298 777 171 (11:59):

Hi..
157 680 834 (12:00):
hello
298 777 171 (12:00):
Can I help you??
I mean, Should I do anything from my end??
157 680 834 (12:01):
We want to start a test. We want to start the system and check if the fans are
running or not.
298 777 171 (12:01):
Ok..
Should I load the fuel cell??
157 680 834 (12:02):
what do you mean with loading the fuel cell?
298 777 171 (12:03):
I mean, should I apply load at the battery terminals so that after some time the
fuell cell cell will switch ON once it reaches 49V
157 680 834 (12:03):
yes, that is what we want to do. And then please check wenn the fuel cell system
starts if the fans in the fuel cell modules are running. You will hear it
298 777 171 (12:04):
Ok..
Let me do it..
Please monitor the fuel cell status in the webinterface and the energy manager..
157 680 834 (12:05):
ok, I will do that
298 777 171 (12:08):
Now i have given a load of 2500W
The H2 valve opened
157 680 834 (12:09):
and do you hear the fans?
298 777 171 (12:10):
I am not sure..
bcoz i am not hearing any fan sound from that..
Now i will increase the load to 3000W, please observe the status of the stack..
should I??
157 680 834 (12:11):
ok, do that
298 777 171 (12:12):
Did you observe that??
The fan of each stack is getting ON and OFF immediately
Thats what I observed..
298 777 171 (12:16):
Now if we reset this list, the status of teh stacks are turning green but the
stacks are getting ON when load is applied..
Sorry, the Stacks are not Getting ON when load is applied
157 680 834 (12:18):
yes, you can reset the alarms, but at the next start of the system the alarms will
appear again
298 777 171 (12:18):
yes exactly..that is what is happening..
I hope the problem is clear now..
to you..
157 680 834 (12:19):
and you say you really can hear the fan going On and Off? I mean the fans are not
so fast in startup and shutdown
298 777 171 (12:20):
Yes..Can I talk to you over the microphone?? In teamviewer so that I can better
explain the problem..
157 680 834 (12:21):
the only problem is that my microphone is not working. And my headset is in the
company
298 777 171 (12:21):
Oh..so can You hear me atleast??
157 680 834 (12:21):
that should work
I can hear you
yes
Ok, it's clear
but I have to think about the situation
298 777 171 (12:23):
Ok please think..
157 680 834 (12:44):
during our test i saw that the DC voltage was dropping down. the voltage was most
of the time at 49.1V but somtimes for a short time at around 47.1V. Maybe that can
cause the problem
298 777 171 (12:44):
Oh..
So what should we do??
157 680 834 (12:44):
I changed the thresholds for the startup voltage. can we try another start of the
system?
298 777 171 (12:45):
For sure..let me load the system..
Well..Let us do one thing..
Please listen to the system performance..I will connect the microphone..
157 680 834 (12:45):
ok, good idea
yes
157 680 834 (12:48):
i can hear the valve
ok, I could not hear the fan
ok
yes, that would be good
157 680 834 (12:52):
the load is still the same
yes, please increase the load
157 680 834 (12:57):
I just resettet the fuel cells after going into alarm, but now the voltage is
increasing
298 777 171 (12:58):
ya..I switched off the load..
157 680 834 (12:58):
ok
I think the problem is the jumping voltage measurment during startup