS REQ


14 R UP
CONC FOOTING BELOW FROST DEPTH 4" CONCRETE SLAB ON GRADE 3 CONC FOOTING BELOW FROST DEPTH
T.O. CONCRETE FOOTING EL = (-) 9'-3"

SECTION 1 PROJECT NAME:


1
1/4" = 1'-0"
NE COLONIAL

BUILDING SECTIONS
PROJECT NUMBER: 10-002
DATE: Issue Date
DRAWN BY: MY

9/24/2009 10:33:28 AM
CHECKED BY: BU, SH

A-03-1
SCALE 1/4" = 1'-0"
ASPHALT SHINGLE ROOFING
ROOFING PAPER (30lb FELT OR EQUIVALENT)
5/8" SHEATHING
ASPHALT SHINGLE RIDGE CAP
ROOFING PAPER (30lb FELT OR EQUIVALENT)
RIDGE VENT &
INSECT SCREEN FREE GREEN
12 FULLY-ADHERED MEMBRANE WATERPROOFING
SEALANT ADHESIVE OVER FLASHING
1/2LB SPF (OPEN CELL) INSULATION 5/8" SHEATHING
MIN
4 ASPHALT SHINGLES
SPRAY APPLIED IGNITION BARRIER www.FreeGreen.com
ROOF CONSTRUCTION: (TOP DOWN)
ASPHALT SHINGLE ROOFING - DRIP EDGE FLASHING 2x10 RAFTERS @ 24" O/C 348 MEDFORD ST. SUITE 1
1x3 STRAPPING @ 16" O/C
30 LB FELT - 12 CHARLESTOWN, MA 02129
FULLY-ADHERED MEMBRANE WATERPROOFING - 1/2" GYPSUM REQ IN OCCUPIED ATTIC
(SINGLE COURSE AT EAVE) AS THERMAL BARRIER FOR SPRAY CLEAT MIN 4 © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
5/8" SHEATHING - FOAM INSULATION IN RAFTERS
2x10 RAFTERS @ 24" O/C (OR AS REQ) - NOTES:
CONT 2x6 BASE PLATE 2x3 KNEE WALL
DRIP EDGE FLASHING W/ CLEAT 1x6 FIBER CEMENT TRIM BOARD
3/4" T&G SUB FLOOR
EXTRUDED GUTTER PROFILE W/ TIES TREATED WOOD NAILER

1x6 FIBER CEMENT TRIM BOARD


6" TO 12"
1x4 FIBER CEMENT TRIM BOARD ATTIC FLOOR JOISTS
(SIZEOPEN
BCB & SPACING AS REQ)
WEB TRUSSES 1x8 FIBER CEMENT TRIM BOARD
1x_ PAINTED WOOD SOFFIT (SIZE & SPACING AS REQ)
2x10 LADDER FRAME RAFTERS 2x12 RIDGE RAFTER
CROWN MOLDING OVER 1x6
TRIM NOTCHED TO RECEIVE SIDING 1/2" SHEATHING
2x_ ATTIC FLOOR RIM JOIST 1/2LB SPF (OPEN CELL) CAVITY INSULATION
CONT 2x6 TOP PLATE
CONT SEALANT 1/2" GYPSUM BOARD ON WALL & CEILING W/
VAPOR SEMI-PERMEABLE LATEX PAINT
BASE BOARD 1x_ PAINTED WOOD SOFFIT

WALL CONSTRUCTION: (OUTSIDE to INSIDE) FINISH FLOOR 1x4 PAINTED WOOD TRIM
5/16" FIBER CEMENT CLAP BOARD SIDING - 3/4" T&G SUB FLOOR 5/16" FIBER CEMENT CLAP BOARD SIDING
CORRUGATED SPACER MESH - (4 1/4" EXPOSURE)
BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE -
1/2" SHEATHING -
CORRUGATED SPACER MESH
2x6 STUD WALL W/ 1/2LB SPF (OPEN CELL) INSULATION -
BUILDING PAPER OR HOUSE WRAP SPRAY FOAM INSULATION
BCB OPEN WEB TRUSSES
DRAINAGE PLANE
2x_ RIM JOIST AS REQ (SIZE & SPACING AS REQ)

CONT 2x6 TOP PLATE


1/2LB SPF (OPEN CELL) CAVITY INSULATION
1/2" GYPSUM ON WALL & CEILING ASPHALT SHINGLE ROOFING - RAKE ASPHALT SHINGLE ROOFING - RIDGE
CONT SEALANT W/ VAPOR SEMI-PERMEABLE LATEX PAINT 2 3
BASE BOARD
3" = 1'-0" 3" = 1'-0"
FINISH FLOOR BASE BOARD
3/4" T&G SUB FLOOR
FINISH FLOOR
3/4" T&G SUB FLOOR

BCB OPEN WEB TRUSSES


2x_ RIM JOIST AS REQ (SIZE & SPACING AS REQ) BASE BOARD
BCB OPEN WEB TRUSSES
PT SILL PLATE AS REQ PT SILL PLATE AS REQ 1" RIGID INSULATION AS THERMAL BREAK
2x_ RIM JOIST AS REQ (SIZE & SPACING AS REQ)
(OMIT SILL AT ENTRY DOORS)
CONT SILL GASKET & SEALANT CONC SLAB ON GRADE AS REQ.
PT SILL PLATE AS REQ
CORRUGATED SPACER MESH REQ INSECT CONT SILL GASKET & SEALANT FINISH FLOOR
ANCHOR BOLTS AS REQ PER
MESH @ TOP & BOTTOM OF WALL TYPICAL 1/2LB SPF (OPEN CELL) CAVITY INSULATION
STRUCTURAL ENGINEER ANCHOR BOLTS AS REQ PER
2x3 PT TOP & BOTTOM PLATE IMPERMEABLE BACK FILL STRUCTURAL ENGINEER
ANCHOR BOLTS AS REQ PER
1/2" NON-PAPER FACED GYPSUM
12" MIN

STRUCTURAL ENGINEER

12" MIN
GROUND SLOPES BOARD ON WALL & CEILING W/ VAPOR

12" MIN
AWAY FROM WALL SEMI-PERMEABLE LATEX PAINT
@ 5% OR 6" PER 10' GROUND SLOPES AWAY FROM
2x3 PT STUD WALL W/ 1/2LB
GROUND SLOPES AWAY FROM WALL @ 5% OR 6" PER 10'
SPF (OPEN CELL) INSULATION
WALL @ 5% OR 6" PER 10'
2x3 STUDS HELD OFF FACE
OF CONC WALL BY 1"
RADIANT HEATING TUBES IN SLAB (OPTIONAL)
SILL GASKET
GRANULAR CAPILLARY BREAK &
CONC FOUNDATION WALL DRAINAGE PAD (NO FINES) REVISION SCHEDULE:
IMPERMEABLE BACK FILL CONC FOUNDATION WALL AS REQ
AS REQ 2" XPS RIGID INSULATION No. Description Date
GRANULAR BACK FILL GRANULAR BACK FILL SPRAY FOAM INSULATION
GRANULAR BACK FILL (UNDER ENTIRE SLAB)
2" XPS RIGID INSULATION DAMPPROOFING SPRAY APPLIED IGNITION BARRIER
DAMPPROOFING (UNDER ENTIRE SLAB)
FILTER FABRIC CONT POLYETHYLENE VAPOR BARRIER/AIR CONC FOUNDATION WALL
CONCRETE SLAB ON GRADE
BARRIER (ALL JOINTS TAPED). FOLD UP ONTO AS REQ
COARSE GRAVEL FILTER FABRIC FOUNDATION WALL AND SECURE W/ PT NAILER 2" XPS RIGID INSULATION
COARSE GRAVEL CONC. FOOTING BELOW
FROST DEPTH

4" PERFORATED DRAIN PIPE


TIE INTO DRY WELL COARSE GRAVEL
SEALANT OVER 1" XPS RIGID INSULATION 4" PERFORATED DRAIN PIPE
CONCRETE FOOTING BELOW TIE INTO DRY WELL
FROST DEPTH AS BOND BREAK MATERIAL & THERMAL BREAK
CAPILLARY BREAK OVER FOOTING CONC. FOOTING BELOW CAPILLARY BREAK OVER FOOTING
(DAMPPROOFING OR MEMBRANE) FROST DEPTH (DAMPPROOFING OR MEMBRANE)

FOUNDATION - CRAWL SPACE -


TYPICAL WALL SECTION CONDITIONED FOUNDATION - SLAB ON GRADE
1 4 5
1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
VENT THROUGH ROOF

EXTERIOR
2x4 STAGGERED STUDS
(SPACING AS REQ)
SEALANT AT ALL SHEATHING AS REQ
SLAB PENETRATIONS

VENT STACK CONC. SLAB AS REQ


PERFORATED DRAIN PIPE ADDED 2" EPS RIGID INSULATION AS REQ PROJECT NAME:
TO "T" TO COUPLE SUB-SLAB 4" GRANULAR CAPILLARY BREAK
PRESSURE FIELD TO VENT STACK & DRAINAGE PAD NO FINES
THIS DETAIL IS TO BE NE COLONIAL
7 1/4"

USED WHEN OPTIMAL


INSULATING PERFORMANCE
IS REQUIRED

DETAILS 1

SPRAY FOAM INSULATION PROJECT NUMBER: 10-002


2x8 TOP & BOTTOM PLATE DATE: Issue Date
ONE VENT FOR EACH PORTION OF FOUNDATION
1/2" GYPSUM BOARD DRAWN BY: MY
IN EPA ZONE 1 RADON AREAS, INSTALL RADON RESISTANT FEATURES BELOW

9/24/2009 10:33:30 AM
THE SLAB. EPA RADON MAP BY COUNTY IS AVAILABLE AT: (WALLS & CEILING) CHECKED BY: BU, SH
http://www.epa.gov/radon/zonemap.html
INTERIOR

RADON DE-PRESSURIZATION DETAIL


STAGGERED EXT STUD WALL
(OPTIONAL)
A-04-1
6 7 SCALE As indicated
1" = 1'-0" 3" = 1'-0"
1 2 FREE GREEN
BUILDING PAPER OR HOUSE WRAP
1/2"SHEATHING
DRAINAGE PLANE TO LAP OVER
ADHESIVE MEMBRANE TAPE & FLASHING 1/2"GYPSUM BOARD, FINISH
STEP 1: CORRUGATED SPACER MESH W/ SEMIPERMEABLE LATEX PAINT
WOOD FRAME WALL WITH www.FreeGreen.com
SHEATHING AND HOUSE WRAP 5/16" FIBER CEMENT CLAP BOARD SIDING
348 MEDFORD ST. SUITE 1

1/8"
2" EPS RIGID INSULATION @ CHARLESTOWN, MA 02129
STEP 2: ALUM FLASHING W/ DRIP
MODIFIED "I" CUT IN HOUSE WRAP EDGE. FASTEN TO FACE OF WALL W/ INSIDE FACE OF HEADER © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
ADHESIVE MEMBRANE TAPE. APPLY STRUCTURAL HEADER
SEALANT BEAD UNDER BOTH FLANGES. (SIZE AS REQ PER R.O.) NOTES:
1x4 FIBER CEMENT TRIM BOARD 1x4 INTERIOR WOOD TRIM 1x_ INTERIOR WOOD TRIM
SILL RIP TO FIT
1/2"GYPSUM BOARD, FINISH

1/4"
ADHESIVE MEMBRANE FLASHING TO LAP W/ SEMIPERMEABLE LATEX PAINT 1x4 INTERIOR WOOD TRIM
OVER NAIL FIN & ONTO WIN FRAME 2x6 STUD WALL W/ SPRAY FOAM 1x_ INTERIOR WOOD TRIM
SEALANT BEAD UNDER NAIL FIN CAVITY INSULATION JAMB EXTENDER RIP TO FIT
1x_ INTERIOR WOOD TRIM WINDOW UNIT AS PER PLANS
1/2"SHEATHING
3 4 JAMB EXTENDER RIP TO FIT
SHIM SPACE
1/4"

STEP 3:
- HOUSEWRAP FOLDED IN;
ALTERNATELY, TUCK HEAD FLAP UNDER
- INSTALL WOOD BACKDAM

STEP 4:
- INSTALL FIRST PIECE OF ADHESIVE
BACKED FLASHING
- INSTALL SECOND PIECE OF ADHESIVE
BACKED FLASHING WINDOW FRAME PROFILE IS
- INSTALL CORNER PATCHES AT SILL SIMILAR FOR FIXED UNITS

WINDOW UNIT AS PER PLANS

PROVIDE PT BLOCKING
SILL GUARD W/ SEALANT BEAD 1x_ INTERIOR WOOD TRIM
SILL RIP TO FIT
5 6
BUILDING PAPER OR HOUSE WRAP
DRAINAGE PLANE TO LAP INTO JAMB
SEALANT
CORRUGATED SPACER MESH
STEP 5: 1x4 INTERIOR WOOD TRIM SEALANT BEAD UNDER
INSTALL WINDOW PLUMB, LEVEL AND 1x4 FIBER CEMENT TRIM BOARD 5/16" FIBER CEMENT CLAP BOARD SIDING
SQUARE PER MANUFACTURER'S WIN NAIL FIN (TYP)
INSTRUCTIONS BUILDING PAPER OR HOUSE WRAP 1x4 FIBER CEMENT TRIM BOARD
ADHESIVE MEMBRANE TO LAP ONTO WIN NAIL FIN
DRAINAGE PLANE TO LAP ONTO
1/2"GYPSUM BOARD, FINISH
STEP 6: SILL AND UNDER SILL GUARD
W/ SEMIPERMEABLE LATEX PAINT
INSTALL JAMB FLASHING FIRST THEN SEALANT
HEAD FLASHING SINGLE OR DBL 2x6 SILL PLATE (AS REQ)
2x6 STUD WALL W/ SPRAY FOAM
CAVITY INSULATION

WINDOW FRAME PROFILE IS


SIMILAR FOR FIXED UNITS

7 8 WINDOW - ANDERSON CLAD - DBL HUNG WINDOW - ANDERSON CLAD - DBL HUNG
- HEAD/SILL DETAIL - JAMB DETAIL
2 3
STEP 7: 3" = 1'-0" 3" = 1'-0"
FOLD DOWN HOUSEWRAP AT HEAD

STEP 8:
APPLY CORNER PATCHES AT HEAD

REVISION SCHEDULE:
No. Description Date

SUGGESTED WINDOW INSTALLATION


(TYPICAL)
1
1" = 1'-0"

1/2" SHEATHING
BUILDING PAPER OR HOUSE WRAP
FIBER CEMENT CORNER BOARDS DRAINAGE W/ MIN 6" OVERLAP AT JOINTS
SEALANT TAPE CORRUGATED SPACER MESH
CORRUGATED SPACER MESH @ CORNERS
SEALANT @ BUT JOINT
BEHIND CORNER BOARDS SEALANT TAPE AT CORNERS
AND CLAP BOARD SIDING 5/16" FIBER CEMENT CLAP BOARD SIDING

5/16" FIBER CEMENT CLAP BOARD SIDING


CORNER BOARDS AS PER
ELEVATIONS
INSULATED OR UNINSULATED WALL SYSTEM
1/2" SHEATHING PT SILL PLATE AS REQ

PROJECT NAME:
SEALANT PT OR CEDAR NAILER
BEHIND BOTTOM COURSE
BUILDING PAPER OR HOUSE WRAP
DRAINAGE W/ MIN 6" OVERLAP AT JOINTS
5/16" FIBER CEMENT CLAP BOARD SIDING
CORRUGATED SPACER MESH
NE COLONIAL
SEALANT 1x8 LOWER BAND BOARD W/ 2x2 CANTED TOP
BUILDING PAPER OR HOUSE WRAP
DRAINAGE W/ MIN 6" OVERLAP AT JOINTS 1x1 CLEAR
S.S. OR GLAV STAPLES
1/2" SHEATHING
INSULATED WALL SYSTEM
CEDAR TRIM
SILL GASKET TYP BETWEEN TREATED
DETAILS 2
WOOD & CONCRETE
1/2" GYPSUM BOARD (WALL & CEILING)
OVER LAP SHEATHING & BUILDING
PAPER 3/4" OVER EDGE OF PROJECT NUMBER: 10-002
FOUNDATION WALL DATE: Issue Date

3/4"
PT OR CLAP BOARD NAILER DRAWN BY: MY

9/24/2009 10:33:33 AM
BEHIND BOTTOM COURSE CHECKED BY: BU, SH

CLAP BOARD SIDING - DRAIN SCREEN -


ISOMETRIC DETAIL 1
CLAP BOARD SIDING - DRAIN SCREEN -
CORNER DETAIL
CLAP BOARD SIDING - DRAIN SCREEN -
BOTTOM OF WALL DETAIL
A-04-2
4 5 6 SCALE As indicated
1" = 1'-0" 3" = 1'-0" 3" = 1'-0"
FREE GREEN
WALL CONSTRUCTION: (OUTSIDE to INSIDE) www.FreeGreen.com
5/16" FIBER CEMENT CLAP BOARD SIDING - DOOR UNIT AS PER PLANS
T.O. ENTRY LEVEL SUB FLOOR T.O. ENTRY LEVEL SUB FLOOR 348 MEDFORD ST. SUITE 1
CORRUGATED SPACER MESH - CHARLESTOWN, MA 02129
BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE - FSC CERTIFIED TROPICAL HARDWOOD
1/2" SHEATHING - PT WOOD OR COMPOSITE DECKING © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
2x6 STUD WALL W/ SPRAY FOAM INSULATION -
2x6 PT CONT TOP RAIL CANTED TO DRAIN
1/2" CLEAR CEDAR TRIM BOARD (MIN 3'-0" ABOVE DECK SURFACE) NOTES:

BUILDING PAPER OR HOUSE WRAP RIM JOIST AS PER PLANS BUILDING PAPER OR HOUSE WRAP RIM JOIST AS PER PLANS

0" - 7"

0" - 7"
DRAINAGE PLANE TO LAP OVER FLASHING DRAINAGE PLANE TO LAP OVER FLASHING
1/8" 1/2" 1/8" 1/2" 2x2 PT RAIL BALUSTERS @ 4 1/2" O/C MAX

4x4 PT RAIL POST @ 4' O/C MAX

FSC CERTIFIED TROPICAL HARDWOOD FSC CERTIFIED TROPICAL HARDWOOD

3" MAX
PT WOOD OR COMPOSITE DECKING PT WOOD OR COMPOSITE DECKING
FLASHING FASTEN TO FACE OF WALL FLASHING FASTEN TO FACE OF WALL
W/ ADHESIVE SEALANT TAPE W/ ADHESIVE SEALANT TAPE
DBL 3/8" DIA HDG STEEL LAG BOLTS
AND WASHERS (2 PER POST)
1/2" FASCIA TRIM BOARD
CONT 2x8 PT HEADER
PT SILL PLATE AS REQ PT SILL PLATE AS REQ
DBL 3/8" HDG LAG BOLTS & DBL 3/8" HDG LAG BOLTS & 3 1/2"x7 3/8" PT LAM BEAM
WASHERS @ 32" O/C WASHERS @ 32" O/C
4x4 PT POST
JOIST HANGER BEYOND JOIST HANGER BEYOND
GALV STEEL POST ANCHOR W/ BOLT
SILL GASKET SILL GASKET
12" DIA CONC SUPPORT W/ FOOTING
1/4" PLASTIC SPACER 1/4" PLASTIC SPACER BELOW FROST DEPTH AS REQ

3/4"

3/4"
2x10 PT LEDGER 2x10 PT LEDGER
ADHESIVE MEMBRANE UNDER LEDGER ADHESIVE MEMBRANE UNDER LEDGER

DECK LEDGER @ WALL - BCB TRUSS DECK LEDGER @ DOOR - BCB TRUSS
FLOOR FLOOR DECK EDGE W/ RAIL
1 2 3
3" = 1'-0" 3" = 1'-0" 1" = 1'-0"

OUTSIDE FACE OF GYPSUM ON OUTSIDE FACE OF GYPSUM ON


2x_ INTERIOR PARTITION 2x_ INTERIOR PARTITION
STAIR BEYOND IF DOUBLE FLIGHT STAIR BEYOND IF DOUBLE FLIGHT SOLID WOOD NOSING

OUTSIDE FACE OF GYPSUM ON


2x_ INTERIOR PARTITION FINISH FLOOR MATERIAL OVER
10" MIN SUB FLOOR SHEATHING 10" MIN
1/2" PLY SHEATHING W/
FINISHED WOOD VENEER
7 3/4" MAX

7 3/4" MAX
SOLID WOOD NOSING 1/2" SOLID WOOD RISER
FINISH FLOOR MATERIAL 1"x11 1/4" SOLID WOOD TREAD DBL PT 2x_ HEADER

3/4" PLY SHEATHING OUTSIDE FACE OF GYPSUM ON PT 2x4 NAILER


MIN 1" THICK FINISHED 2x_ INTERIOR PARTITION
WOOD FACE STRINGER
1" MIN REVISION SCHEDULE:
MIN 1" THICK FINISHED No. Description Date
WOOD FACE STRINGER 2 1/2" WOOD SCREWS
FLOOR FRAMING AS REQ FLOOR FRAMING AS REQ
2x12 NOTCHED STRINGERS 2x12 NOTCHED STRINGERS
DBL 2x_ HEADER AS REQ DBL 2x_ HEADER AS REQ PAINT ON WOOD PRESERVATIVE
MAX 19.2" O/C MAX 19.2" O/C
2x4 BLOCKING 2x4 BLOCKING @ ALL CUTS
2x4 BLOCKING 2x4 BLOCKING
2x3 NAILER FOR GYPSUM BOARD 2x3 NAILER FOR GYPSUM BOARD PT 2x12 NOTCHED STRINGERS
IF UNDERSIDE OF STAIR IS TO BE FINISHED FINISH FLOOR MATERIAL OVER IF UNDERSIDE OF STAIR IS TO BE FINISHED FINISH FLOOR MATERIAL OVER
SUB FLOOR SHEATHING SUB FLOOR SHEATHING
1/2" GYPSUM BOARD 1/2" GYPSUM BOARD PT 2x4 BRACING NAILED TO STRINGER

DECK STAIR TREAD. MATERIAL TO BE


PT 1x_, COMPOSITE DECKING, PT OR FSC
SOLID WOOD NOSING CERTIFIED TROPICAL HARDWOOD.
FINISH FLOOR MATERIAL 1"x11 1/4" SOLID HARD WOOD STAIR TREAD PT 2x4 KICK BOARD OVER 4" CONC
3/4" PLY SHEATHING 1/2" GYPSUM BOARD 1/2" GYPSUM BOARD SLAB
(TERMINATES AT FACE STRINGER) (TERMINATES AT FACE STRINGER) 1/2" DIA x 6" BOLTS EPOXIED
BASE MOUNTED POST INTO SLAB
FOR STAIR RAIL
MIN 1" THICK FINISHED MIN 1" THICK FINISHED
WOOD FACE STRINGER WOOD FACE STRINGER
2x12 NOTCHED OUTSIDE STRINGERS
MUST BE NAILED CONT AT 1" THICK FINISHED WOOD
2x_ FRAMED WALL FACE TRIM MITER AT CORNERS
BLOCKING TO STAIR RISER BLOCKING
2x12 NOTCHED STRINGERS 2x12 NOTCHED OUTSIDE STRINGERS 2x12 NOTCHED STRINGERS MAX 19.2" O/C 2x12 NOTCHED OUTSIDE STRINGER
MAX 19.2" O/C MUST BE NAILED CONT AT MUST BE NAILED CONT AT
DBL 2x_ TOP PLATE ON
2x_ FRAMED WALL BEARING WALL FOR DBL 2x12 2x_ FRAMED WALL
1/2" GYPSUM BOARD IF UNDERSIDE 2x_ FRAMED WALL REQ @ BOTH NOTCHED STAIR END STRINGERS 2x_ FRAMED WALL REQ @ BOTH
OF STAIR IS TO BE FINISHED END STRINGERS END STRINGERS
1/2" GYPSUM BOARD IF UNDERSIDE PROJECT NAME:
OF STAIR IS TO BE FINISHED
STAIRWAYS SHALL NOT BE LESS THAN 36" IN CLEAR WIDTH AT STAIRWAYS SHALL NOT BE LESS THAN 36" IN CLEAR WIDTH AT
ALL POINTS ABOVE THE PERMITTED HANDRAIL HEIGHT.
HANDRAILS SHALL NOT PROJECT MORE THAN 4.5" ON EITHER
ALL POINTS ABOVE THE PERMITTED HANDRAIL HEIGHT.
HANDRAILS SHALL NOT PROJECT MORE THAN 4.5" ON EITHER
NE COLONIAL
SIDE OF THE STAIRWAY AND THE MINIMUM CLEAR WIDTH OF SIDE OF THE STAIRWAY AND THE MINIMUM CLEAR WIDTH OF
THE STAIRWAY AT AND BELOW THE HANDRAIL HEIGHT, THE STAIRWAY AT AND BELOW THE HANDRAIL HEIGHT,
INCLUDING TREADS AND LANDINGS, SHALL NOT BE LESS THAN INCLUDING TREADS AND LANDINGS, SHALL NOT BE LESS THAN
31.5" WHERE HANDRAIL IS ON ONE SIDE AND 27" WHERE
HANDRAILS ARE PROVIDED ON BOTH SIDES. STAIR RISERS
31.5" WHERE HANDRAIL IS ON ONE SIDE AND 27" WHERE
HANDRAILS ARE PROVIDED ON BOTH SIDES. STAIR RISERS
DETAILS 3
MUST NOT EXCEED 7 3/4", STAIR TREADS MUST NOT BE LESS MUST NOT EXCEED 7 3/4", STAIR TREADS MUST NOT BE LESS
THAN 10" AS PER IRC 2009. THAN 10" AS PER IRC 2009.

PROJECT NUMBER: 10-002


INTERIOR STAIR - SECTION DETAIL INTERIOR STAIR - SECTION DETAIL DECK STAIR - ISOMETRIC DETAIL DATE:
5 4 6 Issue Date
1" = 1'-0" 1" = 1'-0" 1" = 1'-0"
DRAWN BY: MY

9/24/2009 10:33:35 AM
CHECKED BY: BU, SH

A-04-3
SCALE As indicated
POST OR COLUMN AS REQ
FREE GREEN
5/8" "TYPE X" GYPSUM BOARD
(TYP. TO GARAGE & MECH. SPACES)
WALL CONSTRUCTION: (OUTSIDE to INSIDE) GARAGE DOOR, STOP
& TRACK BY BLDR.
www.FreeGreen.com
5/16" FIBER CEMENT CLAP BOARD SIDING - 348 MEDFORD ST. SUITE 1
CORRUGATED SPACER MESH - EDGE OF FOUNDATION WALL BELOW CONT. WEATHER STRIPPING CHARLESTOWN, MA 02129
BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE - GARAGE DOOR JAMB (BEYOND)
1/2" SHEATHING - GARAGE DOOR HEADER BEAM AS REQ © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
CONT. WEATHER STRIPPING
2x4 OR 2x6 STUD WALL -
5/8" "TYPE X" GYPSUM BOARD GARAGE DOOR
(TYP. TO GARAGE & MECH. SPACES) NOTES:
ADHESIVE MEMBRANE
(LAP INTO GARAGE DOOR HEAD) 2x4 OR 2x6 STEM WALL
OR BLOCKING AS REQ CONC. SLAB CONC. APRON
FLASHING
SEALANT POLYETHYLENE VAPOR BARRIER DRIVE WAY SLAB
(USE WHITE CONC. OR OPEN PAVERS)
GRANULAR CAPILLARY BREAK AND
DRAINAGE PAD (NO FINES) GRANULAR CAPILLARY BREAK AND
1x3 CLEAR CEDAR TRIM
DRAINAGE PAD (NO FINES)
1/4"

SLAB SLOPES 2" TO


GARAGE DOOR

SEALANT 1x6 CLEAR CEDAR TRIM (RIP TO FIT)


1x6 CLEAR CEDAR TRIM (RIP TO FIT)
SEALANT
CONT. WEATHER STRIPPING
GARAGE DOOR, STOP 1x4 CLEAR CEDAR TRIM
WALL CONSTRUCTION: (OUTSIDE to INSIDE) UNDISTURBED COMPACTED SOIL
& TRACK BY BLDR.
5/16" FIBER CEMENT CLAP BOARD SIDING -
CORRUGATED SPACER MESH - FOUNDATION WALL AS REQ. UNDISTURBED COMPACTED SOIL
BUILDING PAPER OR HOUSE WRAP DRAINAGE PLANE - 1/4"
EXPANSION JOINT
1/2" SHEATHING -
2x4 OR 2x6 STUD WALL -
ADHESIVE MEMBRANE
(LAP INTO GARAGE DOOR JAMB)

GARAGE DOOR HEAD GARAGE DOOR JAMB GARAGE DOOR SILL


1 2 3
3" = 1'-0" 3" = 1'-0" 1" = 1'-0"

CONDITIONED SPACE 1/2" SHEATHING


2x6 WALL W/ SPRAY FOAM INSULATION
5/8" "TYPE X" GYPSUM BOARD
(TYP. TO GARAGE & MECH. SPACES)

2x4 OR 2x6 WALL AS REQ BASE BOARD


5/8" "TYPE X" GYPSUM BOARD FINISH FLOOR
PT SILL PLATE AS REQ (TYP. TO GARAGE & MECH. SPACES) 3/4" T&G SUB FLOOR GARAGE
SILL GASKET
CONC. SLAB
ANCHOR BOLTS AS REQ PER
POLYETHYLENE VAPOR BARRIER
STRUCTURAL ENGINEER
GRANULAR CAPILLARY BREAK AND BCB OPEN WEB TRUSSES
DRAINAGE PAD (NO FINES) (SIZE & SPACING AS REQ) SILL GASKET
6" +
12" MIN

CONC. SLAB
GROUND SLOPES AWAY FROM
WALL @ 5% OR 6" PER 10' SLAB SLOPES 2" TO POLYETHYLENE VAPOR BARRIER
GARAGE DOOR GRANULAR CAPILLARY BREAK AND
DRAINAGE PAD (NO FINES)

6" +
REVISION SCHEDULE:
IMPERMEABLE BACK FILL SLAB SLOPES 2" TO No. Description Date
GARAGE DOOR
FOUNDATION WALL AS REQ.
SEALANT & BACKER ROD @ EXPANSION JOINT
WATER STOP
UNDISTURBED COMPACTED SOIL

SEALANT & BACKER ROD @ EXPANSION JOINT


WATER STOP
GARAGE WALL @ OUTSIDE AIR - GARAGE WALL @ CONDITIONED SPACE - UNDISTURBED COMPACTED SOIL
VERTICAL WALL SECTION VERTICAL WALL SECTION
4 8
1" = 1'-0" 1" = 1'-0"

2x_ TOP PLATE

CROWN MOLDING
2x_ INTERIOR PARTITION 2x8 WOOD CAP PLATE W/
1/2" GYPSUM BOARD ON WALLS & CEILING 2x_ INTERIOR PARTITION 1/4" DIA ROUNDED CORNERS
PROVIDE 1/4" ROUT AT BOTTOM OF
1/2" GYPSUM BOARD ON WALLS & CEILING
CAP PLATE TO RECEIVE GYPSUM
WOOD CASING
HEADER AS REQ PROJECT NAME:
WOOD DOOR FRAME DOUBLE RABBET
BASE CAP MOLDING (SEPARATE) WOOD MOLDING NE COLONIAL
3/4"x3 1/2" WOOD TRIM 2x_ INTERIOR PARTITION
(PROVIDE 1/8" ROUT BEHIND TRIM FOR
1/4"

1/2" GYPSUM BOARD ON WALLS & CEILING


EASE OF INSTALLATION)
SHIM SPACE

BASE SHOE MOLDING (SEPARATE) FINISH FLOOR MATERIAL


INTERIOR SWING DOOR SLAB
DETAILS 4
3/4" T&G SHEATHING

PROJECT NUMBER: 10-002


SIMILAR FOR JAMB DETAIL
DATE: Issue Date
2x_ BASE PLATE
DRAWN BY: Author

9/24/2009 10:33:37 AM
CHECKED BY: Checker

5
INTERIOR TRIM - BASE BOARD &
CORNICE
6
INTERIOR TRIM - DOOR HEAD & JAMB
7
INTERIOR TRIM - PARTITION WALL CAP A-04-4
3" = 1'-0" 3" = 1'-0" 3" = 1'-0" SCALE As indicated
1
A-01-3
A-03-1

Rear1 FREE GREEN


73' - 7"
2' - 3" 19' - 6" 12' - 11" 33' - 11" 5' - 0"

www.FreeGreen.com
348 MEDFORD ST. SUITE 1
WALL LEGEND CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
POURED CONCRETE
FOUNDATION WALL
NOTES:

NOTE: BASEMENTS / CRAWL SPACES / SLABS:


THE BUILDER ASSUMES ALL RESPONSIBILITIES FOR PROVIDING
DIMENSIONS ON THIS PAGE ACCESS FOR DUCT AND PLUMBING CHASES BELOW CONCRETE
REFERENCE OUTSIDE FACES OF SLABS AND THROUGH FOUNDATION WALLS AS REQUIRED. IT IS
CONCRETE FOUNDATION WALLS ALSO THE RESPONSIBILITY OF THE BUILDER TO PROVIDE
PROPOSED LOCATION OF AND PT SILL PLATES ABOVE WHERE ADEQUATE LIGHT AND VENTILATION FOR BASEMENTS AND OR
PRE-FAB CONC BULKHEAD 3' - 9 1/4" THEY OCCUR BASED ON ENTRY CRAWL SPACES AS REQUIRED BY LOCAL CODES.
V.I.F. ALL DIMENSIONS & R.O. LEVEL FLOOR FRAMING PLAN.
4' - 9 1/4" D = COMBINATION SMOKE & CARBON MONOXIDE DETECTORS:
PROPOSED LOCATION DETECTORS SHALL BE INSTALLED OUTSIDE EACH
12" DIA CONC SUPPORT
FOR BASEMENT WINDOW SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF
W/ FOOTING BELOW
V.I.F. ALL DIMENSIONS & R.O. BEDROOMS AND ON EACH STORY OF THE DWELLING
FROST DEPTH TYP (OR AS REQ)
INCLUDING BASEMENTS. ALL DETECTORS SHALL BE
CONNECTED TO A SOUNDING DEVICE OR OTHER
DETECTORS TO PROVIDE AN ALARM AUDIBLE IN ALL
SLEEPING AREAS. ALL DETECTORS SHALL BE APPROVED

2 3/4"
FOOTING AS REQ BELOW FROST DEPTH 12" DIA CONC SUPPORT AND LISTED AND SHALL BE INSTALLED IN ACCORDANCE

3' - 9 1/4"
4' - 0"

4' - 0"
CONC FOUNDATION WALL AS REQ W/ FOOTING BELOW WITH MANUFACTURER'S INSTRUCTIONS.
FROST DEPTH TYP (OR AS REQ)
1 FLOOR TO FLOOR HEIGHTS WILL VARY BASED ON DEPTH OF
FLOOR FRAMING AS DETERMINED BY STRUCTURAL
ENGINEER. STAIR RISERS MUST NOT EXCEED 7 3/4", STAIR
TREADS MUST NOT BE LESS THAN 10" AS PER IRC 2006.
BEAM AS REQ 2 WALL MOUNT STAIR RAIL. MAX PROJECTION MUST NOT
5' - 0"

(ABOVE) PROPOSED LOCATION EXCEED 4 1/2" FROM FACE OF FINISH WALL AS PER IRC 2006.
TOP OF FND WALL FOR BASEMENT WINDOW
EL = (-) 1'-3" TYP V.I.F. ALL DIMENSIONS & R.O.

8' - 0"
BASEMENT SLAB ON GRADE
- 4" CONC SLAB ON GRADE W/ REINFORCING AS REQ PROPOSED LOCATION
- POLYETHYLENE VAPOR BARRIER OR FOR BASEMENT WINDOW
- 2" XPS RIGID INSULATION UNDER ENTIRE SLAB V.I.F. ALL DIMENSIONS & R.O.
15' - 9 1/4"

15' - 2"
- GRANULAR CAPILLARY BREAK AND DRAINAGE PAD (NO FINES)
6' - 0"

D - UNDISTURBED COMPACTED SOIL D


CL
12' - 8 3/4" 2' - 1 1/2" 12' - 5 1/2" 2' - 1 1/2" 13' - 8 3/4" TOP OF FND WALL

6' - 11 1/4"
EL = (-) 1'-3" TYP

FRAME WALL FLUSH TO UNDERSIDE


OF BEAM (THIS WALL ONLY)
5' - 0"

6"x10 1/2" BEAM POCKET BEAM AS REQ 6"x10 1/2" BEAM POCKET
5 1/2" LALLY (ABOVE) 5 1/2" LALLY
COLUMN TYP COLUMN TYP

Right
BEAM AS REQ
CL CL CL
44' - 0"

44' - 0"
1 (ABOVE)
FOOTING AS REQ BELOW FROST DEPTH

A-01-4 FOOTING BELOW SLAB FOOTING BELOW SLAB 1


A-01-2
Left

AS REQ TYP AS REQ TYP


GARAGE SLAB ON GRADE
CONC FOUNDATION WALL AS REQ

CONC STEP FOOTING BELOW


- 4" CONC SLAB ON GRADE W/ REINFORCING AS REQ FROST DEPTH
- POLYETHYLENE VAPOR BARRIER

12' - 0"
- GRANULAR CAPILLARY BREAK AND DRAINAGE PAD (NO FINES)
FRAME THESE WALLS FLUSH TO - UNDISTURBED COMPACTED SOIL
UNDERSIDE OF FLOOR SHEATHING ABOVE
16' - 2 3/4"

REVISION SCHEDULE:
16' - 0"

11' - 2" 12' - 0"


No. Description Date
WALL MOUNTED
HAND RAIL
2 3 1/2" LALLY
PROPOSED LOCATION
COLUMN TYP
FOR BASEMENT WINDOW
D

24' - 10"
V.I.F. ALL DIMENSIONS & R.O. 14 UP
1
14' - 9 1/4" 3' - 11 3/4" 3' - 4" 21' - 1" CL
FOOTING BELOW
V.I.F. V.I.F. V.I.F. V.I.F. GARAGE SLAB AS REQ
FOOTING AS REQ BELOW
FROST DEPTH

CONC FOUNDATION

12' - 10"
BEAM AS REQ WALL AS REQ
(ABOVE)
5' - 9 1/4"
6' - 0"

12" DIA CONC SUPPORT


CL CL CL W/ FOOTING BELOW PROPOSED MECHANICAL ZONE
FROST DEPTH TYP (OR AS REQ) TOP OF FND WALL
2 3/4"

TOP OF FND WALL EL = (-) 1'-10"

CL EL = (-) 1'-3" TYP


2' - 0"

CONC STEP FOOTING BELOW


7' - 3 3/8" 7' - 3 3/8" 12' - 2 1/2" FROST DEPTH

2 3/4"
PROJECT NAME:

NE COLONIAL

FOUNDATION PLAN
2' - 7 1/2" 8' - 4 1/2" 2' - 0" 8' - 4 1/2" 2' - 7 1/2"
PROJECT NUMBER: 10-002
2' - 3" 5' - 0" 27' - 0" 2' - 0" 11' - 4" 2' - 0" 24' - 0"
DATE: Issue Date
73' - 7" DRAWN BY: MY

9/24/2009 10:33:38 AM
CHECKED BY: BU, SH
1Front

A-01-1 A-05-1
FOUNDATION PLAN SCALE 1/4" = 1'-0"
1
1/4" = 1'-0"
1 A-01-3
A-03-1

Rear1

73' - 7"
FREE GREEN
2' - 3" 19' - 6" 12' - 11" 33' - 11" 5' - 0"
FRAMING PAGE LEGEND

COLUMN SUPPORT BELOW


www.FreeGreen.com
348 MEDFORD ST. SUITE 1
POINT LOAD FROM ABOVE CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
PLUMBING DROP

OPEN WEB FLOOR TRUSS GENERAL:

WOOD BEAM THE FRAMING LAYOUT ON THIS PAGE IS INTENDED TO BE A


SUGGESTED LAYOUT ONLY. DESIGN LOADS & WEATHER
STEEL BEAM CONDITIONS VARY BY REGION. AS A RESULT THE SIZE, SPACING &
LAYOUT OF ALL STRUCTURAL ELEMENTS IN THIS HOME DESIGN
STRUCTURAL FRAMING MUST BE APPROVED BY A STRUCTURAL ENGINEER AND CODE
PROPOSED LOCATION OF MEMBER AS NOTED OFFICIAL BASED ON YOUR SPECIFIC SITE LOCATION PRIOR TO
PRE-FAB CONC BULKHEAD CONSTRUCTION.
V.I.F. ALL DIMENSIONS & R.O. 2x_ SOLID BRIDGING

LOAD BEARING PARTITION MATERIAL SPECIFICATIONS: (VERIFY W/ LOCAL CODE)


6x6 PT POST FASTEN TO CONC SUPPORT
W/ GALV STEEL POST ANCHOR TYP JOIST OR BEAM HANGER FLOOR SHEATHING:
DBL 2x12 RIM JOIST 3/4" APA-RATED EXPOSURE 1, T&G,
48/24 SPAN RATING, EXPOSURE 1
10d COMMON NAILS @ 6" O/C B.N. & E.N.,
10d COMMON NAILS @ 10" O/C INT. FRAMING
4' - 0"

4' - 0"
6x6 PT POST FASTEN TO CONC SUPPORT ROOF SHEATHING:
BEAM AS REQ 3 W/ GALV STEEL POST ANCHOR TYP 5/8" APA-RATED EXPOSURE 1,
2x12 RIM JOIST 2x12 RIM JOIST 24" MINIMUM SPAN RATING,
8d COMMON NAILS @ 6" O/C B.N. & E.N.,
8d COMMON NAILS @ 10" O/C INT. FRAMING

SAWN STRUCTURAL FRAMING MEMBERS:


MEMBERS GRADE
5' - 0"

2x_ WALL STUDS D.F. #2


2x_ FLOOR JOISTS & ROOF RAFTERS D.F. #2

DBL 2x12 RIM JOIST


11 1/4" OPEN WEB TRUSSES @ 16" O/C

OR AS REQ BY STRUCTURAL ENGINEER


BEAMS & HEADERS D.F. #1
OR AS REQ BY STRUCTURAL ENGINEER
POSTS (4x,6x,8x) D.F. #1

PT 2x8 DECK JOISTS @ 16" O/C


BEAM BELOW AS REQ
WOOD BEAM MINIMUM ALLOWABLE BENDING STRESS:

20' - 0"
2x8 PT HEADER MEMBERS Fb (PSI)
1 1 1 GLUED LAMINATED TIMBERS 2400

15' - 2"
2x8 PT LEDGER OVER SHEATHING LAMINATED VENEER LUMBER 2700
6' - 0"

INTERIOR HEADERS:
INTERIOR NON-BEARING SPANS USE:
2x4 FLAT FOR SPANS UP TO 3'-0"
4x4 D.F. #2 FOR SPANS UP TO 5'-0"
4x6 D.F. #2 FOR SPANS UP TO 8'-0"

NOTES:
DBL 2x12 RIM JOIST
5' - 0"

1 PROVIDE 2x6 SOLID BRIDGING TO ATTACHE SECURELY TO


BEAM BELOW AS REQ
2 2 2 EACH TRUSS AND AT END WALLS.
2 PROVIDE 2x12 BLOCKING BETWEEN EACH TRUSS.
3 PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS FROM
ABOVE.

Right
3' - 11 3/4"
44' - 0"

44' - 0"
1 3 15' - 0" 6' - 10 3/16" 2x12 HEADER 20' - 11 5/16" 2x12 RIM JOIST A-01-2
A-01-4 1
Left

2x12 LEDGER
EXTRA TRUSS
SISTER 2x12 TO FACE OF TRUSS

FRAME THESE WALLS FLUSH TO


6' - 4 3/4"

1 UNDERSIDE OF FLOOR SHEATHING ABOVE 1

REVISION SCHEDULE:
16' - 0"

2x12 LEDGER
DBL 2x12 RIM JOIST
DBL 2x12 RIM JOIST No. Description Date

3
DBL 1 3/4"x11 1/4" LVL OR AS REQ

24' - 10"
14 UP
DBL 2x12 HEADER
5' - 7 1/2"

11 1/4" OPEN WEB TRUSSES @ 16" O/C 11 1/4" OPEN WEB TRUSSES @ 16" O/C
OR AS REQ BY STRUCTURAL ENGINEER OR AS REQ BY STRUCTURAL ENGINEER

3 BEAM AS REQ
6' - 0"

PT 2x8 DECK JOISTS @ 16" O/C


OR AS REQ BY STRUCTURAL ENGINEER

1
2' - 0"

6x6 PT POST FASTEN TO CONC SUPPORT


W/ GALV STEEL POST ANCHOR TYP
2x8 PT HEADER DBL 2x12 RIM JOIST

2x8 PT LEDGER OVER SHEATHING

PROJECT NAME:

NE COLONIAL

ENTRY LEVEL FLOOR


24' - 0" FRAMING PLAN
PROJECT NUMBER: 10-002
2' - 3" 5' - 0" 27' - 0" 2' - 0" 11' - 4" 2' - 0" 24' - 0"
DATE: Issue Date
73' - 7" DRAWN BY: MY

9/24/2009 10:33:39 AM
CHECKED BY: BU, SH
1Front

A-01-1 A-05-2
ENTRY LEVEL FLOOR FRAMING PLAN SCALE 1/4" = 1'-0"
1
1/4" = 1'-0"
1 A-01-3
A-03-1

Rear1 FREE GREEN


73' - 7"

2' - 3" 19' - 6" 12' - 11" 33' - 11" 5' - 0" FRAMING PAGE LEGEND

COLUMN SUPPORT BELOW


www.FreeGreen.com
348 MEDFORD ST. SUITE 1
POINT LOAD FROM ABOVE CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
PLUMBING DROP

OPEN WEB FLOOR TRUSS GENERAL:

WOOD BEAM THE FRAMING LAYOUT ON THIS PAGE IS INTENDED TO BE A


SUGGESTED LAYOUT ONLY. DESIGN LOADS & WEATHER
STEEL BEAM CONDITIONS VARY BY REGION. AS A RESULT THE SIZE, SPACING &
LAYOUT OF ALL STRUCTURAL ELEMENTS IN THIS HOME DESIGN
STRUCTURAL FRAMING MUST BE APPROVED BY A STRUCTURAL ENGINEER AND CODE
MEMBER AS NOTED OFFICIAL BASED ON YOUR SPECIFIC SITE LOCATION PRIOR TO
CONSTRUCTION.
2x_ SOLID BRIDGING

LOAD BEARING PARTITION MATERIAL SPECIFICATIONS: (VERIFY W/ LOCAL CODE)

JOIST OR BEAM HANGER FLOOR SHEATHING:


3/4" APA-RATED EXPOSURE 1, T&G,
48/24 SPAN RATING, EXPOSURE 1
10d COMMON NAILS @ 6" O/C B.N. & E.N.,
10d COMMON NAILS @ 10" O/C INT. FRAMING
4' - 0"

4' - 0"
ROOF SHEATHING:
5/8" APA-RATED EXPOSURE 1,
2x12 RIM JOIST 2x12 RIM JOIST 2x12 RIM JOIST
24" MINIMUM SPAN RATING,
8d COMMON NAILS @ 6" O/C B.N. & E.N.,
8d COMMON NAILS @ 10" O/C INT. FRAMING

SAWN STRUCTURAL FRAMING MEMBERS:


BEAM AS REQ MEMBERS GRADE
2x_ WALL STUDS D.F. #2
BEAM AS REQ BELOW 2x_ FLOOR JOISTS & ROOF RAFTERS D.F. #2
11 1/4" OPEN WEB TRUSSES @ 16" O/C
BEAMS & HEADERS D.F. #1
OR AS REQ BY STRUCTURAL ENGINEER
POSTS (4x,6x,8x) D.F. #1

2x12 CANTILEVERED JOISTS


WOOD BEAM MINIMUM ALLOWABLE BENDING STRESS:
MEMBERS Fb (PSI)

BEAM AS REQ BELOW


1 1 1 GLUED LAMINATED TIMBERS 2400

15' - 2"
LAMINATED VENEER LUMBER 2700
16' - 0"

16' - 0"
INTERIOR HEADERS:
INTERIOR NON-BEARING SPANS USE:
2x4 FLAT FOR SPANS UP TO 3'-0"
DBL 2x12 RIM JOIST 4x4 D.F. #2 FOR SPANS UP TO 5'-0"
4x6 D.F. #2 FOR SPANS UP TO 8'-0"

NOTES:
DBL 2x12 RIM JOIST
1 PROVIDE 2x6 SOLID BRIDGING TO ATTACHE SECURELY TO
2 HEADER BEAM AS REQ BELOW 2 2 EACH TRUSS AND AT END WALLS.
2 PROVIDE 2x12 BLOCKING BETWEEN EACH TRUSS.
3 IN THIS LOCATION ONLY FUR OUT ROUGH FACE OF OVERHANG
BY 2" (V.I..F.) TO BE FLUSH WITH OUTSIDE FACE OF EXT STUD

Right
WALL ABOVE.
44' - 0"

44' - 0"
1 A-01-2
A-01-4 14 DN 1
Left

11 1/4" OPEN WEB TRUSSES @ 16" O/C


OR AS REQ BY STRUCTURAL ENGINEER

15' - 0" 11' - 1" 8' - 6 3/16" 19' - 3 5/16"

1
1 1 DBL 2x12 RIM JOIST
16' - 0"

REVISION SCHEDULE:
DBL 2x12 RIM JOIST No. Description Date

DBL 1 3/4"x11 1/4 LVL OR AS REQ DBL 1 3/4"x_ LVL AS REQ BELOW

24' - 10"
11 1/4" OPEN WEB TRUSSES @ 16" O/C 11 1/4" OPEN WEB TRUSSES @ 16" O/C DBL 2x12 RIM JOIST
6' - 11"

OR AS REQ BY STRUCTURAL ENGINEER OR AS REQ BY STRUCTURAL ENGINEER

3
2x12 CANTILEVERED JOISTS
BEAM AS REQ
6' - 0"

DBL 2x12

BEAM AS REQ 1 11 1/4" OPEN WEB TRUSSES @ 16" O/C


OR AS REQ BY STRUCTURAL ENGINEER
2' - 0"

2' - 0"
BEAM AS REQ

DBL 2x12 RIM JOIST


PROJECT NAME:

NE COLONIAL

UPPER LEVEL FLR


FRAMING PLAN
PROJECT NUMBER: 10-002
2' - 3" 5' - 0" 27' - 0" 2' - 0" 11' - 4" 2' - 0" 24' - 0"
DATE: Issue Date
73' - 7" DRAWN BY: MY

9/24/2009 10:33:40 AM
CHECKED BY: BU, SH
1Front

A-01-1 A-05-3
UPPER LEVEL FLOOR FRAMING PLAN SCALE
1 1/4" = 1'-0"
1/4" = 1'-0"
1 A-01-3
A-03-1

47' - 9 1/2"
Rear1
FREE GREEN
FRAMING PAGE LEGEND

COLUMN SUPPORT BELOW www.FreeGreen.com


348 MEDFORD ST. SUITE 1
POINT LOAD FROM ABOVE CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
PLUMBING DROP

OPEN WEB FLOOR TRUSS GENERAL:

WOOD BEAM THE FRAMING LAYOUT ON THIS PAGE IS INTENDED TO BE A


SUGGESTED LAYOUT ONLY. DESIGN LOADS & WEATHER
STEEL BEAM CONDITIONS VARY BY REGION. AS A RESULT THE SIZE, SPACING &
LAYOUT OF ALL STRUCTURAL ELEMENTS IN THIS HOME DESIGN
STRUCTURAL FRAMING MUST BE APPROVED BY A STRUCTURAL ENGINEER AND CODE
MEMBER AS NOTED OFFICIAL BASED ON YOUR SPECIFIC SITE LOCATION PRIOR TO
CONSTRUCTION.
2x_ SOLID BRIDGING

LOAD BEARING PARTITION MATERIAL SPECIFICATIONS: (VERIFY W/ LOCAL CODE)


2x10 RAFTERS @ 24" O/C
OR AS REQ PER STRUCTURAL ENGINEER JOIST OR BEAM HANGER FLOOR SHEATHING:
3/4" APA-RATED EXPOSURE 1, T&G,
48/24 SPAN RATING, EXPOSURE 1
2x10 RAFTERS @ 24" O/C 10d COMMON NAILS @ 6" O/C B.N. & E.N.,
OR AS REQ PER STRUCTURAL ENGINEER 10d COMMON NAILS @ 10" O/C INT. FRAMING
RIDGE RIDGE 2x_ BLOCKING BETWEEN RAFTERS
2x_ HEADER ROOF SHEATHING:
2x12 RIM JOIST 2x12 RIM JOIST 5/8" APA-RATED EXPOSURE 1,
24" MINIMUM SPAN RATING,
8d COMMON NAILS @ 6" O/C B.N. & E.N.,
8d COMMON NAILS @ 10" O/C INT. FRAMING

240
SAWN STRUCTURAL FRAMING MEMBERS:
MEMBERS GRADE
2x_ WALL STUDS D.F. #2

SLOPE
11 1/4" OPEN WEB TRUSSES @ 16" O/C 2x_ FLOOR JOISTS & ROOF RAFTERS D.F. #2
OR AS REQ BY STRUCTURAL ENGINEER BEAMS & HEADERS D.F. #1
RIDGE POSTS (4x,6x,8x) D.F. #1

GFI
WOOD BEAM MINIMUM ALLOWABLE BENDING STRESS:
MEMBERS Fb (PSI)

GFI
GFI
1 1 GLUED LAMINATED TIMBERS 2400
LAMINATED VENEER LUMBER 2700
16' - 0"

INTERIOR HEADERS:
INTERIOR NON-BEARING SPANS USE:
2x4 FLAT FOR SPANS UP TO 3'-0"
4x4 D.F. #2 FOR SPANS UP TO 5'-0"

GFI
SLOPE 2x_ BLOCKING BETWEEN RAFTERS

GFI

D
4x6 D.F. #2 FOR SPANS UP TO 8'-0"

GFI

3
3
2x_ HEADER NOTES:
DBL 2x12 RIM JOIST
1 PROVIDE 2x6 SOLID BRIDGING TO ATTACHE SECURELY TO
2 2 EACH TRUSS AND AT END WALLS.
HEADER BEAM AS REQ BELOW
3 2 PROVIDE 2x12 BLOCKING BETWEEN EACH TRUSS.

3
3
3

Right
16 R DN
1 A-01-2
A-01-4 1
Left

38' - 0"

38' - 0"
VALLEY

1 1
2x8 LADDER FRAMED RAKE OVERHANG
16' - 0"

REVISION SCHEDULE:

SLOPE

SLOPE
DBL 2x12 RIM JOIST No. Description Date

RIDGE
2x8 LADDER FRAMED RAKE OVERHANG

11 1/4" OPEN WEB TRUSSES @ 16" O/C


OR AS REQ BY STRUCTURAL ENGINEER

SLOPE

SLOPE
BEAM AS REQ
(BELOW) 2x8 LADDER FRAMED RAKE OVERHANG
2' - 0"

SLOPE
4' - 0"

1
2x10 RAFTERS @ 24" O/C 2x10 RAFTERS @ 24" O/C
OR AS REQ PER STRUCTURAL ENGINEER OR AS REQ PER STRUCTURAL ENGINEER

2x_ HEADER
2x_ BLOCKING BETWEEN RAFTERS
RIDGE 2x10 RAFTERS @ 24" O/C RIDGE 2x_ HEADER
OR AS REQ PER STRUCTURAL ENGINEER 2x_ BLOCKING BETWEEN RAFTERS

PROJECT NAME:

NE COLONIAL

ATTIC FLOOR
FRAMING PLAN
PROJECT NUMBER: 10-002
5' - 0" 14' - 6 1/2" 12' - 5 1/2" 15' - 9 1/2"
DATE: Issue Date
47' - 9 1/2" DRAWN BY: Author

9/24/2009 10:33:41 AM
CHECKED BY: Checker
1Front

A-01-1 A-05-4
ATTIC FLOOR FRAMING PLAN SCALE 1/4" = 1'-0"
1
1/4" = 1'-0"
1 A-01-3
A-03-1

Rear1 FREE GREEN


47' - 9 1/2" 23' - 6 1/2"

FRAMING PAGE LEGEND


www.FreeGreen.com
COLUMN SUPPORT BELOW 348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
POINT LOAD FROM ABOVE
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
PLUMBING DROP
GENERAL:
OPEN WEB FLOOR TRUSS
THE FRAMING LAYOUT ON THIS PAGE IS INTENDED TO BE A
WOOD BEAM
SUGGESTED LAYOUT ONLY. DESIGN LOADS & WEATHER
CONDITIONS VARY BY REGION. AS A RESULT THE SIZE, SPACING &
STEEL BEAM
LAYOUT OF ALL STRUCTURAL ELEMENTS IN THIS HOME DESIGN
MUST BE APPROVED BY A STRUCTURAL ENGINEER AND CODE
STRUCTURAL FRAMING
OFFICIAL BASED ON YOUR SPECIFIC SITE LOCATION PRIOR TO
MEMBER AS NOTED
CONSTRUCTION.
2x_ SOLID BRIDGING
MATERIAL SPECIFICATIONS: (VERIFY W/ LOCAL CODE)
LOAD BEARING PARTITION

2x8 LADDER FRAMED RAKE OVERHANG


FLOOR SHEATHING:
JOIST OR BEAM HANGER 3/4" APA-RATED EXPOSURE 1, T&G,
48/24 SPAN RATING, EXPOSURE 1
10d COMMON NAILS @ 6" O/C B.N. & E.N.,
2x_ BLOCKING BETWEEN RAFTERS 2x_ BLOCKING BETWEEN RAFTERS 10d COMMON NAILS @ 10" O/C INT. FRAMING
2x_ HEADER 2x_ HEADER
ROOF SHEATHING:
5/8" APA-RATED EXPOSURE 1,
24" MINIMUM SPAN RATING,
8d COMMON NAILS @ 6" O/C B.N. & E.N.,
8d COMMON NAILS @ 10" O/C INT. FRAMING

SAWN STRUCTURAL FRAMING MEMBERS:


2x10 ROOF RAFTERS @ 24" O/C MEMBERS GRADE
OR AS REQ BY STRUCTURAL ENGINEER 2x_ WALL STUDS D.F. #2
SLOPE (TYPICAL TO ALL ROOF RAFTERS) 2x_ FLOOR JOISTS & ROOF RAFTERS D.F. #2
BEAMS & HEADERS D.F. #1
POSTS (4x,6x,8x) D.F. #1

2x8 LADDER FRAMED RAKE OVERHANG WOOD BEAM MINIMUM ALLOWABLE BENDING STRESS:
2x8 LADDER FRAMED RAKE OVERHANG MEMBERS Fb (PSI)
GLUED LAMINATED TIMBERS 2400
LAMINATED VENEER LUMBER 2700
16' - 0"

INTERIOR HEADERS:
INTERIOR NON-BEARING SPANS USE:

SLOPE

SLOPE
2x4 FLAT FOR SPANS UP TO 3'-0"
4x4 D.F. #2 FOR SPANS UP TO 5'-0"
RIDGE RAFTER
4x6 D.F. #2 FOR SPANS UP TO 8'-0"

SLOPE

SLOPE

SLOPE
SLOPE

NOTES:

2x6 COLLAR TIES (TYPICAL)


RIDGE RAFTER

2x6 COLLAR TIES (TYPICAL)


RIDGE RAFTER

Right
16 R DN
1 A-01-2
A-01-4 1
Left

38' - 0"

2x_ BLOCKING BETWEEN RAFTERS

40' - 0"
SLOPE

SLOPE
2x6 COLLAR TIES (TYPICAL)
REVISION SCHEDULE:
16' - 0"

No. Description Date

RIDGE RAFTER

SLOPE

SLOPE
DBL 2x_ VALLEY RAFTER DBL 2x_ VALLEY RAFTER

DBL 2x_ VALLEY RAFTER

2x6 COLLAR TIES (TYPICAL)


2x8 LADDER FRAMED RAKE OVERHANG

SLOPE SLOPE

RIDGE RAFTER
2' - 0"

2x_ HEADER 2x_ HEADER DBL 2x_ VALLEY RAFTER


2x_ BLOCKING BETWEEN RAFTERS
4' - 0"

SLOPE SLOPE
SLOPE SLOPE

2x8 LADDER FRAMED RAKE OVERHANG 2x8 LADDER FRAMED RAKE OVERHANG
RIDGE RAFTER RIDGE RAFTER

PROJECT NAME:

NE COLONIAL

ROOF FRAMING
PLAN
PROJECT NUMBER: 10-002
5' - 0" 14' - 6 1/2" 12' - 5 1/2" 15' - 9 1/2" 23' - 6 1/2"
DATE: Issue Date
71' - 4" DRAWN BY: MY

9/24/2009 10:33:41 AM
CHECKED BY: BU, SH
1Front

A-01-1
A-05-5
ATTIC FLOOR FRAMING PLAN SCALE 1/4" = 1'-0"
1
1/4" = 1'-0"
STEP 1: FIND YOUR ZONE 90 D
STEP 2: FROM THE TABLE, DETERMINE OVERHANG DEPTH FOR YOUR WINDOWS 84
STEP 3: CHOOSE YOUR WINDOW SUN SHADING DEVICE FREE GREEN
STEP 4: CHOOSE YOUR MATERIALS 78
16% OF
WINDOW
72 HEIGHT
www.FreeGreen.com

OVERHANG DEPTH (ZONE 1)


348 MEDFORD ST. SUITE 1
66 CHARLESTOWN, MA 02129
© COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
60
ABOUT THIS PAGE:
54

WINDOW HEIGHT (INCHED), H


EXTERNAL WINDOW SHADING DEVICES ARE AN EFFECTIVE METHOD
48 FOR REDUCING HEAT GAINS THROUGH WINDOWS DURING SUMMER.
IN FACT, EXTERNAL SHADING DEVICES CAN REDUCE HEAT GAINS BY
UP TO 80% IF SIZED AND BUILT PROPERLY. WITH THIS IN MIND,
42
H FREEGREEN HAS CREATED THIS PAGE TO ASSIST HOME BUILDERS IN
CONSTRUCTING EFFECTIVE WINDOW SHADING DEVICES. THE
INFORMATION WE PROVIDE INCLUDES A ZONING MAP OF THE UNITED
36 STATES, ZONING CHARTS FOR PROPER SIZING OF SHADING DEVICES
AND A VARIETY OF SHADING DEVICE STYLES AND MATERIALS TO
SUITE DIFFERENT TASTES AND DIFFERENT HOME DESIGNS.
30

24 MATERIAL SPECIFICATION:

WOOD TYPES:
18
· PRESSURE TREATED
· WESTERN RED CEDAR
12 · TROPICAL HARDWOOD (FSC CERTIFIED REQUIRED)
···· MAHOGANY
6 ···· MASSARANDUBA

HARDWARE:
0 6 12 18 24 30 36 42 48 54 60 66 72 78 ALL HARDWARE MUST BE EITHER HOT DIPPED GALVANIZED
BENCH WINDOW SHADING DEVICE STEEL OR STAINLESS STEEL. FREEGREEN RECOMMENDS
1 ONLY STAINLESS STEEL FOR HOUSE LOCATIONS IN CLOSE
OVERHANG DEPTH (INCHED), D 1" = 1'-0"
PROXIMITY TO THE OCEAN.

90 90 D FINISHES:

IF USING PRESSURE TREATED WOOD SEAL & FINISH TO MATCH


84 84 EXTERIOR WINDOW TRIM.

IF USING WESTERN RED CEDAR SEAL & FINISH TO MATCH


78 78 EXTERIOR WINDOW TRIM

IF USING TROPICAL HARDWOOD FINISH MAY NOT BE REQUIRED.


72 72 SEALING AND FINISHING OF TROPICAL HARDWOODS WILL
OVERHANG DEPTH (ZONE 2)

OVERHANG DEPTH (ZONE 3)


VARY BY SPECIES. CONSULT WITH YOUR PROVIDER FOR
RECOMMENDED FINISHES FOR ALL TROPICAL HARDWOOD
66 66 PRODUCTS.

60 60 16% OF
WINDOW
HEIGHT
54 54
WINDOW HEIGHT (INCHED), H

WINDOW HEIGHT (INCHED), H


48 48

42 42

36 36

30 30 H
24 24
REVISION SCHEDULE:
No. Description Date
18 18

12 12

6 6

0 6 12 18 24 30 36 42 48 54 60 66 72 78 0 6 12 18 24 30 36 42 48 54 60 66 72 78
BENCH WINDOW SHADING DEVICE
2
OVERHANG DEPTH (INCHED), D OVERHANG DEPTH (INCHED), D 1" = 1'-0"

90 90

84 84

78 78

72 72
OVERHANG DEPTH (ZONE 4)

OVERHANG DEPTH (ZONE 5)

66 66
D
60 60

54 54
WINDOW HEIGHT (INCHED), H

WINDOW HEIGHT (INCHED), H

48 48 H PROJECT NAME:

42 42
NE COLONIAL
36 36

30 30
WINDOW SHADING
24 24
DETAILS
18 18 PROJECT NUMBER: 10-002
DATE: Issue Date
12 12
DRAWN BY: Author

9/24/2009 10:33:42 AM
6 6 CHECKED BY: Checker

0 6 12 18 24 30 36 42 48 54 60 66 72 78 0 6 12 18 24 30 36 42 48 54 60 66 72 78
3
BENCH WINDOW SHADING DEVICE
A-06-1
OVERHANG DEPTH (INCHED), D OVERHANG DEPTH (INCHED), D 1" = 1'-0" SCALE 1" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
ELECTRICAL OUTLET LEGEND © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
110V
1.
RECEPTICAL NOTES:
S SWITCH
2.
RECEPTICAL
GFI GROUND FAULT CURRENT
3.
INTERRUPTER RECEPTACLE
GFI-WP GFI AND WATER PROOF
4.
RECEPTACLE
M MICROWAVE OVEN
5.
RECEPTICAL
R RANGE
6.
RECEPTICAL
UC UNDER COUNTER
7.
RECEPTICAL
GFI
240 240V
8.
RECEPTICAL
110V FLOOR
9.
RECEPTICAL

GFI GFI GFI


ELECTRICAL SWITCH LEGEND

10. LIGHT SWITCH

GFI
2
11. DOUBLE LIGHT SWITCH

3
12. 3-WAY LIGHT SWITCH

D
13. DIMMER LIGHT SWITCH
GFI

F OCCUPANCY SENSOR
14.
FAN SWITCH
KEY ROOM
15. KR
MASTER CONTROL
KEY SCENE
16. KS
MASTER CONTROL

17. G GRAPHIC EYE


GFI

MICELANEOUS ELECTRICAL SYMBOL LEGEND

18. T THERMOSTAT

SMOKE & CARBON


19. D
MONOXIDE DETECTOR
NATURAL GAS/PROPANE
20.

GFI
HOOKUP
GFI

#C MULTIMEDIA JACK
21. #P (NETWORK/TV)

22. TEL TELEPHONE JACK REVISION SCHEDULE:

GFI
No. Description Date
23. DOOR BELL
DRBL
3

24. CHIME DOOR BELL CHIME


14 UP

25. H20 ICE MAKER

26. CEILING FAN


GFI

LIGHTING LEGEND

27. RD RECESSED DOWN LIGHT

RECESSED DOWN LIGHT PROPOSED MECHANICAL ZONE


28. RD-ES
ENERGY STAR RATED

29. RW RECESSED WALL WASHER

RECESSED ACCENT
30. RA
DIRECTIONAL S S 240

31. RG RECESSED GLASS

32. CEILING BOX SUB LEVEL ELECTRICAL PLAN


1
1/4" = 1'-0"
33. F BATHROOM EXHAUST FAN

34. WALL MOUNTED FIXTURE


PROJECT NAME:

35. LED LINEAR

IN-WALL LED STEP LIGHT


NE COLONIAL
36.
W/ REMOTE TIMER CONTROL

37. FLUORESCENT STRIP

240V OR GAS TANKLESS HOT


SUB LEVEL
38. WH
WATER HEATER ELECTRICAL PLAN
PROJECT NUMBER: 10-002
ELECTRICAL SYMBOL LEGEND
1/4" = 1'-0" DATE: Issue Date
DRAWN BY: MY

9/24/2009 10:33:43 AM
CHECKED BY: BU, SH

E-01-1
SCALE 1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
ELECTRICAL OUTLET LEGEND © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.
110V
1. NOTES:
RECEPTICAL
S SWITCH
2.
RECEPTICAL
GFI GROUND FAULT CURRENT
3.
INTERRUPTER RECEPTACLE
GFI-WP GFI AND WATER PROOF
4.
RECEPTACLE
M MICROWAVE OVEN
5.
RECEPTICAL
R RANGE
6.
RECEPTICAL
UC UNDER COUNTER
7.
RECEPTICAL

8.
240 240V DINING NOOK
RECEPTICAL

4' - 3"
INSTALL IN BASEMENT
110V FLOOR
9. GFI-WP
RECEPTICAL

D
#C
#P
GFI
WH
GFI GFI
BATH 1
D #C

2' - 6"
ELECTRICAL SWITCH LEGEND

3' - 0"
3' - 10" 12' - 0" #P
F

GFI-WP
10. LIGHT SWITCH RD RD RD

GFI
RD RD RD
5' - 11 1/2" 5' - 11 1/2" 1' - 6" 6' - 0" 6' - 0"
1' - 6"
2
11. DOUBLE LIGHT SWITCH

R
KITCHEN GFI 2

1' - 9"

UC
3
12. 3-WAY LIGHT SWITCH

2
RA
FAMILY ROOM

LOCKER
D RD
13. DIMMER LIGHT SWITCH
2' - 6"

3
F OCCUPANCY SENSOR
14. RA

3
FAN SWITCH

3
1' - 9"

MUD ROOM
KEY ROOM
15. KR

3
MASTER CONTROL 1' - 9 1/2" 4' - 0" 8' - 9 1/4" 8' - 6" 4' - 0"

D
KEY SCENE
16.

D
KS RD RD RD RD RD RD RD RD RD RD RD
MASTER CONTROL
3' - 10" 6' - 0" 6' - 0"

3' - 0"
17. G GRAPHIC EYE

3' - 0"
48" REF
#C
3 3 3 GFI R M UC 3
#P
GFI
MICELANEOUS ELECTRICAL SYMBOL LEGEND 3 2

2' - 10"
3 R UP

3' - 5"
18. T THERMOSTAT
3' - 9"

RD
2' - 0" 14 DN
SMOKE & CARBON
19. D
RD
MONOXIDE DETECTOR 2' - 2"

UC
RW
NATURAL GAS/PROPANE

3' - 1"
2' - 0"

20.
HOOKUP WET BAR PANTRY
GARAGE
5' - 0"

RW
#C MULTIMEDIA JACK

GFI
21. #P (NETWORK/TV)

CHIME
D
LIVING ROOM OPEN TO
4' - 0"

22. TEL TELEPHONE JACK ABOVE REVISION SCHEDULE:


RD
No. Description Date
23. DOOR BELL RW
DRBL
D
2' - 0"

GFI
24. CHIME DOOR BELL CHIME
D

16 R UP
RW
ENTRY FOYER D
3

25. H20 ICE MAKER


3' - 8 1/2"

26. CEILING FAN CEILING OUTLETS FOR GARAGE


DOOR OPENER

LIGHTING LEGEND GFI-WP

DRBL
2' - 10"

27. RD RECESSED DOWN LIGHT

GFI
RD RD
RECESSED DOWN LIGHT
28. RD-ES
ENERGY STAR RATED 4' - 1 1/8" 7' - 0 1/8" FRONT PORCH

29. RW RECESSED WALL WASHER


DINING ROOM
RECESSED ACCENT
30. RA
DIRECTIONAL GFI

31. RG RECESSED GLASS

32. CEILING BOX

33. F BATHROOM EXHAUST FAN

ENTRY LEVEL ELECTRICAL PLAN


34. WALL MOUNTED FIXTURE 1
1/4" = 1'-0" PROJECT NAME:

35. LED LINEAR

IN-WALL LED STEP LIGHT


NE COLONIAL
36.
W/ REMOTE TIMER CONTROL

FLUORESCENT STRIP
37.
ENTRY LEVEL
240V OR GAS TANKLESS HOT
38. WH
WATER HEATER ELECTRICAL PLAN
PROJECT NUMBER: 10-002
ELECTRICAL SYMBOL LEGEND
1/4" = 1'-0" DATE: Issue Date
DRAWN BY: MY

9/24/2009 10:33:44 AM
CHECKED BY: BU, SH

E-01-2
SCALE 1/4" = 1'-0"
FREE GREEN
www.FreeGreen.com
348 MEDFORD ST. SUITE 1
CHARLESTOWN, MA 02129
ELECTRICAL OUTLET LEGEND © COPYRIGHT BY FREEGREEN INC. ALL RIGHTS RESERVED.

110V
1. NOTES:
RECEPTICAL
S SWITCH
2.
RECEPTICAL
GFI GROUND FAULT CURRENT
3.
INTERRUPTER RECEPTACLE
GFI-WP GFI AND WATER PROOF
4.
RECEPTACLE
M MICROWAVE OVEN
5.
RECEPTICAL
R RANGE
6.
RECEPTICAL
UC UNDER COUNTER
7.
RECEPTICAL
240 240V
8.
RECEPTICAL
110V FLOOR
9.
RECEPTICAL

240
ELECTRICAL SWITCH LEGEND RD-ES RD-ES

10. LIGHT SWITCH


F
RD-ES
11.
2
DOUBLE LIGHT SWITCH LAUNDRY
KING BED

GFI
3
12. 3-WAY LIGHT SWITCH

GFI
BATH 2 MASTER

GFI
WALK IN
13. D
DIMMER LIGHT SWITCH BED 2 BATH CLOSET
RD-ES
WH
F
OCCUPANCY SENSOR
14. F
FAN SWITCH D

GFI

GFI
KEY ROOM

D
15. KR

GFI
MASTER CONTROL

3
KEY SCENE 3
16. KS RD-ES
MASTER CONTROL RD-ES

GRAPHIC EYE
RD-ES RD-ES RD-ES RD-ES D RD-ES RD-ES
17. G

3
3
MICELANEOUS ELECTRICAL SYMBOL LEGEND

3
16 R DN RD-ES
18. T THERMOSTAT

SMOKE & CARBON


19. D
MONOXIDE DETECTOR RD-ES
WALK IN
20.
NATURAL GAS/PROPANE CLOSET
HOOKUP
KING BED
OPEN TO RD-ES MASTER SUITE RD-ES
#C MULTIMEDIA JACK BELOW
21. #P (NETWORK/TV) D
22. TEL TELEPHONE JACK REVISION SCHEDULE:
BED 1 No. Description Date
23. DOOR BELL RD-ES BED 3
DRBL

24. CHIME DOOR BELL CHIME


3

25. H20 ICE MAKER


RD-ES

26. CEILING FAN D


KING BED

LIGHTING LEGEND SITTING RM

27. RD RECESSED DOWN LIGHT

RECESSED DOWN LIGHT


28. RD-ES
ENERGY STAR RATED
RD-ES

29. RW RECESSED WALL WASHER

RECESSED ACCENT
30. RA
DIRECTIONAL

31. RG RECESSED GLASS

32. CEILING BOX


UPPER LEVEL ELECTRICAL PLAN
1
33. F BATHROOM EXHAUST FAN 1/4" = 1'-0"

34. WALL MOUNTED FIXTURE


PROJECT NAME:

35. LED LINEAR

IN-WALL LED STEP LIGHT


NE COLONIAL
36.
W/ REMOTE TIMER CONTROL

37. FLUORESCENT STRIP


UPPER LEVEL
240V OR GAS TANKLESS HOT
38. WH
WATER HEATER ELECTRICAL PLAN
PROJECT NUMBER: 10-002
ELECTRICAL SYMBOL LEGEND
DATE: Issue Date
1/4" = 1'-0"
DRAWN BY: MY

9/24/2009 10:33:45 AM
CHECKED BY: BU, SH

E-01-3
SCALE 1/4" = 1'-0"