Академический Документы
Профессиональный Документы
Культура Документы
Manufacturer:
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Table of contents
Table of contents
Section 1 Introduction.....................................................................21
Introduction to the technical reference manual.................................21
About the complete set of manuals for an IED............................21
About the technical reference manual.........................................22
Design of the Technical reference manual (TRM).......................23
Introduction.............................................................................23
Principle of operation..............................................................23
Input and output signals.........................................................26
Function block........................................................................26
Setting parameters.................................................................26
Technical data........................................................................26
Intended audience.......................................................................27
Related documents......................................................................27
Revision notes.............................................................................28
Introduction..................................................................................77
Principle of operation...................................................................77
Function block.............................................................................77
Input and output signals..............................................................77
Signal matrix for binary outputs (SMBO)..........................................78
Introduction..................................................................................78
Principle of operation...................................................................78
Function block.............................................................................79
Input and output signals..............................................................79
Signal matrix for mA inputs (SMMI)..................................................80
Introduction..................................................................................80
Principle of operation...................................................................80
Function block.............................................................................80
Input and output signals..............................................................80
Signal matrix for analog inputs (SMAI).............................................81
Introduction..................................................................................81
Principle of operation...................................................................81
Function block.............................................................................81
Input and output signals..............................................................82
Setting parameters......................................................................83
Summation block 3 phase (SUM3Ph)..............................................85
Introduction..................................................................................85
Principle of operation...................................................................85
Function block.............................................................................86
Input and output signals..............................................................86
Setting parameters......................................................................86
Technical data...........................................................................124
High impedance differential protection (PDIF, 87)..........................125
Introduction................................................................................125
Principle of operation.................................................................125
Logic diagram.......................................................................125
Function block...........................................................................126
Input and output signals............................................................126
Setting parameters....................................................................127
Technical data...........................................................................127
Introduction................................................................................207
Principle of operation.................................................................207
Function block...........................................................................210
Input and output signals............................................................210
Setting parameters....................................................................210
Technical data...........................................................................211
Breaker failure protection (RBRF, 50BF)........................................211
Introduction................................................................................212
Principle of operation.................................................................212
Function block...........................................................................215
Input and output signals............................................................215
Setting parameters....................................................................216
Technical data...........................................................................217
Stub protection (PTOC, 50STB).....................................................217
Introduction................................................................................218
Principle of operation.................................................................218
Function block...........................................................................219
Input and output signals............................................................219
Setting parameters....................................................................219
Technical data...........................................................................219
Pole discordance protection (RPLD, 52PD)...................................220
Introduction................................................................................220
Principle of operation.................................................................220
Pole discordance signalling from circuit breaker..................223
Unsymmetrical current detection..........................................223
Function block...........................................................................224
Input and output signals............................................................224
Setting parameters....................................................................224
Technical data...........................................................................225
Principle of operation.................................................................238
Measurement principle.........................................................239
Time delay............................................................................239
Blocking................................................................................243
Design..................................................................................244
Function block...........................................................................246
Input and output signals............................................................246
Setting parameters....................................................................247
Technical data...........................................................................249
Two step residual overvoltage protection (POVM, 59N)................250
Introduction................................................................................250
Principle of operation.................................................................250
Measurement principle.........................................................250
Time delay............................................................................251
Blocking................................................................................253
Design..................................................................................254
Function block...........................................................................255
Input and output signals............................................................255
Setting parameters....................................................................255
Technical data...........................................................................257
Overexcitation protection (PVPH, 24).............................................258
Introduction................................................................................258
Principle of operation.................................................................258
Measured voltage.................................................................261
Operate time of the overexcitation protection.......................262
Cooling.................................................................................265
OEX protection function measurands...................................265
Overexcitation alarm............................................................266
Logic diagram.......................................................................266
Function block...........................................................................267
Input and output signals............................................................267
Setting parameters....................................................................267
Technical data...........................................................................268
Function block...........................................................................323
Input and output signals............................................................323
Setting parameters....................................................................323
Technical data...........................................................................324
Fuse failure supervision (RFUF).....................................................324
Introduction................................................................................324
Principle of operation.................................................................325
Zero sequence ....................................................................325
Negative sequence...............................................................328
du/dt and di/dt.......................................................................328
Operation modes..................................................................329
Dead line detection...............................................................330
Function block...........................................................................330
Input and output signals............................................................330
Setting parameters....................................................................331
Technical data...........................................................................332
Section 11 Control..........................................................................333
Synchrocheck and energizing check (RSYN, 25)...........................333
Introduction................................................................................333
Principle of operation.................................................................333
Basic functionality.................................................................333
Logic diagrams.....................................................................334
Function block...........................................................................340
Input and output signals............................................................341
Setting parameters....................................................................342
Technical data...........................................................................344
Autorecloser (RREC, 79)................................................................345
Introduction................................................................................345
Principle of operation.................................................................346
Logic Diagrams....................................................................346
Auto-reclosing operation Off and On....................................346
Start auto-reclosing and conditions for start of a reclosing
cycle ....................................................................................346
Control of the auto-reclosing open time for shot 1...............347
Long trip signal.....................................................................348
Time sequence diagrams.....................................................353
Function block...........................................................................356
Input and output signals............................................................356
Setting parameters....................................................................357
Technical data...........................................................................359
Apparatus control (APC).................................................................360
Introduction................................................................................360
Principle of operation.................................................................360
Introduction................................................................................393
Principle of operation.................................................................393
Logical node for interlocking (SCILO)........................................396
Introduction...........................................................................396
Principle of operation............................................................396
Function block......................................................................397
Input and output signals.......................................................397
Interlocking for line bay (ABC_LINE).........................................398
Introduction...........................................................................398
Function block......................................................................399
Logic diagram.......................................................................400
Input and output signals.......................................................405
Interlocking for bus-coupler bay (ABC_BC)...............................407
Introduction...........................................................................407
Function block......................................................................408
Logic diagram.......................................................................409
Input and output signals.......................................................413
Interlocking for transformer bay (AB_TRAFO)...........................416
Introduction...........................................................................416
Function block......................................................................417
Logic diagram.......................................................................418
Input and output signals.......................................................421
Interlocking for bus-section breaker (A1A2_BS)........................423
Introduction...........................................................................423
Function block......................................................................423
Logic diagram.......................................................................424
Input and output signals.......................................................425
Interlocking for bus-section disconnector (A1A2_DC)...............427
Introduction...........................................................................427
Function block......................................................................427
Logic diagram.......................................................................428
Input and output signals.......................................................429
Interlocking for busbar earthing switch (BB_ES).......................430
Introduction...........................................................................430
Function block......................................................................430
Logic diagram.......................................................................431
Input and output signals.......................................................431
Interlocking for double CB bay (DB)..........................................431
Introduction...........................................................................431
Function block......................................................................432
Logic diagrams.....................................................................433
Input and output signals ......................................................440
Interlocking for 1 1/2 CB diameter (BH).....................................443
Introduction...........................................................................443
Function blocks....................................................................444
Logic diagrams.....................................................................446
Input and output signals.......................................................453
Logic rotating switch for function selection and LHMI
presentation (GGIO).......................................................................458
Introduction................................................................................458
Principle of operation.................................................................458
Function block...........................................................................460
Input and output signals............................................................461
Setting parameters....................................................................462
Generic double point function block (DPGGIO)..............................463
Introduction................................................................................463
Principle of operation.................................................................463
Function block...........................................................................463
Input and output signals............................................................464
Setting parameters....................................................................464
Introduction................................................................................476
Principle of operation.................................................................476
Zone extension.....................................................................476
Loss-of-load acceleration.....................................................477
Function block...........................................................................478
Input and output signals............................................................478
Setting parameters....................................................................479
Scheme communication logic for residual overcurrent protection
(PSCH, 85).....................................................................................479
Introduction................................................................................480
Principle of operation.................................................................480
Blocking scheme..................................................................480
Permissive under/overreach scheme...................................481
Unblocking scheme..............................................................482
Function block...........................................................................483
Input and output signals............................................................484
Setting parameters....................................................................484
Technical data...........................................................................485
Current reversal and weak-end infeed logic for residual
overcurrent protection (PSCH, 85).................................................485
Introduction................................................................................485
Principle of operation.................................................................486
Directional comparison logic function...................................486
Fault current reversal logic...................................................486
Weak and infeed logic..........................................................486
Function block...........................................................................488
Input and output signals............................................................488
Setting parameters....................................................................488
Technical data...........................................................................489
Section 13 Logic.............................................................................491
Tripping logic (PTRC, 94)...............................................................491
Introduction................................................................................491
Principle of operation.................................................................491
Logic diagram.......................................................................493
Function block...........................................................................496
Input and output signals............................................................496
Setting parameters....................................................................497
Technical data...........................................................................497
Trip matrix logic (GGIO, 94X).........................................................497
Introduction................................................................................497
Principle of operation.................................................................498
Function block...........................................................................500
Input and output signals............................................................500
Setting parameters....................................................................501
Configurable logic blocks (LLD)......................................................502
Introduction................................................................................502
Inverter function block (INV)......................................................502
OR function block (OR).............................................................502
AND function block (AND).........................................................503
Timer function block (Timer)......................................................504
Pulse timer function block (PULSE)..........................................505
Exclusive OR function block (XOR)...........................................505
Set-reset with memory function block (SRM)............................506
Controllable gate function block (GT)........................................506
Settable timer function block (TS).............................................507
Technical data...........................................................................508
Fixed signal function block (FIXD)..................................................508
Introduction................................................................................508
Principle of operation.................................................................508
Function block...........................................................................509
Input and output signals............................................................509
Setting parameters....................................................................509
Section 14 Monitoring.....................................................................511
Measurements (MMXU).................................................................511
Introduction................................................................................512
Principle of operation.................................................................513
Measurement supervision....................................................513
Service values (MMXU, SVR)..............................................517
Current Phasors (MMXU, CP)..............................................521
Voltage phasors (MMXU, VP)..............................................522
Sequence quantities (MSQI, CSQ and VSQ).......................522
Function block...........................................................................522
Input and output signals............................................................523
Setting parameters....................................................................526
Technical data...........................................................................540
Event counter (GGIO).....................................................................540
Introduction................................................................................541
Principle of operation.................................................................541
Reporting..............................................................................541
Design..................................................................................541
Function block...........................................................................542
Input signals..............................................................................542
Setting parameters....................................................................542
Technical data...........................................................................542
Event function (EV).........................................................................543
Introduction................................................................................543
Principle of operation.................................................................543
Function block...........................................................................545
Input and output signals............................................................545
Setting parameters....................................................................546
Fault locator (RFLO).......................................................................548
Introduction................................................................................549
Principle of operation.................................................................549
Measuring Principle..............................................................550
Accurate algorithm for measurement of distance to fault.....551
The non-compensated impedance model............................554
IEC 60870-5-103..................................................................554
Function block...........................................................................555
Input and output signals............................................................555
Setting parameters....................................................................555
Technical data...........................................................................556
Measured value expander block.....................................................557
Introduction................................................................................557
Principle of operation.................................................................557
Function block...........................................................................558
Input and output signals............................................................558
Disturbance report (RDRE)............................................................558
Introduction................................................................................559
Principle of operation.................................................................559
Function block...........................................................................566
Input and output signals............................................................568
Setting parameters....................................................................570
Technical data...........................................................................585
Event list (RDRE)...........................................................................586
Introduction................................................................................586
Principle of operation.................................................................586
Function block...........................................................................587
Input signals..............................................................................587
Technical data...........................................................................587
Indications (RDRE).........................................................................587
Introduction................................................................................587
Principle of operation.................................................................588
Function block...........................................................................589
Input signals..............................................................................589
Technical data...........................................................................589
Event recorder (RDRE)..................................................................589
Introduction................................................................................589
Principle of operation.................................................................590
Function block...........................................................................590
Input signals..............................................................................590
Technical data...........................................................................590
Trip value recorder (RDRE)............................................................591
Introduction................................................................................591
Principle of operation.................................................................591
Function block...........................................................................592
Input signals..............................................................................592
Technical data...........................................................................592
Disturbance recorder (RDRE)........................................................592
Introduction................................................................................592
Principle of operation.................................................................593
Memory and storage............................................................593
IEC 60870-5-103..................................................................594
Function block...........................................................................595
Input and output signals............................................................595
Setting parameters....................................................................595
Technical data...........................................................................595
Section 15 Metering.......................................................................597
Pulse counter logic (GGIO)............................................................597
Introduction................................................................................597
Principle of operation.................................................................597
Function block...........................................................................599
Input and output signals............................................................599
Setting parameters....................................................................600
Technical data...........................................................................601
Section 18 Hardware......................................................................675
Overview.........................................................................................675
Variants of case- and HMI display size.....................................675
Case from the rear side.............................................................677
Hardware modules.........................................................................680
Overview....................................................................................680
Combined backplane module (CBM).........................................681
Introduction...........................................................................681
Functionality.........................................................................681
Design..................................................................................681
Universal backplane module (UBM)..........................................683
Introduction...........................................................................683
Functionality.........................................................................683
Design..................................................................................683
Power supply module (PSM).....................................................685
Introduction...........................................................................685
Design..................................................................................686
Technical data......................................................................686
Numeric processing module (NUM)..........................................686
Introduction...........................................................................686
Functionality.........................................................................687
Block diagram.......................................................................688
Local human-machine interface (LHMI)....................................688
Transformer input module (TRM)..............................................688
Introduction...........................................................................688
Design..................................................................................689
Technical data......................................................................689
Analog digital conversion module, with time synchronization
(ADM) .......................................................................................689
Introduction...........................................................................689
Design..................................................................................690
Binary input module (BIM).........................................................692
Introduction...........................................................................692
Design..................................................................................692
Technical data......................................................................695
Binary output modules (BOM)...................................................696
Introduction...........................................................................696
Design..................................................................................696
Technical data......................................................................698
Binary input/output module (IOM)..............................................699
Introduction...........................................................................699
Design..................................................................................699
Technical data......................................................................700
Section 19 Labels...........................................................................731
Different labels................................................................................731
Section 22 Glossary.......................................................................771
Glossary.........................................................................................771
Section 1 Introduction
en06000097.vsd
The Operator’s Manual (OM) contains instructions on how to operate the protection
IED during normal service once it has been commissioned. The operator’s manual
can be used to find out how to handle disturbances or how to view calculated and
measured network data in order to determine the cause of a fault.
The IED 670 engineering guide (EG) contains instructions on how to engineer the
IED 670 products. The manual guides to use the different tool components for IED
670 engineering. It also guides how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. The third
part is an introduction about the diagnostic tool components available for IED 670
products and the PCM 600 tool.
1.1.3.1 Introduction
Describes how the function works, presents a general background to algorithms and
measurement techniques. Logic diagrams are used to illustrate functionality.
Logic diagrams
Logic diagrams describe the signal logic inside the function block and are bordered
by dashed lines.
Signal names
Input and output logic signals consist of two groups of letters separated by two dashes.
The first group consists of up to four letters and presents the abbreviated name for
the corresponding function. The second group presents the functionality of the
particular signal. According to this explanation, the meaning of the signal BLKTR in
figure 4 is as follows:
• BLKTR informs the user that the signal will BLOCK the TRIP command from
the under-voltage function, when its value is a logical one (1).
Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed.
Input and output signals can be configured using the CAP531 tool. They can be
connected to the inputs and outputs of other functions and to binary inputs and outputs.
Examples of input signals are BLKTR, BLOCK and VTSU. Examples output signals
are TRIP, START, STL1, STL2, STL3.
Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their
values are high (1) only when the corresponding setting parameter is set to the
symbolic value specified within the frame. Example is the signal Block TUV=Yes.
Their logical values correspond automatically to the selected setting value.
Internal signals
Internal signals are illustrated graphically and end approximately. 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
suffix -int is added to the signal name to indicate where the signal starts and continues,
see figure 3.
BLKTR
TEST
TEST
&
Block TUV=Yes BLOCK-int.
>1
BLOCK
VTSU
BLOCK-int.
&
STUL1N
BLOCK-int.
& >1 & TRIP
t
STUL2N
BLOCK-int.
START
&
STUL3N
STL1
STL2
STL3
xx04000375.vsd
External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix “-cont.”, see figure 2 and figure 3.
STZMPP-cont.
>1
STCND
& STNDL1L2-cont.
1L1L2
STNDL2L3-cont.
&
1L2L3
& STNDL3L1-cont.
1L3L1
& STNDL1N-cont.
1L1N
& STNDL2N-cont.
1L2N
STNDL3N-cont.
&
1L3N
>1 STNDPE-cont.
>1
1--VTSZ 1--STND
>1 &
1--BLOCK
BLK-cont.
xx04000376.vsd
STNDL1N-cont.
>1
STNDL2N-cont. 15 ms
& t STL1
STNDL3N-cont.
STNDL1L2-cont. >1 15 ms
& t STL2
STNDL2L3-cont.
15 ms
STNDL3L1-cont. & t STL3
>1
15 ms
& t START
>1
BLK-cont.
xx04000377.vsd
Input and output signals are presented in two separate tables. Each table consists of
two columns. The first column contains the name of the signal and the second column
contains the description of the signal.
Input signals are always on the left hand side, and output signals on the right hand
side. Settings are not displayed. Special kinds of settings are sometimes available.
These are supposed to be connected to constants in the configuration scheme, and are
therefore depicted as inputs. Such signals will be found in the signal list but described
in the settings table.
IEC 61850 - 8 -1
CAP531 Name Logical Node
Inputs TUV1-
PH2PUVM
U3P TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
Outputs
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2 Diagram
ST2L1 Number
ST2L2
ST2L3
en05000330.vsd
These are presented in tables and include all parameters associated with the function
in question.
The technical data section provides specific technical information about the function
or hardware described.
Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in
the protective devices. The installation and commissioning personnel must have a
basic knowledge in the handling electronic equipment.
The local human machine interface is available in a small, and a medium sized model.
The principle difference between the two is the size of the LCD. The small size LCD
has a four lines and the medium size LCD can display the single line diagram with
up to 15 objects.
The local human machine interface is equipped with an LCD that can display the
single line diagram with up to 15 objects.
The local human-machine interface is simple and easy to understand – the whole front
plate is divided into zones, each of them with a well-defined functionality:
2.2.1 Introduction
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and time.
The remaining 5 lines are dynamic. This LCD has no graphic display potential.
2.2.2 Design
The LHMI is identical for both the 1/2, 3/4 and 1/1 cases. The different parts of the
small LHMI is shown in figure 7
1 2 3
en05000055.eps
8 7
3 Indication LEDs
4 Label
5 Local/Remote LEDs
6 RJ 45 port
7 Communication indication LED
8 Keypad
2.3.1 Introduction
The 1/2, 3/4 and 1/1 x 19” cases can be equipped with the medium size LCD. This is
a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28 lines
with up to 40 characters per line. To display the single line diagram, this LCD is
required.
2.3.2 Design
The different parts of the medium size LHMI is shown in figure 8
1 2 3
en05000056.eps
8 7
2.4 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs in the IED 670 series. LCD screens and other details may differ
but the way the keys function is identical. The keypad is illustrated in figure 9.
The keys used to operate the IED are described below in table 1.
The help key brings up two submenus. Key operation and IED information.
Opens the main menu, and used to move to the default screen.
The Local/Remote key is used to set the IED in local or remote control mode.
The E key starts editing mode and confirms setting changes when in editing mode.
The right arrow key navigates forward between screens and moves right in editing mode.
Key Function
The left arrow key navigates backwards between screens and moves left in editing mode.
The up arrow key is used to move up in the single line diagram and in menu tree.
The down arrow key is used to move down in the single line diagram and in menu tree.
2.5 LED
2.5.1 Introduction
The LED module is a unidirectional means of communicating. This means that events
may occur that activate a LED in order to draw the operators attention to something
that has occurred and needs some sort of action.
There are alarm indication LEDs and hardware associated LEDs on the right hand
side of the front panel. The alarm LEDs are found to the right of the LCD screen.
They can show steady or flashing light. Flashing would normally indicate an alarm.
The alarm LEDs are configurable using the PCM 600 tool. This is because they are
dependent on the binary input logic and can therefore not be configured locally on
the HMI. Some typical alarm examples follow:
The RJ45 port has a yellow LED indicating that communication has been established
between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
2.6.1 Introduction
The adaptation of the LHMI to the application and user preferences is made with:
2.6.3.1 Design
The function block LHMI (LocalHMISign) controls and supplies information about
the status of the status indication LEDs. The input and output signals of LHMI are
configured with the PCM 600 tool.
See section "Status indication LEDs" for information about the LEDs.
en05000773.vsd
2.6.4.1 Introduction
The function block HLED (LEDMonitor) controls and supplies information about
the status of the indication LEDs. The input and output signals of HLED are
configured with the PCM 600 tool. The input signal for each LED is selected
individually with the PCM 600 Signal Matrix Tool (SMT). LEDs (number 1–6) for
trip indications are red and LEDs (number 7–15) for start indications are yellow.
Each indication LED on the LHMI can be set individually to operate in six different
sequences; two as follow type and four as latch type. Two of the latching types are
intended to be used as a protection indication system, either in collecting or restarting
mode, with reset functionality. The other two are intended to be used as signalling
system in collecting (coll) mode with an acknowledgment functionality. The light
from the LEDs can be steady (-S) or flickering (-F).
2.6.4.2 Design
The information on the LEDs is stored at loss of the auxiliary power to the IED. The
latest LED picture appears immediately after the IED is successfully restarted.
Operating modes
• Collecting mode
• LEDs which are used in collecting mode of operation are accumulated
continuously until the unit is acknowledged manually. This mode is
suitable when the LEDs are used as a simplified alarm system.
• Re-starting mode
• In the re-starting mode of operation each new start resets all previous active
LEDs and activates only those which appear during one disturbance. Only
LEDs defined for re-starting mode with the latched sequence type 6
(LatchedReset-S) will initiate a reset and a restart at a new disturbance. A
disturbance is defined to end a settable time after the reset of the activated
input signals or when the maximum time limit has been elapsed.
Acknowledgment/reset
• From local HMI
• The active indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function is
positive edge triggered, not level triggered. The acknowledgment/reset is
performed via the Reset-button and menus on the LHMI. For details, refer
to the “Operators manual”.
• Automatic reset
• The automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When
the automatic reset of the LEDs has been performed, still persisting
indications will be indicated with a steady light.
Operating sequences
The sequences can be of type Follow or Latched. For the Follow type the LED follow
the input signal completely. For the Latched type each LED latches to the
corresponding input signal until it is reset.
The figures below show the function of available sequences selectable for each LED
separately. For sequence 1 and 2 (Follow type), the acknowledgment/reset function
is not applicable. Sequence 3 and 4 (Latched type with acknowledgement) are only
working in collecting mode. Sequence 5 is working according to Latched type and
collecting mode while sequence 6 is working according to Latched type and re-
starting mode. The letters S and F in the sequence names have the meaning S = Steady
and F = Flash.
At the activation of the input signal, the indication operates according to the selected
sequence diagrams below.
In the sequence diagrams the LEDs have the characteristics shown in figure 11.
en05000506.vsd
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Activating
signal
LED
en01000228.vsd
Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing instead
of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if the
signal is not present any more. If the signal is still present after acknowledgment it
gets a steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing light
have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the activation
of the input signal, the indication will light up with a steady light. The difference to
sequence 3 and 4 is that indications that are still activated will not be affected by the
reset i.e. immediately after the positive edge of the reset has been executed a new
reading and storing of active signals is performed. Every LED is independent of the
other LEDs in its operation.
Activating
signal
LED
Reset
en01000235.vsd
Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, i.e. immediately after the positive edge
of that the manual reset has been executed a new reading and storing of active signals
is performed. LEDs set for sequence 6 are completely independent in its operation of
LEDs set for other sequences.
Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is activated
until a settable time, tRestart, has elapsed after that all activating signals for the LEDs
set as LatchedReset-S have reset. However if all activating signals have reset and
some signal again becomes active before tRestart has elapsed, the tRestart timer does
not restart the timing sequence. A new disturbance start will be issued first when all
signals have reset after tRestart has elapsed. A diagram of this functionality is shown
in figure 15.
From
disturbance
length control ³1 New
per LED ³1 disturbance
set to
sequence 6
tRestart
& t
&
³1
³1
&
en01000237.vsd
In order not to have a lock-up of the indications in the case of a persisting signal each
LED is provided with a timer, tMax, after which time the influence on the definition
of a disturbance of that specific LED is inhibited. This functionality is shown i
diagram in figure 16.
Activating signal
To LED
To disturbance
AND
tMax length control
t
en05000507.vsd
Disturbance
t Restart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
en01000239.vsd
Figure 18 shows the timing diagram for a new indication after tRestart time has
elapsed.
Disturbance Disturbance
t Restart t Restart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
en01000240.vsd
Figure 19 shows the timing diagram when a new indication appears after the first one
has reset but before tRestart has elapsed.
Disturbance
t Restart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
en01000241.vsd
Disturbance
t Restart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
en01000242.vsd
en05000508.vsd
3.1.1 Introduction
In order to get correct measurement results as well as correct protection operations
the analog input channels must be configured and properly set. It is necessary to define
a reference PhaseAngleRef for correct calculation of phase angles. For power
measuring and all directional and differential functions the directions of the input
currents must be properly defined. The measuring and protection algorithms in IED
670 are using primary system quantities and the set values are done in primary
quantities as well. Therefore it is extremely important to properly set the data about
the connected current and voltage transformers.
en05000456.vsd
The function blocks are not represented in the configuration tool. The
signals appear only in the SMT tool when a TRM is included in the
configuration with the function selector tool. In the SMT tool they can
be mapped to the desired virtual input (SMAI) of the IED670 and used
internally in the configuration.
3.2.1 Introduction
The self-supervision function listens and reacts to internal system events, generated
by the different built-in self-supervision elements. The internal events are saved in
an internal event list.
The self-supervision status can be monitored from the local HMI or a SMS/SCS
system.
Under the Diagnostics menu in the local HMI the present information from the self-
supervision function can be reviewed. The information can be found under
Diagnostics\Internal Events or Diagnostics\IED Status\General. Refer to the
“Installation and Commissioning manual” for a detailed list of supervision signals
that can be generated and displayed in the local HMI.
Some signals are available from the IES (IntErrorSign) function block. The signals
from this function block are sent as events to the station level of the control system.
The signals from the IES function block can also be connected to binary outputs for
signalization via output relays or they can be used as conditions for other functions
if required/desired.
Individual error signals from I/O modules can be obtained from respective module
in the Signal Matrix Tool. Error signals from time synchronization can be obtained
from the time synchronization block TIME.
Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal life of the IED, they are also
called internal signals. The internal signals can be divided into two groups. One group
handles signals that are always present in the IED; standard signals. Another group
handles signals that are collected depending on the hardware configuration. The
standard signals are listed in table 13. The hardware dependent internal signals are
listed in table 14. Explanations of internal signals are listed in table 15.
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see figure
25.
Figure 25: Simplified drawing of A/D converter for the 600 platform.
The technique to split the analogue input signal into two converters with different
amplification makes it possible to supervise the incoming signals under normal
conditions where the signals from the two converters should be identical. An alarm
is given if the signals are out of the boundaries. Another benefit is that it improves
the dynamic performance of the A/D conversion.
When the signal is within measurable limits on both channels, a direct comparison
of the two channels can be performed. If the validation fails, the CPU will be informed
and an alarm will be given.
en04000392.vsd
Table 16: Output signals for the InternalSignal (IS---) function block
Signal Description
FAIL Internal fail
WARNING Internal warning
CPUFAIL CPU fail
CPUWARN CPU warning
TSYNCERR Time synchronization status
RTCERR Real time clock status
3.3.1 Introduction
Use the time synchronization source selector to select a common source of absolute
time for the IED when it is a part of a protection system. This makes comparison of
events and disturbance data between all IEDs in a SA system possible.
Time definitions
The error of a clock is the difference between the actual time of the clock, and the
time the clock is intended to have. The rate accuracy of a clock is normally called the
clock accuracy and means how much the error increases, i.e. how much the clock
gains or loses time. A disciplined clock is a clock that “knows” its own faults and
tries to compensate for them, i.e. a trained clock.
Synchronization principle
From a general point of view synchronization can be seen as a hierarchical structure.
A module is synchronized from a higher level and provides synchronization to lower
levels.
Syncronization from
a higher level
Module
Optional syncronization of
modules at a lower level
en05000206.vsd
The IED has a built-in Real Time Clock (RTC) with a resolution of one nanosecond.
The clock has a built-in calendar that handles leap years through 2098.
RTC at startup
At IED startup, the internal time is free running. If the RTC is still alive since the last
up time, the time in the IED will be quite accurate (may drift 35 ppm), but if the RTC
power has been lost during power off (will happen after 5 days), the IED time will
start at 1970-01-01. For more information, please refer to section "Time
synchronization startup procedure" and section "Example, binary synchronization".
• If the synchronization message, that is similar to the other messages from its
origin has an offset compared to the internal time in the IED, the message is used
directly for synchronization, that is for adjusting the internal clock to obtain zero
offset at the next coming time message.
• If the synchronization message has an offset that is large compared to the other
messages, a “spike-filter” in the IED will remove this time-message.
• If the synchronization message has an offset that is large, and the following
message also has a large offset, the spike filter will not act and the offset in the
synchronization message will be compared to a threshold that defaults to 100
milliseconds. If the offset is more than the threshold, the IED is brought into a
safe state and the clock is thereafter set to the correct time. If the offset is lower
than the threshold, the clock will be adjusted with 1000 ppm until the offset is
removed. With an adjustment of 1000 ppm, it will take 100 seconds or 1.7
minutes to remove an offset of 100 milliseconds.
Synchronization messages configured as coarse will only be used for initial setting
of the time. After this has been done, the messages are checked against the internal
time and only an offset of more than 10 seconds will reset the time.
Rate accuracy
In the REx670 IED, the rate accuracy at cold start is about 100 ppm, but if the IED
is synchronized for a while, the rate accuracy will be approximately 1 ppm if the
surrounding temperature is constant. Normally it will take 20 minutes to reach full
accuracy.
Three main alternatives of external time synchronization are available. Either the
synchronization message is applied via any of the communication ports of the IED
as a telegram message including date and time or as a minute pulse, connected to a
binary input, or via GPS. The minute pulse is used to fine tune already existing time
in the IEDs.
• Coarse message is sent every minute and comprises complete date and time, i.e.
year, month, day, hours, minutes, seconds and milliseconds.
• Fine message is sent every second and comprises only seconds and milliseconds.
IEC60870-5-103 is not used to synchronize the relay, but instead the offset between
the local time in the relay and the time received from 103 is added to all times (in
events and so on) sent via 103. In this way the relay acts as it is synchronized from
various 103 sessions at the same time. Actually, there is a “local” time for each 103
session.
The minute pulse is connected to any channel on any Binary Input Module in the IED.
The electrical characteristic is thereby the same as for any other binary input.
The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute after
the last flank.
Pulse data:
en05000251.vsd
The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.
If contact bounces occurs, only the first pulse will be detected as a minute pulse. The
next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, e.g. it is exactly 60 seconds between the pulses,
contact bounces might occur 49 ms after the actual minute pulse without effecting
the system. If contact bounces occurs more than 50 ms, e.g. it is less than 59950 ms
between the two most adjacent positive (or negative) flanks, the minute pulse will
not be accepted.
en05000425.vsd
Table 18: Output signals for the TIME (TIME-) function block
Signal Description
TSYNCERR Time synchronization error
RTCERR Real time clock error
Table 19: Basic general settings for the TimeSynch (TSYN-) function
Parameter Range Step Default Unit Description
CoarseSyncSrc Off - Off - Coarse time
SPA synchronization
LON source
SNTP
FineSyncSource Off - Off - Fine time
SPA synchronization
LON source
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
SyncMaster Off - Off - Activate IEDas
SNTP-Server synchronization
master
TimeAdjustRate Slow - Fast - Adjust rate for time
Fast synchronization
Table 20: Basic general settings for the TimeSynch (TSYN-) function
Parameter Range Step Default Unit Description
CoarseSyncSrc Off - Off - Coarse time
SPA synchronization
LON source
SNTP
FineSyncSource Off - Off - Fine time
SPA synchronization
LON source
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
SyncMaster Off - Off - Activate IEDas
SNTP-Server synchronization
master
TimeAdjustRate Slow - Slow - Adjust rate for time
Fast synchronization
3.4.1 Introduction
Use the six sets of settings to optimize IED operation for different system conditions.
By creating and switching between fine tuned setting sets, either from the human-
machine interface or configurable binary inputs, results in a highly adaptable IED
that can cope with a variety of system scenarios.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ACGR function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this the PCM 600 configuration tool must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if for example both group four and group
two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal SETCHGD is sending a
pulse with the length according to parameter t, which is set from PCM 600 or in the
local HMI.
The parameter MAXSETGR defines the maximum number of setting groups in use to
switch between.
The above example also includes seven output signals, for confirmation of which
group that is active.
The SGC function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used will
be shown on the PST setting tool.
ACGR-
ActiveGroup
ACTGRP1 GRP1
ACTGRP2 GRP2
ACTGRP3 GRP3
ACTGRP4 GRP4
ACTGRP5 GRP5
ACTGRP6 GRP6
SETCHGD
en05000433.vsd
SGC--
NoOfSetGrp
MAXSETGR
en05000716.vsd
Table 27: Input signals for the ActiveGroup (ACGR-) function block
Signal Description
ACTGRP1 Selects setting group 1 as active
ACTGRP2 Selects setting group 2 as active
ACTGRP3 Selects setting group 3 as active
ACTGRP4 Selects setting group 4 as active
ACTGRP5 Selects setting group 5 as active
ACTGRP6 Selects setting group 6 as active
Table 28: Output signals for the ActiveGroup (ACGR-) function block
Signal Description
GRP1 Setting group 1 is active
GRP2 Setting group 2 is active
GRP3 Setting group 3 is active
GRP4 Setting group 4 is active
GRP5 Setting group 5 is active
GRP6 Setting group 6 is active
SETCHGD Pulse when setting changed
3.5.1 Introduction
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI or PST. To enable these blockings the IED must be set in test
mode. When leaving the test mode, i.e. entering normal mode, these blockings are
disabled and everything is set to normal operation. All testing will be done with
actually set and configured values within the IED. No settings will be changed, thus
mistakes are avoided.
While the IED is in test mode, the ACTIVE output of the function block TEST is
activated. The other two outputs of the function block TEST are showing which is
the generator of the “Test mode: On” state — input from configuration (OUTPUT
output activated) or setting from LHMI (SETTING output activated).
While the IED is in test mode, the yellow START LED will flash and all functions
are blocked. Any function can be de-blocked individually regarding functionality and
event signalling.
Most of the functions in the IED can individually be blocked by means of settings
from the local HMI. To enable these blockings the IED must be set in test mode (the
output ACTIVE in function block TEST is set to true), see example in figure 32.
When leaving the test mode, i.e. entering normal mode, these blockings are disabled
and everything is set to normal operation. All testing will be done with actually set
and configured values within the IED. No settings will be changed, thus no mistakes
are possible.
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so no
outputs will be activated.
The TEST function block might be used to automatically block functions when a test
handle is inserted in a test switch. A contact in the test switch (RTXP24 contact 29-30)
can supply a binary input which in turn is configured to the TEST function block.
Each of the protection functions includes the blocking from TEST function block. A
typical example from the undervoltage function is shown in figure 32.
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
en05000443.vsd
Table 31: Input signals for the Test (TEST-) function block
Signal Description
INPUT Sets terminal in test mode when active
Table 32: Output signals for the Test (TEST-) function block
Signal Description
ACTIVE Terminal in test mode when active
OUTPUT Test input is active
SETTING Test mode setting is (On) or not (Off)
3.6.1 Introduction
There are two functions that allow you to identify each IED individually:
ProductInformation function has only three pre-set, unchangeable but nevertheless
very important settings: SerialNo., Ordering No., and ProductDate, that you can see
on the local HMI, under Diagnostics/IED Status/Identifiers. They are very helpful in
case of support process (such as repair or maintenance).
Identifiers function is actually allowing you to identify the individual IED in your
system, not only in the substation, but in a whole region or a country.
3.7.1 Introduction
The SMBI function block is used within the CAP tool in direct relation with the Signal
Matrix Tool SMT (please see the overview of the engineering process in the
“Application manual”, chapter “Engineering of the IED”). It represents the way
binary inputs are brought in for one IED 670 configuration.
en05000434.vsd
Table 35: Input signals for the SMBI (SI01-) function block
Signal Description
INSTNAME Instance name in Signal Matrix Tool
BI1NAME Signal name for BI1 in Signal Matrix Tool
BI2NAME Signal name for BI2 in Signal Matrix Tool
BI3NAME Signal name for BI3 in Signal Matrix Tool
BI4NAME Signal name for BI4 in Signal Matrix Tool
BI5NAME Signal name for BI5 in Signal Matrix Tool
BI6NAME Signal name for BI6 in Signal Matrix Tool
BI7NAME Signal name for BI7 in Signal Matrix Tool
Table continued on next page
Signal Description
BI8NAME Signal name for BI8 in Signal Matrix Tool
BI9NAME Signal name for BI9 in Signal Matrix Tool
BI10NAME Signal name for BI10 in Signal Matrix Tool
Table 36: Output signals for the SMBI (SI01-) function block
Signal Description
BI1 Binary input 1
BI2 Binary input 2
BI3 Binary input 3
BI4 Binary input 4
BI5 Binary input 5
BI6 Binary input 6
BI7 Binary input 7
BI8 Binary input 8
BI9 Binary input 9
BI10 Binary input 10
3.8.1 Introduction
The SMBO function block is used within the CAP tool in direct relation with the
Signal Matrix Tool SMT (please see the overview of the engineering process in the
“Application manual”, chapter “Engineering of the IED”). It represents the way
binary outputs are sent from one IED 670 configuration.
en05000439.vsd
Table 37: Input signals for the SMBO (SO01-) function block
Signal Description
BO1 Signal name for BO1 in Single Matrix Tool
BO2 Signal name for BO2 in Single Matrix Tool
BO3 Signal name for BO3 in Single Matrix Tool
BO4 Signal name for BO4 in Single Matrix Tool
BO5 Signal name for BO5 in Single Matrix Tool
BO6 Signal name for BO6 in Single Matrix Tool
BO7 Signal name for BO7 in Single Matrix Tool
BO8 Signal name for BO8 in Single Matrix Tool
BO9 Signal name for BO9 in Single Matrix Tool
BO10 Signal name for BO10 in Single Matrix Tool
Table 38: Output signals for the SMBO (SO01-) function block
Signal Description
INSTNAME Instance name in Single Matrix Tool
BO1NAME Signal name for BO1 in Single Matrix Tool
BO2NAME Signal name for BO2 in Single Matrix Tool
BO3NAME Signal name for BO3 in Single Matrix Tool
BO4NAME Signal name for BO4 in Single Matrix Tool
BO5NAME Signal name for BO5 in Single Matrix Tool
BO6NAME Signal name for BO6 in Single Matrix Tool
BO7NAME Signal name for BO7 in Single Matrix Tool
Table continued on next page
Signal Description
BO8NAME Signal name for BO8 in Single Matrix Tool
BO9NAME Signal name for BO9 in Single Matrix Tool
BO10NAME Signal name for BO10 in Single Matrix Tool
3.9.1 Introduction
The SMMI function block is used within the CAP tool in direct relation with the
Signal Matrix Tool SMT (please see the overview of the engineering process in the
“Application manual”, chapter “Engineering of the IED”). It represents the way
milliamp (mA) inputs are brought in for one IED670 configuration.
The outputs on the SMMI are normally connected to the SPGGIO MVGGIO function
block for further use of the mA signals.
en05000440.vsd
Table 39: Input signals for the SMMI (SMI1-) function block
Signal Description
INSTNAME Instance name in Signal Matrix Tool
AI1NAME Signal name for AI1 in Signal Matrix Tool
AI2NAME Signal name for AI2 in Signal Matrix Tool
AI3NAME Signal name for AI3 in Signal Matrix Tool
AI4NAME Signal name for IN4 in Signal Matrix Tool
AI5NAME Signal name for AI5 in Signal Matrix Tool
AI6NAME Signal name for AI6 in Signal Matrix Tool
Table 40: Output signals for the SMMI (SMI1-) function block
Signal Description
AI1 Analog milliampere input 1
AI2 Analog milliampere input 2
AI3 Analog milliampere input 3
AI4 Analog milliampere input 4
AI5 Analog milliampere input 5
AI6 Analog milliampere input 6
3.10.1 Introduction
The SMAI function block (or the pre-processing function block, as it is also known)
is used within the PCM 600 in direct relation with the Signal Matrix Tool SMT (please
see the overview of the engineering process in the “Application manual”, chapter
“Engineering of the IED”). It represents the way analog inputs are brought in for one
IED 670 configuration.
PR01-
SMAI
BLOCK SYNCOUT
DFTSPFC SPFCOUT
GRPNAME AI3P
AI1NAME AI1
AI2NAME AI2
AI3NAME AI3
AI4NAME AI4
TYPE AIN
NOSMPLCY
en05000705.vsd
PR02-
SMAI
BLOCK AI3P
GRPNAME AI1
AI1NAME AI2
AI2NAME AI3
AI3NAME AI4
AI4NAME AIN
TYPE NOSMPLCY
en05000706.vsd
Table 41: Input signals for the SMAI (PR01-) function block
Signal Description
BLOCK Block group 1
DFTSYNC Synchronisation of DFT calculation
DFTSPFC Number of samples per fundamental cycle used for DFT
calculation
GRPNAME Group name for GRP1 in Signal Matrix Tool
AI1NAME Signal name for AI1 in Signal Matrix Tool
AI2NAME Signal name for AI2 in Signal Matrix Tool
AI3NAME Signal name for AI3 in Signal Matrix Tool
AI4NAME Signal name for AI4 in Signal Matrix Tool
Table 42: Output signals for the SMAI (PR01-) function block
Signal Description
SYNCOUT Synchronisation signal from internal DFT reference function
SPFCOUT Number of samples per fundamental cycle from internal DFT
reference function
AI3P Group 1 analog input 3-phase group
AI1 Group 1 analog input 1
Table continued on next page
Signal Description
AI2 Group 1 analog input 2
AI3 Group 1 analog input 3
AI4 Group 1 analog input 4
AIN Group 1 analog input residual for disturbance recorder
Table 43: Input signals for the SMAI (PR02-) function block
Signal Description
BLOCK Block group 2
GRPNAME Group name for GRP2 in Signal Matrix Tool
AI1NAME Signal name for AI1 in Signal Matrix Tool
AI2NAME Signal name for AI2 in Signal Matrix Tool
AI3NAME Signal name for AI3 in Signal Matrix Tool
AI4NAME Signal name for AI4 in Signal Matrix Tool
Table 44: Output signals for the SMAI (PR02-) function block
Signal Description
AI3P Group 2 analog input 3-phase group
AI1 Group 2 analog input 1
AI2 Group 2 analog input 2
AI3 Group 2 analog input 3
AI4 Group 2 analog input 4
AIN Group 2 analog input residual for disturbance recorder
3.11.1 Introduction
The SUM3Ph function block is used in order to get the sum of two sets of 3 ph analog
signals (of the same type) for those IED functions that might need it.
en05000441.vsd
Table 47: Input signals for the Sum3Ph (SU01-) function block
Signal Description
BLOCK Block
DFTSYNC Synchronisation of DFT calculation
DFTSPFC Number of samples per fundamental cycle used for DFT
calculation
G1AI3P Group 1 analog input 3-phase group
G2AI3P Group 2 analog input 3-phase group
Table 48: Output signals for the Sum3Ph (SU01-) function block
Signal Description
AI3P Group analog input 3-phase group
AI1 Group 1 analog input
AI2 Group 2 analog input
AI3 Group 3 analog input
AI4 Group 4 analog input
4.1.1 Introduction
The line differential function compares the currents entering and leaving the protected
overhead line or cable. It offers phase-segregated true current differential protection
with high sensitivity and provides phase selection information for single-pole
tripping.
The three terminal version is used for conventional two-terminal lines with or without
1 1/2 circuit breaker arrangement in one end, as well as three terminal lines with single
breaker arrangements at all terminals.
Protected zone
en05000039.vsd
The six terminal version is used for conventional two-terminal lines with 1 1/2 circuit
breaker arrangements in both ends, as well as multi terminal lines with up to five
terminals.
Protected zone
RED RED
670 Comm. Channel 670
en05000040.vsd
The current differential algorithm in RED 670 provides high sensitivity for internal
faults, at the same time as it has excellent stability for external faults. Current samples
from all CTs are exchanged between the IEDs in the line ends (master-master mode)
or sent to one IED (master-slave mode) for evaluation.
A restrained dual biased slope evaluation is made where the bias current is the highest
phase current in any line end giving a secure through fault stability even with heavily
saturated CTs. In addition to the restrained evaluation, an unrestrained high
differential current setting can be used for fast tripping of internal faults with very
high currents.
A special feature with RED 670 is that applications with small power transformers
(rated current less than 50% of differential current setting) connected as line taps
without measurement in the tap can be handled. The normal load current is here
considered to be negligible, and special measures need only to be taken in the event
of a short circuit on the LV side of the transformer. In this application, the tripping
of the differential protection can be time delayed for low differential currents in order
to achieve coordination with down stream over current relays.
One or two power transformers can be included in the line differential protection
zone. Both two- and three-winding transformers are correctly represented with vector
group compensations made in the algorithm. The function includes 2nd and 5th
harmonic restraint and zero sequence current elimination.
Protected zone
64 kbit/s communication channel is needed between every IED included in the same
line differential protection zone. In the latter, current samples are sent from all slave
IEDs to one master IED where the evaluation is made, and trip signals are sent to the
remote ends when needed. In this system, a 64 kbit/s communication channel is only
needed between the master, and each one of the slave terminals.
Protected zone
RED RED
670 670
Comm.
Channels
en05000043.vsd
Protected zone
RED RED
670 670
Comm.
Channels
en05000044.vsd
Current samples from IEDs located geographically apart from each other, must be
time coordinated so that the current differential algorithm can be executed correctly.
In RED 670 it is possible to make this coordination in two different ways. The echo
method of time synchronizing is normally used whereas for applications where
transmit and receive times can differ, the optional built in GPS receivers shall be used.
In the line differential function, measured current values from local and remote line
ends are evaluated in order to distinguish between internal or external faults, or
undisturbed conditions.
The local currents are fed to the IED via the Analogue Input Modules and thereafter
they pass the Analog to Digital Converter, see figure 45.
The remote currents are received to the IED as samples via a communication link.
When entering the IED, they are processed in the Line Differential Communication
Module (LDCM) where they are time coordinated with the local current samples, and
interpolated in order to be comparable with the local samples.
In the Pre-Processing Block, the real and imaginary parts of the fundamental
frequency phase currents and negative sequence currents are derived. Together with
the current samples, they are then forwarded to the differential function block where
three different analyses are carried out.
The first analysis is the classical differential and bias current evaluation with the
characteristic as seen in figure 46. The line differential function is phase segregated
where the differential current is the vectorial sum of all measured currents taken
separately for each phase. The bias current, on the other hand, is considered as the
greatest phase current in any line end and it is common for all three phases. The two
slopes (SlopeSection1, SlopeSection2) and breakpoints (EndSection1, EndSection2)
can be set in the PCM 600 tool or via the HMI.
Current values plotted above the characteristic formed by IdMin and the dual slope
will give a start in that phase. The level IdMinHigh is a setting value that is used to
temporarily decrease the sensitivity in situations when:
There is also an unrestrained high differential current setting that can be used for fast
tripping of internal faults with very high currents.
Operate current
[ in pu of IBase]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate IdMinHigh
3 C
conditionally
A B
2
Section 1 Section 2 Section 3
SlopeSection3
1
IdMin
SlopeSection2 Restrain
0
0 1 2 3 4 5
en05000300.vsd
where:
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
The second analysis is the 2nd and 5th harmonic analysis on the differential current.
Occurrence of these harmonics over a level that is set separately for each one will
block tripping action from the biased slope evaluation.
The third analysis is the negative sequence current analysis. Effectively this is a fault
discriminator that distinguishes between internal and external faults. It works such
that the phase angle of the negative sequence current from the local end is compared
with the phase angle of the sum of the negative sequence currents from the remote
ends. The characteristic for this fault discriminator is shown in figure 47, where the
directional characteristic is defined by the two setting parameters IminNegSeq and
NegSeqRoa.
90 deg
120 deg
If one or the Internal/external
other of fault boundary
currents is too
low, then no
measurement NegSeqROA
is done, and
(Relay
120 degrees
Operate
is mapped Angle)
IMinNegSeq
External Internal
fault fault
region region
270 deg
en05000188.vsd
Reference direction of currents is considered to be towards the line. Thus, when both
currents to be compared have this direction, the phase difference between them will
ideally be zero. In the opposite case, when one current is entering and the other is
leaving the protected object, the phase difference will ideally be 180 degree. In case
either the local or the sum of the remote negative sequence currents or both is below
the set level, the fault discriminator will not make any fault classification and the
value 120 degree is set. This value is then an indication that negative sequence
directional comparison has not been possible to make, and it does not mean
classification as external fault.
With reference to figure 45, the outputs from the three analysis blocks are fed to the
output logic. Figure 48 shows a simplified block diagram of this output logic where
only trip commands and no alarm signals are shown for simplicity.
Remembering that current values plotted above the characteristic formed by IdMin
and the dual slope in figure 47 are said to give a start, the output logic can be
summarized as follows:
• A start in one phase, gives a trip under the condition that the content of 2nd and
5th harmonic is below the set level for these harmonics. Otherwise it is blocked
as long as the harmonic is above the set level. However, when a line is energized
the current setting value IdMinHigh is used. Effectively this means that the line
A-B-C in figure 46 forms the characteristic.
• Current values above the unrestrained limit gives a trip irrespective of any
presence of harmonics.
• Classification of a fault as internal by the negative sequence fault discriminator,
will give a trip under the condition that a start has occurred in that phase. This
means that any harmonic blocking is then overridden. However, occurrence of
harmonics at the same time as the differential current is below the level
IdMinHigh, will block a trip even though the fault is classified as internal. This
latter condition is to prevent unwanted trips when energizing a line tap
transformer.
• Classification of a fault as external by the negative sequence fault discriminator
will cause IdMinHigh to be used as the lower limit for the restrained characteristic
according to figure 46. Cross blocking will also be activated in this situation.
Values of the pre-fault differential currents are not updated under disturbance
conditions. The updating process is resumed 50 ms after normal conditions have been
restored. Normal conditions are only considered if there are no start signals, neither
internal nor external fault is declared, the power system is symmetrical, etc.
It is thus obvious that the change in charging current that the fault causes by decreasing
the system voltage is not considered in the algorithm, a matter that is further discussed
in the Application Manual for RED670.
It shall be noted that all small pre-fault differential currents are subtracted, no matter
what their origin. Besides the true charging currents, the following currents are
eliminated:
In RED670 the time coordination is made with the so-called echo method, which can
be complemented with GPS synchronization as an option.
Each IED has an accurate local clock with a very small time drift. This clock makes
time tagging of telegrams, and the echo method is then used to find out the time
difference between the clocks in two ends of a power line.
Referring to figure 49, it works such that the transmission time to send a message
from station B to station A (T1 → T2) and receive a message from A to B (T3 →
T4) is measured. The time instances T2 and T3 are taken with the local clock reference
of station A, and the time instances T1 and T4 are taken with the local clock reference
of station B.
T2 T3
A
B
T1 T4
en05000293.vsd
Calculation of the delay time one-way Td and the time difference Δt between the
clocks in A and B is then possible to do with equation 2 and equation 3, which are
only valid under the condition that the send and receive times are equal.
(T2 - T1 ) + (T4 - T3 )
Td =
2 (Equation 2)
(T1 + T4 ) - (T2 + T3 )
Dt =
2 (Equation 3)
In RED 670 Δt is calculated every time a telegram is received, and the time difference
is then used to adjust and interpolate the current measurements from the remote end
before the current differential algorithm is executed.
When the delay symmetry is lost, the expression for Δt given above is no longer valid,
and GPS synchronization of the local IED clocks must be used.
Including the optional GPS, means that there will be one GPS receiver module in
each IED, synchronizing its local IED clock. As GPS synchronization is very
accurate, in the order of 1 μs, all IEDs in the same line differential scheme will have
the same clock reference. It is then possible to detect asymmetric transmission time
delay and compensate for it.
When the IED is equipped with GPS, this hardware is integrated in the IED. Besides
the GPS receiver itself, it also consists of filters and regulators for post processing of
the GPS time synch pulse, which is necessary to achieve a reliable GPS
synchronization. Especially short interruptions and spurious out of synch GPS signals
are handled securely in this way.
Communication principle
For a two-terminal line, the current from the local CT needs to be communicated over
a 64 kbit/s channel to the remote line end, and the remote end current communicated
back on the same channel. In case of e.g. a three terminal line another 64 kbit/s channel
will be needed to exchange the same local current with the third line end current, etc.
In one-and-a-half breaker arrangements, there are two local currents meaning two 64
kbit/s channels to each remote substation. Alternatively, it is possible to add together
the two local currents before sending them and in that way reduce the number of
communication channels needed. This is achieved by selecting proper setting for
parameter TransmCurr (CT-SUM, CT-DIFF1 or CT-DIFF2). However, by doing it
this way there will be reduced information about bias currents. For further information
and discussions on this matter, refer to the “Application manual” for RED670.
Protected zone
RED RED
670 670
Comm. Channels
en05000292.vsd
In the master-slave system, current samples are sent from all slave IEDs to one master
IED where the evaluation is made and trip signals are sent to the remote ends when
needed. In this system, a 64 kbit/s communication channel is only needed between
the master, and each one of the slave terminals as shown in figure 51.
Protected zone
RED RED
670 670
Comm. Channels
en05000291.vsd
Test mode
The line differential function in one IED can be set in test mode. This will block the
trip outputs on that IED, and set the remote IEDs in a remote test mode, such that
injected currents will be echoed back phase shifted and with a settable amplitude. The
trip outputs in the remote terminals will also be blocked automatically. For further
information on this, refer to the “Installation and Commissioning manual” for
RED670.
Time
0 5 10 15 20 25 30 35 (ms)
en05000290.vsd
where:
x is the current sampling moment
Telecom. Network
LD LD
CM CM
LD LD
CM CM
Telecom. Network
Primary
channel
Secondary redundant
channel en05000289.vsd
Figure 53: Direct fibre optical connection between two terminals with LDOM
over longer distances.
For a three-, four- or five terminal line in a master-master configuration, a loss of one
communication channel will not cause the line differential protection to be
unserviceable. Instead it will automatically revert to a partial master-slave mode with
the two IEDs that have an unserviceable communication link between them, will serve
as slaves.
For more details about the remote communication see Chapter "Remote
communication". See also the “Application manual”.
There is space for eight binary signals integrated in the telegram of the line differential
analog communication. For further information about this, refer to section "Binary
signal transfer to remote end".
L3D--
L3CPDIF
I3P1 TRIP
I3P2 TRL1
I3P3 TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
NSANGLE
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
ID2HL1
ID2HL2
ID2HL3
ID5HL1
ID5HL2
ID5HL3
IDL1
IDL2
IDL3
ICHARGE
en05000667.vsd
L6D--
L6CPDIF
I3P1 TRIP
I3P2 TRL1
I3P3 TRL2
I3P4 TRL3
I3P5 TRIPRES
I3P6 TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
NSANGLE
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
ID2HL1
ID2HL2
ID2HL3
ID5HL1
ID5HL2
ID5HL3
IDL1
IDL2
IDL3
ICHARGE
en05000666.vsd
LT3D-
LT3CPDIF_87LT
I3P1 TRIP
I3P2 TRL1
I3P3 TRL2
TRL3
TRIPRES
TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
en06000254.vsd
LT6D-
LT6CPDIF_87LT
I3P1 TRIP
I3P2 TRL1
I3P3 TRL2
I3P4 TRL3
I3P5 TRIPRES
I3P6 TRIPUNRE
TRIPENHA
START
STL1
STL2
STL3
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
en06000255.vsd
LDL--
LineDiffLogic
CTFAIL TRIP
OUTSERV TRL1
BLOCK TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD
en05000394.vsd
Table 50: Input signals for the L3CPDIF_87L (L3D--) function block
Signal Description
I3P1 Group signal for three phase current channel 1
I3P2 Group signal for three phase current channel 2
I3P3 Group signal for three phase current channel 3
Table 51: Output signals for the L3CPDIF_87L (L3D--) function block
Signal Description
TRIP Common, main, trip output signal
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TRIPRES Trip by restrained differential protection
TRIPUNRE Trip by unrestrained differential protection
TRIPENHA Trip by enhanced restrained differential protection
START Common, main, start output signal
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
BLK2H Common block signal, due to 2nd harmonic
BLK2HL1 Block signal due to 2nd harmonic, phase L1
BLK2HL2 Block signal due to 2nd harmonic, phase L2
BLK2HL3 Block signal due to 2nd harmonic, phase L3
BLK5H Common block signal, due to 5-th harmonic
BLK5HL1 Block signal due to 5th harmonic, phase L1
BLK5HL2 Block signal due to 5th harmonic, phase L2
Table continued on next page
Signal Description
BLK5HL3 Block signal due to 5th harmonic, phase L3
NSANGLE Angle between local and remote neg. seq. currents
IDL1MAG Magnitude of fund. freq. differential current, phase L1
IDL2MAG Magnitude of fund. freq. differential current, phase L2
IDL3MAG Magnitude of fund. freq. differential current, phase L3
IBIAS Magnitude of the bias current, common for L1, L2, L3
IDNSMAG Magnitude of the negative sequence differential current
ID2HL1 Magnitude of the 2nd harm. diff. current, phase L1
ID2HL2 Magnitude of the 2nd harm. diff. current, phase L2
ID2HL3 Magnitude of the 2nd harm. diff. current, phase L3
ID5HL1 Magnitude of the 5th harm. diff. current, phase L1
ID5HL2 Magnitude of the 5th harm. diff. current, phase L2
ID5HL3 Magnitude of the 5th harm. diff. current, phase L3
IDL1 Instantaneous differential current, phase L1
IDL2 Instantaneous differential current, phase L2
IDL3 Instantaneous differential current, phase L3
ICHARGE Amount of compensated charging current
Table 52: Input signals for the L6CPDIF_87L (L6D--) function block
Signal Description
I3P1 Group signal for three phase current channel 1
I3P2 Group signal for three phase current channel 2
I3P3 Group signal for three phase current channel 3
I3P4 Group signal for three phase current channel 4
I3P5 Group signal for three phase current channel 5
I3P6 Group signal for three phase current channel 6
Table 53: Output signals for the L6CPDIF_87L (L6D--) function block
Signal Description
TRIP Common, main, trip output signal
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TRIPRES Trip by restrained differential protection
TRIPUNRE Trip by unrestrained differential protection
TRIPENHA Trip by enhanced restrained differential protection
START Common, main, start output signal
Table continued on next page
Signal Description
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
BLK2H Common block signal, due to 2nd harmonic
BLK2HL1 Block signal due to 2nd harmonic, phase L1
BLK2HL2 Block signal due to 2nd harmonic, phase L2
BLK2HL3 Block signal due to 2nd harmonic, phase L3
BLK5H Common block signal, due to 5-th harmonic
BLK5HL1 Block signal due to 5th harmonic, phase L1
BLK5HL2 Block signal due to 5th harmonic, phase L2
BLK5HL3 Block signal due to 5th harmonic, phase L3
NSANGLE Angle between local and remote neg. seq. currents
IDL1MAG Magnitude of fund. freq. differential current, phase L1
IDL2MAG Magnitude of fund. freq. differential current, phase L2
IDL3MAG Magnitude of fund. freq. differential current, phase L3
IBIAS Magnitude of the bias current, common for L1, L2, L3
IDNSMAG Magnitude of the negative sequence differential current
ID2HL1 Magnitude of the 2nd harm. diff. current, phase L1
ID2HL2 Magnitude of the 2nd harm. diff. current, phase L2
ID2HL3 Magnitude of the 2nd harm. diff. current, phase L3
ID5HL1 Magnitude of the 5th harm. diff. current, phase L1
ID5HL2 Magnitude of the 5th harm. diff. current, phase L2
ID5HL3 Magnitude of the 5th harm. diff. current, phase L3
IDL1 Instantaneous differential current, phase L1
IDL2 Instantaneous differential current, phase L2
IDL3 Instantaneous differential current, phase L3
ICHARGE Amount of compensated charging current
Table 54: Input signals for the LT3CPDIF_87L (LT3D-) function block
Signal Description
I3P1 Group signal for three phase current channel 1
I3P2 Group signal for three phase current channel 2
I3P3 Group signal for three phase current channel 3
Table 55: Output signals for the LT3CPDIF_87L (LT3D-) function block
Signal Description
TRIP Common, main, trip output signal
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TRIPRES Trip by restrained differential protection
TRIPUNRE Trip by unrestrained differential protection
TRIPENHA Trip by enhanced restrained differential protection
START Common, main, start output signal
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
BLK2H Common block signal, due to 2nd harmonic
BLK2HL1 Block signal due to 2nd harmonic, phase L1
BLK2HL2 Block signal due to 2nd harmonic, phase L2
BLK2HL3 Block signal due to 2nd harmonic, phase L3
BLK5H Common block signal, due to 5-th harmonic
BLK5HL1 Block signal due to 5th harmonic, phase L1
BLK5HL2 Block signal due to 5th harmonic, phase L2
BLK5HL3 Block signal due to 5th harmonic, phase L3
NSANGLE Angle between local and remote neg. seq. currents
IDL1MAG Magnitude of fund. freq. differential current, phase L1
IDL2MAG Magnitude of fund. freq. differential current, phase L2
IDL3MAG Magnitude of fund. freq. differential current, phase L3
IBIAS Magnitude of the bias current, common for L1, L2, L3
IDNSMAG Magnitude of the negative sequence differential current
ID2HL1 Magnitude of the 2nd harm. diff. current, phase L1
ID2HL2 Magnitude of the 2nd harm. diff. current, phase L2
ID2HL3 Magnitude of the 2nd harm. diff. current, phase L3
ID5HL1 Magnitude of the 5th harm. diff. current, phase L1
ID5HL2 Magnitude of the 5th harm. diff. current, phase L2
ID5HL3 Magnitude of the 5th harm. diff. current, phase L3
IDL1 Instantaneous differential current, phase L1
IDL2 Instantaneous differential current, phase L2
IDL3 Instantaneous differential current, phase L3
ICHARGE Amount of compensated charging current
Table 56: Input signals for the LT6CPDIF_87L (LT6D-) function block
Signal Description
I3P1 Group signal for three phase current channel 1
I3P2 Group signal for three phase current channel 2
I3P3 Group signal for three phase current channel 3
I3P4 Group signal for three phase current channel 4
I3P5 Group signal for three phase current channel 5
I3P6 Group signal for three phase current channel 6
Table 57: Output signals for the LT6CPDIF_87L (LT6D-) function block
Signal Description
TRIP Common, main, trip output signal
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TRIPRES Trip by restrained differential protection
TRIPUNRE Trip by unrestrained differential protection
TRIPENHA Trip by enhanced restrained differential protection
START Common, main, start output signal
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
BLK2H Common block signal, due to 2nd harmonic
BLK2HL1 Block signal due to 2nd harmonic, phase L1
BLK2HL2 Block signal due to 2nd harmonic, phase L2
BLK2HL3 Block signal due to 2nd harmonic, phase L3
BLK5H Common block signal, due to 5-th harmonic
BLK5HL1 Block signal due to 5th harmonic, phase L1
BLK5HL2 Block signal due to 5th harmonic, phase L2
BLK5HL3 Block signal due to 5th harmonic, phase L3
NSANGLE Angle between local and remote neg. seq. currents
IDL1MAG Magnitude of fund. freq. differential current, phase L1
IDL2MAG Magnitude of fund. freq. differential current, phase L2
IDL3MAG Magnitude of fund. freq. differential current, phase L3
IBIAS Magnitude of the bias current, common for L1, L2, L3
IDNSMAG Magnitude of the negative sequence differential current
ID2HL1 Magnitude of the 2nd harm. diff. current, phase L1
ID2HL2 Magnitude of the 2nd harm. diff. current, phase L2
ID2HL3 Magnitude of the 2nd harm. diff. current, phase L3
Table continued on next page
Signal Description
ID5HL1 Magnitude of the 5th harm. diff. current, phase L1
ID5HL2 Magnitude of the 5th harm. diff. current, phase L2
ID5HL3 Magnitude of the 5th harm. diff. current, phase L3
IDL1 Instantaneous differential current, phase L1
IDL2 Instantaneous differential current, phase L2
IDL3 Instantaneous differential current, phase L3
ICHARGE Amount of compensated charging current
Table 58: Input signals for the LineDiffLogic (LDL--) function block
Signal Description
CTFAIL CT failure indication from local CT supervision
OUTSERV Input for indicating that the terminal is out of service
BLOCK Block of function
Table 59: Output signals for the LDLPDIF_87L (LDL--) function block
Signal Description
TRIP General trip from differential protection system
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TRLOCAL Trip from local differential function
TRLOCL1 Trip from local differential function in phase L1
TRLOCL2 Trip from local differential function in phase L2
TRLOCL3 Trip from local differential function in phase L3
TRREMOTE Trip from remote differential function
DIFLBLKD Local line differential function blocked
Table 61: Parameter group settings for the L3CPDIF_87L (L3D--) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IdMin 0.20 - 2.00 0.01 0.50 IB Oper - restr charact.,
section 1 sensitivity,
multiple IBase
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, as
multiple of reference
current IBase
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, as
multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 0.1 40.0 % Slope in section 2 of
operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 0.1 80.0 % Slope in section 3 of
operate- restrain
characteristic, in %
IdMinHigh 0.20 - 10.00 0.01 1.00 IB Initial lower
sensitivity, as
multiple of IBase
IntervIdMinHig 0.250 - 60.000 0.001 1.000 s Time interval of initial
lower sensitivity, in
sec
IdUnre 1.00 - 50.00 0.01 10.00 IB Unrestrained
differential current
limit, multiple of
IBase
NegSeqDiff Off - On - On/Off selection for
On internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 1.0 60.0 Deg Internal/external
fault discriminator
Operate Angle,
degrees
Table continued on next page
Table 63: Parameter group settings for the L6CPDIF (L6D--) function
Parameter Range Step Default Unit Description
Operation Off - Off - Differential
On Protection Function
Operation Off/ On
IdMin 0.20 - 2.00 0.01 0.50 IB Oper - restr charact.,
section 1 sensitivity,
multiple IBase
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, as
multiple of reference
current IBase
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, as
multiple of reference
current IBase
Table continued on next page
Table 65: Parameter group settings for the LT3CPDIF_87L (LT3D-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IdMin 0.20 - 2.00 0.01 0.50 IB Oper - restr charact.,
section 1 sensitivity,
multiple IBase
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, as
multiple of reference
current IBase
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, as
multiple of reference
current IBase
SlopeSection2 10.0 - 50.0 0.1 40.0 % Slope in section 2 of
operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 0.1 80.0 % Slope in section 3 of
operate- restrain
characteristic, in %
IdMinHigh 0.20 - 10.00 0.01 1.00 IB Initial lower
sensitivity, as
multiple of IBase
IntervIdMinHig 0.250 - 60.000 0.001 1.000 s Time interval of initial
lower sensitivity, in
sec
IdUnre 1.00 - 50.00 0.01 10.00 IB Unrestrained
differential current
limit, multiple of
IBase
NegSeqDiff Off - On - On/Off selection for
On internal / external
fault discriminator
Table continued on next page
Table 66: Basic general settings for the LT6CPDIF_87LT (LT6D-) function
Parameter Range Step Default Unit Description
NoOfTerminals 2 - 2 - Number of current
3 terminals of the
4 protected circuit
5
6
Chan2IsLocal No - No - 2-nd local current
Yes connected to input
channel 2, Yes/ No
IBase 50.0 - 9999.9 0.1 3000.0 A Base (reference)
current of the
differential
protection
ZerSeqCurSubtr Off - Off - Off/On for
ON elimination of zero
seq. from diff. and
bias curr
TraAOnInpCh No Transf A - No Transf A - Power transformer
1 A applied on input
2 channel X
3
4
5
6
RatVoltW1TraA 1.0 - 9999.9 0.1 130.0 kV Transformer A
rated voltage (kV)
on winding 1 (HV
winding)
RatVoltW2TraA 1.0 - 9999.9 0.1 130.0 kV Transformer A
rated voltage (kV)
on winding 2 (LV
winding)
Table continued on next page
Table 67: Basic parameter group settings for the LT6CPDIF_87LT (LT6D-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
ON
IdMin 0.20 - 2.00 0.01 0.30 IB Oper - restr
charact., section 1
sensitivity, multiple
IBase
IdMinHigh 0.20 - 10.00 0.01 0.80 IB Initial lower
sensitivity, as
multiple of IBase
tIdMinHigh 0.000 - 60.000 0.001 1.000 s Time interval of
initial lower
sensitivity, in sec
IdUnre 1.00 - 50.00 0.01 10.00 IB Unrestrained
differential current
limit, multiple of
IBase
NegSeqDiffEn Off - ON - Off/On selection for
ON internal / external
fault discriminator
NegSeqROA 30.0 - 120.0 1.0 60.0 Deg Internal/external
fault discriminator
Operate Angle,
degrees
IMinNegSeq 0.01 - 0.20 0.01 0.04 IB Min. value of neg.
seq. curr. as
multiple of IBase
CrossBlockEn No - No - Off/On selection of
Yes the cross -block
logic
I2/I1Ratio 5.0 - 100.0 1.0 10.0 % Max. ratio of 2nd
harm. to
fundamental harm
dif. curr. in %
I5/I1Ratio 5.0 - 100.0 1.0 25.0 % Max. ratio of 5th
harm. to
fundamental harm
dif. curr. in %
ChargCurEnable Off - Off - Off/On selection for
ON compensation of
charging currents
AddDelay Off - Off - On/Off selection for
ON delayed diff. trip
command
IMaxAddDelay 0.20 - 5.00 0.01 1.00 IB Below limit, extra
delay can be
applied, multiple of
IBase
tDefTime 0.000 - 6.000 0.001 0.000 s Definite time
additional delay in
seconds
tMinInv 0.001 - 6.000 0.001 0.010 s Inverse Delay
Minimum Time. In
seconds
Table continued on next page
Table 68: Advanced parameter group settings for the LT6CPDIF_87LT (LT6D-) function
Parameter Range Step Default Unit Description
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, as
multiple of
reference current
IBase
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, as
multiple of
reference current
IBase
SlopeSection2 10.0 - 50.0 0.1 40.0 % Slope in section 2
of operate-restrain
characteristic, in %
SlopeSection3 30.0 - 100.0 0.1 80.0 % Slope in section 3
of operate- restrain
characteristic, in %
p 0.01 - 1000.00 0.01 0.02 - Settable curve
parameter, user-
programmable
curve type.
a 0.01 - 1000.00 0.01 0.14 - Settable curve
parameter, user-
programmable
curve type.
Table continued on next page
SlopeSection2 (10.0-50.0)% -
SlopeSection3 (30.0-100.0)% -
EndSection 1 (20–150)% of Ibase -
4.2.1 Introduction
The high impedance differential protection can be used when the involved CT cores
have same turn ratio and similar magnetizing characteristic. It utilizes an external
summation of the phases and neutral current and a series resistor and a voltage
dependent resistor externally to the relay.
The logic diagram see figure 59 shows the operation principles for the high impedance
differential protection function. It is a basically a simple one step relay with an
additional lower alarm level. The function can be totally blocked totally or only
tripping by activating inputs from external signals.
en05000363.vsd
Table 71: Input signals for the HZPDIF_87 (HZD1-) function block
Signal Description
ISI Group signal for current input
BLOCK Block of function
BLKTR Block of trip
Table 72: Output signals for the HZPDIF_87 (HZD1-) function block
Signal Description
TRIP Trip signal
ALARM Alarm signal
MEASVOLT Measured RMS voltage on CT secondary side
Table 73: Parameter group settings for the HZPDIF_87 (HZD1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
U>Alarm 2 - 500 1 10 V Alarm voltage level in
volts on CT
secondary side
tAlarm 0.000 - 60.000 0.001 5.000 s Time delay to activate
alarm
U>Trip 5 - 900 1 100 V Operate voltage level
in volts on CT
secondary side
SeriesResistor 10 - 20000 1 250 ohm Value of series
resistor in Ohms
5.1.1 Introduction
The line distance protection is a three zone full scheme protection with three fault
loops for phase to phase faults and three fault loops for phase to earth fault for each
of the independent zones. Individual settings for each zone resistive and reactive reach
gives flexibility for use onoverhead lines and cables of different types and lengths.
The function has a functionality for load encroachment which increases the possibility
to detect high resistive faults on heavily loaded lines(see figure 61).
Forward
operation
Reverse
operation
en05000034.vsd
Figure 61: Typical distance protection zone with load encroachment function
activated
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together with
different communication schemes, for the protection of power lines and cables in
complex network configurations, such as parallel lines, multi-terminal lines etc.
The execution of the different fault loops within the IED670 are of full scheme type,
which means that each fault loop for phase to earth faults and phase to phase faults
for forward and reverse faults are executed in parallel.
Figure 62 presents an outline of the different measuring loops for the basic five,
impedance-measuring zones l.
en05000458.vsd
Figure 62: The different measuring loops at line-earth fault and phase-phase
fault.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a start element to select correct voltages and current
depending on fault type. Each distance protection zone performs like one independent
distance protection relay with six measuring elements.
The distance measuring zone include six impedance measuring loops; three intended
for phase-to-earth faults, and three intended for phase-to-phase as well as three-phase
faults.
The distance measuring zone will essentially operate according to the non-directional
impedance characteristics presented in figure 63 and figure 64. The phase-to-earth
characteristic is illustrated with the full loop reach while the phase-to-phase
characteristic presents the per-phase reach.
X0 - X1
Xn =
3
X1+Xn R0 - R1
Rn =
3
f N f N
R (Ohm/loop)
RFPE RFPE
X1+Xn
X (Ohm/phase)
2·X1
R (Ohm/phase)
RFPP RFPP
2·X1
The fault loop reach with respect to each fault type may also be presented as in
figure 65. Note in particular the difference in definition regarding the (fault) resistive
reach for phase-to-phase faults and three-phase faults.
ILn R1 + j X1
Phase-to-earth
UL1
element
Phase-to-earth
fault in phase L1 RFPE
(Arc + tower
resistance)
0
IN (R0-R1)/3 +
j (X0-X1)/3 )
IL1 R1 + j X1 Phase-to-phase
UL1 element L1-L2
Phase-to-phase
fault in phase RFPP
L1-L2 IL2
UL2 (Arc resistance)
R1 + j X1
where:
n designates anyone of the three phases (1, 2 or 3) and
m represents the phase that is leading phase n with 120 degrees (i.e. 3, 1 or 2).
The R1 and jX1 in figure 65 represents the positive sequence impedance from the
measuring point to the fault location. The RFPE and RFPP is the eventual fault
resistance in the fault place.
Regarding the illustration of three-phase fault in figure 65, there is of course fault
current flowing also in the third phase during a three-phase fault. The illustration
merely reflects the loop measurement, which is made phase-to-phase.
The theoretical parameters p and q outline the area of operation in quadrant 1 when
varied from 0 to 1.0. That is, for any combination of p and q, where both are between
0 and 1.0, the corresponding impedance is within the reach of the characteristic.
X X X
R R R
en05000182.vsd
The operation of the distance measuring zone is blocked if the magnitude of input
currents fall below certain threshold values.
For zone 1 with load compensation feature the additional criterion applies, that all
phase-to-earth loops will be blocked when IN < IMinOpIN, regardless of the phase
currents.
ILn is the RMS value of the current in phase Ln. IN is the RMS value of the vector
sum of the three phase currents, i.e. residual current 3I0.
ILmLn is the RMS value of the vector difference between phase currents Lm and Ln.
Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The
calculation of the apparent impedances at ph-ph faults follows equation 4 (example
for a phase L1 to phase L2 fault).
UL1 – UL2
Zapp = -------------------------
I L1 – IL2
(Equation 4)
Here U and I represent the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3)
U L1
Z app = ------------------------------
I L1 + I N × KN
(Equation 5)
Where:
UL1, IL1 and IN are the phase voltage, phase current and residual current present to the IED
KN is defined as:
X0 - X1
KN =
3X1
where X0 and X1 is zero and positive sequence reactance from the measuring point
to the fault on the protected line.
Here IN is a phasor of the residual current in relay point. This results in the same
reach along the line for all types of faults.
The formula given in equation 6 is only valid for no loaded radial feeder applications.
When load is considered in the case of single line to earth fault, conventional distance
protection might overreach at exporting end and underreach at importing end. REx670
has an adaptive load compensation which increases the security in such applications.
Measuring elements receive current and voltage information from the A/D converter.
The check sums are calculated and compared, and the information is distributed into
memory locations. For each of the six supervised fault loops, sampled values of
voltage (U), current (I), and changes in current between samples (DI) are brought
from the input memory and fed to a recursive Fourier filter.
The filter provides two orthogonal values for each input. These values are related to
the loop impedance according to equation 7,
X Di
U = R × i + ------ × -----
w 0 Dt
(Equation 7)
X D Re ( I )
Re ( U ) = R × Re ( I ) + ------ × ------------------
w0 Dt
(Equation 8)
X DIm ( I )
Im ( U ) = R × Im ( I ) + ------ × -----------------
w0 Dt
(Equation 9)
with
w0 = 2 × p × f 0
(Equation 10)
where:
Re designates the real component of current and voltage,
Im designates the imaginary component of current and voltage and
f0 designates the rated system frequency
The algorithm calculates Rm measured resistance from the equation for the real value
of the voltage and substitute it in the equation for the imaginary part. The equation
for the Xm measured reactance can then be solved. The final result is equal to:
Im ( U ) × DRe ( I ) – Re ( U ) × D Im ( I )
R m = ------------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – D Im ( I ) × Re ( I )
(Equation 11)
Re ( U ) × Im ( I ) – Im ( U ) × Re ( I )
Xm = w 0 × Dt × -------------------------------------------------------------------------------
DRe ( I ) × Im ( I ) – DIm ( I ) × Re ( I )
(Equation 12)
The calculated Rm and Xm values are updated each sample and compared with the set
zone reach. The adaptive tripping counter counts the number of permissive tripping
results. This effectively removes any influence of errors introduced by the capacitive
voltage transformers or by other factors.
The directional evaluations are performed simultaneously in both forward and reverse
directions, and in all six fault loops. Positive sequence voltage and a phase locked
positive sequence memory voltage are used as a reference. This ensures unlimited
directional sensitivity for faults close to the relay point.
The evaluation of the directionality is taken place in the function block ZD.
Equation 13 and equation 14 are used to classify that the fault is in forward direction
for line-to-earth fault and phase-phase fault.
For the L1-L2 element, the equation in forward direction is according to.
where:
ArgDir is the setting for the lower boundary of the forward directional characteristic, by default set
to 15 (= -15 degrees) and
ArgNegRes is the setting for the upper boundary of the forward directional characteristic, by default
set to 115 degrees, see figure 67.
U1L1 is positive sequence phase voltage in phase L1
U1L1L2M is memorized voltage difference between phase L1 and L2 (L2 lagging L1)
The setting of ArgDir and ArgNegRes is by default set to 15 (= -15) and 115 degrees
respectively.(see figure 67) and it should not be changed unless system studies has
shown the necessity.
The ZD gives a binary coded signal on the output STDIR depending on the evaluation
where STFWL1N=1 adds 1, STRVL1N=1 adds 2, STFWL2N=1 adds 4 etc.
ArgNegRes
ArgDir
R
en05000722.vsd
Figure 67: Setting angles for discrimination of forward and reverse fault
For close-in three-phase faults, the U1L1M memory voltage, based on the same
positive sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is
restored.
• If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition seals
in.
The STCND input signal represents a connection of six different integer values from
the phase selection function within the IED, which are converted within the zone
measuring function into corresponding boolean expressions for each condition
separately. It is connected to the PHS function block output STCDZ.
The internal input signal DIRCND is used to give condition for directionality for the
distance measuring zones. The signal contains binary coded information for both
forward and reverse direction. The zone measurement function filter out the relevant
signals on the STDIR input depending on the setting of the parameter
OperationDir. It shall be configured to the STDIR output on the ZD block.
Composition of the phase starting signals for a case, when the zone operates in a non-
directional mode, is presented in figure 69.
Results of the directional measurement enter the logic circuits, when the zone operates
in directional (forward or reverse) mode, see figure 70.
STNDL1N
AND
DIRL1N
OR STZMPE.
&
STNDL2N
DIRL2N AND
STNDL3N 15 ms
OR STL1
& t
DIRL3N AND
STNDL1L2
DIRL1L2 AND 15 ms
OR STL2
& t
STNDL2L3
DIRL2L3 AND
15 ms
OR STL3
STNDL3L1 & t
DIRL3L1 AND
OR STZMPP
&
BLK
15 ms
OR START
& t
en05000778.vsd
Tripping conditions for the distance protection zone one are symbolically presented
in figure 71.
Figure 71: Tripping logic for the distance protection zone one
ZM01-
ZMQPDIS
I3P TRIP
U3P TRL1
BLOCK TRL2
VTSZ TRL3
BLKTR START
STCND STL1
DIRCND STL2
STL3
STND
en05000695.vsd
ZD01-
ZDRDIR
I3P STDIR
U3P
en05000681.vsd
Table 75: Input signals for the ZMQPDIS_21 (ZM01-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
VTSZ Blocks all output by fuse failure signal
BLKTR Blocks all trip outputs
STCND External start condition (loop enabler)
DIRCND External directional condition
Table 76: Output signals for the ZMQPDIS_21 (ZM01-) function block
Signal Description
TRIP General Trip, issued from any phase or loop
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
Table continued on next page
Signal Description
START General Start, issued from any phase or loop
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
STND Non-directional start, issued from any phase or loop
Table 77: Input signals for the ZDRDIR (ZD01-) function block
Signal Description
I3P Group connection
U3P Group connection
Table 78: Output signals for the ZDRDIR (ZD01-) function block
Signal Description
STDIR All start signals binary coded
Table 79: Parameter group settings for the ZMQPDIS_21 (ZM01-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base current, i.e.
rated current
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, i.e.
rated voltage
OperationDir Off - Forward - Operation mode of
Non-directional directionality NonDir /
Forward Forw / Rev
Reverse
X1 0.10 - 3000.00 0.01 30.00 ohm/p Positive sequence
reactance reach
R1 0.10 - 1000.00 0.01 5.00 ohm/p Positive seq.
resistance for zone
characteristic angle
X0 0.10 - 9000.00 0.01 100.00 ohm/p Zero sequence
reactance reach
R0 0.50 - 3000.00 0.01 15.00 ohm/p Zero seq. resistance
for zone characteristic
angle
RFPP 1.00 - 3000.00 0.01 30.00 ohm/l Fault resistance
reach in ohm/loop,
Ph-Ph
Table continued on next page
Table 80: Parameter group settings for the ZDRDIR (ZD01-) function
Parameter Range Step Default Unit Description
ArgNegRes 90 - 175 1 115 Deg Angle to blinder in
second quadrant for
forward direction
ArgDir 5 - 45 1 15 Deg Angle to blinder in
fourth quadrant for
forward direction
IMinOp 1 - 99999 1 10 %IB Minimum operate
current in % of IBase
IBase 1 - 99999 1 3000 A Base Current
UBase 0.05 - 2000.00 0.05 400.00 kV Base Voltage
5.2.1 Introduction
The operation of transmission networks today is in many cases close to the stability
limit. Due to environmental considerations the rate of expansion and reinforcement
of the power system is reduced e.g. difficulties to get permission to build new power
lines. The ability to accurate and reliable classifying the different types of fault so
that single pole tripping and auto-reclosing can be used plays an important roll in this
matter. The PHS function is designed to accurate select the proper fault loop in the
distance function dependent on the fault type.
The heavy load transfer that is common in many transmission networks may in some
cases be in opposite to the wanted fault resistance coverage. Therefore the function
has an built in algorithm for load encroachment, which gives the possibility to enlarge
the resistive setting of both the PHS and the measuring zones without interfering with
the load.
The extensive output signals from the PHS gives also important information about
faulty phase(s) which can be used for fault analysis.
The characteristic is basically non-directional, but the PHS function uses information
from the directional function block to discriminate whether the fault is in forward or
reverse. The directional lines are drawn as "line-dot-dot-line" in the figures below.
1. Residual current criteria, i.e. separation of faults with and without earth
connection
2. Regular quadrilateral impedance characteristic
3. Load encroachment characteristics is always active but can be switched off by
selecting a high setting.
X X X
60°
60° R
R R
60° 60°
en05000668.vsd
The setting of the load encroachment function may influence the total operating
characteristic, (for more information, refer to section "Load encroachment").
The input DIRCND contains binary coded information about the directional coming
from the directionality block. It shall be connected to the STDIR output on the ZD
block. This information is also transferred to the input DIRCND on the distance
measuring zones, i.e. the ZM block. The code built up for the directionality is as
follows:
STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+
+STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+
+STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048
If the binary information is 1 then it will be considered that we have start in forward
direction in phase L1. If the binary code is 5 then we have start in forward direction
in phase L1 and L2 etc.
For a phase-to-earth fault, the measured impedance by PHS function will be according
to equation 15.
ULn
ZPHSn =
ILn
(Equation 15)
where:
n corresponds to the particular phase (n=1, 2 or 3)
The characteristic for the PHS function at phase to earth fault is according to
figure 75. The characteristic has a fixed angle for the resistive boundary in the first
quadrant of 60°.
The resistance RN and reactance XN is the impedance in the earth return path defined
according to equation 16 and equation 17.
R0 - R1
RN =
3
(Equation 16)
X 0 - X1
XN =
3
(Equation 17)
X (ohm/loop)
Kr·(X1+XN)
RFRvPE RFFwPE
X1+XN
60 deg
RFFwPE
RFRvPE R (Ohm/loop)
60 deg
X1
1
Kr =
tan(60 deg)
RFRvPE RFFwPE
Kr·(X1+XN)
en06000396.vsd
Figure 75: Characteristic of PHS for phase to earth fault (setting parameters in
italic), ohm/loop domain
Besides this, the 3I0 residual current must fulfil the conditions according to
equation 18 and equation 19.
3 × I 0 ³ 0.5 × IM in O p
(Equation 18)
3 × I0 ³ INReleasePE
------------------------------------ × Iphmax
100 (Equation 19)
where:
IMinOp is the minimum operation current for forward zones,
INReleasePE is the setting for the minimum residual current needed to enable operation in the ph-E
fault loops (in %) and
Iphmax is the maximum phase current in any of three phases.
For a phase-to-phase fault, the measured by the PHS function will be according to
equation 20.
ULm - ULn
ZPHS =
-2 × ILn
(Equation 20)
ULm is the leading phase voltage, ULn the lagging phase voltage and ILn the phase
current in the lagging phase n.
X (ohm/phase)
0.5·FRvPP 0.5·RFFwPP
Kr·X1
X1
0.5·RFFwPP
60 deg
R (ohm/phase)
60 deg
0.5·RFRvPP
X1
1
Kr =
tan(60 deg)
Kr·X1
0.5·RFRvPP 0.5·RFFwPP
en05000670.vsd
Figure 76: The operation characteristic for PHS at phase-to-phase fault (setting
parameters in Italic), ohm/phase domain
In the same way as the condition for phase-to-earth fault, there are current conditions
that have to be fulfilled in order to release the phase-to-phase loop. Those are
according to equation 21 or equation 22.
3I 0 < IN Re leasePE
(Equation 21)
where:
INRelease is 3I0 limit for releasing phase-to-earth measuring loops,
INBlockPP is 3I0 limit for blocking phase-to-phase measuring loop and
Iphmax is maximal magnitude of the phase currents.
The operation condition for three phase faults are the same as for phase-to-phase fault
i.e. equation 20, equation 21 and equation 22 are used to release the operation of the
function.
X (ohm/phase)
4 × X1
3
90 deg
0.5·RFFwPP·K3
X1·K3 4 × RFFwPP
6
R (ohm/phase)
0.5·RFRvPP·K3
K3 = 2 / sqrt(3)
30 deg
en05000671.vsd
Figure 77: The characteristic of PHS for three phase fault (setting parameters
in italic)
Each of the six measuring loops has its own load (encroachment) characteristic based
on the corresponding loop impedance. The load encroachment functionality is always
active, but can be switched off by selecting a high setting.
The outline of the characteristic is presented in figure 78. As illustrated, the resistive
blinders are set individually in forward and reverse direction while the angle of the
sector is the same in all four quadrants.
RLdFw
ARGLd ARGLd
R
ARGLd ARGLd
RLdRv
en05000196.vsd
When STCNDI is selected the operation characteristic will be as the right illustration
in figure 79. The reach will in this case be limit by the minimum operation current
and the distance measuring zones.
X X
R R
STCNDZ STCNDI
en05000197.vsd
When the "phase selection" is set to operate together with a distance measuring zone
the resultant operate characteristic could look something like in figure 80. The figure
shows a distance measuring zone operating in forward direction. Thus, the operate
area is highlighted in black.
"Phase selection"
"quadrilateral" zone
Load encroachment
characteristic
Directional line
en05000673.vsd
X (ohm/phase)
Phase selection
”Quadrilateral” zone
R (ohm/phase)
en05000674.vsd
Figure 81: Operation characteristic for PHS in forward direction for three-phase
fault, ohm/phase domain
The operation of the PHS function is blocked if the magnitude of input currents falls
below certain threshold values.
The phase-to-earth loop Ln is blocked if ILn<IMinOpPE, where ILn is the RMS value
of the current in phase Ln.
Figure 82: Phase-to-phase and phase-to-earth operating conditions (residual current criteria)
en06000258.vsd
Table 82: Input signals for the FDPSPDIS_21 (PHS--) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
DIRCND External directional condition
Table 83: Output signals for the FDPSPDIS_21 (PHS--) function block
Signal Description
STFWL1 Fault detected in phase L1 - forward direction
STFWL2 Fault detected in phase L2 - forward direction
STFWL3 Fault detected in phase L3 - forward direction
STFWPE Earth fault detected in forward direction
STRVL1 Fault detected in phase L1 - reverse direction
STRVL2 Fault detected in phase L2 - reverse direction
STRVL3 Fault detected in phase L3 - reverse direction
STRVPE Earth fault detected in reverse direction
STNDL1 Non directional start in L1
STNDL2 Non directional start in L2
Table continued on next page
Signal Description
STNDL3 Non directional start in L3
STNDPE Non directional start, phase-earth
STFW1PH Start in forward direction for single-phase fault
STFW2PH Start in forward direction for two- phase fault
STFW3PH Start in forward direction for thre-phase fault
STPE Current conditions release of phase-earth measuring
elements
STPP Current conditions release of phase-phase measuring
elements
STCNDZ Start condition (PHS,LE and I based)
STCNDI Start condition (LE and I based)
Table 84: Parameter group settings for the FDPSPDIS_21 (PHS--) function
Parameter Range Step Default Unit Description
IBase 1 - 99999 1 3000 A Base current for
current settings
INBlockPP 10 - 100 1 40 %IPh 3I0 limit for blocking
phase-to-phase
measuring loops
INReleasePE 10 - 100 1 20 %IPh 3I0 limit for releasing
phase-to-earth
measuring loops
RLdFw 1.00 - 3000.00 0.01 80.00 ohm/p Forward resistive
reach within the load
impedance area
RLdRv 1.00 - 3000.00 0.01 80.00 ohm/p Reverse resistive
reach within the load
impedance area
ArgLd 5 - 70 1 30 Deg Load angle
determining the load
impedance area
X1 0.50 - 3000.00 0.01 40.00 ohm/p Positive sequence
reactance reach
X0 0.50 - 9000.00 0.01 120.00 ohm/p Zero sequence
reactance reach
RFFwPP 0.50 - 3000.00 0.01 30.00 ohm/l Fault resistance
reach, Ph-Ph, forward
RFRvPP 0.50 - 3000.00 0.01 30.00 ohm/l Fault resistance
reach, Ph-Ph, reverse
RFFwPE 1.00 - 9000.00 0.01 100.00 ohm/l Fault resistance
reach, Ph-E, forward
Table continued on next page
5.3.1 Introduction
Power swings may occur after disconnection of heavy loads or trip of big generation
plants.
Power swing detection function is used to detect power swings and initiate block of
selected distance protection zones. Occurrence of earth fault currents during a power
swing can block the power swing detection function to allow fault clearance.
Its principle of operation is based on the measurement of the time it takes for a power
swing transient impedance to pass through the impedance area between the outer and
the inner characteristics. Power swings are identified by transition times longer than
a transition time set on corresponding timers. The impedance measuring principle is
the same as that used for the distance protection zones. The impedance and the
characteristic passing times are measured in all three phases separately. One-out-of-
three or two-out-of-three operating modes can be selected according to the specific
system operating conditions.
æ U L1 ö
Reçç ÷÷ £ Rset
è IL1 ø (Equation 23)
æ U L1 ö
Imçç ÷÷ £ Xset
è IL1 ø (Equation 24)
The Rset and Xset are R and X boundaries which are more explained in the following
sections.
where:
kLdRFw is a settable multiplication factor less than 1
The slope of the load encroachment inner and outer boundary is defined by setting
the parameter ARGLd.
The load encroachment in the fourth quadrant uses the same settings as in the first
quadrant (same ARGLd and RLdOutFw and calculated RLdInFw).
The quadrilateral characteristic in the first quadrant is tilted to get a better adaptation
to the distance zones. The angle is the same as the line angle and derived from the
setting of the reactive reach inner boundary X1InFw and the line resistance for the
inner boundary R1LIn. The fault resistance coverage for the inner boundary is set by
the parameter R1FInFw.
From the setting parameter RLdOutFw and the calculated value RLdInFw a distance
between the inner and outer boundary, DFw, is calculated. This value is valid for R
direction in first and fourth quadrant and for X direction in first and second quadrant.
cone. The distance to the inner resistive load boundary RLdInRv is determined by
using the setting parameter kLdRRv in equation 26.
From the setting parameter RLdOutRv and the calculated value RLdInRv a distance
between the inner and outer boundary, DRv, is calculated. This value is valid for R
direction in second and third quadrant and for X direction in third and fourth quadrant.
The inner resistive characteristic in the second quadrant outside the load
encroachment part corresponds to the setting parameter R1FInRv for the inner
boundary. The outer boundary is internally calculated as the sum of DRv+R1FInRv.
The inner resistive characteristic in the third quadrant outside the load encroachment
zone consist of the sum of the settings R1FInRv and the line resistance R1LIn. The
argument of the tilted lines outside the load encroachment is the same as the tilted
lines in the first quadrant. The distance between the inner and outer boundary is the
same as for the load encroachment in reverse direction i.e. DRv.
The inner characteristic for the reactive reach in forward direction correspond to the
setting parameter X1InFw and the outer boundary is defined as X1InFw + DFw.
The inner characteristic for the reactive reach in reverse direction correspond to the
setting parameter X1InRv for the inner boundary and the outer boundary is defined
as X1InRv + DRv.
The operation of the function is only released if the magnitude of the current is above
the setting of the min operating current, IMinOpPE.
• The "1-of-3" operating mode is based on detection of power swing in any of the
three phases. Figure 88 presents a composition of a detection signal PSD-DET-
L1 in this particular phase.
• The "2-of-3" operating mode is based on detection of power swing in at least two
out of three phases. Figure 89 presents a composition of the detection signals
DET1of3 and DET2of3.
The tP1 timer in figure 88 serve as detection of initial power swings, which are usually
not as fast as the later swings are. The tP2 timer become activated for the detection
of the consecutive swings, if the measured impedance exit the operate area and returns
within the time delay, set on the tW waiting timer. The upper part of figure 88 (input
signal ZOUTL1, ZINL1, AND-gates and tP-timers etc.) are duplicated for phase L2
and L3. All tP1 and tP2 timers in the figure have the same settings.
Figure 89: Detection of power-swing for 1-of-3 and 2-of-3 operating mode
ZOUTL1 ZOUT
OR
ZOUTL2 ZINL1
ZIN
ZOUTL3 AND ZINL2 OR
ZINL3
tEF
TRSP
t AND
I0CHECK
10 ms
AND t
BLKI02 OR
tR1
AND t INHIBIT
OR
-loop
tR2
BLKI01 AND t
BLOCK
-loop
DET1of3 - int.
REL1PH
AND
BLK1PH
tH
DET2of3 - int. OR t
REL2PH
AND
BLK2PH OR START
AND
EXTERNAL
en05000114.vsd
Figure 90 presents a simplified logic diagram for the PSD function. The internal
signals DET1of3 and DET2of3 relate to the detailed logic diagrams in figure 88 and
figure 89 respectively.
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated. The
characteristic will in this case be only quadrilateral.
There are four different ways to form the internal INHIBIT signal:
time, which is longer than the time delay set on tR2 timer. It is possible to disable
this condition by connecting the logical 1 signal to the BLKI01 functional input.
• The INHIBIT internal signal is activated after the time delay, set on tR1 timer,
if an earth fault appears during the power swing (input IOCHECK is high) and
the power swing has been detected before the earth fault (activation of the signal
I0CHECK). It is possible to disable this condition by connecting the logical 1
signal to the BLKI02 functional input.
• The INHIBIT logical signals becomes logical 1, if the functional input I0CHECK
appears within the time delay, set on tEF timer and the impedance has been seen
within the outer characteristic of the PSD operate characteristic in all three
phases. This function prevents the operation of the PSD function in cases, when
the circuit breaker closes onto persistent single-phase fault after single-pole auto-
reclosing dead time, if the initial single-phase fault and single-pole opening of
the circuit breaker causes the power swing in the remaining two phases.
en05000383.vsd
Table 86: Input signals for the ZMRPSB_78 (PSD1-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
BLKI01 Block inhibit of start output for slow swing condition
BLKI02 Block inhibit of start output for subsequent residual current
detection
BLK1PH Block one-out-of-three-phase operating mode
REL1PH Release one-out-of-three-phase operating mode
BLK2PH Block two-out-of-three-phase operating mode
REL2PH Release two-out-of-three-phase operating mode
Table continued on next page
Signal Description
I0CHECK Residual current (3I0) detection used to inhibit start output
TRSP Single-pole tripping command issued by tripping function
EXTERNAL Input for external detection of power swing
Table 87: Output signals for the ZMRPSB_78 (PSD1-) function block
Signal Description
START Power swing detected
ZOUT Measured impedance within outer impedance boundary
ZIN Measured impedance within inner impedance boundary
Table 88: Parameter group settings for the ZMRPSB_78 (PSD1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Mode On /
On Off
X1InFw 0.10 - 3000.00 0.01 30.00 ohm Inner reactive
boundary, forward
R1LIn 0.10 - 1000.00 0.01 30.00 ohm Line resistance for
inner characteristic
angle
R1FInFw 0.10 - 1000.00 0.01 30.00 ohm Fault resistance
coverage to inner
resistive line, forward
X1InRv 0.10 - 3000.00 0.01 30.00 ohm Inner reactive
boundary, reverse
R1FInRv 0.10 - 1000.00 0.01 30.00 ohm Fault resistance line
to inner resistive
boundary, reverse
OperationLdCh Off - On - Operation of load
On discrimination
characteristic
RLdOutFw 0.10 - 3000.00 0.01 30.00 ohm Outer resistive load
boundary, forward
ArgLd 5 - 70 1 25 Deg Load angle
determining load
impedance area
RLdOutRv 0.10 - 3000.00 0.01 30.00 ohm Outer resistive load
boundary, reverse
kLdRFw 0.50 - 0.90 0.01 0.75 Mult Multiplication factor
for inner resistive load
boundary, forward
kLdRRv 0.50 - 0.90 0.01 0.75 Mult Multiplication factor
for inner resistive load
boundary, reverse
Table continued on next page
5.4.1 Introduction
Automatic switch onto fault logic is a function that gives an instantaneous trip at
closing of breaker onto a fault. A dead line detection check is provided to activate the
function when the line is dead.
SOTF-BC 1000 ms
SOTF-DLCND 200 ms >1 t
& t 15 ms
SOTF-NDACC SOTF-TRIP
& t
SOTF-BLOCK &
en00000492.vsd
Figure 92: Simplified diagram for automatic switch onto fault logic function.
The external activation is achieved by an input (BC), which should be set high for
activation, and low when the breaker has closed. This is carried out by an NC auxiliary
contact of the circuit breaker or by the closing order to the breaker.
The internal automatic activation is controlled by the internal dead line detection
(DLD) function. The function gives an internal output signal DLD when the current
and voltage for each phase is below the setting parameter IPh< and UPh<, see figure
93. The SOTF function will be activated if the signal is present for more than 200 ms
at the same time as the non-directional impedance starting signal NDACC is not
activated.
Iph_L1 1
1<2
AND
IPh< 2
Uph_L1 1
1<2
UPh< 2
Iph_L2 1
1<2
AND AND SOTF-DLD
IPh< 2
Uph_L2 1
1<2
UPh< 2
Iph_L3 1
1<2
AND
IPh< 2
Uph_L3 1
1<2
UPh< 2
en05000737.vsd
Figure 93: Simplified logic diagram for dead line detection function in SOTF.
en05000377.vsd
Table 90: Input signals for the ZPSOF (SOTF-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
BC Enabling of SOTF
NDACC Non Directional Zone to be accelerated by SOTF
Table 91: Output signals for the ZPSOF (SOTF-) function block
Signal Description
TRIP Trip output
Table 92: Parameter group settings for the ZPSOF (SOTF-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current levels
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage levels
IPh< 1 - 100 1 20 %IB Current level for
detection of dead line
in % of IBase
UPh< 1 - 100 1 70 %UB Voltage level for
detection of dead line
in % of UBase
Delay following dead line detection input before SOTF 200 ms ± 0.5% ± 10 ms
function is automatically enabled
Time period after circuit breaker closure in which 1000 ms ± 0.5% ± 10 ms
SOTF function is active
6.1.1 Introduction
The instantaneous three phase overcurrent function has a low transient overreach and
short tripping time to allow use as a high set short-circuit protection function, with
the reach limited to less than typical eighty percent of the power line at minimum
source impedance.
There is also a possibility to activate a preset change of the set operation current
(StValMult) via a binary input (ENMULT). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
en04000391.vsd
Table 94: Input signals for the PHPIOC_50 (IOC1-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
ENMULT Enable current start value multiplier
Table 95: Output signals for the PHPIOC_50 (IOC1-) function block
Signal Description
TRIP Trip signal from any phase
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
Table 96: Parameter group settings for the PHPIOC_50 (IOC1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
OpMode 2 out of 3 - 1 out of 3 - Select operation
1 out of 3 mode 2-out of 3 / 1-
out of 3
IP>> 1 - 2500 1 200 %IB Operate phase
current level in % of
IBase
StValMult 0.5 - 5.0 0.1 1.0 - Multiplier for operate
current level
6.2.1 Introduction
The four step phase overcurrent function has an inverse or definite time delay
independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional
user defined time characteristic.
U3P
TRIP
Harmonic harmRestrBlock
I3P Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
en05000740.vsd
A common setting for all steps, StPhaseSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out
of 3 or 3 out of 3.
The sampled analogue phase currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of each phase current the
RMS value of each phase current is derived. These phase current values are fed to
the TOC function. In a comparator, for each phase current, the RMS values are
compared to the set operation current value of the function (I1>, I2>, I3> or I4>). If
a phase current is larger than the set operation current a signal from the comparator
for this phase and step is set to true. This signal will, without delay, activate the output
signal Start for this phase/step, the Start signal common for all three phases for this
step and a common Start signal.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and compared to a set restrain current level.
The function can use a directional option. The direction of the fault current is given
as current angle in relation to the voltage angle. The fault current and fault voltage
for the directional function is dependent of the fault type. To enable directional
measurement at close in faults, causing low measured voltage, the polarization
voltage is a combination of the apparent voltage (80%) and a memory voltage (20%).
The following combinations are used.
U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
U refL1 = U L1 I dirL1 = I L1
U refL 2 = U L 2 I dirL 2 = I L 2
U refL 3 = U L 3 I dirL 3 = I L 3
The directional setting is given as a characteristic angle AngleRCA for the function
and an angle window AngleRCA-maxFwdAng to AngleRCA+minFwdAng.
Reverse
Uref
RCA
ROA
ROA Forward
Idir
en05000745.vsd
A minimum current for directional phase start current signal can be set:
IminOpPhSel.
If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or some type of
inverse time characteristic. A wide range of standardized inverse time characteristics
is available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in chapter "Time inverse
characteristics".
Different types of reset time can be selected as described in chapter "Time inverse
characteristics".
en05000708.vsd
Table 98: Input signals for the PH4POCM_51_67 (TOC1-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
BLKTR Block of trip
BLKST1 Block of Step1
BLKST2 Block of Step2
Table continued on next page
Signal Description
BLKST3 Block of Step3
BLKST4 Block of Step4
ENMULT1 When activated, the current multiplier is in use for step1
ENMULT2 When activated, the current multiplier is in use for step2
ENMULT3 When activated, the current multiplier is in use for step3
ENMULT4 When activated, the current multiplier is in use for step4
Table 99: Output signals for the PH4POCM_51_67 (TOC1-) function block
Signal Description
TRIP Trip
TR1 Common trip signal from step1
TR2 Common trip signal from step2
TR3 Common trip signal from step3
TR4 Common trip signal from step4
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
TRL3 Trip signal from phase L3
TR1L1 Trip signal from step1 phase L1
TR1L2 Trip signal from step1 phase L2
TR1L3 Trip signal from step1 phase L3
TR2L1 Trip signal from step2 phase L1
TR2L2 Trip signal from step2 phase L2
TR2L3 Trip signal from step2 phase L3
TR3L1 Trip signal from step3 phase L1
TR3L2 Trip signal from step3 phase L2
TR3L3 Trip signal from step3 phase L3
TR4L1 Trip signal from step4 phase L1
TR4L2 Trip signal from step4 phase L2
TR4L3 Trip signal from step4 phase L3
START General start signal
ST1 Common start signal from step1
ST2 Common start signal from step2
ST3 Common start signal from step3
ST4 Common start signal from step4
STL1 Start signal from phase L1
STL2 Start signal from phase L2
STL3 Start signal from phase L3
ST1L1 Start signal from step1 phase L1
Table continued on next page
Signal Description
ST1L2 Start signal from step1 phase L2
ST1L3 Start signal from step1 phase L3
ST2L1 Start signal from step2 phase L1
ST2L2 Start signal from step2 phase L2
ST2L3 Start signal from step2 phase L3
ST3L1 Start signal from step3 phase L1
ST3L2 Start signal from step3 phase L2
ST3L3 Start signal from step3 phase L3
ST4L1 Start signal from step4 phase L1
ST4L2 Start signal from step4 phase L2
ST4L3 Start signal from step4 phase L3
2NDHARM Block from second harmonic detection
DIRL1 Direction for phase1
DIRL2 Direction for phase2
DIRL3 Direction for phase3
Table 100: Parameter group settings for the PH4POCM_51_67 (TOC1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 - Base setting for
current values
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage levels in kV
MaxFwdAng 40.0 - 70.0 0.1 50.0 Deg Maximum forward
angle
MinFwdAng 75.0 - 90.0 0.1 80.0 Deg Minimum forward
angle
AngleRCA -70.0 - -50.0 1.0 -65.0 Deg Relay characteristic
angle (RCA)
IMinOpPhSel 1 - 100 1 7 %IB Minimum current for
phase selection in %
of IBase
StartPhSel Not Used - 1 out of 3 - Number of phases
1 out of 3 required for op (1 of 3,
2 out of 3 2 of 3, 3 of 3)
3 out of 3
2ndHarmStab 5 - 100 1 20 %IB Operate level of 2nd
harm restrain op in %
of Fundamental
Table continued on next page
6.3.1 Introduction
The single input overcurrent function has a low transient overreach and short tripping
times to allow use as a high set short circuit protection function, with the reach limited
to less than typical eighty percent of the power line at minimum source impedance.
The function can be configured to measure the residual current from the three phase
current inputs or the current from a separate current input.
There is also a possibility to activate a preset change of the set operation current via
a binary input (enable multiplier MULTEN). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
The function can be blocked from the binary input BLOCK. The trip signals from the
function can be blocked from the binary input BLKAR, that can be activated during
single pole trip and autoreclosing sequences.
en04000393.vsd
Table 102: Input signals for the EFPIOC_50N (IEF1-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
BLKAR Block input for auto reclose
MULTEN Enable current multiplier
Table 103: Output signals for the EFPIOC_50N (IEF1-) function block
Signal Description
TRIP Trip signal
Table 104: Parameter group settings for the EFPIOC_50N (IEF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
IN>> 1 - 2500 1 200 %IB Operate residual
current level in % of
IBase
StValMult 0.5 - 5.0 0.1 1.0 - Multiplier for operate
current level
6.4.1 Introduction
The four step single input overcurrent function has an inverse or definite time delay
independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional
user defined characteristic.
The function can be used as main protection for phase to earth faults.
The function can be used to provide a system back-up e.g. in the case of the primary
protection being out of service due to communication or voltage transformer circuit
failure.
The function can be configured to measure the residual current from the three phase
current inputs or the current from a separate current input.
• The direction element, indicate earth current fault direction. The directional
check uses 3I0cos(ϕ-ϕRCA) for comparison
• The harmonic Restraint Blocking function
• 4 step over current function
• Switch On To Fault function (SOTF), including Under Time
• Mode Selection
• Blocking at parallel transformers
signal to
communication
scheme
Directional Check
Element
enableDir
harmRestrBlock
3I0 Harmonic
Restraint ³1
Element
CB
pos
or cmd
enableDir
Mode
Selection enableStep1-4
DirectionalMode1-4
en05000741.vsd
The sampled analog residual current is pre-processed in a discrete Fourier filter (DFT)
block. From the fundamental frequency component the RMS value of the residual
current is derived. This residual current value is fed to the TEF function. In a
comparator the RMS value is compared to the set operation current value of the
function (IN1>, IN2>, IN3> or IN4>). If the residual current is larger than the set
operation current a signal from the comparator for this step is set to true. This signal
will, without delay, activate the output signal Start for this step and a common Start
signal.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from
the pre-processing of the phase currents and compared to a set restrain current level.
The function can use a directional option. A fault is in the forward direction if the
residual current component 3I0cos(ϕ-ϕRCA) is larger than a set level. The angle ϕ
is the angle between the residual current and the polarizing voltage (–3U0). The angle
is defined positive when the residual current lags the reference voltage. The
AngleRCA is the characteristic angle of the directional function.
Operation
IN>Dir
en05000285.vsd
If no blockings are given the start signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or some type of
inverse time characteristic. A wide range of standardized inverse time characteristics
is available. It is also possible to create a tailor made time characteristic. The
possibilities for inverse time characteristics are described in chapter 23 "Time inverse
characteristics"
Different types of reset time can be selected as described in chapter 23 "Time inverse
characteristics"
harmonic restrain signal will latched as long as the residual current measured by the
relay is larger than a selected step current level.
The function can be blocked from the binary input BLOCK. The start signals from
the function can be blocked from the binary input BLKST. The trip signals from the
function can be blocked from the binary input BLKTR.
Integrated in the four step residual overcurrent protection are Switch on to fault logic
(SOTF) and undertime logic. The parameter SOFT is set to activate either SOTF or
undertime function or both. When the circuit breaker is closing there is a risk to close
energize a permanent fault, for example during an autoreclosing sequence. The SOTF
function will enable fast fault clearance during such situations. The time the SOTF/
Undertime function will be active after activation is set by the parameter t4U.
The SOFT function uses the start signal from step 2 or 3, which is set by parameter
Step3ForSOTF. The function is activated from change in circuit breaker position or
from circuit breaker close command pulse. The parameter ActivationSOTF can be set
for activation of CB position open change, CB position closed change or CB close
command. In case of a residual current start from step 2 or 3 (dependent on setting)
the function will give a trip after a set delay tSOTF. This delay is normally set to a
short time (default 100 ms).
The undertime function uses the start signal from step 4. The function will normally
be set to a lower current level than the SOTF function. The undertime function can
also be blocked by the 2nd harmonic restrain function. This enables high sensitivity
even if power transformer inrush currents can occur. The detection of unsymmetrical
CB poles after switching is thus possible. The function is activated from change in
circuit breaker position or from circuit breaker close and open command pulse. This
is set by parameter ActUnderTime. The parameter ActUnderTime can be set for
activation of CB position change or CB close/open command. In case of a residual
current start from step 4 the function will give a trip after a set delay tUnderTime.
This delay is normally set to a relatively short time (default 300 ms).
en04000395.vsd
Table 106: Input signals for the EF4PEFM_51N67N (TEF1-) function block
Signal Description
BLOCK Block of function
I3P Group signal for current input
BLKTR Block of trip
U3P Group signal for voltage input
BLKST1 Block of step 1 (Start and trip)
BLKST2 Block of step 2 (Start and trip)
BLKST3 Block of step 3 (Start and trip)
BLKST4 Block of step 4 (Start and trip)
ENMULT1 When activated, the current multiplier is in use for step1
ENMULT2 When activated, the current multiplier is in use for step2
ENMULT3 When activated, the current multiplier is in use for step3
ENMULT4 When activated, the current multiplier is in use for step4
CBPOS Breaker position
CLOSECB Breaker close command
OPENCB Breaker open command
Table 107: Output signals for the EF4PEFM_51N67N (TEF1-) function block
Signal Description
TRIP Trip
TRIN1 Trip signal from step 1
TRIN2 Trip signal from step 2
TRIN3 Trip signal from step 3
TRIN4 Trip signal from step 4
TRSOTF Trip signal from earth fault switch onto fault function
START General start signal
STIN1 Start signal step 1
STIN2 Start signal step 2
STIN3 Start signal step 3
STIN4 Start signal step 4
STSOTF Start signal from earth fault switch onto fault function
STFW Forward directional start signal
STRV Reverse directional start signal
2NDHARMD 2nd harmonic block signal
Table 108: Parameter group settings for the EF4PEFM_51N67N (TEF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation mode Off /
On On
IBase 1 - 99999 1 3000 A Base setting for
current values
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage level in kV
IMinOpFund 1 - 2500 1 3 %IB Minimum
fundamental
frequency current
level in % of IBase
AngleRCA -180 - 180 1 65 Deg Relay characteristic
angle (RCA)
3UO>Dir 1 - 100 1 5 %UB Minimum polarizing
quantity in % of
UBase
IN>DirCmp 1 - 100 1 3 %IB Operate residual
current level for
DirComp in % of
IBase
tDirCmp 0.000 - 60.000 0.001 10.000 s Time delay for
DirComp
Table continued on next page
6.5.1 Introduction
The increasing utilizing of the power system closer to the thermal limits have
generated a need of a thermal overload function also for power lines.
A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload function can allow the protected circuit to operate
closer to the thermal limits.
The three phase current measuring function has an I2t characteristic with settable time
constant and a thermal memory.
An alarm level gives early warning to allow operators to take action well before the
line will be tripped.
From the largest of the three phase currents a final temperature is calculated according
to the expression:
2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø (Equation 33)
where:
I is the largest phase current,
Iref is a given reference current and
If this temperature is larger than the set operate temperature level a start output signal
START is activated.
æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-
è ø (Equation 34)
where:
Qn is the calculated present temperature,
When the component temperature reaches the set alarm level AlarmTemp the output
signal ALARM is set. When the component temperature reaches the set trip level
TripTemp the output signal TRIP is set.
There is also a calculation of the present time to operation with the present current.
This calculation is only performed if the final temperature is calculated to be above
the operation temperature:
æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø (Equation 35)
The calculated time to trip can be monitored as it is exported from the function as a
real figure TTRIP.
After a trip, caused by the thermal overload protection function, there can be a lockout
to reconnect the tripped circuit. The output lockout signal LOCKOUT is activated
when the device temperature is above the set lockout release temperature setting
ReclTemp.
The time to lockout release is calculated, i.e. a calculation of the cooling time to a set
value. The thermal content of the function can be reset with input RESET.
æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q final - Q n
è ø (Equation 36)
In some applications the measured current can involve a number of parallel lines.
This is often used for cable lines where one bay connects several parallel cables. By
setting the parameter IMult to the number of parallel lines (cables) the actual current
on one line is used in the protection algorithm. To activate this option the input
ENMULT must be activated.
The function has a reset input: RESET. By activating this input the calculated
temperature is reset to its default initial value. This is useful during testing when
secondary injected current has given a calculated “false” temperature level.
actual temperature
Calculation
of actual
temperature
trip signal
Actual Temp
> TripTemp initiate lockout
Calculation
of time to time to reset of lockout
reset of
lockout
en05000736.vsd
en04000396.vsd
Table 110: Input signals for the LPTTR_26 (THL1-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
ENMULT Current multiplyer used when THOL is for two or more lines
RESET Reset of internal thermal load counter
Table 111: Output signals for the LPTTR_26 (THL1-) function block
Signal Description
TRIP Trip
START Start Signal
ALARM Alarm signal
LOCKOUT Lockout signal
Table 112: Parameter group settings for the LPTTR_26 (THL1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
HystTemp 0 - 50 1 10 - Hysteresis for start
temperature
IBase 0 - 99999 1 3000 A Base current in A
IMult 1-5 1 1 - Current multiplier
when THOL is used
for two or more lines
IRef 0 - 400 1 100 %IB The load current (in
%of IBase) leading to
TRef temperature
Table continued on next page
Table 113: Thermal overload protection, one time constant (PTTR, 26)
Function Range or value Accuracy
Reference current (0-400)% of Ibase ± 1.0% of Ir
I = Imeasured
6.6.1 Introduction
The circuit breaker failure function ensures fast back-up tripping of surrounding
breakers. The breaker failure protection operation can be current based, contact based
or adaptive combination between these two principles.
A current check with extremely short reset time is used as a check criteria to achieve
a high security against unnecessary operation.
The breaker failure protection can be single- or three-phase started to allow use with
single phase tripping applications. For the three-phase version of the breaker failure
protection the current criteria can be set to operate only if two out of four e.g. two
phases or one phase plus the residual current starts. This gives a higher security to
the back-up trip command.
The function can be programmed to give a single- or three phase re-trip of the own
breaker to avoid unnecessary tripping of surrounding breakers at an incorrect starting
due to mistakes during testing.
The start signal can be phase selective or general (for all three phases). Phase selective
start signals enable single pole re-trip function. This means that a second attempt to
open the breaker is done. The re-trip attempt can be made after a set time delay. For
transmission lines single pole trip and autoreclosing is often used. The re-trip function
can be phase selective if it is initiated from phase selective line protection. The re-
trip function can be done with or without current check. With the current check the
re-trip is only performed if the current through the circuit breaker is larger than the
operate current level.
The start signal can be an internal or external protection trip signal. If this start signal
gets high at the same time as current is detected through the circuit breaker, the back-
up trip timer is started. If the opening of the breaker is successful this is detected by
the function, both by detection of low RMS current and by a special adapted
algorithm. The special algorithm enables a very fast detection of successful breaker
opening, i.e. fast resetting of the current measurement. If the current detection has
not detected breaker opening before the back-up timer has run its time a back-up trip
is initiated. There is also a possibility to have a second back-up trip output activated
after an added settable time after the first back-up trip.
• The minimum length of the re-trip pulse, the back-up trip pulse and the back-up
trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-
Current
AND
BLOCK
Current & t1 tp
STIL1
Contact t TRRETL1
AND AND
START
OR
STL1
OR
TRRET
OR
AND AND
CBCLDL1
Contact
L2 L3
en05000832.vsd
Internal logical signals STIL1, STIL2, STIL3 have logical value 1 when current in
respective phase has magnitude larger than setting parameter IP>.
Internal logical signal STN has logical value 1 when neutral current has magnitude
larger than setting parameter IN>.
t2
1 of 4 t
OR
t3 tp
t TRBU2
2 of 3
AND
CBALARM
CBFLT CBALARM
t
en06000223.vsd
en04000397.vsd
Table 114: Input signals for the CCRBRF_50BF (BFP1-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
START Three phase start of breaker failure protection function
STL1 Start signal of phase L1
Table continued on next page
Signal Description
STL2 Start signal of phase L2
STL3 Start signal of phase L3
CBCLDL1 Circuit breaker closed in phase L1
CBCLDL2 Circuit breaker closed in phase L2
CBCLDL3 Circuit breaker closed in phase L3
CBFLT CB faulty, unable to trip. Back-up trip instantanously.
Table 115: Output signals for the CCRBRF_50BF (BFP1-) function block
Signal Description
TRBU Back-up trip by breaker failure protection function
TRBU2 Second back-up trip by breaker failure protection function
TRRET Retrip by breaker failure protection function
TRRETL1 Retrip by breaker failure protection function phase L1
TRRETL2 Retrip by breaker failure protection function phase L2
TRRETL3 Retrip by breaker failure protection function phase L3
CBALARM Alarm for faulty circuit breaker
Table 116: Parameter group settings for the CCRBRF_50BF (BFP1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current level settings
FunctionMode Current - Current - Detection for back-up
Contact trip Current/Cont/
Current&Contact Current and Cont
BuTripMode 2 out of 4 - 1 out of 3 - Back-up trip mode, 2
1 out of 3 out of 4, 1 out of 3 or
1 out of 4 1 out of 4
RetripMode Retrip Off - Retrip Off - Operation mode of re-
I> Check trip logic: OFF/I>
No I> Check check/No I> check
IP> 5 - 200 1 10 %IB Operate level in % of
IBase
I>BlkCont 5 - 200 1 20 %IB Current for blocking of
CB contact operation
in % of IBase
IN> 2 - 200 1 10 %IB Operate residual level
in % of IBase
t1 0.000 - 60.000 0.001 0.000 s Time delay of re-trip
Table continued on next page
6.7.1 Introduction
When a power line is taken out of service for maintenance and the line disconnector
is opened in multi-breaker arrangements the voltage transformers will mostly be
outside on the disconnected part. The primary line distance protection will thus not
be able to operate and must be blocked.
The stub protection covers the zone between the current transformers and the open
disconnector. The three phase instantaneous overcurrent function is released from a
NO (b) auxiliary contact on the line disconnector.
BLOCK
TRIP
STIL1 AND
STIL2 OR
STIL3
RELEASE
en05000731.vsd
en05000678.vsd
Table 118: Input signals for the STBPTOC_50STB (STB1-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
BLKTR Block of trip
RELEASE Release of stub protection
Table 119: Output signals for the STBPTOC_50STB (STB1-) function block
Signal Description
TRIP Trip
START General start
Table 120: Parameter group settings for the STBPTOC_50STB (STB1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
ReleaseMode Release - Release - Release of stub
Continuous protection
I> 1 - 2500 1 200 %IB Operate current level
in % of IBase
t 0.000 - 60.000 0.001 0.000 s Time delay
6.8.1 Introduction
Single pole operated circuit breakers can due to electrical or mechanical failures end
up with the different poles in different positions (close-open). This can cause negative
and zero sequence currents which gives thermal stress on rotating machines and can
cause unwanted operation of zero sequence current functions.
Normally the own breaker is tripped to correct the positions. If the situation consists
the remote end can be intertripped to clear the unsymmetrical load situation.
The pole discordance function operates based on information from auxiliary contacts
of the circuit breaker for the three phases with additional criteria from unsymmetrical
phase current when required.
C.B.
en05000287.vsd
This single binary signal is connected to a binary input of the IED. The appearance
of this signal will start a timer that will give a trip signal after the set delay.
There is also a possibility to connect all phase selective auxiliary contacts (phase
contact open and phase contact closed) to binary inputs of the IED. This is shown in
figure 112
C.B.
+
poleOneOpened from C.B.
en05000288.vsd
In this case the logic is realized within the function. If the inputs are indicating pole
discordance the trip timer is started. This timer will give a trip signal after the set
delay.
values are fed to the PD function. The difference between the smallest and the largest
phase current is derived. If this difference is larger than a set ratio the trip timer is
started. This timer will give a trip signal after the set delay. The current based pole
discordance function can be set to be active either continuously or only directly in
connection to breaker open or close command.
The function also has a binary input that can be configured from the autoreclosing
function, so that the pole discordance function can be blocked during sequences with
a single pole open if single pole autoreclosing is used.
The simplified block diagram of the current and contact based pole discordance
function is shown in figure 113.
BLOCK
OR
BLKDBYAR
PolPosAuxCont
AND
POLE1OPN
POLE1CL
POLE2OPN
Discordance
POLE2CL
detection
POLE3OPN
POLE3CL t 150 ms
t TRIP
AND
OR
PD Signal from CB
AND
EXTPDIND
CLOSECMD t+200 ms
OR
OPENCMD
AND
Unsymmetry current
detection
en05000747.vsd
Figure 113: Simplified block diagram of pole discordance function - contact and
current based
• The terminal is in TEST mode (TEST-ACTIVE is high) and the function has
been blocked from the HMI (BlockPD=Yes)
• The input signal BLOCK is high
• The input signal BLKDBYAR is high
The BLOCK signal is a general purpose blocking signal of the pole discordance
function. It can be connected to a binary input of the terminal in order to receive a
block command from external devices or can be software connected to other internal
functions of the terminal itself in order to receive a block command from internal
functions. Through OR gate it can be connected to both binary inputs and internal
function outputs.
The BLKDBYAR signal blocks the pole discordance operation when a single phase
autoreclosing cycle is in progress. It can be connected to the output signal AR01-1PT1
if the autoreclosing function is integrated in the terminal; if the autoreclosing function
is an external device, then BLKDBYAR has to be connected to a binary input of the
terminal and this binary input is connected to a signalization “1phase autoreclosing
in progress” from the external autoreclosing device.
If the pole discordance function is enabled, then two different criteria will generate
a trip signal TRIP:
If one or two poles of the circuit breaker have failed to open or to close (pole
discordance status), then the function input EXTPDIND is activated from the pole
discordance signal derived from the circuit breaker auxiliary contacts (one NO contact
for each phase connected in parallel, and in series with one NC contact for each phase
connected in parallel) and, after a settable time interval t (0-60 s), a 150 ms trip pulse
command TRIP is generated by the pole discordance function.
• any phase current is lower than 80% of the highest current in the remaining two
phases
• the highest phase current is greater than 10% of the rated current
If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set time
delay t (0-60 s) if the detection occurs in the next 200 ms after the circuit breaker has
received a command to open trip or close and if the unbalance persists. The 200 ms
limitation is for avoiding unwanted operation during unsymmetrical load conditions.
The pole discordance function is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
information) and OPENCMD (for opening command information). These inputs can
be connected to terminal binary inputs if the information are generated from the field
(i.e. from auxiliary contacts of the close and open push buttons) or may be software
connected to the outputs of other integrated functions (i.e. close command from a
control function or a general trip from integrated protections).
en05000321.vsd
Table 122: Input signals for the CCRPLD_52PD (PD01-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
BLKDBYAR Block of function at CB single phase auto re-closing cycle
CLOSECMD Close order to CB
OPENCMD Open order to CB
EXTPDIND Pole discordance signal from CB logic
POLE1OPN Pole one opened indication from CB
POLE1CL Pole one closed indication from CB
POLE2OPN Pole two opened indication from CB
POLE2CL Pole two closed indication from CB
POLE3OPN Pole three opened indication from CB
POLE3CL Pole three closed indication from CB
Table 123: Output signals for the CCRPLD_52PD (PD01-) function block
Signal Description
TRIP Trip signal to CB
START Trip condition TRUE, waiting for time delay
Table 124: Parameter group settings for the CCRPLD_52PD (PD01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current levels
TimeDelayTrip 0.000 - 60.000 0.001 0.300 s Time delay between
trip condition and trip
signal
ContSel Off - Off - Contact function
PD signal from CB selection
Pole pos aux cont.
CurrSel Off - Off - Current function
CB oper monitor selection
Continuous
monitor
CurrUnsymLevel 0 - 100 1 80 % Unsym magn of
lowest phase current
compared to the
highest.
CurrRelLevel 0 - 100 1 10 %IB Current magnitude for
release of the function
in % of IBase
7.1.1 Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
The function can be used to open circuit breakers to prepare for system restoration at
power outages or as long-time delayed back-up to primary protection.
The function has two voltage steps, each with inverse or definite time delay.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.
The undervoltage protection function measures the phase to earth voltages, if the
voltage transformer is connected phase to earth to the analogue voltage inputs. The
setting of the analogue inputs are given as primary phase to phase voltage and
secondary phase to phase voltage. The function will operate if the phase to earth
voltage gets lover than the set percentage of the phase to earth voltage corresponding
to the set base voltage UBase. This means operation for phase to earth voltage under:
If the voltage transformer is connected phase to phase to the analogue input, the setting
of the analogue inputs are given as primary phase to phase voltage and secondary
phase to phase voltage divided by √ 3. The function will operate if the phase to phase
voltage gets lover than the set percentage of the phase to phase voltage corresponding
to the set base voltage UBase.
All the three phase to earth voltages are measured continuously, and compared with
the set values, U1< and U2<. The parameters OpMode1 and OpMode2 influence the
requirements to activate the start outputs. Either "1 out of 3", "2 out of 3" or "3 out
of 3" phases have to be lower than the corresponding set point to issue the
corresponding start signal.
To avoid oscillations of the output start signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (IDMT). For the inverse time delay three different modes are available; inverse
curve A, inverse curve B, and a programmable inverse curve.
k
t=
æ U < -U ö
ç ÷
è U< ø (Equation 39)
k × 480
t= 2.0
+ 0.055
æ U < -U ö
ç 32 × - 0.5 ÷
è U< ø (Equation 40)
é ù
ê ú
k×A
t=ê ú+D
êæ U < -U ö ú
p
êç B × -C÷ ú
ëè U< ø û (Equation 41)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval U< down to U< *(1.0 –
CrvSatn/100) the used voltage will be: U< *(1.0 – CrvSatn/100). If the programmable
curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100 (Equation 42)
The lowest phase voltage is always used for the inverse time delay integration, see
figure 115. The details of the different inverse time characteristics are shown in
section "Inverse characteristics".
Voltage
UL1
UL2
UL3
IDMT Voltage
Time
en05000009.vsd
Figure 115: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the undervoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by some special voltage level dependent time curves for the inverse
time mode (IDMT). If the start condition, with respect to the measured voltage ceases
during the delay time, and is not fulfilled again within a user defined reset time
(tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for the inverse
time) the corresponding start output is reset. Here it should be noted that after leaving
the hysteresis area, the start condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area. Note that for the undervoltage
function the IDMT reset time is constant and does not depend on the voltage
fluctuations during the drop-off period. However, there are three ways to reset the
timer, either the timer is reset instantaneously, or the timer value is frozen during the
reset time, or the timer value is linearly decreased during the reset time. See
figure 116 and figure 117.
tReset
tReset 1
Voltage 1 Measured
START Voltage
Hysteresis
TRIP
U1<
Time
START t1
TRIP
Time
Integrator Froozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset en05000010.vsd
Figure 116: Voltage profile not causing a reset of the start signal for step 1, and definite time delay
tReset1
Voltage
tReset1
START
START
Hysteresis Measured Voltage
TRIP
U1<
Time
START t1
TRIP
Time Integrator
Froozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset en05000011.vsd
Figure 117: Voltage profile causing a reset of the start signal for step 1, and definite time delay
7.1.2.3 Blocking
The undervoltage function can be partially or totally blocked, by binary input signals
or by parameter settings, where:
If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the start outputs of step 1, are blocked. The
characteristic of the blocking is set by the IntBlkSel1 parameter. This internal blocking
can also be set to "off" resulting in no voltage based blocking. Corresponding settings
and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will get
very low. The event will start both the under voltage function and the blocking
function, as seen in figure 118. The delay of the blocking function must be set less
than the time delay of under voltage function.
U Disconnection
Normal voltage
U1<
U2<
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466.vsd
7.1.2.4 Design
Step 1
Time integrator TR1L2
MinVoltSelect t1 TRIP
or tReset1
ResetTypeCrv1 TR1L3
TR1
OR
Comparator ST2L1
UL1 < U2< Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 < U2< 1 out of 3
2 outof 3 ST2L3
Phase 3 Start
Comparator 3 out of 3
&
UL3 < U2< Trip ST2
Output OR
Step 2
Time integrator TR2L2
MinVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
OR START
TRIP
OR
en05000012.vsd
en05000330.vsd
Table 126: Input signals for the PH2PUVM_27 (TUV1-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
BLKTR1 Block of operate signal, step 1
BLKST1 Block of step 1
BLKTR2 Block of operate signal, step 2
BLKST2 Block of step 2
Table 127: Output signals for the PH2PUVM_27 (TUV1-) function block
Signal Description
TRIP Operate signal
TR1 Operate signal for step 1
TR1L1 Operate signal for phase 1, step 1
TR1L2 Operate signal for phase 2, step 1
TR1L3 Operate signal for phase 3, step 1
TR2 Operate signal for step 2
TR2L1 Operate signal for phase 1, step 2
TR2L2 Operate signal for phase 2, step 2
TR2L3 Operate signal for phase 3, step 2
Table continued on next page
Signal Description
START Start signal
ST1 Start signal for step1
ST1L1 Start signal for phase 1, step 1
ST1L2 Start signal for phase 2, step 1
ST1L3 Start signal for phase 3, step 1
ST2 Start signal for step 2
ST2L1 Start signal for phase 1, step 2
ST2L2 Start signal for phase 2, step 2
ST2L3 Start signal for phase 3, step 2
Table 128: Basic parameter group settings for the PH2PUVM_27 (TUV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A characteristic
Inverse curve B selection, step 1
Prog. inv. curve
OpMode1 1 out of 3 - 1 out of 3 - Operation Mode, 1
2 out of 3 out of 3 / 2 out of 3 / 3
3 out of 3 out of 3, step 1
U1< 1 - 100 1 70 %UB Voltage setting/start
val (DT & IDMT) in %
of UBase, step 1
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
k1 0.05 0.01 0.05 - 1.10 - Time multiplier in
IDMT mode, step 1
IntBlkSel1 Off - Off - Internal (low level)
Block of trip blocking mode, step 1
Block all
IntBlkStVal1 1 - 100 1 20 %UB Voltage setting for
internal blocking in %
of UBase, step 1
tBlkUV1 0.000 - 60.000 0.001 0.000 s Time delay of internal
(low level) blocking for
step 1
HystAbs1 0.0 - 100.0 0.1 0.5 %UB Absolute hysteresis in
% of UBase, step 1
Table continued on next page
Table 129: Advanced parameter group settings for the PH2PUVM_27 (TUV1-) function
Parameter Range Step Default Unit Description
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
ACrv1 1.000 0.001 0.005 - 200.000 - Setting A for
programmable under
voltage IDMT curve,
step 1
Table continued on next page
7.2.1 Introduction
Overvoltages will occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines.
The function can be used as open line end detector, normally then combined with
directional reactive over-power function or as system voltage supervision, normally
then giving alarm only or switching in reactors or switch out capacitor banks to control
the voltage.
The function has two voltage steps, each of them with inverse or definite time delayed.
The overvoltage function has an extremely high reset ratio to allow setting close to
system service voltage.
The two-step overvoltage protection function (TOV) is used to detect high power
system voltage. The function has two steps with separate time delays. If one, two or
three phase voltages increase above the set value, a corresponding start signal is
issued. TOV can be set to start/trip based on "one out of three", "two out of three",
or "three out of three" of the measured phase voltages, being above the set point. If
the phase voltage remains above the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued. The time delay
characteristic is individually chosen for the two steps and can be either definite time
delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.
The overvoltage protection function measures the phase to earth voltages, if the
voltage transformer is connected phase to earth to the analogue voltage inputs. The
setting of the analogue inputs are given as primary phase to phase voltage and
secondary phase to phase voltage. The function will operate if the phase to earth
voltage gets higher than the set percentage of the phase to earth voltage corresponding
to the set base voltage UBase. This means operation for phase to earth voltage over
If the voltage transformer is connected phase to phase to the analogue input, the setting
of the analogue inputs are given as primary phase to phase voltage and secondary
phase to phase voltage divided by √3. The function will operate if the phase to phase
voltage gets higher than the set percentage of the phase to phase voltage corresponding
to the set base voltage UBase.
All the three phase voltages are measured continuously, and compared with the set
values, U1> and U2>. The parameters OpMode1 and OpMode2 influence the
requirements to activate the start outputs. Either "1 out of 3", "2 out of 3" or "3 out
of 3" phases have to be higher than the corresponding set point to issue the
corresponding start signal.
To avoid oscillations of the output start signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (IDMT). For the inverse time delay four different modes are available; inverse
curve A, inverse curve B, inverse curve C, and a programmable inverse curve.
k
t=
æ U < -U ö
ç ÷
è U< ø (Equation 44)
k × 480
t= 2.0
æ U -U > ö
ç 32 × - 0.5 ÷ - 0.035
è U> ø (Equation 45)
k × 480
t= 3.0
æ U -U > ö
ç 32 × - 0.5 ÷ - 0.035
è U> ø (Equation 46)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø (Equation 47)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval U< down to U< *(1.0 –
CrvSatn/100) the used voltage will be: U< *(1.0 – CrvSatn/100). If the programmable
curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100 (Equation 48)
The highest phase voltage is always used for the inverse time delay integration, see
figure 121. The details of the different inverse time characteristics are shown in
section "Inverse characteristics"
Voltage
IDMT Voltage
UL1
UL2
UL3
Time
en05000016.vsd
Figure 121: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by selected voltage level dependent time curves for the inverse time
mode (IDMT). If the start condition, with respect to the measured voltage ceases
during the delay time, and is not fulfilled again within a user defined reset time
(tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for the inverse
time) the corresponding start output is reset, after that the defined reset time has
elapsed. Here it should be noted that after leaving the hysteresis area, the start
condition must be fulfilled again and it is not sufficient for the signal to only return
back to the hysteresis area. It is also remarkable that for the overvoltage function the
IDMT reset time is constant and does not depend on the voltage fluctuations during
the drop-off period. However, there are three ways to reset the timer, either the timer
is reset instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 122 and figure 123.
tReset1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured Voltage
Time
START t1
TRIP
Time Integrator
Linear Decrease
Froozen Timer
t1
Instantaneous Time
Reset
en05000017.vsd
Figure 122: Voltage profile note causing a reset of the start signal for step 1, and definite time delay
tReset1
Voltage tReset1
START
START TRIP
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Froozen Timer
t1
Time
Instantaneous
Linear Decrease
Reset en05000018.vsd
Figure 123: Voltage profile causing a reset of the start signal for step 1, and definite time delay
7.2.2.3 Blocking
The overvoltage function can be partially or totally blocked, by binary input signals
where:
7.2.2.4 Design
OR TR1
Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
2 outof 3 ST2L3
3 out of 3 Phase 3 Start
Comparator &
UL3 > U2> Trip ST2
OR
Output
START Logic TR2L1
Step 2
Time integrator TR2L2
MaxVoltSelect t2 TRIP
or tReset2
ResetTypeCrv2 TR2L3
TR2
OR
START
OR
TRIP
OR
en05000013.vsd
en05000328.vsd
Table 131: Input signals for the PH2POVM_59 (TOV1-) function block
Signal Description
U3P Group signal for three phase voltage input
BLOCK Block of function
BLKTR1 Block of operate signal, step 1
BLKST1 Block of step 1
BLKTR2 Block of operate signal, step 2
BLKST2 Block of step 2
Table 132: Output signals for the PH2POVM_59 (TOV1-) function block
Signal Description
TRIP Operate signal
TR1 Operate signal for step 1
TR1L1 Operate signal from phase 1, step 1
TR1L2 Operate signal from phase 2, step 1
TR1L3 Operate signal from phase 3, step 1
TR2 Operate signal for step 2
TR2L1 Operate signal from phase 1, step 2
TR2L2 Operate signal from phase 2, step 2
TR2L3 Operate signal from phase 3, step 2
Table continued on next page
Signal Description
START Start signal
ST1 Start signal for step1
ST1L1 Start signal from phase 1, step 1
ST1L2 Start signal from phase 2, step 1
ST1L3 Start signal from phase 3, step 1
ST2 Start signal for step 2
ST2L1 Start signal from phase 1, step 2
ST2L2 Start signal from phase 2, step 2
ST2L3 Start signal from phase 3, step 2
Table 133: Parameter group settings for the PH2POVM_59 (TOV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A charcteristic
Inverse curve B selection, step 1
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - 1 out of 3 - Operation mode, 1
2 out of 3 out of 3 / 2 out of 3 / 3
3 out of 3 out of 3, step 1
U1> 1 - 200 1 120 %UB Voltage setting/start
val (DT & IDMT) in %
of UBase, step 1
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
k1 0.05 - 1.10 0.01 0.05 - Time multiplier in
IDMT mode, step 1
Table continued on next page
7.3.1 Introduction
Residual voltages will occur in the power system during earth faults.
The function can be configured to calculate the residual voltage from the three phase
voltage input transformers or from a single phase voltage input transformer fed from
an open delta or neutral point voltage transformer.
The function has two voltage steps, each with inverse or definite time delayed.
The voltage related settings are made in percent of the base voltage, which is set in
kV, phase-phase.
The residual voltage is measured continuously, and compared with the set values,
U1> and U2>.
To avoid oscillations of the output start signal, a hysteresis has been included.
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (IDMT). For the inverse time delay four different modes are available; inverse
curve A, inverse curve B, inverse curve C, and a programmable inverse curve.
k
t=
æ U < -U ö
ç ÷
è U< ø (Equation 49)
k × 480
t= 2.0
æ U -U > ö
ç 32 × - 0.5 ÷ - 0.035
è U> ø (Equation 50)
k × 480
t= 3.0
æ U -U > ö
ç 32 × - 0.5 ÷ - 0.035
è U> ø (Equation 51)
k×A
t= p
+D
æ U -U > ö
çB× -C÷
è U> ø (Equation 52)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval U> up to U> *(1.0 +
CrvSatn/100) the used voltage will be: U> *(1.0 + CrvSatn/100). If the programmable
curve is used this parameter must be calculated so that:
CrvSatn
B× -C > 0
100 (Equation 53)
The details of the different inverse time characteristics are shown in chapter "Inverse
characteristics".
Trip signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves for
the inverse time mode (IDMT). If the start condition, with respect to the measured
voltage ceases during the delay time, and is not fulfilled again within a user defined
reset time (tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for the
inverse time) the corresponding start output is reset, after that the defined reset time
has elapsed. Here it should be noted that after leaving the hysteresis area, the start
condition must be fulfilled again and it is not sufficient for the signal to only return
back to the hysteresis area. It is also remarkable that for the overvoltage function the
IDMT reset time is constant and does not depend on the voltage fluctuations during
the drop-off period. However, there are three ways to reset the timer, either the timer
is reset instantaneously, or the timer value is frozen during the reset time, or the timer
value is linearly decreased during the reset time. See figure 126 and figure 127.
tReset
1
tReset1
Voltage
START
TRIP
U1>
Hysteresis
Measured
Voltage
Time
START t1
TRIP
Time
Integrator Linear Decrease
Froozen Timer
t1
Instantaneous Time
Reset en05000019.vsd
Figure 126: Voltage profile not causing a reset of the start signal for step 1, and definite time delay
tReset1
Voltage tReset1
START TRIP
START
Hysteresis
U1>
Measured Voltage
Time
START t1
TRIP
Time Integrator
Froozen Timer
t1
Time
Instantaneous
Linear Decrease en05000020.vsd
Reset
Figure 127: Voltage profile causing a reset of the start signal for step 1, and definite time delay
7.3.2.3 Blocking
The residual overvoltage function can be partially or totally blocked, by binary input
signals where:
7.3.2.4 Design
ST2
Comparator Phase 1
UN > U2> TR2
Start
START &
Trip START
Output OR
Time integrator
Logic
t2 TRIP
tReset2
Step 2
ResetTypeCrv2 TRIP
OR
en05000748.vsd
en05000327.vsd
Table 135: Input signals for the R2POVM_59N (TRV1-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
BLKTR1 Block of operate signal, step 1
BLKST1 Block of step 1
BLKTR2 Block of operate signal, step 2
BLKST2 Block of step 2
Table 136: Output signals for the R2POVM_59N (TRV1-) function block
Signal Description
TRIP Operate signal
TR1 Operate signal for step 1
TR2 Operate signal for step 2
START Start signal
ST1 Start signal for step 1
ST2 Start signal for step 2
Table 137: Parameter group settings for the R2POVM_59N (TRV1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage, phase-
phase in kV
Characterist1 Definite time - Definite time - Operation
Inverse curve A characteristic
Inverse curve B selection, step 1
Inverse curve C
Prog. inv. curve
U1> 1 - 200 1 30 %UB Voltage setting/start
val (DT & IDMT), step
1 in % of UBase
t1 0.000 - 60.000 0.001 5.000 s Operate time delay in
DT mode, step 1.
tReset1 0.000 - 60.000 0.001 0.025 s Time delay in DT
reset (s), step 1
t1Min 0.000 - 60.000 0.001 5.000 s Minimum operate
time in IDMT mode
(s), step 1
ResetTypeCrv1 Instantaneous - Instantaneous - IDMT mode reset type
Frozen timer selector, step 1
Linearly
decreased
tIReset1 0.000 - 60.000 0.001 0.025 s Time delay in IDMT
reset (s), step 1
k1 0.05 - 1.10 0.01 0.05 - Time multiplier in
IDMT mode, step 1
ACrv1 0.005 - 200.000 0.001 1.000 - Setting A for
programmable over
voltage IDMT curve,
step 1
BCrv1 0.50 - 100.00 0.01 1.00 - Setting B for
programmable over
voltage IDMT curve,
step 1
CCrv1 0.0 - 1.0 0.1 0.0 - Setting C for
programmable over
voltage IDMT curve,
step 1
DCrv1 0.000 - 60.000 0.001 0.000 - Setting D for
programmable over
voltage IDMT curve,
step 1
PCrv1 0.000 - 3.000 0.001 1.000 - Setting P for
programmable over
voltage IDMT curve,
step 1
CrvSat1 0 - 100 1 0 % Tuning param for
prog. over voltage
IDMT curve, step 1
HystAbs1 0.0 - 100.0 0.1 0.5 %UB Absolute hysteresis in
% of UBase, step 1
Table continued on next page
7.4.1 Introduction
When the laminated core of a power transformer is subjected to a magnetic flux
density beyond its design limits, stray flux will flow into non-laminated components
not designed to carry flux and cause eddy currents to flow. The eddy currents can
cause excessive heating and severe damage to insulation and adjacent parts in a
relatively short time.
Modern design transformers are more sensitive to overexcitation than earlier types.
This is a result of the more efficient designs and designs which rely on the
improvement in the uniformity of the excitation level of modern systems. Thus, if
E = 4.44 × f × n × B max × A
(Equation 54)
V E¤f
M = relative æè -------öø = ------------------------
Hz ( Ur ) ¤ ( fr )
(Equation 55)
The IEC 60076 - 1 standard requires that transformers shall be capable of operating
continuously at 10% above rated voltage at no load, and rated frequency. At no load,
the ratio of the actual generator terminal voltage to the actual frequency should not
exceed 1.1 times the ratio of transformer rated voltage to the rated frequency on a
sustained basis, see equation 56.
---- £ 1.1 × Ur
E ------
f fr
(Equation 56)
E V/Hz>
---- £ ---------------------
f fr (Equation 57)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz> is an OEX setting parameter. The setting range is 1.0 pu to 1.5 pu. If the user
does not know exactly what to set, then the standard IEC 60076 - 1, section 4.4, the
default value V/Hz> = 1.10 pu shall be used.
V E¤f
M = relative æè -------öø = --------------
Hz Ur ¤ fr
(Equation 58)
It is clear from the above formula that, for an unloaded power transformer, M = 1 for
any E and f, where the ratio E / f is equal to Ur / fr. A power transformer is not
overexcited as long as the relative excitation is M ≤ V/Hz>, V/Hz> expressed in pu.
The relative overexcitation is thus defined as shown in equation 59.
As an example, at a transformer with a 15% short circuit impedance Xsc, the full load,
0.8 power factor, 105% voltage on the load side, the actual flux level in the transformer
core, will not be significantly different from that at the 110% voltage, no load, rated
frequency, provided that the short circuit impedance X can be equally divided
between the primary and the secondary winding: Xleak = Xleak1 = Xleak2 = Xsc /
2 = 0.075 pu..
OEX calculates the internal induced voltage E if Xleak (meaning the leakage
reactance of the winding where OEX is connected) is known to the user. The
assumption taken for 2-winding power transformers that Xleak = Xsc / 2 is
unfortunately most often not true. For a 2-winding power transformer the leakage
reactances of the two windings depend on how the windings are located on the core
with respect to each other. In the case of three-winding power transformers the
situation is still more complex. If a user has the knowledge on the leakage reactance,
then it should applied. If a user has no idea about it, Xleak can be set to Xc/2. The
OEX protection will then take the given measured terminal voltage U, as the induced
voltage E.
If one phase-to-phase voltage is available from the side where OEX protection is
applied, then OEX protection function block shall be set to measure this voltage,
MeasuredU. The particular voltage which is used determines the two currents that
must be used. If, for example, voltage Uab is fed to OEX, then currents Ia, and Ib
must be applied, etc. From these two input currents, current Iab = Ia - Ib is calculated
internally by the OEX protection algorithm. The phase-to-phase voltage must be
higher than 70% of the rated value, otherwise the OEX protection algorithm is exited
without calculating the excitation. ERROR output is set to 1, and the displayed value
of relative excitation V / Hz shows 0.000.
If three phase-to-earth voltages are available from the side where OEX is connected,
then OEX protection function block shall be set to measure positive sequence voltage.
In this case the positive sequence voltage and the positive sequence current are used
by OEX protection. A check is made within OEX protection if the positive sequence
voltage is higher than 70% rated phase-to-earth voltage; below this value, OEX is
exited immediately, and no excitation is calculated. ERROR output is set to 1, and
the displayed value of relative excitation V / Hz shows 0.000.
The frequency value is received from the pre-processing block. The function is in
operation for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 and
60 Hz respectively.
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They
can match well a transformer core capability.
0.18 × k 0.18 × k
t o p = --------------------------------------------- = ----------------------------------------
2 2
( M – V/Hz> ) overexcitation (Equation 60)
where:
M is excitation, mean value in the interval from t = 0 to t = top
V/Hz> is maximum continuously allowed voltage at no load, and rated frequency, in pu and
k is time multiplier setting for inverse time functions, see figure 131.
Parameter k (“time multiplier setting”) selects one delay curve from the family of curves.
t op
2
ò ( M(t) – V/Hz> ) dt ³ 0.18 × k
0 (Equation 61)
A digital, numerical relay will instead look for the lowest j (i.e. j = n) where it becomes
true that:
n
2
Dt × å ( M(j) – V/Hz> ) ³ 0.18 × k
j=k (Equation 62)
where:
Dt is the time interval between two successive executions of overexcitation function and
M(j) - V/Hz> is the relative excitation at (time j) in excess of the normal (rated) excitation which is given
as Ur/fr.
As long as M > V/Hz> (i.e. overexcitation condition), the above sum can only be
larger with time, and if the overexcitation persists, the protected transformer will be
tripped at j = n.
Inverse delays as per figure 131, can be modified (limited) by two special definite
delay settings, namely tMax and tMin, see figure 130.
delay in s
tMax
overexcitation
tMin
0 Mmax - V/Hz> Overexcitation M-V/Hz>
99001067.vsd
A definite maximum time, tMax, can be used to limit the operate time at low degrees
of overexcitation. Inverse delays longer than tMax will not be allowed. In case the
inverse delay is longer than tMax, OEX trips after tMax seconds.
A definite minimum time, tMin, can be used to limit the operate time at high degrees
of overexcitation. In case the inverse delay is shorter than tMin, OEX function trips
after tMin seconds. Also, the inverse delay law is no more valid beyond excitation
Mmax. Beyond Mmax (beyond overexcitation Mmax - V/Hz>), the delay will always
be tMin, no matter what overexcitation.
1000
100
k = 60
k = 20
k = 10
10 k=9
k=8
k=7
k=6
k=5
k=4
k=3
k=2
k=1
1
1 2 3 4 5 10 20 30 40
OVEREXCITATION IN % (M-Emaxcont)*100)
en01000373.vsd
The critical value of excitation Mmax is determined indirectly via OEX protection
function setting V/Hz>>. V/Hz>> can be thought of as a no-load-rated-frequency
voltage, where the inverse law should be replaced by a short definite delay, tMin. If,
for example, V/Hz>> = 1.40 pu, then Mmax is according to equation 63.
(V/Hz>>) ¤ f
Mmax = -------------------------
- = 1.40
Ur ¤ fr
(Equation 63)
The Tailor-Made law allows a user to design an arbitrary delay characteristic. In this
case the interval between M = V/Hz>, and M = Mmax is automatically divided into
five equal subintervals, with six delays. (settings t1, t2, t3, t4, t5, and t6) as shown in
the figure 132. These times should be set so that t1 => t2 => t3 => t4 => t5 => t6.
delay in s
tMax
under- tMin
excitation Overexcitation M-Emaxcont
0 Mmax - Emaxcont Excitation M
Emaxcont Mmax
99001068.vsd
Delays between two consecutive points, for example t3 and t4, are obtained by linear
interpolation.
Should it happen that tMax be lower than, for example, delays t1, and t2, the actual
delay would be tMax. Above Mmax, the delay can only be tMin.
7.4.2.3 Cooling
A service value data item called Time to trip, and designated on the display by tTRIP
is available in seconds on the local HMI, or monitoring tool. This value is an
estimation of the remaining time to trip if the overexcitation remained on the level it
had when the estimation was done. This information can be useful with small or
moderate overexcitations. If the overexcitation is so low that the valid delay is
tMax, then the estimation of the remaining time to trip is done against tMax.
V E¤f
M = relative æ -------ö = --------------
è Hzø Uf ¤ fr
(Equation 64)
If less than V / Hz = V/Hz> (in pu) is shown on the HMI display (or read via SM/
RET521), the power transformer is underexcited. If the value of V/Hz is shown which
is equal to V/Hz> (in pu), it means that the excitation is exactly equal to the power
transformer continuous capability. If a value higher than the value of V/Hz> is shown,
the protected power transformer is overexcited. For example, if V/Hz = 1.100 is
shown, while V/Hz> = 1.1 pu, then the power transformer is exactly on its maximum
continuous excitation limit.
The third item of the OEX protection service report is the thermal status of the
protected power transformer iron core, designated on the display by ThermalStatus.
This gives the thermal status in % of the trip value which corresponds to 100%.
Thermal Status should reach 100% at the same time, when tTRIP reaches 0 seconds.
If the protected power transformer is then for some reason not switched off, the
ThermalStaus shall go over 100%.
If the delay as per IEEE law, or Tailor-made Law, is limited by tMax, and/or TMin,
then the Thermal Status will generally not reach 100% at the same time, when tTRIP
reaches 0 seconds. For example, if, at low degrees of overexcitation, the very long
delay is limited by tMax, then the OEX TRIP output signal will be set to 1 before the
Thermal status reaches 100%.
A separate step, AlarmLevel, is provided for alarming purpose. The voltages are
normally set 2% lower and has a definite time delay, tAlarm. This will give the
operator an early abnormal voltages warning.
Simplification of the diagram is in the way the IEEE and Tailor-made delays are
calculated. The cooling process is not shown. It is not shown that voltage and
frequency are separately checked against their respective limit values.
en05000329.vsd
Table 139: Input signals for the OEXPVPH (OEX1-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK External block
RESET Reset operation
Table 140: Output signals for the OEXPVPH (OEX1-) function block
Signal Description
ERROR General function error
TRIP Trip from overexcitation function
START Overexcitation above set operate level (instantaneous)
ALARM Overexcitation above set alarm level (delayed)
Table 141: Parameter group settings for the OEXPVPH (OEX1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base current (rated
phase current)
UBase 0.05 - 2000.00 0.05 400.00 kV Base voltage (main
voltage) in kV
MeasuredU Ph-Ph - Ph-Ph - Input voltage
Pos Seq selection (pos. seq/
one phase-to-phase)
Table continued on next page
(0.18 × k )
IEEE : t =
( M - 1) 2
8.1.1 Introduction
Underfrequency occurs as a result of lack of generation in the network.
The function can be used for load shedding systems, remedial action schemes, gas
turbine start-up etc.
The function is provided with an undervoltage blocking. The operation may be based
on single phase, phase-to-phase or positive sequence voltage measurement.
To avoid oscillations of the output start signal, a hysteresis has been included, see
section "Inverse characteristics".
The time delay for the underfrequency function can be either a settable definite time
delay or a voltage magnitude dependent time delay, where the time delay depends on
the voltage level; a high voltage level gives a longer time delay and a low voltage
level causes a short time delay. For the definite time delay, the setting tTrip sets the
time delay, see figure 135and figure 136. For the voltage dependent time delay the
measured voltage level and the settings UNom, UMin, Exponent, tMax and tMin set
the time delay according to figure 137 and equation 66. The setting
TimerOperation is used to decide what type of time delay to apply. The output
STARTDUR, gives the time elapsed from the issue of the start output, in percent of
the total operation time available in PST.
Trip signal issuing requires that the underfrequency condition continues for at least
the user set time delay. If the start condition, with respect to the measured frequency
ceases during the delay time, and is not fulfilled again within a user defined reset
time, tReset, the start output is reset, after that the defined reset time has elapsed. Here
it should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the hysteresis
area.
On the output of the underfrequency function a 100 ms pulse is issued, after a time
delay corresponding to the setting of TimeDlyRestore, when the measured frequency
returns to the level corresponding to the setting RestoreFreq.
tReset
tReset
Frequency
START
Hysteresis Measured
TRIP Frequency
StartFrequency
Time
START tTRip
TRIP
Time Integrator
tTrip
Time
en05000721.vsd
Figure 135: Frequency profile not causing a reset of the start signal
tReset
Frequency tReset
START START Hysteresis Measured
TRIP Frequency
StartFrequency
Time
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000723.vsd
Since the fundamental frequency in a power system is the same all over the system,
except some deviations during power oscillations, another criterion is needed to
decide, where to take actions, based on low frequency. In many applications the
voltage level is very suitable, and in most cases is load shedding preferable in areas
with low voltage. Therefore, a voltage dependent time delay has been introduced, to
make sure that load shedding, or other actions, take place at the right location. At
constant voltage, U, the voltage dependent time delay is calculated according to
equation 66. At non-constant voltage, the actual time delay is integrated in a similar
way as for the inverse time characteristic for the undervoltage and overvoltage
functions.
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû (Equation 66)
where:
t is the voltage dependent time delay (at constant voltage),
UMin = 90%
UNom = 100%
tMax = 1.0 s
tMin = 0.0 s
Exponent = 0, 1, 2, 3 and 4
1
0
1
Exponenent
TimeDlyOperate [s]
2
3
0.5 4
0
90 95 100
U [% of UBase]
en05000075.vsd
8.1.2.4 Blocking
If the measured voltage level decreases below the setting of IntBlkStVal, both the start
and the trip outputs, are blocked.
8.1.2.5 Design
Block
BLOCK BLKDMAGN
OR
Comparator
U < IntBlockLevel
TimeDlyReset TRIP
100 ms
Comparator RESTORE
TimeDlyRestore
f > RestoreFreq
en05000726.vsd
en05000326.vsd
Table 143: Input signals for the SAPTUF_81 (TUF1-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
BLKTRIP Blocking operate output.
BLKREST Blocking restore output.
Table 144: Output signals for the SAPTUF_81 (TUF1-) function block
Signal Description
TRIP Operate/trip signal for frequency.
START Start/pick-up signal for frequency.
RESTORE Restore signal for load restoring purposes.
BLKDMAGN Blocking indication due to low amplitude.
Table 145: Basic parameter group settings for the SAPTUF_81 (TUF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV.
StartFrequency 35.00 - 75.00 0.01 48.80 Hz Frequency setting/
start value.
tTrip 0.000 - 60.000 0.001 0.200 s Operate time delay.
TimeDlyRestore 0.000 - 60.000 0.001 0.000 s Restore time delay.
RestoreFreq 45.00 - 65.00 0.01 50.10 Hz Restore frequency
level after operation.
TimerOperation Definite timer - Definite timer - Setting for choosing
Volt based timer timer mode.
UNom 50 - 150 1 100 %UB Nominal voltage in %
of UBase for voltage
based timer.
UMin 50 - 150 1 90 %UB Lower operation limit
in % of UBase for
voltage based timer.
Table continued on next page
Table 146: Advanced parameter group settings for the SAPTUF_81 (TUF1-) function
Parameter Range Step Default Unit Description
IntBlkStVal 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
tReset 0.000 - 60.000 0.001 0.000 s Time delay for reset.
8.2.1 Introduction
Overfrequency will occur at sudden load drops or shunt faults in the power network.
In some cases close to generating part governor problems can also cause
overfrequency.
The function can be used for generation shedding, remedial action schemes etc. It can
also be used as a sub-nominal frequency stage initiating load restoring.
The function is provided with an undervoltage blocking. The operation may be based
on single phase, phase-to-phase or positive sequence voltage measurement.
set value for a time period corresponding to the chosen time delay, the corresponding
trip signal is issued. To avoid an unwanted trip due to uncertain frequency
measurement at low voltage magnitude, a voltage controlled blocking of the function
is available, i.e. if the voltage is lower than the set blocking voltage the function is
blocked and no start or trip signal is issued.
The time delay for the overfrequency function is a settable definite time delay,
specified by the setting tTrip, see figure 140 and figure 141. The output STARTDUR,
gives the time elapsed from the issue of the start output, in percent of the total
operation time available in PST.
Trip signal issuing requires that the overfrequency condition continues for at least the
user set time delay. If the start condition, with respect to the measured frequency
ceases during the delay time, and is not fulfilled again within a user defined reset
time, tReset, the start output is reset, after that the defined reset time has elapsed. Here
it should be noted that after leaving the hysteresis area, the start condition must be
fulfilled again and it is not sufficient for the signal to only return back to the hysteresis
area.
tReset
tReset
Frequency
START
TRIP
StartFrequency
Hysteresis Measured
Frequency
Time
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000732.vsd
Figure 140: Frequency profile not causing a reset of the start signal
tReset
Frequency tReset
START START TRIP
Hysteresis
StartFrequency
Measured
Frequency
Time
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000733.vsd
8.2.2.3 Blocking
The overfrequency function can be partially or totally blocked, by binary input signals
or by parameter settings, where:
If the measured voltage level decreases below the setting of IntBlkStVal, both the start
and the trip outputs, are blocked.
8.2.2.4 Design
power system. The time integrator operates due to a definite delay time. The design
of the overfrequency function is schematically described in figure 142.
BLOCK
BLKTRIP BLOCK
OR BLKDMAGN
Comparator
U < IntBlockLevel
Start
&
Trip
Voltage Time integrator Output
Logic
Definite Time Delay START START
Frequency Comparator
f > StartFrequency TimeDlyOperate
TRIP
TimeDlyReset
TRIP
en05000735.vsd
en05000325.vsd
Table 147: Input signals for the SAPTOF_81 (TOF1-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
BLKTRIP Blocking operate output.
Table 148: Output signals for the SAPTOF_81 (TOF1-) function block
Signal Description
TRIP Operate/trip signal for frequency.
START Start/pick-up signal for frequency.
BLKDMAGN Blocking indication due to low amplitude.
Table 149: Parameter group settings for the SAPTOF_81 (TOF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV.
StartFrequency 35.00 - 75.00 0.01 51.20 Hz Frequency setting/
start value.
IntBlkStVall 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
tTrip 0.000 - 60.000 0.001 0.000 s Operate time delay.
tReset 0.000 - 60.000 0.001 0.000 s Time delay for reset.
8.3.1 Introduction
Rate of change of frequency function gives an early indication of a main disturbance
in the system.
The function can be used for generation shedding, load shedding, remedial action
schemes etc.
The function is provided with an undervoltage blocking. The operation may be based
on single phase, phase-to-phase or positive sequence voltage measurement.
To avoid oscillations of the output start signal, a hysteresis has been included, see
section "Inverse characteristics".
The rate-of-change of frequency function has a settable definite time delay, tTrip.
The output STARTDUR, gives the time elapsed from the issue of the start output, in
percent of the total operation time.
Trip signal issuing requires that the rate-of-change of frequency condition continues
for at least the user set time delay, tTrip. If the start condition, with respect to the
measured frequency ceases during the delay time, and is not fulfilled again within a
user defined reset time, tReset, the start output is reset, after that the defined reset
time has elapsed. Here it should be noted that after leaving the hysteresis area, the
start condition must be fulfilled again and it is not sufficient for the signal to only
return back into the hysteresis area, see figure 144-147.
The RESTORE output of the rate-of-change of frequency function is set, after a time
delay equal to the setting of tRestore, when the measured frequency has returned to
the level corresponding to RestoreFreq, after an issue of the TRIP output signal. If
tRestore is set to 0.000 s the restore functionality is disabled, and no output will be
given. The restore functionality is only active for lowering frequency conditions and
the restore sequence is disabled if a new negative frequency gradient is detected
during the restore period, defined by the settings RestoreFreq and tRestore.
Rate-of-Change
of Frequency
Time
tReset
tReset
Measured Rate-of-
START Change of Frequency
Hysteresis
TRIP
StartFreqGrad
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000727.vsd
Figure 144: Rate-of-change of frequency profile, set for frequency decrease conditions, not causing a reset of
the start signal
Rate-of-Change
of Frequency
Time
tReset
tReset
START START Measured
Hysteresis Rate-of-Change
TRIP of Frequency
StartFreqGrad
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000728.vsd
Figure 145: Frequency profile, set for frequency decrease conditions, causing a reset of the start signal
tReset
Rate-of-Change
of Frequency tReset
START
TRIP
StartFreqGrad
Measured Rate-of-
Hysteresis
Change of Frequency
Time
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000729.vsd
Figure 146: Rate-of-change of frequency profile, set for frequency increase conditions, not causing a reset of
the start signal
Rate-of-Change
of Frequency tReset
tReset
START START TRIP
Hysteresis
StartFreqGrad
Measured
Rate-of-Change
of Frequency
Time
START tTrip
TRIP
Time Integrator
tTrip
Time
en05000730.vsd
Figure 147: Frequency profile, set for frequency increase conditions, causing a reset of the start signal
8.3.2.3 Blocking
If the measured voltage level decreases below the setting of IntBlockLevel, both the
start and the trip outputs, are blocked.
8.3.2.4 Design
BLOCK
BLKTRIP
BLKRESET BLOCK
OR
Start
Rate-of-Change Time integrator &
Comparator
of Frequency Trip
If
Definite Time Delay Output
[StartFreqGrad<0 START START
Logic
AND
TimeDlyOperate
df/dt < StartFreqGrad]
OR
TimeDlyReset
[StartFreqGrad>0
AND
TRIP
df/dt > StartFreqGrad]
Then
START
100 ms
en05000835.vsd
en05000322.vsd
Table 150: Input signals for the SAPFRC_81 (RCF1-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
BLKTRIP Blocking operate output.
BLKREST Blocking restore output.
Table 151: Output signals for the SAPFRC_81 (RCF1-) function block
Signal Description
TRIP Operate/trip signal for frequencyGradient
START Start/pick-up signal for frequencyGradient
RESTORE Restore signal for load restoring purposes.
BLKDMAGN Blocking indication due to low amplitude
Table 152: Parameter group settings for the SAPFRC_81 (RCF1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for the
phase-phase voltage
in kV
StartFreqGrad -10.00 - 10.00 0.01 0.50 Hz/s Frequency gradient
start value. Sign
defines direction.
IntBlockLevel 0 - 100 1 50 %UB Internal blocking level
in % of UBase.
Table continued on next page
I< I>
U< U>
9.1.1 Introduction
The function can be utilized as a negative sequence current protection detecting
unsymmetrical conditions such as open phase or unsymmetrical faults.
The function can also be used to improve phase selection for high resistive earth faults,
outside the distance protection reach, for the transmission line. Three functions are
used which measures the neutral current and each of the three phase voltages. This
will give an independence from load currents and this phase selection will be used in
conjunction with the detection of the earth fault from the directional earth fault
protection function.
The function is always connected to three-phase current and three-phase voltage input
in the configuration tool, but it will always measure only one current and one voltage
quantity selected by the end user in the setting tool.
The user can select to measure one of the current quantities shown in table 154.
11 Phase2-Phase3 GF function will measure the current phasor internally calculated as the
vector difference between the phase L2 current phasor and phase L3
current phasor (i.e. IL2-IL3)
12 Phase3-Phase1 GF function will measure the current phasor internally calculated as the
vector difference between the phase L3 current phasor and phase L1
current phasor (i.e. IL3-IL1)
13 MaxPh-Ph GF function will measure ph-ph current phasor with the maximum
magnitude
14 MinPh-Ph GF function will measure ph-ph current phasor with the minimum
magnitude
15 UnbalancePh-Ph GF function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
ph-ph current phasor with maximum magnitude and ph-ph current phasor
with minimum magnitude. Phase angle will be set to 0° all the time
The user can select to measure one of the voltage quantities shown in table 155:
11 Phase2-Phase3 GF function will measure the voltage phasor internally calculated as the
vector difference between the phase L2 voltage phasor and phase L3
voltage phasor (i.e. UL2-UL3)
12 Phase3-Phase1 GF function will measure the voltage phasor internally calculated as the
vector difference between the phase L3 voltage phasor and phase L1
voltage phasor (i.e. UL3-UL1)
13 MaxPh-Ph GF function will measure ph-ph voltage phasor with the maximum
magnitude
14 MinPh-Ph GF function will measure ph-ph voltage phasor with the minimum
magnitude
15 UnbalancePh-Ph GF function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
ph-ph voltage phasor with maximum magnitude and ph-ph voltage
phasor with minimum magnitude. Phase angle will be set to 0° all the time
It is important to notice that the voltage selection from table 155 is always applicable
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-ground voltages UL1, UL2 & UL3 or three
phase-to-phase voltages UL1L2, UL2L3 & UL3L1). This information about actual VT
connection is entered as a setting parameter for the pre-processing block, which will
then take automatic care about it.
The user can select one of the current quantities shown in table 156 for built-in current
restraint feature:
The parameter settings for the base quantities, which represent the base (i.e. 100%)
for pickup levels of all measuring stages shall be entered as setting parameters for
every GF function.
1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table 154.
2. rated phase current of the protected object in primary amperes multiplied by √3
(i.e. 1,732 x Iphase), when the measured Current Quantity is selected from 10 to
15, as shown in table 154.
1. rated phase-to-ground voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 155.
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 155.
Two overcurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overcurrent step simply compares the magnitude of the measured current quantity
(see table 154) with the set pickup level. Non-directional overcurrent step will pickup
if the magnitude of the measured current quantity is bigger than this set level. Reset
ratio is settable, with default value of 0.96. However depending on other enabled
built-in features this overcurrent pickup might not cause the overcurrent step start
signal. Start signal will only come if all of the enabled built-in features in the
overcurrent step are fulfilled at the same time.
This feature will simple prevent overcurrent step start if the second-to-first harmonic
ratio in the measured current exceeds the set level.
Directional feature
The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 154) and measured
voltage phasor (see table 155). In protection terminology it means that the PGPF
function can be made directional by enabling this built-in feature. In that case
overcurrent protection step will only operate if the current flow is in accordance with
the set direction (i.e. Forward, which means towards the protected object, or
Reverse, which means from the protected object). For this feature it is of the outmost
importance to understand that the measured voltage phasor (see table 155) and
measured current phasor (see table 154) will be used for directional decision.
Therefore it is the sole responsibility of the end user to select the appropriate current
and voltage signals in order to get a proper directional decision. The PGPF function
will NOT do this automatically. It will just simply use the current and voltage phasors
selected by the end user to check for the directional criteria.
Table 157 gives an overview of the typical choices (but not the only possible ones)
for these two quantities for traditional directional relays.
Table 157: Typical current and voltage choices for directional feature
Set value for the Set value for the
parameter CurrentInput parameter Comment
VoltageInput
PosSeq PosSeq Directional positive sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to -90°
depending on the power
NegSeq -NegSeq Directional negative sequence overcurrent function is
obtained. Typical setting for RCADir is from -45° to -90°
depending on the power system voltage level (i.e. X/R
ratio)
3ZeroSeq -3ZeroSeq Directional zero sequence overcurrent function is
obtained. Typical setting for RCADir is from 0° to -90°
depending on the power system earthing (i.e. solidly
earthed, earthed via resistor, etc.)
Phase1 Phase2-Phase3 Directional overcurrent function for the first phase is
obtained. Typical setting for RCADir is +30° or +45°
Phase2 Phase3-Phase1 Directional overcurrent function for the second phase
is obtained. Typical setting for RCADir is +30° or +45°
Phase3 Phase1-Phase2 Directional overcurrent function for the third phase is
obtained. Typical setting for RCADir is +30° or +45°
Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
• the magnitude of the measured current is bigger than the set pick-up level
• the phasor of the measured current is within the operating region (defined by the
relay operate angle, ROADir parameter setting; see figure 150).
U=-3U0
RCADir
Operate region
mta line
en05000252.vsd
where:
RCADir is -75°
ROADir is 50°
The second principle, referred to as "IcosPhi&U" in the parameter setting tool, checks
that:
• that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
• that the phasor of the measured current is within the operating region (defined
by the I·cos(Φ) straight line and the relay operate angle, ROADir parameter
setting; see figure 150).
U=-3U0
RCADir
Operate region
mta line
en05000253.vsd
where:
RCADir is -75°
ROADir is 50°
Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the pre-
set value. User can select one of the following three options:
It shall also be noted that the memory duration is limited in the algorithm to 100 ms.
After that time the current direction will be locked to the one determined during
memory time and it will re-set only if the current fails below set pickup level or voltage
goes above set voltage memory limit.
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
ULowLimit_OC1 UHighLimit_OC1
Selected Voltage
Magnitude
en05000324.vsd
Figure 152: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Slope mode of operation
StartCurr_OC1
VDepFact_OC1 * StartCurr_OC1
en05000323.vsd
Figure 153: Example for OC1 step current pickup level variation as function of
measured voltage magnitude in Step mode of operation
This feature will simple change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will
as well affect the pickup current value for calculation of operate times for IDMT
curves (i.e. overcurrent with IDMT curve will operate faster during low voltage
conditions).
IMeasured
ea ain
ar tr
te es
ra *I r
pe eff
O t rCo
es
I>R
IsetHigh
IsetLow
atan(RestrCoeff)
Restraint
en05000255.vsd
This feature will simple prevent overcurrent step to start if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for
calculation of operate times for IDMT curves. This means that the IDMT curve
operate time will not be influenced by the restrain current magnitude.
When set, the start signal will start definite time delay or inverse (i.e. IDMT) time
delay in accordance with the end user setting. If the start signal has value one for
longer time than the set time delay, the overcurrent step will set its trip signal to one.
Reset of the start and trip signal can be instantaneous or time delay in accordance
with the end user setting.
Two undercurrent protection steps are available. They are absolutely identical and
therefore only one will be explained here. Undercurrent step simply compares the
magnitude of the measured current quantity (see table 154) with the set pickup level.
The undercurrent step will pickup and set its start signal to one if the magnitude of
the measured current quantity is smaller than this set level. The start signal will start
definite time delay with set time delay. If the start signal has value one for longer
time than the set time delay the undercurrent step will set its trip signal to one. Reset
of the start and trip signal can be instantaneous or time delay in accordance with the
setting.
Two overvoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Overvoltage step simply compares the magnitude of the measured voltage quantity
(see table 155) with the set pickup level. The overvoltage step will pickup if the
magnitude of the measured voltage quantity is bigger than this set level. Reset ratio
is settable, with default value of 0.99.
The start signal will start definite time delay or inverse (i.e. IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer time
than the set time delay, the overvoltage step will set its trip signal to one. Reset of the
start and trip signal can be instantaneous or time delay in accordance with the end
user setting.
Two undervoltage protection steps are available. They are absolutely identical and
therefore only one will be explained here.
Undervoltage step simply compares the magnitude of the measured voltage quantity
(see table 155 with the set pickup level. The undervoltage step will pickup if the
magnitude of the measured voltage quantity is smaller than this set level. Reset ratio
is settable, with default value of 1.01.
The start signal will start definite time delay or inverse (i.e. IDMT) time delay in
accordance with the end user setting. If the start signal has value one for longer time
than the set time delay, the undervoltage step will set its trip signal to one. Reset of
the start and trip signal can be instantaneous or time delay in accordance with the end
user setting.
The simplified internal logics, for the PGPF function are shown in the following
figures.
REx670
ADM PGPF function
Phasor calculation of
scaling with CT ratio
individual currents
A/D conversion
Phasors &
samples
the built-in protection Selected voltage
elements
Phasors &
samples
en05000169.vsd
Figure 155: Treatment of measured currents within IED for PGPF function
Figure 155 shows how internal treatment of measured currents is done for
multipurpose protection function
The following currents and voltages are inputs to the multipurpose protection
function. They must all be expressed in true power system (primary) Amperes and
kilovolts.
1. Selects one current from the three phase input system (see table "") for internally
measured current.
2. Selects one voltage from the three phase input system (see table "") for internally
measured voltage.
3. Selects one current from the three phase input system (see table "") for internally
measured restraint current.
CURRENT
UC1
nd TRUC1
2 Harmonic
Selected current restraint
STUC2
UC2
TRUC2
2nd Harmonic
restraint
STOC1
OC1 TROC1
STOC2
OC2 TROC2
2nd Harmonic
restraint
Current restraint ³1
UDIRLOW
Directionality DIROC2
Voltage control /
restraint
STOV1
OV1 TROV1
STOV2
OV2 TROV2
STUV1
Selected voltage
UV1 TRUV1
STUV2
UV2 TRUV2
VOLTAGE
en05000170.vsd
Figure 156: PGPF function main logic diagram for built in protection elements
1. The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its
START and TRIP output signals.
2. More detailed internal logic for every protection element is given in the following
four figures
3. Common START and TRIP signals from all built-in protection elements & steps
(internal OR logic) are available from multipurpose function as well.
Enable
second
harmonic Second
harmonic check
1 DEF time BLKTROC
selected DEF 1 TROC1
AND
OR
Selected current a
a>b
b
OC1=On STOC1
AND
StartCurr_OC1 BLKOC1
X
Inverse
Selected voltage
Current
Restraint
Feature
Selected restrain current Imeasured > k Irestraint
en05000831.vsd
Figure 157: Simplified internal logic diagram for built-in first overcurrent step i.e. OC1 (step OC2 has the same
internal logic)
Operation_UC1=On
STUC1
en05000750.vsd
Figure 158: Simplified internal logic diagram for built-in first undercurrent step i.e. UC1 (step UC2 has the same
internal logic)
Inverse
Operation_OV1=On
Inverse time
BLKOV1 selected
en05000751.vsd
Figure 159: Simplified internal logic diagram for built-in first overvoltage step i.e.OV1 (step OV2 has the same
internal logic)
Inverse
Operation_UV1=On
Inverse time
BLKUV1 selected
en05000752.vsd
Figure 160: Simplified internal logic diagram for built-in first undervoltage step i.e.UV1 (step UV2 has the same
internal logic)
en05000372.vsd
Table 158: Input signals for the CVGAPC (GF01-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
BLOCK Block of function
BLKOC1 Block of over current function OC1
BLKOC1TR Block of trip for over current function OC1
ENMLTOC1 When activated, the current multiplier is in use for OC1
BLKOC2 Block of over current function OC2
BLKOC2TR Block of trip for over current function OC2
ENMLTOC2 When activated, the current multiplier is in use for OC2
BLKUC1 Block of under current function UC1
BLKUC1TR Block of trip for under current function UC1
BLKUC2 Block of under current function UC2
BLKUC2TR Block of trip for under current function UC2
BLKOV1 Block of over voltage function OV1
BLKOV1TR Block of trip for over voltage function OV1
BLKOV2 Block of over voltage function OV2
BLKOV2TR Block of trip for over voltage function OV2
BLKUV1 Block of under voltage function UV1
BLKUV1TR Block of trip for under voltage function UV1
BLKUV2 Block of under voltage function UV2
BLKUV2TR Block of trip for under voltage function UV2
Table 159: Output signals for the CVGAPC (GF01-) function block
Signal Description
TRIP General trip signal
TROC1 Trip signal from overcurrent function OC1
TROC2 Trip signal from overcurrent function OC2
TRUC1 Trip signal from undercurrent function UC1
TRUC2 Trip signal from undercurrent function UC2
TROV1 Trip signal from overvoltage function OV1
TROV2 Trip signal from overvoltage function OV2
TRUV1 Trip signal from undervoltage function UV1
TRUV2 Trip signal from undervoltage function UV2
START General start signal
STOC1 Start signal from overcurrent function OC1
STOC2 Start signal from overcurrent function OC2
STUC1 Start signal from undercurrent function UC1
Table continued on next page
Signal Description
STUC2 Start signal from undercurrent function UC2
STOV1 Start signal from overvoltage function OV1
STOV2 Start signal from overvoltage function OV2
STUV1 Start signal from undervoltage function UV1
STUV2 Start signal from undervoltage function UV2
BLK2ND Block from second harmonic detection
DIROC1 Directional mode of OC1 (nondir, forward,reverse)
DIROC2 Directional mode of OC2 (nondir, forward,reverse)
UDIRLOW Low voltage for directional polarization
CURRENT Measured current value
ICOSFI Measured current multiplied with cos (Phi)
VOLTAGE Measured voltage value
UIANGLE Angle between voltage and current
Table 160: Basic parameter group settings for the CVGAPC (GF01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
CurrentInput phase1 - MaxPh - Select current signal
phase2 which will be
phase3 measured inside
PosSeq function
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
IBase 1 - 99999 1 3000 A Base Current
Table continued on next page
Table 161: Advanced parameter group settings for the CVGAPC (GF01-) function
Parameter Range Step Default Unit Description
CurrMult_OC1 2.0 0.1 1.0 - 10.0 - Multiplier for scaling
the current setting
value for OC1
ResCrvType_OC1 Instantaneous - Instantaneous - Selection of reset
IEC Reset curve type for OC1
ANSI reset
tResetDef_OC1 0.00 - 6000.00 0.01 0.00 s Reset time delay used
in IEC Definite Time
curve OC1
P_OC1 0.020 0.001 0.001 - 10.000 - Parameter P for
customer
programmable curve
for OC1
A_OC1 0.140 0.001 0.000 - 999.000 - Parameter A for
customer
programmable curve
for OC1
B_OC1 0.000 0.001 0.000 - 99.000 - Parameter B for
customer
programmable curve
for OC1
C_OC1 1.000 0.001 0.000 - 1.000 - Parameter C for
customer
programmable curve
for OC1
PR_OC1 0.500 0.001 0.005 - 3.000 - Parameter PR for
customer
programmable curve
for OC1
Table continued on next page
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of Ubase ± 1.0% of Ur for U<Ur
± 1.0% of U for U>Ur
High and low voltage limit, (1.0 - 200.0)% of Ubase ± 1.0% of Ur for U<Ur
voltage dependent operation ± 1.0% of U for U>Ur
10.1.1 Introduction
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth fault current and negative
sequence current functions.
The current circuit supervision function compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
The FAIL output will be set to a logical one when the following criteria are fulfilled:
• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the
numerical value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the
set operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• The current circuit supervision is enabled by setting Operation = On.
The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms a ALARM will
be issued. In this case the FAIL and ALARM will remain activated 1 s after the AND-
gate resets. This prevents unwanted resetting of the blocking function when phase
current supervision element(s) operate, e.g. during a fault.
Figure 162: Simplified logic diagram for the current circuit supervision
| åI phase | - | I ref |
Slope = 1
Operation
Slope = 0.8
area
I MinOp
| åI phase | + | I ref |
99000068.vsd
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S
I phase | + | I ref | respectively, the slope can not be above 2.
en05000389.vsd
Table 163: Input signals for the CCSRDIF (CCS1-) function block
Signal Description
I3P Group signal for three phase current input
IREF TBD
BLOCK Block of function
Table 164: Output signals for the CCSRDIF (CCS1-) function block
Signal Description
FAIL Detection of current circuit failure
ALARM Alarm for current circuit failure
Table 165: Parameter group settings for the CCSRDIF (CCS1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A IBase value for
current level
detectors
Ip>Block 5 - 500 1 150 %IB Block of the function
at high phase current,
in % of IBase
IMinOp 5 - 200 1 20 %IB Minimum operate
current differential
level in % of IBase
10.2.1 Introduction
The aim of the fuse failure supervision function (FSD) is to block voltage measuring
functions at failures in the secondary circuits between the voltage transformer and
the IED in order to avoid unwanted operations that otherwise might occur.
The fuse failure supervision function basically has two different algorithms, negative
sequence and zero sequence based algorithm and an additional delta voltage and delta
current algorithm.
The negative sequence detection algorithm is recommended for IEDs used in isolated
or high-impedance earthed networks. It is based on the negative-sequence measuring
quantities, a high value of voltage 3·U2 without the presence of the negative-sequence
current 3·I2.
The zero sequence detection algorithm is recommended for IEDs used in directly or
low impedance earthed networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3·U0 without the presence of the residual current
3·I0.
A criterion based on delta current and delta voltage measurements can be added to
the fuse failure supervision function in order to detect a three phase fuse failure, which
in practice is more associated with voltage transformer switching during station
operations.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation
The function can be set in five different modes by setting the parameter OpMode.
The zero sequence function continuously measure the internal currents and voltages
in all three phases and calculate:
The measured signals are compared with their respective set values 3U0< and
3I0>.
The function enable the internal signal fuseFailDetected if the measured zero
sequence voltage is higher than the set value 3U0>, the measured zero sequence
current is below the set value 3I0< and the operation mode selector (OpMode is set
to 2 (zero sequence mode). This will activate the output signal BLKU, intended to
block voltage related protection functions in the IED. The output signal BLKZ will
be activated as well if not the internal dead line detection is activaded at the same
time.
If the fuseFailDetected signal is present for more than 5 seconds at the same time as
all phase voltages are below the set value UPh> and the setting parameter ISealIn is
set to On, the function will activate the output signals 3PH, BLKU and BLKZ. The
same signals will aslo be activated if all phase voltages are below the value UPh>,
SealIn=On and any of the phase voltages below the setting value for more than 5
seconds.
It is recommended to always set SealIn to On since this will secure that no unwanted
operation of fuse failure will occur at closing command of breaker when the line is
already energized from the other end. The system voltages shall be normal before
fuse failure is allowed to be activated and initiate block of different protection
functions.
The output signal BLKU can also be activated if no phase voltages is below the setting
UPh> for more than 60 seconds at the same time as the zero sequence voltage is
above the set value 3U0> for more than 5 seconds, all phase currents are below the
setting IDLD< (operate level for dead line detection) and the circuit breaker is closed
(input CBCLOSED is activated). This condition covers for fuse failure at open
breaker position.
Fuse failure condition is unlatched when the normal voltage conditions are restored.
Fuse failure condition is stored in the non volatile memory in the IED. In the new
start-up procedure the IED checks the stored value in its non volatile memory and
establishes the corresponding starting conditions.
TEST
TEST ACTIVE
AND
BlocFuse = Yes
BLOCK
OR
BLKTRIP
fufailStarted AND
OR
All UL less
than Uph>
3PH
AND
SealIn = On AND
5s
Any UL less AND
OR t
than Uph>
setLatch U I
BLKZ
200 ms AND
AND OR
deadLineCondition t
150 ms
MCBOP
t
60 sec
All UL> UPh> t
AND
UN > 3U0> for
t>5 s AND
en06000394.vsd
Figure 165: Simplified logic diagram for fuse failure supervision function, zero sequence based
The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to other
internal functions of the IED itself in order to receive a block command from internal
functions. Through OR gate it can be connected to both binary inputs and internal
function outputs.
The input BLKSP is intended to be connected to the trip output at any of the protection
functions included in the IED. When activated for more than 20 ms, the operation of
the fuse failure is blocked during a fixed time of 100 ms. The aim is to increase the
security against unwanted operations during the opening of the breaker, which might
cause unbalance conditions for which the fuse failure might operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-off time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input to
the N.C. auxiliary contact of the miniature circuit breaker protecting the VT secondary
circuit. The MCBOP signal sets the output signals BLKU and BLKZ in order to block
all the voltage related functions when the MCB is open independent of the setting of
OpMode selector. The additional drop-off timer of 150 ms prolongs the presence of
MCBOP signal to prevent the unwanted operation of voltage dependent function due
to non simultaneous closing of the main contacts of the miniature circuit breaker.
The input signal DISCPOS is supposed to be connected via a terminal binary input
to the N.C. auxiliary contact of the line disconnector. The DISCPOS signal sets the
output signal BLKU in order to block the voltage related functions when the line
disconnector is open. The impedance protection function is not affected by the
position of the line disconnector since there will be no line currents that can cause
maloperation of the distance protection. If DISCPOS=0 it signifies that the line is
connected to the system and when the DISCPOS=1 it signifies that the line is
disconnected from the system and the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check etc.) except for the impedance protection.
The function output BLKZ can be used for blocking the impedance protection
function.
The BLKZ will only be activated if not the internal dead line detection is activated
at the same time.
The fuse failure condition is unlatched when the normal voltage conditions are
restored.
When the output 3PH is activated, all three voltage are low.
The negative sequence operates in the same way as the zero sequence, but it calculates
the negative sequence component of current and voltage.
The function enable the internal signal fuseFailDetected if the measured negative
sequence voltage is higher than the set value 3U2>, the measured negative sequence
current is below the value 3I2< and the operation mode selector (OpMode) is set to
1 (negative sequence mode).
The delta function can be activated by setting the parameter OperationDUDI to On.
When it is selected On it operates in parallel with the sequence based algorithm.
The current and voltage is continuously measured in all three phases and the following
quantities are calculated:
The calculated delta quantities are compared with their respective set values DI< and
DU>.
The delta current and delta voltage algorithm, detects a fuse failure if a sufficient
negative change in voltage amplitude without a sufficient change in current amplitude
is detected in each phase separately. This check is performed if the circuit breaker is
closed. Information about the circuit breaker position is brought to the function input
CBCLOSED through a binary input of the IED.
There are two conditions for activating the internal STDU signal and set the latch:
The first criterion requires that the delta condition shall be fulfilled in any phase at
the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to bee an
important disadvantage, connect the CBCLOSED input to FALSE. In this way only
the second criterion can activate the delta function.
The second criterion means that detection of failure in one phase together with high
current for the same phase will set the latch. The measured phase current is used to
reduce the risk of false fuse failure detection. If the current on the protected line is
low, a voltage drop in the system (not caused by fuse failure) is not by certain followed
by current change and a false fuse failure might occur. To prevent that the phase
current criterion is introduced.
If the signal setLatchΔUΔI is set (see figure 165) and if all measured voltages are low
(lower than the setting UPh>) the output 3PH will be activated indicating fuse failure
in all three phases. The output BLKU and BLKZ will be activated as well.
If the signal setLatchΔUΔI is activated but not all three phases are below the setting
UPh> only BLKU will be activated.
The BLKZ will be activated as well if not the internal dead line detection is activated.
The fuse failure supervision function can be switched on or off by the setting
parameter Operation to On or Off.
• OMode = 3; Both negative and zero sequence is activated and working in parallel
in an OR-condition
• OpMode = 4; Both negative and zero sequence is activated and working in series
(AND-condition for operation)
• OpMode = 5; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be
activated).
The function input signal deadLineCondition (see figure 165) is related to the internal
dead line detection function. This signal is activated from the dead line condition
function when the voltage and the current in at least one phase is below their respective
setting values UDLD< and IDLD<. It prevents the blocking of the impedance
protection by a fuse failure detection during dead line condition (that occurs also
during single pole auto-reclosing). The 200 ms drop-off timer prolongs the dead line
condition after the line-energization in order to prevent the blocking of the impedance
protection for unequal pole closing.
en05000700.vsd
Table 167: Input signals for the SDDRFUF (FSD1-) function block
Signal Description
BLOCK Block of function
I3P Group signal for current input
U3P Group signal for voltage input
CBCLOSED Active when circuit breaker is closed
Table continued on next page
Signal Description
MCBOP Active when external MCB opens protected voltage circuit
DISCPOS Active when line disconnector is open
BLKSP Blocks operation of function when active
Table 168: Output signals for the SDDRFUF (FSD1-) function block
Signal Description
BLKZ Start of current and voltage controlled function
BLKU General start of function
3PH Three-phase start of function
Table 169: Parameter group settings for the SDDRFUF (FSD1-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base value for current
settings in A
UBase 0.05 - 2000.00 0.05 400.00 kV Base value for voltage
settings in kV
OpMode Off - UZsIZs - Operating mode
UNsINs selection
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 1 30 %UB Operate level of
residual overvoltage
element in % of
UBase
3I0< 1 - 100 1 10 %IB Operate level of
residual undercurrent
element in % of IBase
3U2> 1 - 100 1 30 %UB Operate level of neg
seq overvoltage
element in % of
UBase
3I2< 1 - 100 1 10 %IB Operate level of neg
seq undercurrent
element in % of IBase
OperationDUDI Off - Off - Operation of change
On based function Off/On
Table continued on next page
Section 11 Control
11.1.1 Introduction
The synchrocheck function checks that the voltages on both sides of the circuit breaker
are in synchronism, or with at least one side dead to ensure that closing can be done
safely.
The function includes a built-in voltage selection scheme for double bus and one- and
a half or ring busbar arrangements.
Manual closing as well as automatic reclosing can be checked by the function and
can have different settings, e.g. the allowed frequency difference can be set to allow
wider limits for the auto-reclose attempt than for the manual closing.
The synchronism check function measures the conditions across the circuit breaker
and compares them to set limits. The output is only given when all measured quantities
are simultaneously within their set limits.
The energizing check function measures the bus and line voltages and compares them
to both high and low threshold detectors. The output is only given when the actual
measured quantities match the set conditions.
For single circuit breaker and 1 1/2 circuit breaker arrangements, the SYN function
blocks have the capability to make the necessary voltage selection. For single circuit
breaker arrangements, selection of the correct voltage is made using auxiliary contacts
of the bus disconnectors. For 1 1/2 circuit breaker arrangements, correct voltage
selection is made using auxiliary contacts of the bus disconnectors as well as the
circuit breakers
The internal logic for each function block as well as the Input and Outputs and the
setting parameters with default setting and setting ranges is described in this
document. For application related information, please refer to the “Application
manual”.
The logic diagrams that follow illustrate the main principles of the Synchrocheck
function components such as Synchronism check, Energizing check and Voltage
selection, and are intended to simplify the understanding of the function.
Synchronism check
The voltage difference, frequency difference and phase angle difference values are
measured in the IED centrally and are available for the Synchrocheck function for
evaluation. If the bus voltage is connected as phase-phase and the line voltage as
phase-neutral (or the opposite), this need to be compensated. This is done with a
setting, which scales up the line voltage to a level equal to the bus voltage.
When the function is set to Operation = On, the measuring will start.
The function will compare the bus and line voltage values with the set values for
UHighBusSync and UHighLineSync.
If both sides are higher than the set values the measured values are compared with
the set values for acceptable frequency, phase angle and voltage difference FreqDiff,
PhaseDiff and UDiff. If a compensation factor is set due to the use of different voltages
on the Bus and Line, the factor is deducted from the line voltage before the comparison
of the phase angle values.
The frequency on both sides of the circuit breaker is also measured. The frequencies
must not deviate from the rated frequency more than +/-5Hz. The frequency
difference between the bus frequency and the line frequency is measured and may
not exceed the set value.
Two sets of settings for frequency difference and phase angle difference are available
and used for the Manual closing and Auto-Reclose functions respectively as required.
The inputs BLOCK and BLKSYNCH are available for total block of the complete
Synchrocheck function and block of the Synchronism check function respectively.
TSTAUTSY will allow testing of the function where the fulfilled conditions are
connected to a separate test output
Two outputs MANSYOK resp. AUTOSYOK are activated when the actual measured
conditions match the set conditions for the respective output. The output signal can
be delayed independently for MANSYOK conditions and for ARSYNOK.
Energizing check
Voltage values are measured in the IED centrally and are available for evaluation by
the Synchrocheck function. If the bus voltage is connected as phase-phase and the
line voltage as phase-neutral, (or the opposite) this needs to be compensated. This is
done with a setting, which scales the line voltage to a level equal to the bus voltage.
The function measures voltages on the busbar and the line to verify whether they are
live or dead. This is done by comparing with the set values UHighLineEnerg and
ULowLineEnerg for bus respectively line energizing.
The frequency on both sides of the circuit breaker is also measured. The frequencies
must not deviate from the rated frequency more than +/-5Hz. The frequency
difference between the bus frequency and the line frequency is measured and shall
not exceed a set value.
The Energizing direction can be selected individually for the Manual and the
Automatic functions respectively. When the conditions are met the outputs
AUTOENOK and MANENOK respectively will be activated if the fuse supervision
conditions are fulfilled. The output signal can be delayed independently for
MANENOK conditions and for AUTOENOK.
The inputs BLOCK and BLKENERG are available for total block of the complete
Synchrocheck function resp. block of the Energizing check function. TSTENOK will
allow testing of the function where the fulfilled conditions are connected to a separate
test output.
OperationSync = On
AND TSTSYNOK
AND
TSTSYNC AND
BLKSYNC AND
BLOCK OR
SYNOK
AND
AND
SelectedFuseOK
0-60 s
AND t
OR
tSync
0-60 s
AND t
AND
tSync2
UDiff 50 ms
AND t
UHighBusSync
UOK
AND
UHighLineSync
UDIFF
1
FRDIFFA
FreqDiffA 1
FRDIFFM
FreqDiffM 1
PHDIFFA
PhaseDiffA 1
PHDIFFM
PhaseDiffM 1
UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue
en05000790.vsd
Figure 167: Simplified logic diagram for the Synchronism check function
Voltage selection
The voltage selection module including supervision of included voltage transformer
fuses for the different arrangements is a basic part of the Synchrocheck function and
determines the parameters fed to the Synchronism check and Energizing check
functions. This includes the selection of the appropriate Line and Bus voltages and
fuse supervision.
The voltage selection type to be used is set with the parameter CBConfig. The
different alternatives are described below.
If NoVoltageSel is set the default voltages used will be ULine1 and UBus1. This is
also the case when external voltage selection is provided. Fuse failure supervision for
the used inputs must also be connected.
The voltage selection function selected voltages and fuse conditions are the
Synchronism check and Energizing check inputs.
For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts
to supply Disconnector Open and Closed positions but it is of course also possible to
use an inverter for one of the positions.
The function also checks the fuse-failure signals for bus 1, bus 2 and line voltage
transformers. Inputs UB1OK-UB1FF supervise the fuse for Bus 1. UB2OK-UB2FF
supervises the fuse for Bus 2 and ULNOK-ULNFF supervises the fuse for the Line
voltage transformer. The inputs fail (FF) or healthy (OK) can alternatively be used
dependent on the available signal. If a fuse-failure is detected in the selected voltage
source an output signal USELFAIL is set. This output signal is true if the selected
bus or line voltages have a fuse failure. This output as well as the function can be
blocked with the input signal BLOCK. The function logic diagram is shown in figure
168.
B1QOPEN
B1SEL
B1QCLD AND
B2QOPEN B2SEL
1
B2QCLD AND
AND invalidSelection
bus1Voltage
busVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
AND selectedFuseOK
UB2OK AND
UB2FF OR USELFAIL
AND
ULN1OK
ULN1FF OR
BLOCK
en05000779.vsd
Figure 168: Logic diagram for the voltage selection function of a single circuit
breaker with double busbars
This voltage selection function uses the binary inputs from the disconnectors and
circuit breakers auxiliary contacts to select the right voltage for the Synchrocheck
(Synchronism and Energizing check) function. For the bus circuit breaker one side
of the circuit breaker is connected to the busbar and the other side is connected either
to line 1, line 2 or the other busbar depending on the arrangement.
The tie circuit breaker is connected either to bus 1 or line 1 on one side and the other
side is connected either to bus 2 or line 2. Four different output combinations are
possible, bus to bus, bus to line, line to bus and line to line.
The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2. If
a fuse-failure is detected in the selected voltage an output signal USELFAIL is set.
This output signal is true if the selected bus or line voltages have a fuse failure. This
output as well as the function can be blocked with the input signal BLOCK.The
function block diagram for the voltage selection of a bus circuit breaker is shown in
169 and for the tie circuit breaker in 170
LN1QOPEN
AND
LN1SEL
LN1QCLD
B1QOPEN
LN2SEL
B1QCLD AND AND
OR
B2SEL
LN2QOPEN
LN2QCLD AND
AND invalidSelection
AND
B2QOPEN
B2QCLD AND
line1Voltage
lineVoltage
line2Voltage
bus2Voltage
UB1OK
UB1FF OR
OR
UB2OK AND
AND selectedFuseOK
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000780.vsd
Figure 169: Simplified logic diagram for the voltage selection function for a bus
circuit breaker in a 1 1/2 breaker arrangement.
LN1QOPEN
LN1SEL
LN1QCLD AND
B1SEL
1
B1QOPEN AND
AND
B1QCLD AND
line1Voltage
busVoltage
bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
OR invalidSelection
B2QOPEN AND
AND
B2QCLD AND
line2Voltage
lineVoltage
bus2Voltage
UB1OK AND
UB1FF OR
OR
UB2OK AND selectedFuseOK
AND
UB2FF OR
USELFAIL
ULN1OK AND
AND
ULN1FF OR
ULN2OK
AND
ULN2FF OR
BLOCK
en05000781.vsd
Figure 170: Simplified logic diagram for the voltage selection function for the tie
circuit breaker in 1 1/2 breaker arrangement.
SYN1-
SECRSYN
U3PBB1 B1SEL
U3PBB2 B2SEL
U3PLN1 LN1SEL
U3PLN2 LN2SEL
B1QOPEN USELFAIL
B1QCLD AUTOENOK
B2QOPEN MANENOK
B2QCLD TSTENOK
LN1QOPEN MANSYOK
LN1QCLD TSTMANSY
LN2QOPEN UDIFF
LN2QCLD FRDIFFM
UB1OK FRDIFFA
UB1FF PHDIFFM
UB2OK PHDIFFA
UB2FF UOK
ULN1OK AUTOSYOK
ULN1FF TSTAUTSY
ULN2OK
ULN2FF
TSTENERG
TSTSYNC
BLKENERG
BLKSYNC
BLOCK
en05000702.vsd
Table 171: Input signals for the SECRSYN_25 (SYN1-) function block
Signal Description
U3PBB1 Group signal for voltage input busbar 1
U3PBB2 Group signal for voltage input busbar 2
U3PLN1 Group signal for voltage input line 1
U3PLN2 Group signal for voltage input line 2
B1QOPEN Open status for CB or disconnector connected to bus1
B1QCLD Close status for CB or disconnector connected to bus1
B2QOPEN Open status for CB or disconnector connected to bus2
B2QCLD Close status for CB or disconnector connected to bus2
LN1QOPEN Open status for CB or disconnector connected to line1
LN1QCLD Close status for CB or disconnector connected to line1
LN2QOPEN Open status for CB or disconnector connected to line2
LN2QCLD Close status for CB or disconnector connected to line2
UB1OK Bus1 voltage transformer OK
UB1FF Bus1 voltage transformer fuse failure
Table continued on next page
Signal Description
UB2OK Bus2 voltage transformer OK
UB2FF Bus2 voltage transformer fuse failure
ULN1OK Line1 voltage transformer OK
ULN1FF Line1 voltage transformer fuse failure
ULN2OK Line2 voltage transformer OK
ULN2FF Line2 voltage transformer fuse failure
TSTENERG Energizing check in test mode
TSTSYNC Synchrocheck in test mode
BLKENERG Energizing check blocked
BLKSYNC Synchrocheck blocked
BLOCK Block of function
Table 172: Output signals for the SECRSYN_25 (SYN1-) function block
Signal Description
B1SEL Bus1 selected
B2SEL Bus2 selected
LN1SEL Line1 selected
LN2SEL Line2 selected
USELFAIL Selected voltage transformer fuse failed
AUTOENOK Automatic energizing check OK
MANENOK Manual energizing check OK
TSTENOK Energizing check OK test output
MANSYOK Manual synchro check OK
TSTMANSY Manual synchro check OK test output
UDIFF Voltage difference out of limit
FRDIFFM Frequency difference out of limit for Manual operation
FRDIFFA Frequency difference out of limit for Auto operation
PHDIFFM Phase angle difference out of limit for Manual Operation
PHDIFFA Phase angle difference out of limit for Auto operation
UOK Voltage amplitudes above set limits
AUTOSYOK Auto synchro check OK
TSTAUTSY Auto synchro check OK test output
Table 173: Basic parameter group settings for the SECRSYN_25 (SYN1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
SelPhaseBus1 phase1 - phase2 - Select phase for bus1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseBus2 phase1 - phase2 - Select phase for bus2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine1 phase1 - phase2 - Select phase for line1
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
SelPhaseLine2 phase1 - phase2 - Select phase for line2
phase2
phase3
phase1-phase2
phase2-phase3
phase3-phase1
CBConfig No voltage sel. - No voltage sel. - Select CB
Double bus configuration
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
UBase 0.001 - 9999.999 0.001 400.000 kV Base voltage in kV
PhaseShift -180 - 180 5 0 Deg Phase shift
URatio 0.20 - 5.00 0.01 1.00 - Voltage ratio
OperationSync Off - On - Operation for
On synchronism check
function Off/On
UHighBusSync 50.0 - 120.0 1.0 80.0 %UB Voltage high limit bus
for synchrocheck in %
of UBase
UHighLineSync 50.0 - 120.0 1.0 80.0 %UB Voltage high limit line
for synchrocheck in %
of UBase
UDiff 2.0 - 50.0 1.0 15.0 %UB Voltage difference
limit between bus and
line in % of UBase
FreqDiffM 0.003 - 1.000 0.001 0.050 Hz Frequency difference
limit between bus and
line Manual
FreqDiffA 0.003 - 1.000 0.001 0.200 Hz Frequency difference
limit between bus and
line Auto
Table continued on next page
11.2.1 Introduction
The autoreclosing function provides high-speed and/or delayed auto-reclosing for
single or multi-breaker applications.
Up to five reclosing attempts can be programmed. The first attempt can be single-,
two and/or three phase for single phase or multi-phase faults respectively.
The logic diagrams below illustrate the principles applicable in the understanding of
the functionality.
Operation of the automatic reclosing can be set to Off or On via the setting parameters
and through external control. With the setting Operation=ON, the function is
activated while with the setting Operation=OFF the function is deactivated. With the
setting Operation=External ctrl, the activation/deactivation is made by input signal
pulses, for example from a control system.
When the function is set On and is operative the output SETON is activated (high).
Other input conditions such as CBPOS and CBREADY must also be fulfilled. At this
point the automatic recloser is prepared to start the reclosing cycle and the output
signal READY on the AR function block is activated (high).
The usual way in which to start a reclosing cycle, or sequence, is to start it when a
line protection tripping has occurred, by applying a signal to the START input. Should
it be necessary to adjust three-phase auto-reclosing open time, (dead time) for
different power system configurations or during tripping at different protection
stages, the input STARTHS (start high-speed reclosing) can also be used.
closed, 52b). One also has to configure and connect signals from manual trip
commands to input INHIBIT.
The logic for switching the auto-recloser ON/OFF and the starting of the reclosing is
shown in figure 172. The following should be considered.
• Setting Operation can be set to Off, External ctrl or ON. External ctrl offers the
possibility of switching by external switches to inputs ON and OFF,
communication commands to the same inputs etc.
• Autoreclose AR is normally started by tripping. It is either a Zone 1 and
Communication aided trip or a general trip. If the general trip is used the function
must be blocked from all back-up tripping connected to INHIBIT. In both
alternatives the breaker failure function must be connected to inhibit the function.
START makes a first attempt with synchrocheck, STARTHS makes its first
attempt without synchrocheck. TRSOTF starts shots 2-5.
• Circuit breaker checks that the breaker was closed for a certain length of time
before the starting occurred and that the CB has sufficient stored energy to
perform an auto-reclosing sequence and is connected to inputs CBPOS and
CBREADY.
Operation:On
Operation:Off
Operation:External Ctrl
OR
ON AND SETON
AND S
OR
OFF AND R
START
STARTHS OR
OR initiate
autoInitiate
Additional conditions
TRSOTF AND
start
120 ms
CBREADY AND
t AND
AND S
tCBClosedMin
CBPOS CB Closed
t R
AND
Blocking conditions READY
AND
OR
Inhibit condistions
count 0
en05000782.vsd
It is possible to use up to four different time settings for the first shot, and one
extension time. There are separate settings for single-, two- and three-phase auto-
reclosing open times, t1 1Ph, t1 2Ph, t1 3Ph. If no particular input signal is applied,
An auto-reclosing open time extension delay, tExtended t1, can be added to the normal
shot 1 delay. It is intended to come into use if the communication channel for
permissive line protection is lost. In a case like this there can be a significant time
difference in fault clearance at the two line ends. A longer auto-reclosing open time
can then be useful. This extension time is controlled by setting parameter Extended
t1 = On and the input PLCLOST.
In normal circumstances the trip command resets quickly due to fault clearing. The
user can set a maximum trip pulse duration tTrip. When trip signals are longer, the
auto-reclosing open time is extended by tExtended t1. If Extended t1 = Off. A long
trip signal interrupts the reclosing sequence in the same way as a signal to input
INHIBIT.
Extended t1
PLCLOST Extend t1
initiate AND OR AND
AND
tTrip
t
AND
start
long duration
AND
(block AR)
en05000783.vsd
Figure 173: Control of extended auto-reclosing open time and long trip pulse
detection
be set to TRUE (set high). Another possibility is to set the output of the synchro-check
function to a permanently activated state. At confirmation from the synchro-check,
or if the reclosing is of single-phase or two-phase type, the signal passes on. At single-
phase, two-phase reclosing and at three-phase high-speed reclosing started by
STARTHS, synchronization is not checked, and the state of the SYNC input is
disregarded.
The synchronism check or energizing check must be fulfilled within a set time
interval, tSync. If it is not, or if other conditions are not met, the reclosing is interrupted
and blocked.
The reclaim timer defines a time from the issue of the reclosing command, after which
the reclosing function resets. Should a new trip occur during this time, it is treated as
a continuation of the first fault. The reclaim timer is started when the CB closing
command is given.
A number of outputs for Autoreclosing state control keeps track of the actual state in
the reclosing sequence.
t1 1Ph
"AR Open time" timers
t
SYNC
initiate AND Blocking X
CBREADY AND OR
AR State
tSync Control
AND t
COUNTER
0 Shot 0
CL Shot 1
1
2 Shot 2
3 Shot 3
tReclaim
Pulse AR (above) AND t R 4 Shot 4
OR Shot 5
5
TR2P LOGIC Reclaim Timer On
TR3P reclosing
1PT1
programs
start 2PT1
initiate 3PHS INPROGR
Shot 0 3PT1 OR
Shot 1 3PT2
Shot 2
Shot 3 3PT3
Shot 4
Shot 5 3PT4
PERMIT1P
3PT5
PREP3P
1
Y Blocking tInhibit
OR Inhibit Y
INHIBIT t
en05000784.vsd
tPulse
pulse
**) AND CLOSECB
OR
initiate
50 ms
2PT1 AND
counter
COUNT2P
counter COUNTAR
RSTCOUNT
en05000785.vsd
Figure 175: Pulsing of closing command and driving the operation counters
Transient fault
After the reclosing command the reclaim timer tReclaim starts running for the set
time. If no tripping occurs within this time, the auto-reclosing will reset.
Normally the signal UNSUCCL appears when a new trip and start is received after
the last reclosing shot has been made and the auto-reclosing function is blocked. The
signal resets once the reclaim time has elapsed. The “unsuccessful“ signal can also
be made to depend on CB position input. The parameter UnsucClByCBChk should
then be set to CBCheck, and a timer tUnsucCl should also be set. If the CB does not
respond to the closing command and does not close, but remains open, the output
UNSUCCL is set high after time tUnsucCl.
initiate
block start AND
OR UNSUCCL
AND S
shot 0
R
UnsucClByCBchk = CBcheck
eno5000786.vsd
tAutoContWait
t
AND
CLOSECB
AND
S Q
AND
CBPOS CBClosed
OR
initiate
START OR
en05000787.vsd
StartByCBOpen = On
START AND
STARTHS AND
start
³1
100 ms
AND
100 ms
AND
en05000788.vsd
Some examples of the timing of internal and external signals at typical transient and
permanent faults are shown below in figures 179 to 182.
Fault
CB POS
Closed Open Closed
CB READY
START (Trip)
SYNC
tReclaim
READY
INPROG
1PT1
ACTIVE
PREP3P
SUCCL
Time
en04000196.vsd
Fault
CB POS Open
Closed Open C C
CB READY
START (Trip)
TR3P
SYNC
READY
INPROGR
3PT1 t1 3Ph
3PT2 t2 3Ph
ACTIVE tReclaim
PREP3P
UNSUCCL
Time
en04000197.vsd
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
AR01-CLOSECB t1s
AR01-P3P
AR01-UNSUC
tReclaim
en04000198.vsd
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-START
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
t2
AR01-CLOSECB t1s
AR01-P3P
AR01-UNSUC
tReclaim
en04000199.vsd
Figure 182: Permanent single-phase fault. Program 1ph + 3ph or 1/2ph + 3ph,
two-shot reclosing
en04000402.vsd
Table 175: Input signals for the SMBRREC_79 (AR01-) function block
Signal Description
ON Switches the AR on (at Operation = ExternalCtrl)
OFF Switches the AR off (at Operation = ExternalCtrl)
BLKON Sets the AR in blocked state
BLKOFF Releases the AR from the blocked state
RESET Resets the AR to initial conditions
INHIBIT Interrupts and inhibits reclosing sequence
START Reclosing sequence starts by a protection trip signal
STARTHS Start HS reclosing without SC: t13PhHS
TRSOTF Makes AR to continue to shots 2-5 at a trip from SOTF
SKIPHS Will skip the high speed shot and continue on delayed shots.
TR2P Signal to the AR that a two-phase tripping occurred
TR3P Signal to the AR that a three-phase tripping occurred
THOLHOLD Hold the AR in wait state
CBREADY CB must be ready for CO/OCO operation to allow start / close
CBPOS Status of the circuit breaker Closed/Open
PLCLOST Power line carrier or other form of permissive sigÂnal lost
SYNC Synchronizing check fulfilled (for 3Ph attempts)
WAIT Wait for master (in Multi-breaker arrangements)
RSTCOUNT Resets all counters
Table 176: Output signals for the SMBRREC_79 (AR01-) function block
Signal Description
BLOCKED The AR is in blocked state
SETON The AR operation is switched on, operative
READY Indicates that the AR function is ready for a new sequence
ACTIVE Reclosing sequence in progress
SUCCL Activated if CB closes during the time tUnsucCl
UNSUCCL Reclosing unsuccessful, signal resets after the reclaim time
INPROGR Reclosing shot in progress, activated during open time
1PT1 Single-phase reclosing is in progress, shot 1
2PT1 Two-phase reclosing is in progress, shot 1
3PT1 Three-phase reclosing in progress, shot 1
3PT2 Three-phase reclosing in progress, shot 2
3PT3 Three-phase reclosing in progress, shot 3
3PT4 Three-phase reclosing in progress, shot 4
3PT5 Three-phase reclosing in progress, shot 5
PERMIT1P Permit single-phase trip, inverse signal to PREP3P
PREP3P Prepare three-phase trip, control of the next trip operation
CLOSECB Closing command for CB
WFMASTER Signal to Slave issued by Master for sequential reclosing
COUNT1P Counting the number of single-phase reclosing shots
COUNT2P Counting the number of two-phase reclosing shots
COUNT3P1 Counting the number of three-phase reclosing shot 1
COUNT3P2 Counting the number of three-phase reclosing shot 2
COUNT3P3 Counting the number of three-phase reclosing shot 3
COUNT3P4 Counting the number of three-phase reclosing shot 4
COUNT3P5 Counting the number of three-phase reclosing shot 5
COUNTAR Counting total number of reclosing shots
Table 177: Parameter group settings for the SMBRREC_79 (AR01-) function
Parameter Range Step Default Unit Description
Operation Off - External ctrl - 0 = Off, 1 =
External ctrl ExternalCtrl, 2 = On
On
NoOfShots 1 - 1 - Max number of
2 reclosing shots 1-5
3
4
5
FirstShot 3 phase - 1/2/3ph - Restriction of fault
1/2/3ph type for shot 1
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
StartByCBOpen Off - Off - To be set ON if AR is
On to be started by CB
open position
CBAuxContType NormClosed - NormOpen - Select the CB aux
NormOpen contact type NC/NO
for CBPOS input
CBReadyType CO - CO - Select type of circuit
OCO breaker ready signal
CO/OCO
t1 1Ph 0.000 - 60.000 0.001 1.000 s Open time for shot 1,
single-phase
t1 2Ph 0.000 - 60.000 0.001 1.000 s Open time for shot 1,
two-phase
t1 3Ph 0.000 - 60.000 0.001 6.000 s Open time for shot 1,
delayed reclosing 3ph
t1 3PhHS 0.000 - 60.000 0.001 0.400 s Open time for shot 1,
high speed reclosing
3ph
t2 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 2,
three-phase
t3 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 3,
three-phase
t4 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 4,
three-phase
t5 3Ph 0.00 - 6000.00 0.01 30.00 s Open time for shot 5,
three-phase
tReclaim 0.00 - 6000.00 0.01 60.00 s Duration of the
reclaim time
tSync 0.00 - 6000.00 0.01 30.00 s Maximum wait time
for synchrocheck OK
Extended t1 Off - Off - Extended open time
On for loss of permissive
channel
tExtended t1 0.000 - 60.000 0.001 0.400 s Open time extended
by this value if
Extended t1 is true
Table continued on next page
11.3.1 Introduction
The apparatus control is a function for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck,
operator place selection and external or internal blockings.
the interaction and status of each process object ensures consistency in the process
information used by higher-level control functions.
Primary apparatuses such as breakers and disconnectors are controlled and supervised
by one software module (SCSWI) each. Because the number and type of signals
connected to a breaker and a disconnector are almost the same, the same software is
used to handle these two types of apparatuses.
The software module is connected to the physical process in the switchyard via an
interface module by means of a number of digital inputs and outputs. One type of
interface module is intended for a circuit breaker (SXCBR) and another type is
intended for a disconnector or earthing switch (SXSWI). Four types of function blocks
are available to cover most of the control and supervision within the bay. These
function blocks are interconnected to form a control function reflecting the switchyard
configuration. The total number used depends on the switchyard configuration. These
four types are:
The three latter functions are logical nodes according to IEC 61850. The function
blocks LocalRemote and LocRemControl, to handle the local/remote switch, and the
function blocks QCRSV and RESIN, for the reservation function, also belong to the
apparatus control function. The principles of operation, function block, input and
output signals and setting parameters for all these functions are described below.
11.3.3.1 Introduction
This function is used to handle the selection of the operator place per bay. The bay
control function also provides blocking functions that can be distributed to different
apparatuses within the bay.
The functionality of the bay control function is not defined in the IEC 61850–8–1
standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay e.g. switch control functions,
voltage control functions and measurement functions.
are here defined so that remote means that operation is allowed from station/remote
level and local from the IED level. The local/remote switch is normally situated on
the control/protection IED itself, which means that the position of the switch and its
validity information are connected internally, and not via I/O boards. When the switch
is mounted separately on the IED the signals are connected to the function via I/O
boards.
When the local panel switch is in Off position all commands from remote and local
level will be ignored. If the position for the local/remote switch is not valid the PSTO
output will always be set to faulty state (3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch, the
function blocks LocalRemote and LocRemControl are needed and connected to
QCBAY. For more information, see section "Local/Remote switch (LocalRemote,
LocRemControl)".
Table 179: PSTO values for different Local panel switch positions
Local panel switch PSTO value AllPSTOValid Possible locations that shall be able to
positions (configuration operate
parameter)
0 = Off 0 -- Not possible to operate
1 = Local 1 FALSE Local Panel
1 = Local 5 TRUE Local or Remote level without any
priority
2 = Remote 2 FALSE Remote level
2 = Remote 5 TRUE Local or Remote level without any
priority
3 = Faulty 3 -- Not possible to operate
Blockings
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:
• Blocking of position indications, BL_UPD. This input will block all inputs
related to apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
• Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC
61850–8–1). If DO Behavior is set to "blocked" it means that the function is
active, but no outputs are generated, no reporting, control commands are rejected
and functional and configuration data is visible.
The switching of the Local/Remote switch requires an Control level password. This
will be requested at attempt to operate if authority levels has been defined in the IED.
Default password is "abb".
en05000796.vsd
Table 180: Input signals for the QCBAY (CB01-) function block
Signal Description
LR_OFF External Local/Remote switch is in Off position
LR_LOC External Local/Remote switch is in Local position
LR_REM External Local/Remote switch is in Remote position
LR_VALID Data representing the L/R switch position is valid
BL_UPD Steady signal to block the position updates
BL_CMD Steady signal to block the command
Table 181: Output signals for the QCBAY (CB01-) function block
Signal Description
PSTO The value for the operator place allocation
UPD_BLKD The update of position is blocked
CMD_BLKD The function is blocked for commands
11.3.4.1 Introduction
The signals from the local LCD HMI or from an external local/remote switch are
applied via function blocks LocalRemote and LocRemControl to the Bay control
QCBAY function block. A parameter in function block LocalRemote is set to choose
if the switch signals are coming from the local LCD HMI or from an external hardware
switch connected via binary inputs.
The function block LocalRemote handles the signals coming from the local/remote
switch. The connections are seen in figure 185, where the inputs on function block
LocalRemote are connected to binary inputs if an external switch is used. When a
local LCD HMI is used, the inputs are not used and are set to FALSE in the
configuration. The outputs from the LocalRemote function block control the output
PSTO (Permitted Source To Operate) on QCBAY.
LR01- CB01-
LocalRemote QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD
LR02- CB02-
LocalRemote QCBAY
CTRLOFF OFF LR_OFF PSTO
LOCCTRL LOCAL LR_LOC UPD_BLKD
REMCTRL REMOTE LR_REM CMD_BLKD
LHMICTRL VALID LR_VALID
BL_UPD
BL_CMD
LRC1-
LocRemControl
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO10 HMICTR10
PSTO11 HMICTR11
PSTO12 HMICTR12
en05000250.vsd
Figure 185: Configuration for the local/remote handling for a local LCD HMI with
two bays and two screen pages
If the IED contains control functions for several bays, the local/remote position can
be different for the included bays. When the local LCD HMI is used the position of
the local/remote switch can be different depending on which single line diagram
screen page that is presented on the local HMI. The function block LocRemControl
controls the presentation of the LEDs for the local/remote position to applicable bay
and screen page.
LR01-
LocalRemote
CT RLOFF OFF
LOCCT RL LOCAL
REMCT RL REMOT E
LHMICT RL VALID
en05000360.vsd
LRC1-
LocRemControl
PST O1 HMICT R1
PST O2 HMICT R2
PST O3 HMICT R3
PST O4 HMICT R4
PST O5 HMICT R5
PST O6 HMICT R6
PST O7 HMICT R7
PST O8 HMICT R8
PST O9 HMICT R9
PST O10 HMICT R10
PST O11 HMICT R11
PST O12 HMICT R12
en05000361.vsd
Table 183: Input signals for the LocalRemote (LR01-) function block
Signal Description
CTRLOFF Disable control
LOCCTRL Local in control
REMCTRL Remote in control
LHMICTRL LHMI control
Table 184: Output signals for the LocalRemote (LR01-) function block
Signal Description
OFF Control is disabled
LOCAL Local control is activated
REMOTE Remote control is activated
VALID Outputs are valid
Table 185: Input signals for the LocRemControl (LRC1-) function block
Signal Description
PSTO1 PSTO input channel 1
PSTO2 PSTO input channel 2
PSTO3 PSTO input channel 3
PSTO4 PSTO input channel 4
PSTO5 PSTO input channel 5
PSTO6 PSTO input channel 6
PSTO7 PSTO input channel 7
PSTO8 PSTO input channel 8
Table continued on next page
Signal Description
PSTO9 PSTO input channel 9
PSTO10 PSTO input channel 10
PSTO11 PSTO input channel 11
PSTO12 PSTO input channel 12
Table 186: Output signals for the LocRemControl (LRC1-) function block
Signal Description
HMICTR1 Bitmask output 1 to local remote LHMI input
HMICTR2 Bitmask output 2 to local remote LHMI input
HMICTR3 Bitmask output 3 to local remote LHMI input
HMICTR4 Bitmask output 4 to local remote LHMI input
HMICTR5 Bitmask output 5 to local remote LHMI input
HMICTR6 Bitmask output 6 to local remote LHMI input
HMICTR7 Bitmask output 7 to local remote LHMI input
HMICTR8 Bitmask output 8 to local remote LHMI input
HMICTR9 Bitmask output 9 to local remote LHMI input
HMICTR10 Bitmask output 10 to local remote LHMI input
HMICTR11 Bitmask output 11 to local remote LHMI input
HMICTR12 Bitmask output 12 to local remote LHMI input
11.3.5.1 Introduction
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may handle
and operate on one three-phase device or three one-phase switching devices.
The function is provided with verification checks for the select - execute sequence,
i.e. checks the conditions prior each step of the operation. The involved functions for
these condition verifications are interlocking, reservation, blockings and
synchrocheck.
Command handling
Two types of command models can be used. The two command models are "direct
with enhanced security" and "SBO (Select-Before-Operate) with enhanced security".
Which one of these two command models that are used is defined by the parameter
CtlModel. The meaning with "direct with enhanced security" model is that no select
is required. The meaning with "SBO with enhanced security" model is that a select
is required before execute.
There is not any relation between the command direction and the
actual position. For example, if the switch is in close position it is
possible to execute a close command.
Evaluation of position
In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the one-
phase switches, following principles will be applied:
The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will change
position at any time due to a trip. Such situation is here called pole discordance and
is supervised by this function. In case of a pole discordance situation, i.e. the position
of the one-phase switches are not equal for a time longer than the setting
tPoleDiscord, an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause" values
from the switch modules XCBR/XSWI. At error the "cause" value with highest
priority is shown.
Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC61850 communication from the operator place.
The different block conditions will only affect the operation of this
function, i.e. no blocking signals will be "forwarded" to other
functions. The above blocking outputs are stored in a non-volatile
memory.
When there is no positive confirmation from the synchrocheck function, the SCSWI
will send a start signal START_SY to the synchronizing function, which will send
the closing command to the SXCBR when the synchronizing conditions are fulfilled,
see figure 188. If no synchronizing function is included, the timer for supervision of
the "synchronizing in progress signal" is set to 0, which means no start of the
synchronizing function. The SCSWI will then set the attribute "blocked-by-
synchrocheck" in the "cause" signal. See also the time diagram in figure 192.
SCSWI SXCBR
EXE_CL
OR CLOSE
SYNC_OK
START_SY
SY_INPRO
SECRSYN
CLOSE. CB
Synchro Synchronizing
Check function
en05000091.vsd
Time diagrams
The SCSWI function has timers for evaluating different time supervision conditions.
These timers are explained here.
The timer tSelect is used for supervising the time between the select and the execute
command signal, i.e. the time the operator has to perform the command execution
after the selection of the object to operate.
select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
The parameter tResResponse is used to set the maximum allowed time to make the
reservation, i.e. the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.
select
command termination
tResResponse t1>tResResponse, then
timer 1-of-n-control in 'cause'
t1 is set
en05000093.vsd
The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 191.
execute command
position L1 open
close
position L2 open
close
position L3 open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination *
position open
close
The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
execute command
SYNC_OK
tSynchrocheck
t1
START_SY
SY_INPRO
en05000095.vsd
Error handling
Depending on what error that occurs during the command sequence the error signal
will be set with a value. Table 188 describes vendor specific cause values in addition
to these specified in IEC 61850-8-1 standard.The list of values of the “cause” are in
order of priority. The values are available over the IEC 61850. An output L_CAUSE
on the function block indicates the latest value of the error during the command.
en05000337.vsd
Table 189: Input signals for the SCSWI (CS01-) function block
Signal Description
BLOCK Block of function
PSTO Operator place selection
L_SEL Select signal from local panel
L_OPEN Open signal from local panel
L_CLOSE Close signal from local panel
AU_OPEN Used for local automation function
AU_CLOSE Used for local automation function
BL_CMD Steady signal for block of the command
RES_GRT Positive acknowledge that all reservations are made
RES_EXT Reservation is made externally
SY_INPRO Synchronizing function in progress
SYNC_OK Closing is permitted at set to true by the synchrocheck
EN_OPEN Enables open operation
EN_CLOSE Enables close operation
XPOS1 Group signal for XCBR input
XPOS2 Group signal for XCBR input
XPOS3 Group signal for XCBR input
Table 190: Output signals for the SCSWI (CS01-) function block
Signal Description
EXE_OP Execute command for open direction
EXE_CL Execute command for close direction
SELECTED The select conditions are fulfilled
RES_RQ Request signal to the reservation function
START_SY Starts the synchronizing function
POSITION Position indication
OPENPOS Open position indication
CLOSEPOS Closed position indication
POLEDISC The positions for poles L1-L3 are not equal after a set time
CMD_BLK Commands are blocked
L_CAUSE Latest value of the error indication during command
XOUT Execution information to XCBR/XSWI
11.3.6.1 Introduction
The purpose of this function is to provide the actual status of positions and to perform
the control operations, i.e. pass all the commands to primary apparatuses in the form
of circuit breakers via output boards and to supervise the switching operation and
position.
The intended user of this function is other functions such as e.g. Switch controller,
protection functions, autorecloser function or an IEC 61850 client residing in another
IED or the operator place. This switch function executes commands, evaluate block
conditions and evaluate different time supervision conditions. Only if all conditions
indicate a switch operation to be allowed, the function performs the execution
command. In case of erroneous conditions, the function indicates an appropriate
"cause" value.
The function has an operation counter for closing and opening commands. The
counter value can be read remotely from the operator place. The value is reset from
a binary input or remotely from the operator place.
Local/Remote switch
One binary input signal LR_SWI is included in this function to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard level.
If the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection functions
are rejected. The functionality of the local/remote switch is described in figure 194.
Local= Operation at
UE switch yard level
TR
en05000096.vsd
Blocking principles
The function includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients e.g. operators place,
protection functions, autoreclosure etc.
Substitution
The substitution part in this function is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous of some reason. The function will
then use the manually entered value instead of the value for positions determined by
the process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 195 explains these two timers during the execute phase.
OPENPOS
CLOSEPOS
en05000097.vsd
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter AdaptivePulse. Figure 196 shows the principle of
the execute output pulse. The adaptively parameter will have affect on both execute
output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, i.e. tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close position
and a close command is executed. In these cases, with the additional condition that
the configuration parameter AdaptivePulse is true, the execute output pulse is always
activated and resets when tStartMove has elapsed. If the configuration parameter
AdaptivePulse is set to false the execution output remains active until the pulse
duration timer has elapsed.
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
Error handling
Depending on what error that occurs during the command sequence the error signal
will be set with a value. Table 192 describes vendor specific cause values in addition
to these specified in IEC 61850-8-1 standard. The list of values of the “cause” are in
order of priority. The values are available over the IEC 61850. An output L_CAUSE
on the function block indicates the latest value of the error during the command.
Table 192: Vendor specific cause values for Apparatus control in priority order
Apparatus control Description
function
–22 wrongCTLModel
–23 blockedForCommand
–24 blocked-for-open-command
–25 blocked-for-close-command
–30 longOperationTime
–31 switch-not-start-moving
–32 persistent-intermediate-state
–33 switch-returned-to-initial-position
–34 switch-in-bad-state
–35 not-expected-final-position
en05000338.vsd
Table 193: Input signals for the SXCBR (XC01-) function block
Signal Description
BLOCK Block of function
LR_SWI Local/Remote switch indication from switchyard
OPEN Pulsed signal used to immediately open the switch
CLOSE Pulsed signal used to immediately close the switch
BL_OPEN Signal to block the open command
BL_CLOSE Signal to block the close command
Table continued on next page
Signal Description
BL_UPD Steady signal for block of the position updating
POSOPEN Signal for open position of apparatus from I/O
POSCLOSE Signal for close position of apparatus from I/O
TR_OPEN Signal for open position of truck from I/O
TR_CLOSE Signal for close position of truck from I/O
RS_CNT Resets the operation counter
XIN Execution information from CSWI
Table 194: Output signals for the SXCBR (XC01-) function block
Signal Description
XPOS Group signal for XCBR output
EXE_OP Executes the command for open direction
EXE_CL Executes the command for close direction
SUBSTED Indication that the position is substituted
OP_BLKD Indication that the function is blocked for open commands
CL_BLKD Indication that the function is blocked for close commands
UPD_BLKD The update of position indication is blocked
OPENPOS Apparatus open position
CLOSEPOS Apparatus closed position
TR_POS Truck position indication
CNT_VAL The value of the operation counter
L_CAUSE Latest value of the error indication during command
11.3.7.1 Introduction
The purpose of this function is to provide the actual status of positions and to perform
the control operations, i.e. pass all the commands to primary apparatuses in the form
of disconnectors or earthing switches via output boards and to supervise the switching
operation and position.
The intended user of this function is other functions such as e.g. Switch controller,
protection functions, autorecloser function or a 61850 client residing in another IED
or the operator place. This switch function executes commands, evaluate block
conditions and evaluate different time supervision conditions. Only if all conditions
indicate a switch operation to be allowed, the function performs the execution
command. In case of erroneous conditions, the function indicates an appropriate
"cause" value.
The function has an operation counter for closing and opening commands. The
counter value can be read remotely from the operator place. The value is reset from
a binary input or remotely from the operator place.
Local/Remote switch
One binary input signal LR_SWI is included in this function to indicate the local/
remote switch position from switchyard provided via the I/O board. If this signal is
set to TRUE it means that change of position is allowed only from switchyard level.
If the signal is set to FALSE it means that command from IED or higher level is
permitted. When the signal is set to TRUE all commands (for change of position)
from internal IED clients are rejected, even trip commands from protection functions
are rejected. The functionality of the local/remote switch is described in figure 199.
Local= Operation at
UE switch yard level
TR
en05000096.vsd
Blocking principles
The function includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients e.g. operators place,
protection functions, autoreclosure etc.
Substitution
The substitution part in this function is used for manual set of the position for the
switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous of some reason. The function will
then use the manually entered value instead of the value for positions determined by
the process.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 200 explains these two timers during the execute phase.
OPENPOS
CLOSEPOS
en05000097.vsd
The timers tOpenPulse and tClosePulse are the length of the execute output pulses
to be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter AdaptivePulse. Figure 201 shows the principle of
the execute output pulse. The adaptively parameter will have affect on both execute
output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
If the pulse is set to be adaptive, it is not possible for the pulse to exceed
tOpenPulse or tClosePulse.
• the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, i.e. tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close position
and a close command is executed. In these cases, with the additional condition that
the configuration parameter AdaptivePulse is true, the execute output pulse is always
activated and resets when tStartMove has elapsed. If the configuration parameter
AdaptivePulse is set to false the execution output remains active until the pulse
duration timer has elapsed.
OPENPOS
CLOSEPOS
EXE_OP AdaptivePulse=FALSE
tOpenPulse
EXE_OP AdaptivePulse=TRUE
tOpenPulse
tStartMove timer
en05000099.vsd
Error handling
Depending on what error that occurs during the command sequence the error signal
will be set with a value. Table 196 describes possible values of the "cause" in priority
order. The values are available over the IEC 61850. An output L_CAUSE on the
function block indicates the latest value of the error during the command.
en05000339.vsd
Table 197: Input signals for the SXSWI (XS01-) function block
Signal Description
BLOCK Block of function
LR_SWI Local/Remote switch indication from switchyard
OPEN Pulsed signal used to immediately open the switch
CLOSE Pulsed signal used to immediately close the switch
BL_OPEN Signal to block the open command
BL_CLOSE Signal to block the close command
BL_UPD Steady signal for block of the position updating
POSOPEN Signal for open position of apparatus from I/O
POSCLOSE Signal for close position of apparatus from I/O
RS_CNT Resets the operation counter
XIN Execution information from CSWI
Table 198: Output signals for the SXSWI (XS01-) function block
Signal Description
XPOS Group signal for XSWI output
EXE_OP Executes the command for open direction
EXE_CL Executes the command for close direction
SUBSTED Indication that the position is substituted
OP_BLKD Indication that the function is blocked for open commands
CL_BLKD Indication that the function is blocked for close commands
UPD_BLKD The update of position indication is blocked
OPENPOS Apparatus open position
CLOSEPOS Apparatus closed position
CNT_VAL The value of the operation counter
L_CAUSE Latest value of the error indication during command
11.3.8.1 Introduction
The function block QCRSV handles the reservation. The function starts to operate in
two ways. It starts when there is a request for reservation of the own bay or if there
is a request for reservation from another bay. It is only possible to reserve the function
if it is not currently reserved. The signal that can reserve the own bay is the input
signal RES_RQx (x=1-8) coming from switch controller SCWI. The signals for
request from another bay are the outputs RE_RQ_B and V_RE_RQ from function
block RESIN. These signals are included in signal EXCH_OUT from RESIN and are
connected to RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay
only (TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.
If the RESERVED output is not set, the selection is made with the output RES_GRTx
(where x=1-8 is the number of the requesting apparatus), which is connected to switch
controller SCSWI. If the bay already is reserved the command sequence will be reset
and the SCSWI will set the attribute "1-of-n-control" in the "cause" signal.
When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-n-
control" in the "cause" signal.
The reservation function can also be overridden in the own bay with the OVERRIDE
input signal, i.e. reserving the own bay without waiting for the external acknowledge.
If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The both functions QCRSV have to communicate and this is done through
the input EXCH_IN and EXCH_OUT according to figure 10. If more then one
QCRSV are used, the execution order is very important. The execution order must
be in the way that the first QCRSV has a lower number than the next one.
CR01-
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_RQ2 RES_GRT3
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6
RES_RQ6 RES_GRT7
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B
OVERRIDE RESERVED
RES_DATA EXCH_OUT
CR02-
QCRSV
EXCH_IN RES_GRT1
RES_RQ1 RES_GRT2
RES_BAYS
RES_RQ2 RES_GRT3 ³1
RES_RQ3 RES_GRT4
RES_RQ4 RES_GRT5
RES_RQ5 RES_GRT6 ACK_TO_B
RES_RQ6 RES_GRT7 ³1
RES_RQ7 RES_GRT8
RES_RQ8 RES_BAYS
BLK_RES ACK_TO_B RESERVED
³1
OVERRIDE RESERVED
RES_DATA EXCH_OUT
en05000088.vsd
en05000340.vsd
Table 200: Input signals for the QCRSV (CR01-) function block
Signal Description
EXCH_IN Used for exchange signals between different BayRes blocks
RES_RQ1 Signal for app. 1 that requests to do a reservation
RES_RQ2 Signal for app. 2 that requests to do a reservation
RES_RQ3 Signal for app. 3 that requests to do a reservation
RES_RQ4 Signal for app. 4 that requests to do a reservation
RES_RQ5 Signal for app. 5 that requests to do a reservation
RES_RQ6 Signal for app. 6 that requests to do a reservation
RES_RQ7 Signal for app. 7 that requests to do a reservation
RES_RQ8 Signal for app. 8 that requests to do a reservation
BLK_RES Reservation is not possible and the output signals are reset
OVERRIDE Signal to override the reservation
RES_DATA Reservation data coming from function block ResIn
Table 201: Output signals for the QCRSV (CR01-) function block
Signal Description
RES_GRT1 Reservation is made and the app. 1 is allowed to operate
RES_GRT2 Reservation is made and the app. 2 is allowed to operate
RES_GRT3 Reservation is made and the app. 3 is allowed to operate
RES_GRT4 Reservation is made and the app. 4 is allowed to operate
RES_GRT5 Reservation is made and the app. 5 is allowed to operate
RES_GRT6 Reservation is made and the app. 6 is allowed to operate
RES_GRT7 Reservation is made and the app. 7 is allowed to operate
Table continued on next page
Signal Description
RES_GRT8 Reservation is made and the app. 8 is allowed to operate
RES_BAYS Request for reservation of other bays
ACK_TO_B Acknowledge to other bays that this bay is reserved
RESERVED Indicates that the bay is reserved
EXCH_OUT Used for exchange signals between different BayRes blocks
11.3.9.1 Introduction
The function block RESIN receives the reservation information from other bays. The
number of instances is the same as the number of involved bays (up to 60 instances
are available).
The reservation input function is based purely on Boolean logic conditions. The logic
diagram in figure 206 shows how the output signals are created. The inputs of the
function block are connected to a receive function block representing signals
transferred over the station bus from another bay.
EXCH_IN INT
BIN
ACK_F_B
&
FutureUse
³1
ANY_ACK
BAY_ACK ³1
VALID_TX
&
BAY_VAL ³1
RE_RQ_B
³1
BAY_RES &
V _RE_RQ
³1
BIN
EXCH_OUT
INT
en05000089.vsd
Figure 207 describes the principle of the data exchange between all RESIN modules
in the current bay. There is one RESIN function block per "other bay" used in the
reservation mechanism. The output signal EXCH_OUT in the last RESIN functions
block are connected to the module QCRSV that handles the reservation function in
the own bay. The value to the input EXCH_IN on the first RESIN module in the chain
has the integer value 5. This is provided by the use of instance number one of the
function block RESIN (RE01-), where the input EXCH_IN is set to #5, but is hidden
for the user.
RE01-
RESIN
BAY_ACK ACK_F_B
Bay 1 BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
RE02-
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
Bay 2 BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
REnn-
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
CR01-
Bay n BAY_VAL VALID_TX
BAY_RES RE_RQ_B QCRSV
V_RE_RQ
EXCH_OUT RES_DATA
en05000090.vsd
en05000341.vsd
Table 203: Input signals for the RESIN (RE01-) function block
Signal Description
BAY_ACK Another bay has acknow. the reservation req. from this bay
BAY_VAL The reserv. and acknow. signals from another bay are valid
BAY_RES Request from other bay to reserve this bay
Table 204: Output signals for the RESIN (RE01-) function block
Signal Description
ACK_F_B All other bays have acknow. the reserv. req. from this bay
ANY_ACK Any other bay has acknow. the reserv. req. from this bay
VALID_TX The reserv. and acknow. signals from other bays are valid
RE_RQ_B Request from other bay to reserve this bay
V_RE_RQ Check if the request of reserving this bay is valid
EXCH_OUT Used for exchange signals between different ResIn blocks
11.4 Interlocking
11.4.1 Introduction
The interlocking function blocks the possibility to operate high-voltage switching
devices, for instance when a disconnector is under load, in order to prevent material
damage and/or accidental human injury.
Each control IED has interlocking functions for different switchyard arrangements,
each handling the interlocking of one bay. The function is distributed to each control
IED and not dependent on any central function. For the station-wide interlocking, the
IEDs communicate via the station bus or by using hard wired binary inputs/outputs.
The interlocking conditions depend on the circuit configuration and status of the
installation at any given time.
The reservation function (see section "Apparatus control (APC)") is used to ensure
that HV apparatuses that might affect the interlock are blocked during the time gap,
which arises between position updates. This can be done by means of the
communication system, reserving all HV apparatuses that might influence the
After the selection and reservation of an apparatus, the function has complete data on
the status of all apparatuses in the switchyard that are affected by the selection. Other
operators cannot interfere with the reserved apparatus or the status of switching
devices that may affect it.
The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a bay.
The interlocking logic in a module is different, depending on the bay function and
the switchyard arrangements, that is, double-breaker or 1 1/2 breaker bays have
different modules. Specific interlocking conditions and connections between standard
interlocking modules are performed with an engineering tool. Bay-level interlocking
signals can include the following kind of information:
Apparatus control
Interlocking
modules
modules in
SCILO SCSWI
other bays SXSWI
Apparatus control
modules
Interlocking SCILO SCSWI SXCBR
module
Apparatus control
modules
en04000526.vsd SCILO SCSWI SXSWI
Bays communicate via the station bus and can convey information regarding the
following:
• Unearthed busbars
• Busbars connected together
• Other bays connected to a busbar
• Received data from other bays is valid
Station bus
Disc QB1 and QB2 closed Disc QB1 and QB2 closed WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
...
WA1 not earthed WA1 not earthed
WA2 not earthed WA2 not earthed WA1 and WA2 interconn
WA1 and WA2 interconn WA1 and WA2 interconn in other bay
..
WA1
WA2
QB1 QB2 QB1 QB2 QB1 QB2 QC1 QC2
QB9 QB9
en05000494.vsd
When invalid data such as intermediate position, loss of a control terminal, or input
board error are used as conditions for the interlocking condition in a bay, a release
for execution of the function will not be given.
On the station HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
The input signals EXDU_xx shall be set to true if there is no transmission error at the
transfer of information from other bays. Required signals with designations ending
in TR are intended for transfer to other bays.
11.4.3.1 Introduction
The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a defined
end position e.g. open, then the appropriate enable signal (in this case EN_OPEN) is
false. The enable signals EN_OPEN and EN_CLOSE can be true at the same time
only in the intermediate and bad position state and if they are enabled by the
interlocking function. The position inputs come from the logical nodes Circuit
breaker/switch SXCBR/SXSWI and the enable signals come from the interlocking
logic. The outputs are connected to the logical node Switch controller SCSWI. One
instance per switching device is needed.
POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&
OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd
en05000359.vsd
Table 206: Input signals for the SCILO (CI01-) function block
Signal Description
POSOPEN Open position of switch device
POSCLOSE Closed position of switch device
OPEN_EN Open operation from interlocking logic is enabled
CLOSE_EN Close operation from interlocking logic is enabled
Table 207: Output signals for the SCILO (CI01-) function block
Signal Description
EN_OPEN Open operation at closed or interm. or bad pos. is enabled
EN_CLOSE Close operation at open or interm. or bad pos. is enabled
11.4.4.1 Introduction
The interlocking module ABC_LINE is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 213. The module can also be
used for a double busbar arrangement without transfer busbar or a single busbar
arrangement with/without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB7
QC1
QA1
QC2
QB9
QC9
en04000478.vsd
en05000357.vsd
ABC_LINE
QA1_OP
QA1_CL =1 VPQA1
QB9_OP
QB9_CL =1 VPQB9
QA1CLREL
QB1_OP
QB1_CL =1 VPQB1 QA1CLITL
& 1
QB2_OP
QB2_CL =1 VPQB2
QB7_OP
QB7_CL =1 VPQB7
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC9_OP
QC9_CL =1 VPQC9
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQC1 QB9REL
VPQC2 & >1
QB9ITL
1
VPQC9
QA1_OP
QC1_OP
QC2_OP
QC9_OP
QB9_EX1
VPQC2
VPQC9
&
QC2_CL
QC9_CL
QB9_EX2
en04000527.vsd
VPQA1 QB1REL
& ³1
VPQB2
VPQC1 1 QB1ITL
VPQC2
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2 &
VP_BC_12
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1 &
VPQC11
QC1_CL
QC11_CL
EXDU_ES
QB1EX3
en04000528.vsd
VPQA1 QB2REL
& ³1
VPQB1
VPQC1 1 QB2ITL
VPQC2
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1 &
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1 &
VPQC21
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000529.vsd
VPQC9 QB7REL
& >1
VPQC71
VP_BB7_D 1 QB7ITL
VP_BC_17
VP_BC_27
QC9_OP
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
QB7_EX1
VPQA1
VPQB1
VPQC9
&
VPQB9
VPQC71
VP_BB7_D
VP_BC_17
QA1_CL
QB1_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
QB7_EX2
VPQA1
VPQB2
& >1
VPQC9
VPQB9
VPQC71
VP_BB7_D
VP_BC_27
QA1_CL
QB2_CL
QC9_OP
QB9_CL
QC71_OP
EXDU_ES
BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
QB7_EX3
VPQC9
VPQC71
&
QC9_CL
QC71_CL
EXDU_ES
QB7_EX4
VPQB1 QC1REL
VPQB2 QC1ITL
VPQB9 & 1
QC2REL
QB1_OP
QB2_OP QC2ITL
1
QB9_OP
VPQB7
VPQB9 QC9REL
VPVOLT &
QC9ITL
QB7_OP 1
QB9_OP
VOLT_OFF
en04000531.vsd
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000532.vsd
Table 208: Input signals for the ABC_LINE (IF01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB9_OP QB9 is in open position
QB9_CL QB9 is in closed position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
QB7_OP QB7 is in open position
QB7_CL QB7 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QC9_OP QC9 is in open position
QC9_CL QC9 is in closed position
QC11_OP Earthing switch QC11 on busbar WA1 is in open position
QC11_CL Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP Earthing switch QC21 on busbar WA2 is in open position
QC21_CL Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP Earthing switch QC71 on busbar WA7 is in open position
Table continued on next page
Signal Description
QC71_CL Earthing switch QC71 on busbar WA7 is in closed position
BB7_D_OP Disconnectors on busbar WA7 except in the own bay are
open
BC_12_CL A bus coupler connection exists between busbar WA1 and
WA2
BC_17_OP No bus coupler connection exists between busbar WA1 and
WA7
BC_17_CL A bus coupler connection exists between busbar WA1 and
WA7
BC_27_OP No bus coupler connection exists between busbar WA2 and
WA7
BC_27_CL A bus coupler connection exists between busbar WA2 and
WA7
VOLT_OFF There is no voltage on the line and not VT (fuse) failure
VOLT_ON There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D Switch status of the disconnectors on busbar WA7 are valid
VP_BC_12 Status of the bus coupler app. between WA1 and WA2 are
valid
VP_BC_17 Status of the bus coupler app. between WA1 and WA7 are
valid
VP_BC_27 Status of the bus coupler app. between WA2 and WA7 are
valid
EXDU_ES No transm error from any bay containing earthing switches
EXDU_BPB No transm error from any bay with disconnectors on WA7
EXDU_BC No transmission error from any bus coupler bay
QB9_EX1 External condition for apparatus QB9
QB9_EX2 External condition for apparatus QB9
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
QB1_EX3 External condition for apparatus QB1
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
QB2_EX3 External condition for apparatus QB2
QB7_EX1 External condition for apparatus QB7
QB7_EX2 External condition for apparatus QB7
QB7_EX3 External condition for apparatus QB7
QB7_EX4 External condition for apparatus QB7
Table 209: Output signals for the ABC_LINE (IF01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB9REL Switching of QB9 is allowed
QB9ITL Switching of QB9 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QB7REL Switching of QB7 is allowed
QB7ITL Switching of QB7 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QC9REL Switching of QC9 is allowed
QC9ITL Switching of QC9 is forbidden
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
QB2OPTR QB2 is in open position
QB2CLTR QB2 is in closed position
QB7OPTR QB7 is in open position
QB7CLTR QB7 is in closed position
QB12OPTR QB1 or QB2 or both are in open position
QB12CLTR QB1 and QB2 are not in open position
VPQB1TR Switch status of QB1 is valid (open or closed)
VPQB2TR Switch status of QB2 is valid (open or closed)
VPQB7TR Switch status of QB7 is valid (open or closed)
VPQB12TR Switch status of QB1 and QB2 are valid (open or closed)
11.4.5.1 Introduction
The interlocking module ABC_BC is used for a bus-coupler bay connected to a double
busbar arrangement according to figure 215. The module can also be used for a single
busbar arrangement with transfer busbar or double busbar arrangement without
transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
QB1 QB2 QB20 QB7
QC1
QA1
QC2
en04000514.vsd
en05000350.vsd
ABC_BC
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB20_OP
QB20_CL =1 VPQB20
QB7_OP
QB7_CL =1 VPQB7
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
QC71_OP
QC71_CL =1 VPQC71
VPQB1
QB1_OP QA1OPREL
& >1 QA1OPITL
QA1O_EX1 1
VPQB20
QB20_OP &
QA1O_EX2
VP_BBTR
BBTR_OP &
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQB7 & 1
VPQB20
en04000533.vsd
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VP_BC_12
&
QB2_CL
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000534.vsd
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VP_BC_12
&
QB1_CL
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000535.vsd
VPQA1
VPQB20 QB7REL
& >1
VPQC1 QB7ITL
VPQC2 1
VPQC71
QA1_OP
QB20_OP
QC1_OP
QC2_OP
QC71_OP
EXDU_ES
QB7_EX1
VPQC2
VPQC71
&
QC2_CL
QC71_CL
EXDU_ES
QB7_EX2
VPQA1
VPQB7 QB20REL
& >1
VPQC1 QB20ITL
VPQC2 1
VPQC21
QA1_OP
QB7_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB20_EX1
VPQC2
VPQC21
&
QC2_CL
QC21_CL
EXDU_ES
QB20_EX2
en04000536.vsd
VPQB1 QC1REL
VPQB20 QC1ITL
& 1
VPQB7
QC2REL
VPQB2
QB1_OP QC2ITL
1
QB20_OP
QB7_OP
QB2_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB20_OP QB220OTR
QB2_OP & QB220CTR
VPQB20 1
VQB220TR
VPQB2 &
QB7_OP QB7OPTR
QB7_CL QB7CLTR
VPQB7 VPQB7TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
QA1_OP BC12OPTR
QB1_OP >1 BC12CLTR
QB20_OP 1
VPQA1
VPBC12TR
VPQB1 &
VPQB20
QA1_OP BC17OPTR
QB1_OP >1 BC17CLTR
QB7_OP 1
VPQA1
VPBC17TR
VPQB1 &
VPQB7
QA1_OP BC27OPTR
QB2_OP >1 BC27CLTR
QB7_OP 1
VPQA1
VPBC27TR
VPQB2 &
VPQB7
en04000537.vsd
Table 210: Input signals for the ABC_BC (IG01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
Table continued on next page
Signal Description
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
QB7_OP QB7 is in open position
QB7_CL QB7 is in closed position
QB20_OP QB20 is in open position
QB20_CL QB20 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QC11_OP Earthing switch QC11 on busbar WA1 is in open position
QC11_CL Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP Earthing switch QC21 on busbar WA2 is in open position
QC21_CL Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP Earthing switch QC71 on busbar WA7 is in open position
QC71_CL Earthing switch QC71 on busbar WA7 is in closed position
BBTR_OP No busbar transfer is in progress
BC_12_CL A bus coupler connection exists between busbar WA1 and
WA2
VP_BBTR Status are valid for app. involved in the busbar transfer
VP_BC_12 Status of the bus coupler app. between WA1 and WA2 are
valid
EXDU_ES No transm error from any bay containing earthing switches
EXDU_12 No transm error from any bay connected to WA1/WA2
busbars
EXDU_BC No transmission error from any other bus coupler bay
QA1O_EX1 External open condition for apparatus QA1
QA1O_EX2 External open condition for apparatus QA1
QA1O_EX3 External open condition for apparatus QA1
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
QB1_EX3 External condition for apparatus QB1
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
QB2_EX3 External condition for apparatus QB2
QB20_EX1 External condition for apparatus QB20
QB20_EX2 External condition for apparatus QB20
QB7_EX1 External condition for apparatus QB7
QB7_EX2 External condition for apparatus QB7
Table 211: Output signals for the ABC_BC (IG01-) function block
Signal Description
QA1OPREL Opening of QA1 is allowed
QA1OPITL Opening of QA1 is forbidden
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QB7REL Switching of QB7 is allowed
QB7ITL Switching of QB7 is forbidden
QB20REL Switching of QB20 is allowed
QB20ITL Switching of QB20 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
QB220OTR QB2 and QB20 are in open position
QB220CTR QB2 or QB20 or both are not in open position
QB7OPTR QB7 is in open position
QB7CLTR QB7 is in closed position
QB12OPTR QB1 or QB2 or both are in open position
QB12CLTR QB1 and QB2 are not in open position
BC12OPTR No connection via the own bus coupler between WA1 and
WA2
BC12CLTR Conn. exists via the own bus coupler between WA1 and WA2
BC17OPTR No connection via the own bus coupler between WA1 and
WA7
BC17CLTR Conn. exists via the own bus coupler between WA1 and WA7
BC27OPTR No connection via the own bus coupler between WA2 and
WA7
BC27CLTR Conn. exists via the own bus coupler between WA2 and WA7
VPQB1TR Switch status of QB1 is valid (open or closed)
VQB220TR Switch status of QB2 and QB20 are valid (open or closed)
VPQB7TR Switch status of QB7 is valid (open or closed)
VPQB12TR Switch status of QB1 and QB2 are valid (open or closed)
Table continued on next page
Signal Description
VPBC12TR Status of the bus coupler app. between WA1 and WA2 are
valid
VPBC17TR Status of the bus coupler app. between WA1 and WA7 are
valid
VPBC27TR Status of the bus coupler app. between WA2 and WA7 are
valid
11.4.6.1 Introduction
WA1 (A)
WA2 (B)
QB1 QB2
QC1
QA1
AB_TRAFO
QC2
QC3
QA2
QA2 and QC4 are not
QC4 used in this interlocking
QB3 QB4
en04000515.vsd
en05000358.vsd
AB_TRAFO
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB3_OP
QB3_CL =1 VPQB3
QB4_OP
QB4_CL =1 VPQB4
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
QC21_OP
QC21_CL =1 VPQC21
VPQB1 QA1CLREL
VPQB2 QA1CLITL
VPQC1 & 1
VPQC2
VPQB3
VPQB4
VPQC3
QA1_EX2
QC3_OP
QA1_EX3
QC1_CL >1
QC2_CL
QC3_CL &
QA1_EX1
en04000538.vsd
VPQA1
VPQB2 QB1REL
& >1
VPQC1 QB1ITL
VPQC2 1
VPQC3
VPQC11
QA1_OP
QB2_OP
QC1_OP
QC2_OP
QC3_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQB2
VPQC3
&
VP_BC_12
QB2_CL
QC3_OP
BC_12_CL
EXDU_BC
QB1_EX2
VPQC1
VPQC2
&
VPQC3
VPQC11
QC1_CL
QC2_CL
QC3_CL
QC11_CL
EXDU_ES
QB1_EX3
en04000539.vsd
VPQA1
VPQB1 QB2REL
& >1
VPQC1 QB2ITL
VPQC2 1
VPQC3
VPQC21
QA1_OP
QB1_OP
QC1_OP
QC2_OP
QC3_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQB1
VPQC3
&
VP_BC_12
QB1_CL
QC3_OP
BC_12_CL
EXDU_BC
QB2_EX2
VPQC1
VPQC2
&
VPQC3
VPQC21
QC1_CL
QC2_CL
QC3_CL
QC21_CL
EXDU_ES
QB2_EX3
en04000540.vsd
VPQB1 QC1REL
VPQB2 QC1ITL
& 1
VPQB3
QC2REL
VPQB4
QB1_OP QC2ITL
1
QB2_OP
QB3_OP
QB4_OP
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP QB12OPTR
QB2_OP >1 QB12CLTR
VPQB1 1
VPQB12TR
VPQB2 &
en04000541.vsd
Table 212: Input signals for the AB_TRAFO (IE01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QB3_OP QB3 is in open position
QB3_CL QB3 is in closed position
QB4_OP QB4 is in open position
QB4_CL QB4 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QC11_OP QC11 on busbar WA1 is in open position
QC11_CL QC11 on busbar WA1 is in closed position
QC21_OP QC21 on busbar WA2 is in open position
QC21_CL QC21 on busbar WA2 is in closed position
Table continued on next page
Signal Description
BC_12_CL A bus coupler connection exists between busbar WA1 and
WA2
VP_BC_12 Status of the bus coupler app. between WA1 and WA2 are
valid
EXDU_ES No transm error from any bay containing earthing switches
EXDU_BC No transmission error from any bus coupler bay
QA1_EX1 External condition for apparatus QA1
QA1_EX2 External condition for apparatus QA1
QA1_EX3 External condition for apparatus QA1
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
QB1_EX3 External condition for apparatus QB1
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
QB2_EX3 External condition for apparatus QB2
Table 213: Output signals for the AB_TRAFO (IE01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
QB2OPTR QB2 is in open position
QB2CLTR QB2 is in closed position
QB12OPTR QB1 or QB2 or both are in open position
QB12CLTR QB1 and QB2 are not in open position
VPQB1TR Switch status of QB1 is valid (open or closed)
VPQB2TR Switch status of QB2 is valid (open or closed)
VPQB12TR Switch status of QB1 and QB2 are valid (open or closed)
11.4.7.1 Introduction
The interlocking module A1A2_BS is used for one bus-section circuit breaker
between section 1 and 2 according to figure 219. The module can be used for different
busbars, which includes a bus-section circuit breaker.
QA1
QC3 QC4
en04000516.vsd
A1A2_BS
en05000348.vsd
A1A2_BS
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB2_OP
QB2_CL =1 VPQB2
QC3_OP
QC3_CL =1 VPQC3
QC4_OP
QC4_CL =1 VPQC4
S1QC1_OP
S1QC1_CL =1 VPS1QC1
S2QC2_OP
S2QC2_CL =1 VPS2QC2
VPQB1
QB1_OP QA1OPREL
& >1
QA1O_EX1 QA1OPITL
1
VPQB2
QB2_OP
&
QA1O_EX2
VP_BBTR
BBTR_OP
&
EXDU_12
QA1O_EX3
VPQB1 QA1CLREL
VPQB2 & QA1CLITL
1
VPQA1
VPQC3 QB1REL
& >1
VPQC4 QB1ITL
1
VPS1QC1
QA1_OP
QC3_OP
QC4_OP
S1QC1_OP
EXDU_ES
QB1_EX1
VPQC3
VPS1QC1
&
QC3_CL
S1QC1_CL
EXDU_ES
QB1_EX2
en04000542.vsd
VPQA1
VPQC3 QB2REL
VPQC4 & >1
QB2ITL
VPS2QC2 1
QA1_OP
QC3_OP
QC4_OP
S2QC2_OP
EXDU_ES
QB2_EX1
VPQC4
VPS2QC2
&
QC4_CL
S2QC2_CL
EXDU_ES
QB2_EX2
VPQB1 QC3REL
VPQB2 QC3ITL
QB1_OP & 1
QC4REL
QB2_OP
QC4ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
QB1_OP S1S2OPTR
QB2_OP >1 S1S2CLTR
QA1_OP 1
VPQB1
VPS1S2TR
VPQB2 &
VPQA1
en04000543.vsd
Table 214: Input signals for the A1A2_BS (IH01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
Table continued on next page
Signal Description
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QC4_OP QC4 is in open position
QC4_CL QC4 is in closed position
S1QC1_OP QC1 on bus section 1 is in open position
S1QC1_CL QC1 on bus section 1 is in closed position
S2QC2_OP QC2 on bus section 2 is in open position
S2QC2_CL QC2 on bus section 2 is in closed position
BBTR_OP No busbar transfer is in progress
VP_BBTR Status are valid for app. involved in the busbar transfer
EXDU_12 No transm error from any bay connected to busbar 1 and 2
EXDU_ES No transm error from bays containing earth. sw. QC1 or QC2
QA1O_EX1 External open condition for apparatus QA1
QA1O_EX2 External open condition for apparatus QA1
QA1O_EX3 External open condition for apparatus QA1
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
Table 215: Output signals for the A1A2_BS (IH01-) function block
Signal Description
QA1OPREL Opening of QA1 is allowed
QA1OPITL Opening of QA1 is forbidden
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QC3REL Switching of QC3 is allowed
QC3ITL Switching of QC3 is forbidden
QC4REL Switching of QC4 is allowed
QC4ITL Switching of QC4 is forbidden
S1S2OPTR No bus section connection between bus section 1 and 2
S1S2CLTR Bus coupler connection between bus section 1 and 2 exists
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
Table continued on next page
Signal Description
QB2OPTR QB2 is in open position
QB2CLTR QB2 is in closed position
VPS1S2TR Status of the app. between bus section 1 and 2 are valid
VPQB1TR Switch status of QB1 is valid (open or closed)
VPQB2TR Switch status of QB2 is valid (open or closed)
11.4.8.1 Introduction
The interlocking module A1A2_DC is used for one bus-section disconnector between
section 1 and 2 according to figure 221. The module can be used for different busbars,
which includes a bus-section disconnector.
QB
WA1 (A1) WA2 (A2)
QC1 QC2
A1A2_DC en04000492.vsd
en05000349.vsd
A1A2_DC
QB_OP
VPQB VPDCTR
QB_CL =1
DCOPTR
DCCLTR
S1QC1_OP
VPS1QC1
S1QC1_CL =1
S2QC2_OP
VPS2QC2
S2QC2_CL =1
VPS1QC1
VPS2QC2
VPS1_DC & >1 QBOPREL
S1QC1_OP QBOPITL
1
S2QC2_OP
S1DC_OP
EXDU_ES
EXDU_BB
QBOP_EX1
VPS1QC1
VPS2QC2
VPS2_DC &
S1QC1_OP
S2QC2_OP
S2DC_OP
EXDU_ES
EXDU_BB
QBOP_EX2
VPS1QC1
VPS2QC2
S1QC1_CL &
S2QC2_CL
EXDU_ES
QBOP_EX3
en04000544.vsd
Table 216: Input signals for the A1A2_DC (II01-) function block
Signal Description
QB_OP QB is in open position
QB_CL QB is in closed position
S1QC1_OP QC1 on bus section 1 is in open position
S1QC1_CL QC1 on bus section 1 is in closed position
S2QC2_OP QC2 on bus section 2 is in open position
S2QC2_CL QC2 on bus section 2 is in closed position
S1DC_OP All disconnectors on bus section 1 are in open position
S2DC_OP All disconnectors on bus section 2 are in open position
VPS1_DC Switch status of disconnectors on bus section 1 are valid
VPS2_DC Switch status of disconnectors on bus section 2 are valid
EXDU_ES No transm error from bays containing earth. sw. QC1 or QC2
EXDU_BB No transm error from bays with disc conn to section 1 and 2
QBCL_EX1 External close condition for section disconnector QB
QBCL_EX2 External close condition for section disconnector QB
QBOP_EX1 External open condition for section disconnector QB
QBOP_EX2 External open condition for section disconnector QB
QBOP_EX3 External open condition for section disconnector QB
Table 217: Output signals for the A1A2_DC (II01-) function block
Signal Description
QBOPREL Opening of QB is allowed
QBOPITL Opening of QB is forbidden
QBCLREL Closing of QB is allowed
QBCLITL Closing of QB is forbidden
DCOPTR The bus section disconnector is in open position
DCCLTR The bus section disconnector is in closed position
VPDCTR Switch status of QB is valid (open or closed)
11.4.9.1 Introduction
The interlocking module BB_ES is used for one busbar earthing switch on any busbar
parts according to figure 223.
QC
en04000504.vsd
en05000347.vsd
BB_ES
VP_BB_DC QCREL
BB_DC_OP QCITL
EXDU_BB & 1
QC_OP BBESOPTR
QC_CL BBESCLTR
en04000546.vsd
Table 218: Input signals for the BB_ES (IJ01-) function block
Signal Description
QC_OP Busbar earthing switch QC is in open position
QC_CL Busbar earthing switch QC is in closed position
BB_DC_OP All disconnectors on this busbar part are open
VP_BB_DC Status for all disconnectors on this busbar part are valid
EXDU_BB No transm error from bays with disc on this busbar part
Table 219: Output signals for the BB_ES (IJ01-) function block
Signal Description
QCREL Switching of QC is allowed
QCITL Switching of QC is forbidden
BBESOPTR QC on this busbar part is in open position
BBESCLTR QC on this busbar part is in closed position
11.4.10.1 Introduction
The interlocking modules DB_BUS_A, DB_LINE and DB_BUS_B are used for a
line connected to a double circuit breaker arrangement according to figure 225.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC4
QA1 QA2
DB_BUS_A DB_BUS_B
QC2 QC5
QB61 QB62
QC3
QB9
DB_LINE
QC9
en04000518.vsd
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE is the connection from the line to the circuit breaker parts that are connected
to the busbars. DB_BUS_A and DB_BUS_B are the connections from the line to the
busbars.
IB01-
DB_BUS_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB1_OP QB61REL
QB1_CL QB61ITL
QB61_OP QB1REL
QB61_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QB1OPTR
QC3_CL QB1CLTR
QC11_OP VPQB1TR
QC11_CL
EXDU_ES
QB61_EX1
QB61_EX2
QB1_EX1
QB1_EX2
en05000354.vsd
IA01-
DB_LINE
QA1_OP QB9REL
QA1_CL QB9ITL
QA2_OP QC3REL
QA2_CL QC3ITL
QB61_OP QC9REL
QB61_CL QC9ITL
QC1_OP
QC1_CL
QC2_OP
QC2_CL
QB62_OP
QB62_CL
QC4_OP
QC4_CL
QC5_OP
QC5_CL
QB9_OP
QB9_CL
QC3_OP
QC3_CL
QC9_OP
QC9_CL
VOLT_OFF
VOLT_ON
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
en05000356.vsd
IC01-
DB_BUS_B
QA2_OP QA2CLREL
QA2_CL QA2CLITL
QB2_OP QB62REL
QB2_CL QB62ITL
QB62_OP QB2REL
QB62_CL QB2ITL
QC4_OP QC4REL
QC4_CL QC4ITL
QC5_OP QC5REL
QC5_CL QC5ITL
QC3_OP QB2OPTR
QC3_CL QB2CLTR
QC21_OP VPQB2TR
QC21_CL
EXDU_ES
QB62_EX1
QB62_EX2
QB2_EX1
QB2_EX2
en05000355.vsd
DB_BUS_A
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB1_OP
QB1_CL =1 VPQB1
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
QC11_OP
QC11_CL =1 VPQC11
VPQB61 QA1CLREL
VPQB1 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB61_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB61_EX2
VPQA1
VPQC1 QB1REL
& >1
VPQC2 QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
en04000547.vsd
VPQB61 QC1REL
VPQB1 QC1ITL
& 1
QB61_OP QC2REL
QB1_OP QC2ITL
1
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000548.vsd
DB_LINE
QA1_OP
QA1_CL =1 VPQA1
QA2_OP
QA2_CL =1 VPQA2
QB61_OP
QB61_CL =1 VPQB61
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QB62_OP
QB62_CL =1 VPQB62
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QB9_OP
QB9_CL =1 VPQB9
QC3_OP
QC3_CL =1 VPQC3
QC9_OP
QC9_CL =1 VPQC9
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQA1
VPQA2 QB9REL
VPQC1 & >1
QB9ITL
1
VPQC2
VPQC3
VPQC4
VPQC5
VPQC9
QA1_OP
QA2_OP
QC1_OP
QC2_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX1
& en04000549.vsd
VPQA1
VPQC1
VPQC2 & >1
VPQC3
VPQC9
VPQB62
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QC9_OP
QB62_OP
QB9_EX2
VPQA2
VPQB61
&
VPQC3
VPQC4
VPQC5
VPQC9
QA2_OP
QB61_OP
QC3_OP
QC4_OP
QC5_OP
QC9_OP
QB9_EX3
VPQC3
VPQC9
&
VPQB61
VPQB62
QC3_OP
QC9_OP
QB61_OP
QB62_OP
QB9_EX4
VPQC3
VPQC9
&
QC3_CL
QC9_CL
QB9_EX5
en04000550.vsd
VPQB61
VPQB62 QC3REL
VPQB9 &
QC3ITL
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT QC9REL
QB9_OP &
QC9ITL
1
VOLT_OFF
en04000551.vsd
DB_BUS_B
QA2_OP
QA2_CL =1 VPQA2
QB62_OP
QB62_CL =1 VPQB62
QB2_OP
QB2_CL =1 VPQB2
QC4_OP
QC4_CL =1 VPQC4
QC5_OP
QC5_CL =1 VPQC5
QC3_OP
QC3_CL =1 VPQC3
QC21_OP
QC21_CL =1 VPQC21
VPQB62 QA2CLREL
VPQB2 & QA2CLITL
1
VPQA2
VPQC4 QB62REL
& >1
VPQC5 QB62ITL
1
VPQC3
QA2_OP
QC4_OP
QC5_OP
QC3_OP
QB62_EX1
VPQC5
VPQC3
&
QC5_CL
QC3_CL
QB62_EX2
VPQA2
VPQC4 QB2REL
& >1
VPQC5 QB2ITL
1
VPQC21
QA2_OP
QC4_OP
QC5_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC4
VPQC21
&
QC4_CL
QC21_CL
EXDU_ES
QB2_EX2
en04000552.vsd
VPQB62 QC4REL
VPQB2 QC4ITL
& 1
QB62_OP QC5REL
QB2_OP QC5ITL
1
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000553.vsd
Table 220: Input signals for the DB_BUS_A (IB01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
QB61_OP QB61 is in open position
QB61_CL QB61 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QC11_OP Earthing switch QC11 on busbar WA1 is in open position
QC11_CL Earthing switch QC11 on busbar WA1 is in closed position
EXDU_ES No transm error from bay containing earthing switch QC11
QB61_EX1 External condition for apparatus QB61
QB61_EX2 External condition for apparatus QB61
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
Table 221: Output signals for the DB_BUS_A (IB01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB61REL Switching of QB61 is allowed
Table continued on next page
Signal Description
QB61ITL Switching of QB61 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
VPQB1TR Switch status of QB1 is valid (open or closed)
Table 222: Input signals for the DB_LINE (IA01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QA2_OP QA2 is in open position
QA2_CL QA2 is in closed position
QB61_OP QB61 is in open position
QB61_CL QB61 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QB62_OP QB62 is in open position
QB62_CL QB62 is in closed position
QC4_OP QC4 is in open position
QC4_CL QC4 is in closed position
QC5_OP QC5 is in open position
QC5_CL QC5 is in closed position
QB9_OP QB9 is in open position
QB9_CL QB9 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QC9_OP QC9 is in open position
QC9_CL QC9 is in closed position
VOLT_OFF There is no voltage on the line and not VT (fuse) failure
VOLT_ON There is voltage on the line or there is a VT (fuse) failure
QB9_EX1 External condition for apparatus QB9
Table continued on next page
Signal Description
QB9_EX2 External condition for apparatus QB9
QB9_EX3 External condition for apparatus QB9
QB9_EX4 External condition for apparatus QB9
QB9_EX5 External condition for apparatus QB9
Table 223: Output signals for the DB_LINE (IA01-) function block
Signal Description
QB9REL Switching of QB9 is allowed
QB9ITL Switching of QB9 is forbidden
QC3REL Switching of QC3 is allowed
QC3ITL Switching of QC3 is forbidden
QC9REL Switching of QC9 is allowed
QC9ITL Switching of QC9 is forbidden
Table 224: Input signals for the DB_BUS_B (IC01-) function block
Signal Description
QA2_OP QA2 is in open position
QA2_CL QA2 is in closed position
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
QB62_OP QB62 is in open position
QB62_CL QB62 is in closed position
QC4_OP QC4 is in open position
QC4_CL QC4 is in closed position
QC5_OP QC5 is in open position
QC5_CL QC5 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QC21_OP Earthing switch QC21 on busbar WA2 is in open position
QC21_CL Earthing switch QC21 on busbar WA2 is in closed position
EXDU_ES No transm error from bay containing earthing switch QC21
QB62_EX1 External condition for apparatus QB62
QB62_EX2 External condition for apparatus QB62
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
Table 225: Output signals for the DB_BUS_B (IC01-) function block
Signal Description
QA2CLREL Closing of QA2 is allowed
QA2CLITL Closing of QA2 is forbidden
QB62REL Switching of QB62 is allowed
QB62ITL Switching of QB62 is forbidden
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QC4REL Switching of QC4 is allowed
QC4ITL Switching of QC4 is forbidden
QC5REL Switching of QC5 is allowed
QC5ITL Switching of QC5 is forbidden
QB2OPTR QB2 is in open position
QB2CLTR QB2 is in closed position
VPQB2TR Switch status of QB2 is valid (open or closed)
11.4.11.1 Introduction
The interlocking modules BH_LINE_A, BH_CONN and BH_LINE_B are used for
lines connected to a breaker-and-a-half diameter according to figure 229.
WA1 (A)
WA2 (B)
QB1 QB2
QC1 QC1
QA1 QA1
QC2 QC2
QB6 QB6
QC3 QC3
BH_LINE_A BH_LINE_B
QB9 QB9
QC1 QC2
QC9 QC9
BH_CONN
en04000513.vsd
Three types of interlocking modules per diameter are defined. BH_LINE_A and
BH_LINE_B are the connections from a line to a busbar. BH_CONN is the
connection between the two lines of the diameter in the breaker and a half switchyard
layout.
IL01-
BH_LINE_A
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB6_OP QB6REL
QB6_CL QB6ITL
QB1_OP QB1REL
QB1_CL QB1ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
QC3_OP QC3REL
QC3_CL QC3ITL
QB9_OP QB9REL
QB9_CL QB9ITL
QC9_OP QC9REL
QC9_CL QC9ITL
CQA1_OP QB1OPTR
CQA1_CL QB1CLTR
CQB61_OP VPQB1TR
CQB61_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC11_OP
QC11_CL
VOLT_OFF
VOLT_ON
EXDU_ES
QB6_EX1
QB6_EX2
QB1_EX1
QB1_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
en05000352.vsd
IM01-
BH_LINE_B
QA1_OP QA1CLREL
QA1_CL QA1CLIT L
QB6_OP QB6REL
QB6_CL QB6IT L
QB2_OP QB2REL
QB2_CL QB2IT L
QC1_OP QC1REL
QC1_CL QC1IT L
QC2_OP QC2REL
QC2_CL QC2IT L
QC3_OP QC3REL
QC3_CL QC3IT L
QB9_OP QB9REL
QB9_CL QB9IT L
QC9_OP QC9REL
QC9_CL QC9IT L
CQA1_OP QB2OPT R
CQA1_CL QB2CLT R
CQB62_OP VPQB2T R
CQB62_CL
CQC1_OP
CQC1_CL
CQC2_OP
CQC2_CL
QC21_OP
QC21_CL
VOLT _OFF
VOLT _ON
EXDU_ES
QB6_EX1
QB6_EX2
QB2_EX1
QB2_EX2
QB9_EX1
QB9_EX2
QB9_EX3
QB9_EX4
QB9_EX5
QB9_EX6
QB9_EX7
en05000353.vsd
IK01-
BH_CONN
QA1_OP QA1CLREL
QA1_CL QA1CLITL
QB61_OP QB61REL
QB61_CL QB61ITL
QB62_OP QB62REL
QB62_CL QB62ITL
QC1_OP QC1REL
QC1_CL QC1ITL
QC2_OP QC2REL
QC2_CL QC2ITL
1QC3_OP
1QC3_CL
2QC3_OP
2QC3_CL
QB61_EX1
QB61_EX2
QB62_EX1
QB62_EX2
en05000351.vsd
BH_LINE_A
QA1_OP
QA1_CL =1 VPQA1
QB1_OP
QB1_CL =1 VPQB1
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB61_OP
CQB61_CL =1 VPCQB61
QC11_OP
QC11_CL =1 VPQC11
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB1 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000554.vsd
VPQA1
VPQC1 QB1REL
VPQC2 & >1
QB1ITL
1
VPQC11
QA1_OP
QC1_OP
QC2_OP
QC11_OP
EXDU_ES
QB1_EX1
VPQC1
VPQC11
&
QC1_CL
QC11_CL
EXDU_ES
QB1_EX2
VPQB1 QC1REL
VPQB6 QC1ITL
QB1_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB61 &
QC3ITL
1
QB6_OP
QB9_OP
CQB61_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB61
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000555.vsd
CQB61_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB1_OP QB1OPTR
QB1_CL QB1CLTR
VPQB1 VPQB1TR
en04000556.vsd
BH_LINE_B
QA1_OP
QA1_CL =1 VPQA1
QB2_OP
QB2_CL =1 VPQB2
QB6_OP
QB6_CL =1 VPQB6
QC9_OP
QC9_CL =1 VPQC9
QB9_OP
QB9_CL =1 VPQB9
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
QC3_OP
QC3_CL =1 VPQC3
CQA1_OP
CQA1_CL =1 VPCQA1
CQC1_OP
CQC1_CL =1 VPCQC1
CQC2_OP
CQC2_CL =1 VPCQC2
CQB62_OP
CQB62_CL =1 VPCQB62
QC21_OP
QC21_CL =1 VPQC21
VOLT_OFF
VOLT_ON =1 VPVOLT
VPQB2 QA1CLREL
VPQB6 QA1CLITL
& 1
VPQB9
VPQA1
VPQC1 QB6REL
VPQC2 & >1
QB6ITL
1
VPQC3
QA1_OP
QC1_OP
QC2_OP
QC3_OP
QB6_EX1
VPQC2
VPQC3
&
QC2_CL
QC3_CL
QB6_EX2
en04000557.vsd
VPQA1
VPQC1 QB2REL
VPQC2 & >1
QB2ITL
1
VPQC21
QA1_OP
QC1_OP
QC2_OP
QC21_OP
EXDU_ES
QB2_EX1
VPQC1
VPQC21
&
QC1_CL
QC21_CL
EXDU_ES
QB2_EX2
VPQB2 QC1REL
VPQB6 QC1ITL
QB2_OP & 1
QC2REL
QB6_OP QC2ITL
VPQB6 1
VPQB9 QC3REL
VPCQB62 &
QC3ITL
1
QB6_OP
QB9_OP
CQB62_OP
VPQA1 QB9REL
VPQB6 QB9ITL
VPQC9 & >1 1
VPQC1
VPQC2
VPQC3
VPCQA1
VPCQB62
VPCQC1
VPCQC2
QB9_EX1
QB6_OP
QB9_EX2
>1
QA1_OP
QC1_OP
QC2_OP &
QB9_EX3
en04000558.vsd
CQB62_OP
QB9_EX4
>1 & >1
CQA1_OP
CQC1_OP
CQC2_OP &
QB9_EX5
QC9_OP
QC3_OP
QB9_EX6
VPQC9
VPQC3
&
QC9_CL
QC3_CL
QB9_EX7
VPQB9 QC9REL
VPVOLT QC9ITL
QB9_OP & 1
VOLT_OFF
QB2_OP QB2OPTR
QB2_CL QB2CLTR
VPQB2 VPQB2TR
en04000559.vsd
BH_CONN
QA1_OP
QA1_CL =1 VPQA1
QB61_OP
QB61_CL =1 VPQB61
QB62_OP
QB62_CL =1 VPQB62
QC1_OP
QC1_CL =1 VPQC1
QC2_OP
QC2_CL =1 VPQC2
1QC3_OP
1QC3_CL =1 VP1QC3
2QC3_OP
2QC3_CL =1 VP2QC3
VPQB61 QA1CLREL
VPQB62 & QA1CLITL
1
VPQA1
VPQC1 QB61REL
& >1
VPQC2 QB61ITL
1
VP1QC3
QA1_OP
QC1_OP
QC2_OP
1QC3_OP
QB61_EX1
VPQC1
VP1QC3
&
QC1_CL
1QC3_CL
QB61_EX2
VPQA1
VPQC1 QB62REL
& >1
VPQC2 QB62ITL
1
VP2QC3
QA1_OP
QC1_OP
QC2_OP
2QC3_OP
QB62_EX1
VPQC2
VP2QC3
&
QC2_CL
2QC3_CL
QB62_EX2
VPQB61 QC1REL
VPQB62 QC1ITL
& 1
QB61_OP QC2REL
QB62_OP QC2ITL
1
en04000560.vsd
Table 226: Input signals for the BH_LINE_A (IL01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB6_OP QB6 is in open position
QB6_CL QB6 is in close position
QB1_OP QB1 is in open position
QB1_CL QB1 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QB9_OP QB9 is in open position
QB9_CL QB9 is in closed position
QC9_OP QC9 is in open position
QC9_CL QC9 is in closed position
CQA1_OP QA1 in module BH_CONN is in open position
CQA1_CL QA1 in module BH_CONN is in closed position
CQB61_OP QB61 in module BH_CONN is in open position
CQB61_CL QB61 in module BH_CONN is in closed position
CQC1_OP QC1 in module BH_CONN is in open position
CQC1_CL QC1 in module BH_CONN is in closed position
CQC2_OP QC2 in module BH_CONN is in open position
CQC2_CL QC2 in module BH_CONN is in closed position
QC11_OP Earthing switch QC11 on busbar WA1 is in open position
QC11_CL Earthing switch QC11 on busbar WA1 is in closed position
VOLT_OFF There is no voltage on line and not VT (fuse) failure
VOLT_ON There is voltage on the line or there is a VT (fuse) failure
EXDU_ES No transm error from bay containing earthing switch QC11
QB6_EX1 External condition for apparatus QB6
QB6_EX2 External condition for apparatus QB6
QB1_EX1 External condition for apparatus QB1
QB1_EX2 External condition for apparatus QB1
QB9_EX1 External condition for apparatus QB9
QB9_EX2 External condition for apparatus QB9
QB9_EX3 External condition for apparatus QB9
QB9_EX4 External condition for apparatus QB9
Table continued on next page
Signal Description
QB9_EX5 External condition for apparatus QB9
QB9_EX6 External condition for apparatus QB9
QB9_EX7 External condition for apparatus QB9
Table 227: Output signals for the BH_LINE_A (IL01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB6REL Switching of QB6 is allowed
QB6ITL Switching of QB6 is forbidden
QB1REL Switching of QB1 is allowed
QB1ITL Switching of QB1 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QC3REL Switching of QC3 is allowed
QC3ITL Switching of QC3 is forbidden
QB9REL Switching of QB9 is allowed
QB9ITL Switching of QB9 is forbidden
QC9REL Switching of QC9 is allowed
QC9ITL Switching of QC9 is forbidden
QB1OPTR QB1 is in open position
QB1CLTR QB1 is in closed position
VPQB1TR Switch status of QB1 is valid (open or closed)
Table 228: Input signals for the BH_LINE_B (IM01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB6_OP QB6 is in open position
QB6_CL QB6 is in close position
QB2_OP QB2 is in open position
QB2_CL QB2 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
Table continued on next page
Signal Description
QC2_CL QC2 is in closed position
QC3_OP QC3 is in open position
QC3_CL QC3 is in closed position
QB9_OP QB9 is in open position
QB9_CL QB9 is in closed position
QC9_OP QC9 is in open position
QC9_CL QC9 is in closed position
CQA1_OP QA1 in module BH_CONN is in open position
CQA1_CL QA1 in module BH_CONN is in closed position
CQB62_OP QB62 in module BH_CONN is in open position
CQB62_CL QB62 in module BH_CONN is in closed position
CQC1_OP QC1 in module BH_CONN is in open position
CQC1_CL QC1 in module BH_CONN is in closed position
CQC2_OP QC2 in module BH_CONN is in open position
CQC2_CL QC2 in module BH_CONN is in closed position
QC21_OP Earthing switch QC21 on busbar WA2 is in open position
QC21_CL Earthing switch QC21 on busbar WA2 is in closed position
VOLT_OFF There is no voltage on line and not VT (fuse) failure
VOLT_ON There is voltage on the line or there is a VT (fuse) failure
EXDU_ES No transm error from bay containing earthing switch QC21
QB6_EX1 External condition for apparatus QB6
QB6_EX2 External condition for apparatus QB6
QB2_EX1 External condition for apparatus QB2
QB2_EX2 External condition for apparatus QB2
QB9_EX1 External condition for apparatus QB9
QB9_EX2 External condition for apparatus QB9
QB9_EX3 External condition for apparatus QB9
QB9_EX4 External condition for apparatus QB9
QB9_EX5 External condition for apparatus QB9
QB9_EX6 External condition for apparatus QB9
QB9_EX7 External condition for apparatus QB9
Table 229: Output signals for the BH_LINE_B (IM01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB6REL Switching of QB6 is allowed
QB6ITL Switching of QB6 is forbidden
Table continued on next page
Signal Description
QB2REL Switching of QB2 is allowed
QB2ITL Switching of QB2 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
QC3REL Switching of QC3 is allowed
QC3ITL Switching of QC3 is forbidden
QB9REL Switching of QB9 is allowed
QB9ITL Switching of QB9 is forbidden
QC9REL Switching of QC9 is allowed
QC9ITL Switching of QC9 is forbidden
QB2OPTR QB2 is in open position
QB2CLTR QB2 is in closed position
VPQB2TR Switch status of QB2 is valid (open or closed)
Table 230: Input signals for the BH_CONN (IK01-) function block
Signal Description
QA1_OP QA1 is in open position
QA1_CL QA1 is in closed position
QB61_OP QB61 is in open position
QB61_CL QB61 is in closed position
QB62_OP QB62 is in open position
QB62_CL QB62 is in closed position
QC1_OP QC1 is in open position
QC1_CL QC1 is in closed position
QC2_OP QC2 is in open position
QC2_CL QC2 is in closed position
1QC3_OP QC3 on line 1 is in open position
1QC3_CL QC3 on line 1 is in closed position
2QC3_OP QC3 on line 2 is in open position
2QC3_CL QC3 on line 2 is in closed position
QB61_EX1 External condition for apparatus QB61
QB61_EX2 External condition for apparatus QB61
QB62_EX1 External condition for apparatus QB62
QB62_EX2 External condition for apparatus QB62
Table 231: Output signals for the BH_CONN (IK01-) function block
Signal Description
QA1CLREL Closing of QA1 is allowed
QA1CLITL Closing of QA1 is forbidden
QB61REL Switching of QB61 is allowed
QB61ITL Switching of QB61 is forbidden
QB62REL Switching of QB62 is allowed
QB62ITL Switching of QB62 is forbidden
QC1REL Switching of QC1 is allowed
QC1ITL Switching of QC1 is forbidden
QC2REL Switching of QC2 is allowed
QC2ITL Switching of QC2 is forbidden
11.5.1 Introduction
The Logic rotating switch for function selection and LHMI presentation (LSR, or the
selector switch function block, as it is also known) is used within the CAP tool in
order to get a selector switch functionality similar with the one provided by a hardware
selector switch. Hardware selector switches are used extensively by utilities, in order
to have different functions operating on pre-set values. Hardware switches are
however sources for maintenance issues, lower system reliability and extended
purchase portfolio. The virtual selector switches eliminate all these problems.
The LSR has two operating inputs – UP and DOWN. When a signal is received on
the UP input, the block will activate the output next to the present activated output,
in ascending order (if the present activated output is 3 – for example and one operates
the UP input, then the output 4 will be activated). When a signal is received on the
DOWN input, the block will activate the output next to the present activated output,
in descending order (if the present activated output is 3 – for example and one operates
the DOWN input, then the output 2 will be activated). Depending on the output
settings the output signals can be steady or pulsed. In case of steady signals, in case
of UP or DOWN operation, the previously active output will be deactivated. Also,
depending on the settings one can have a time delay between the UP or DOWN
activation signal positive front and the output activation.
Repeated down or up when end position has been reached will give repeated pulses
on the selected step. This can e.g. be used to have multiple activations on two position
switches.
One can block the function operation, by activating the BLOCK input. In this case,
the present position will be kept and further operation will be blocked. The operator
place (local or remote) is specified through the PSTO input.
The LSR function block has also an integer value output, that generates the actual
position number. The positions names are fully settable by the user.
en05000658.vsd
Table 232: Input signals for the SSGGIO (LRS1-) function block
Signal Description
BLOCK Block of function.
PSTO Operator place selection.
UP Binary "UP" command
DOWN Binary "DOWN" command
Table 233: Output signals for the SSGGIO (LRS1-) function block
Signal Description
SWPOS01 Selector switch position 1
SWPOS02 Selector switch position 2
SWPOS03 Selector switch position 3
SWPOS04 Selector switch position 4
SWPOS05 Selector switch position 5
SWPOS06 Selector switch position 6
SWPOS07 Selector switch position 7
SWPOS08 Selector switch position 8
SWPOS09 Selector switch position 9
SWPOS10 Selector switch position 10
SWPOS11 Selector switch position 11
SWPOS12 Selector switch position 12
SWPOS13 Selector switch position 13
SWPOS14 Selector switch position 14
SWPOS15 Selector switch position 15
SWPOS16 Selector switch position 16
SWPOS17 Selector switch position 17
SWPOS18 Selector switch position 18
SWPOS19 Selector switch position 19
SWPOS20 Selector switch position 20
SWPOS21 Selector switch position 21
SWPOS22 Selector switch position 22
SWPOS23 Selector switch position 23
SWPOS24 Selector switch position 24
SWPOS25 Selector switch position 25
SWPOS26 Selector switch position 26
SWPOS27 Selector switch position 27
SWPOS28 Selector switch position 28
Table continued on next page
Signal Description
SWPOS29 Selector switch position 29
SWPOS30 Selector switch position 30
SWPOS31 Selector switch position 31
SWPOS32 Selector switch position 32
SWPOSN Switch position (integer).
NAME01 User define string for position 1
NAME02 User define string for position 2
NAME03 User define string for position 3
NAME04 User define string for position 4
NAME05 User define string for position 5
NAME06 User define string for position 6
NAME07 User define string for position 7
NAME08 User define string for position 8
NAME09 User define string for position 9
NAME10 User define string for position 10
NAME11 User define string for position 11
NAME12 User define string for position 12
NAME13 User define string for position 13
NAME14 User define string for position 14
NAME15 User define string for position 15
NAME16 User define string for position 16
NAME17 User define string for position 17
NAME18 User define string for position 18
NAME19 User define string for position 19
NAME20 User define string for position 20
NAME21 User define string for position 21
NAME22 User define string for position 22
NAME23 User define string for position 23
NAME24 User define string for position 24
NAME25 User define string for position 25
NAME26 User define string for position 26
NAME27 User define string for position 27
NAME28 User define string for position 28
NAME29 User define string for position 29
NAME30 User define string for position 30
NAME31 User define string for position 31
NAME32 User define string for position 32
Table 235: Parameter group settings for the SSGGIO (LRS1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off/On
On
NrPos 2 - 32 1 32 - Number of positions
in the switch
OutType Pulsed - Steady - Output type, steady
Steady (=1) or pulse (=0)
tPulse 0.000 - 60.000 0.001 0.200 s Operate pulse
duration, in [s]
tDelay 0.000 - 60000.000 0.010 0.000 s Time delay on the
output, in [s]
11.6.1 Introduction
The DPGGIO function block is used to send three logical signals to other systems or
equipment in the substation. It is especially conceived to be used in the interlocking
and reservation station-wide logics.
en07000200.vsd
Table 236: Input signals for the DPGGIO (DP01-) function block
Signal Description
OPEN Open indication
CLOSE Close indication
VALID Valid indication
Table 237: Output signals for the DPGGIO (DP01-) function block
Signal Description
POSITION Double point indication
Also Local acceleration logic (ZCLC) is discussed which is a function that can
generate instantaneous tripping as a result of remote end faults without any
telecommunication.
The chapter contains a short description of the design, simplified logical block
diagrams, figure of the function block, input and output signals and setting
parameters.
12.1.1 Introduction
To achieve instantaneous fault clearance for all line faults, a scheme communication
logic is provided. All types of communication schemes e.g. permissive underreach,
permissive overreach, blocking, intertrip etc. are available. The built-in
communication module (LDCM) can be used for scheme communication signalling
when included.
Logic for loss of load and/or local acceleration in co-operation with autoreclose
function is also provided for application where no communication channel is
available.
A permissive scheme is inherently faster and has better security against false tripping
than a blocking scheme. On the other hand, a permissive scheme depends on a
received signal for a fast trip, so its dependability is lower than that of a blocking
scheme.
The received signal, which shall be connected to CR, is used to not release the zone
to be accelerated to clear the fault instantaneously (after time tCoord). The
overreaching zone to be accelerated is connected to the input CACC, see
figure 235.
In case of external faults, the blocking signal (CR) must be received before the settable
timer tCoord elapses, to prevent a false trip, see figure 235.
The function can be totally blocked by activating the input BLOCK, block of trip by
activating the input BLKTR, Block of carrier send by activating the input BLKCS.
tCoord
CACC
t TRIP
CR AND
en05000512.vsd
The logic for trip carrier in permissive scheme is shown in figure 236.
tCoord
CACC
t TRIP
CR AND
en05000513.vsd
The permissive underreach scheme has the same blocking possibilities as mentioned
for blocking scheme above.
The logic for trip carrier is the same as for permissive underreach, i.e. figure 236.
The permissive overreach scheme has the same blocking possibilities as mentioned
for blocking scheme above.
The unblocking function uses a carrier guard signal CRG, which must always be
present, even when no CR signal is received. The absence of the CRG signal for a
time longer than the setting tSecurity time is used as a CR signal, see figure 237. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The carrier received signal created by the unblocking function is reset 150 ms after
the security timer has elapsed. When that occurs an output signal LCG is activated
for signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG
en05000746.vsd
The unblocking function can be set in three operation modes (setting Unblock):
In the direct inter-trip scheme, the carrier send signal CS is sent from an underreaching
zone that is tripping the line.
The received signal CR is directly transferred to a TRIP for tripping without local
criteria. The signal is further processed in the tripping logic. In case of single-pole
tripping in multi-phase systems, a phase selection is performed.
The simplified logic diagram for the complete logic is shown in figure 238.
Unblock =
Off
CR
Unblock =
OR CRL
NoRestart AND
CRL
Unblock =
tSecurit
Restart
y
CRG 1 t AND
SchemeType =
Intertrip
CSUR
tSendMi
n AND
OR
BLOCK AND
CSBLK OR
CRL
Schemetype =
Permissive UR AND CS
OR
tCoord
AND 25 ms
OR t TRIP
CACC t
Schemetype =
Permissive OR
CSOR OR AND
AND
tSendMin
OR
AND
SchemeType =
Blocking
BLKCS
AND
en05000515.vsd
Figure 238: Scheme communication logic for distance protection, simplified logic
diagram
en05000332.vsd
Table 238: Input signals for the ZCPSCH_85 (ZCOM-) function block
Signal Description
BLOCK Block of function
BLKTR Signal for block of trip output from communication logic
BLKCS Block of carrier send in permissive OR and blocking schemes
CSBLK Reverse directed distance protection zone signal
CACC Permissive distance protection zone signal
CSOR Overreaching distance protection zone signal
CSUR Underreaching distance protection zone signal
CR Carrier Signal Received
CRG Carrier guard signal received
Table 239: Output signals for the ZCPSCH_85 (ZCOM-) function block
Signal Description
TRIP Trip output
CS Carrier Send signal
CRL Carrier signal received or missing carrier guard signal
LCG Loss of carrier guard signal
Table 240: Parameter group settings for the ZCPSCH_85 (ZCOM-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
SchemeType Off - Permissive UR - Scheme type
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 0.001 0.035 s Co-ordination time for
blocking
communication
scheme
tSendMin 0.000 - 60.000 0.001 0.100 s Minimum duration of a
carrier send signal
Unblock Off - Off - Operation mode of
NoRestart unblocking logic
Restart
tSecurity 0.000 - 60.000 0.001 0.035 s Security timer for loss
of carrier guard
detection
Table 241: Scheme communication logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Scheme type Intertrip -
Permissive UR
Permissive OR
Blocking
Co-ordination time for blocking (0.000-60.000) s ± 0.5% ± 10 ms
communication scheme
Minimum duration of a carrier send (0.000-60.000) s ± 0.5% ± 10 ms
signal
Security timer for loss of carrier guard (0.000-60.000) s ± 0.5% ± 10 ms
detection
Operation mode of unblocking logic Off -
NoRestart
Restart
12.2.1 Introduction
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach protection schemes in application with
parallel lines when the overreach from the two ends overlaps on the parallel line.
The weak-end infeed logic is used in cases where the apparent power behind the
protection can be too low to activate the distance protection function. When activated,
received carrier signal together with local under voltage criteria and no reverse zone
operation gives an instantaneous trip. The received signal is also echoed back to
accelerate the sending end.
The current reversal logic uses a reverse zone connected to the input IRLV to
recognize the fault on the parallel line. When the reverse zone has been activated for
a certain settable time tPickUpRev it prevents sending of a communication signal and
activation of trip signal for a predefined time tDelayRev. This makes it possible for
the carrier receive signal to reset before the carrier aided trip signal is activated due
to the current reversal by the forward directed zone, see figure 240.
The preventing of sending carrier send signal CS and activating of the TRIP in the
scheme communication block ZCOM is carried out by connecting the IRLV signal
to input BLOCK in the ZCOM function.
The function has an internal 10 ms drop-off timer which secure that the current
reversal logic will be activated for short input signals even if the pick-up timer is set
to zero.
The WEI function sends back (echoes) the received carrier signal under the condition
that no fault has been detected on the weak end by different fault detection elements
(distance protection in forward and reverse direction).
The WEI function returns the received carrier signal, see figure 241, when:
• The functional input CRL is active. This input is usually connected to the CRL
output on the scheme communication logic ZCOM.
• The WEI function is not blocked by the active signal connected to the WEIBLK1
functional input or to the VTSZ functional input. The latest is usually configured
to the STGEN functional output of the fuse-failure function.
• No active signal has been present for at least 200 ms on the WEIBLK2 functional
input. An OR combination of all fault detection functions (not undervoltage) as
present within the terminal is usually used for this purpose.
When an echo function is used in both terminals, a spurious signal can be looped
round by the echo logics. To avoid a continuous lock-up of the system, the duration
of the echoed signal is limited to 200 ms.
en05000334.vsd
Table 242: Input signals for the ZCRWPSCH_85 (ZCAL-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
IRVBLK Block of current reversal function
IRV Activation of current reversal logic
WEIBLK1 Block of WEI logic
WEIBLK2 Block of WEI logic due to operation of other protections
VTSZ Block of trip from WEI logic through fuse-failure function
CBOPEN Block of trip from WEI logic by an open breaker
CRL POR Carrier receive for WEI logic
Table 243: Output signals for the ZCRWPSCH_85 (ZCAL-) function block
Signal Description
IRVL Operation of current reversal logic
TRWEI Trip of WEI logic
TRWEIL1 Trip of WEI logic in phase L1
TRWEIL2 Trip of WEI logic in phase L2
TRWEIL3 Trip of WEI logic in phase L3
ECHO Carrier send by WEI logic
Table 244: Parameter group settings for the ZCRWPSCH_85 (ZCAL-) function
Parameter Range Step Default Unit Description
CurrRev Off - Off - Operating mode of
On Current Reversal
Logic
tPickUpRev 0.000 - 60.000 0.001 0.020 s Pickup time for
current reversal logic
tDelayRev 0.000 - 60.000 0.001 0.060 s Time Delay to prevent
Carrier send and local
trip
WEI Off - Off - Operating mode of
Echo WEI logic
Echo & Trip
tPickUpWEI 0.000 - 60.000 0.001 0.010 s Coordination time for
the WEI logic
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage level
UPP< 10 - 90 1 70 %UB Phase to Phase
voltage for detection
of fault condition
UPN< 10 - 90 1 70 %UB Phase to Neutral
voltage for detection
of fault condition
Table 245: Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Function Range or value Accuracy
Detection level phase to neutral (10-90)% of Ubase ± 1.0% of Ur
voltage
Detection level phase to phase (10-90)% of Ubase ± 1.0% of Ur
voltage
Reset ratio <105% -
Table continued on next page
12.3.1 Introduction
To achieve fast clearing of faults on the whole line, when no communication channel
is available, local acceleration logic (ZCLC) can be used. This logic enables fast fault
clearing during certain conditions, but naturally, it can not fully replace a
communication channel.
The logic can be controlled either by the auto re-closer (zone extension) or by the
loss of load current (loss-of-load acceleration).
The overreaching zone is connected to the input -EXACC. For this reason, configure
the ARREADY functional input to a READY functional output of a used auto-
reclosing function or via the selected binary input to an external autoreclosing device,
see figure 244.
After the auto-recloser initiates the close command and remains in the reclaim state,
there will be no ARREADY signal, and the protection will trip normally with step
distance time functions. In case of a fault on the adjacent line within the overreaching
zone range, an unwanted auto-reclosing cycle will occur. The step distance function
at the reclosing attempt will prevent an unwanted retrip when the breaker is reclosed.
On the other hand, at a persistent line fault on line section not covered by instantaneous
zone (normally zone 1) only the first trip will be "instantaneous".
The function will be blocked if the input BLOCK is activated (common with loss of
load acceleration).
When the "acceleration" is controlled by a loss of load, the overreaching zone used
for "acceleration" connected to LLACC is not allowed to trip "instantaneously" during
normal non-fault system conditions. When all three-phase currents have been above
the set value MinCurr for more than setting tLowCurr, an overreaching zone will be
allowed to trip "instantaneously" during a fault condition when one or two of the
phase currents will become low due to a three phase trip at the opposite terminal, see
figure 245. The current measurement is performed internally and the STILL signal
becomes logical one under the described conditions. The load current in a healthy
phase is in this way used to indicate the tripping at the opposite terminal. Note that
this function will not operate in case of three-phase faults, because none of the phase
currents will be low when the opposite terminal is tripped.
Breaker closing signals can if decided be connected to block the function during
normal closing.
en05000333.vsd
Table 246: Input signals for the ZCLC (ZCLC-) function block
Signal Description
I3P Group signal for current input
BLOCK Block of function
ARREADY Autoreclosure ready, releases function used for fast trip
NDST Non directional criteria used to prevent instantaneous trip
EXACC Connected to function used for tripping at zone xtension
BC Breaker Close
LLACC Connected to function used for tripping at loss of load
Table 247: Output signals for the ZCLC (ZCLC-) function block
Signal Description
TRZE Trip by zone extension
TRLL Trip by loss of load
Table 248: Parameter group settings for the ZCLC (ZCLC-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
IBase 1 - 99999 1 3000 A Base setting for
current values
LoadCurr 1 - 100 1 10 %IB Load current before
disturbance in % of
IBase
LossOfLoad Off - Off - Enable/Disable
On operation of Loss of
load.
ZoneExtension Off - Off - Enable/Disable
On operation of Zone
extension
MinCurr 1 - 100 1 5 %IB Lev taken as curr loss
due to remote CB trip
in % of IBase
tLowCurr 0.000 - 60.000 0.001 0.200 s Time delay on pick-up
for MINCURR value
tLoadOn 0.000 - 60.000 0.001 0.000 s Time delay on pick-up
for load current
release
tLoadOff 0.000 - 60.000 0.001 0.300 s Time delay on drop off
for load current
release
12.4.1 Introduction
To achieve fast fault clearance of earth faults on the part of the line not covered by
the instantaneous step of the residual overcurrent protection, the directional residual
overcurrent protection can be supported with a logic that uses communication
channels.
The communication logic module for directional residual current protection for the
REx670 IEDs enables blocking as well as permissive under/overreach schemes. The
logic can also be supported by additional logic for weak-end-infeed and current
reversal, included in the EFCA function.
In the blocking scheme a signal is sent to the other line end if the directional element
detects an earth fault in the reverse direction. When the forward directional element
operates, it trips after a short time delay if no blocking signal is received from the
other line end. The time delay, normally 30 – 40 ms, depends on the communication
transmission time and a chosen safety margin.
One advantage of the blocking scheme is that only one channel (carrier frequency) is
needed if the ratio of source impedances at both end is approximately equal for zero
and positive sequence source impedances, the channel can be shared with the
impedance-measuring system, if that system also works in the blocking mode. The
power line carrier communication signal is transmitted on a healthy line and no signal
attenuation will occur due to the fault.
If the fault is on the line, the forward direction measuring element operates. If no
blocking signal comes from the other line end via the CR binary input (carrier receive)
the TRIP output is activated after the tCoord set time delay.
In the permissive scheme the forward directed earth fault measuring element sends a
permissive signal to the other end, if an earth fault is detected in the forward direction.
The directional element at the other line end must wait for a permissive signal before
activating an operation signal. Independent channels must be available for the
communication in each direction.
An impedance measuring relay which works in the same type of permissive mode,
with one channel in each direction, can share the channels with the communication
scheme for residual overcurrent protection. If the impedance measuring relay works
in the permissive overreach mode, common channels can be used in single-line
applications. In case of double lines connected to a common bus at both ends, use
common channels only if the ratio Z1S/Z0S (positive through zero-sequence source
impedance) is about equal at both ends. If the ratio is different, the impedance
measuring and the directional earth-fault current system of the healthy line may detect
a fault in different directions, which could result in unwanted tripping.
Common channels cannot be used when the weak-end-infeed function is used in the
distance or earth fault protection.
In case of an internal earth fault, the forward directed measuring element operates
and sends a permissive signal to the remote end via the CS output (carrier send). Local
tripping is permitted when the forward direction measuring element operates and a
permissive signal is received via the CR binary input (carrier receive).
The permissive scheme can of either underreach or overreach type. In the underreach
alternative an underreach directional residual overcurrent measurement element will
be used as sending criterion of the permissive send signal CSUR.
The unblocking function uses a carrier guard signal CRG, which must always be
present, even when no CR signal is received. The absence of the CRG signal for a
time longer than the setting tSecurity time is used as a CR signal, see figure 248. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The carrier received signal created by the unblocking function is reset 150 ms after
the security timer has elapsed. When that occurs an output signal LCG is activated
for signalling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
CR
tSecurity CRL
t >1
1
CRG
200 ms 150 ms
t OR t AND
AND
LCG
en05000746.vsd
The unblocking function can be set in three operation modes (setting Unblock):
en05000659.vsd
Table 249: Input signals for the ECPSCH_85 (EFC1-) function block
Signal Description
BLOCK Block of function
BLKTR Signal for blocking trip due to communication logic
BLKCS Signal for blocking CS in Overreach and Blocking schemes
CSBLK Reverse residual overcurrent signal for Carrier Send
CACC Signal to be used for tripping by Communication Scheme
CSOR Overreaching residual overcurrent signal for Carrier Send
CSUR Underreaching residual overcurrent signal for Carrier Send
CR Carrier Receive for Communication Scheme Logic
CRG Carrier guard signal received
Table 250: Output signals for the ECPSCH_85 (EFC1-) function block
Signal Description
TRIP Trip by Communication Scheme Logic
CS Carrier Send by Communication Scheme Logic
CRL Carrier Receive from Communication Scheme Logic
LCG loss of carrier guard signal
Table 251: Parameter group settings for the ECPSCH_85 (EFC1-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off / On
On
SchemeType Off - Permissive UR - Scheme type, Mode
Intertrip of Operation
Permissive UR
Permissive OR
Blocking
tCoord 0.000 - 60.000 0.001 0.035 s Communication
scheme coordination
time
tSendMin 0.000 - 60.000 0.001 0.100 s Minimum duration of a
carrier send signal
Unblock Off - Off - Operation mode of
NoRestart unblocking logic
Restart
tSecurity 0.000 - 60.000 0.001 0.035 s Security timer for loss
of carrier guard
detection
Table 252: Scheme communication logic for residual overcurrent protection (PSCH, 85)
Function Range or value Accuracy
Communication scheme (0.000-60.000) s ± 0.5% ± 10 ms
coordination time
Scheme type Permissive UR -
Permissive OR
Blocking
12.5.1 Introduction
The EFCA additional communication logic is a supplement to the EFC scheme
communication logic for the residual overcurrent protection.
To achieve fast fault clearing for all earth faults on the line, the directional earth-fault
protection function can be supported with logic, that uses communication channels.
REx670 terminals have for this reason available additions to scheme communication
logic.
The directional comparison function contains logic for blocking overreach and
permissive overreach schemes.
The circuits for the permissive overreach scheme contain logic for current reversal
and weak end infeed functions. These functions are not required for the blocking
overreach scheme.
Use the independent or inverse time functions in the directional earth-fault protection
module to get back-up tripping in case the communication equipment malfunctions
and prevents operation of the directional comparison logic.
Connect the necessary signal from the auto-recloser for blocking of the directional
comparison scheme, during a single-phase auto-reclosing cycle, to the BLOCK input
of the directional comparison module.
The fault current reversal logic uses a reverse directed element, connected to IRV,
which recognizes that the fault is in reverse direction. When the reverse direction
element is activated during the tPickUp time, the IRVL signal is activated, see
figure 250. The logic is now ready to handle a current reversal without tripping. IRVL
will be connected to the block input on the permissive overreach scheme.
When the fault current is reversed on the non faulty line, IRV is deactivated and
IRVBLK is activated. The reset of IRVL is delayed by the tDelay time, see
figure 250. This ensures the reset of the carrier receive CR signal.
The weak end infeed function can be set to send only an echo signal (WEI=Echo) or
an echo signal and a trip signal (WEI=Trip). See figure 251 and figure 252.
The weak end infeed logic uses normally a reverse and a forward direction element,
connected to WEIBLK via an OR-gate. See figure 251. If neither the forward nor the
reverse directional measuring element is activated during the last 200 ms. The weak-
end-infeed logic echoes back the received permissive signal. See figure 251.
If the forward or the reverse directional measuring element is activated during the
last 200 ms, the fault current is sufficient for the IED to detect the fault with the earth-
fault function that is in operation.
With the Trip setting, the logic sends an echo according to above. Further, it activates
the TRWEI signal to trip the breaker if the echo conditions are fulfilled and the neutral
point voltage is above the set operate value for 3U0>
The voltage signal that is used to calculate the zero sequence voltage is set in the
earth-fault function that is in operation.
The weak end infeed echo sent to the strong line end has a maximum duration of 200
ms. When this time period has elapsed, the conditions that enable the echo signal to
be sent are set to zero for a time period of 50 ms. This avoids ringing action if the
weak end echo is selected for both line ends.
en05000335.vsd
Table 253: Input signals for the ECRWPSCH_85 (EFCA-) function block
Signal Description
U3P Group signal for voltage input
BLOCK Block of function
IRVBLK Block of current reversal function
IRV Activation of current reversal logic
WEIBLK1 Block of WEI Logic
WEIBLK2 Block of WEI logic due to operation of other protections
VTSZ Block of trip from WEI logic through fuse-failure function
CBOPEN Block of trip from WEI logic by an open breaker
CRL POR Carrier receive for WEI logic
Table 254: Output signals for the ECRWPSCH_85 (EFCA-) function block
Signal Description
IRVL Operation of current reversal logic
TRWEI Trip of WEI logic
ECHO Carrier send by WEI logic
CR POR Carrier signal received from remote end
Table 255: Parameter group settings for the ZCRWPSCH_85 (ZCAL-) function
Parameter Range Step Default Unit Description
CurrRev Off - Off - Operating mode of
On Current Reversal
Logic
tPickUpRev 0.000 - 60.000 0.001 0.020 s Pickup time for
current reversal logic
tDelayRev 0.000 - 60.000 0.001 0.060 s Time Delay to prevent
Carrier send and local
trip
WEI Off - Off - Operating mode of
Echo WEI logic
Echo & Trip
tPickUpWEI 0.000 - 60.000 0.001 0.010 s Coordination time for
the WEI logic
UBase 0.05 - 2000.00 0.05 400.00 kV Base setting for
voltage level
UPP< 10 - 90 1 70 %UB Phase to Phase
voltage for detection
of fault condition
UPN< 10 - 90 1 70 %UB Phase to Neutral
voltage for detection
of fault condition
Table 256: Current reversal and weak-end infeed logic for residual overcurrent protection (PSCH,
85)
Function Range or value Accuracy
Operate voltage 3Uo for WEI trip (5-70)% of Ubase ± 1.0% of Ur
Section 13 Logic
13.1.1 Introduction
A function block for protection tripping is provided for each circuit breaker involved
in the tripping of the fault. It provides the pulse prolongation to ensure a trip pulse of
sufficient length, as well as all functionality necessary for correct co-operation with
autoreclosing functions.
The trip function block includes functionality for evolving faults and breaker lock-
out.
For three-pole tripping, TRPx function has a single input (TRIN) through which all
trip output signals from the protection functions within the IED, or from external
protection functions via one or more of the IEDs binary inputs, are routed. It has a
single trip output (TRIP) for connection to one or more of the IEDs binary outputs,
as well as to other functions within the IED requiring this signal.
BLOCK
tTripMin TRIP
TRIN OR
AND t
Operation Mode = On
Program = 3Ph
en05000789.vsd
The TRPx function for single- and two-pole tripping has additional phase segregated
inputs for this, as well as inputs for faulted phase selection. The latter inputs enable
single- and two-pole tripping for those functions which do not have their own phase
selection capability, and therefore which have just a single trip output and not phase
segregated trip outputs for routing through the phase segregated trip inputs of the
expanded TRPx function. Examples of such protection functions are the residual
overcurrent protections. The expanded TRPx function has two inputs for these
functions, one for impedance tripping (e.g. carrier-aided tripping commands from the
scheme communication logic), and one for earth fault tripping (e.g. tripping output
from a residual overcurrent protection). Additional logic secures a three-pole final
trip command for these protection functions in the absence of the required phase
selection signals.
The expanded TRPx function has three trip outputs TRL1, TRL2, TRL3 (besides the
trip output TRIP), one per phase, for connection to one or more of the IEDs binary
outputs, as well as to other functions within the IED requiring these signals. There
are also separate output signals indicating single pole, two pole or three pole trip.
These signals are important for cooperation with the auto-reclosing function.
The expanded TRPx function is equipped with logic which secures correct operation
for evolving faults as well as for reclosing on to persistent faults. A special input is
also provided which disables single- and two-pole tripping, forcing all tripping to be
three-pole.
In multi-breaker arrangements, one TRPx function block is used for each breaker.
This can be the case if single pole tripping and auto-reclosing is used.
The breaker close lockout function can be activated from an external trip signal from
another protection function via input (SETLKOUT) or internally at a three pole trip,
if desired.
It is possible to lockout seal in the tripping output signals or use blocking of closing
only the choice is by setting TripLockout.
TRINL1
TRINL2
OR
TRINL3
1PTRZ OR
1PTREF
OR
TRIN RSTTRIP - cont.
AND
Program = 3ph
en05000517.vsd
en05000707.vsd
Table 257: Input signals for the SMPPTRC_94 (TRP1-) function block
Signal Description
BLOCK Block of function
BLKLKOUT Blocks circuit breaker lockout output (CLLKOUT)
TRIN Trip all phases
TRINL1 Trip phase 1
TRINL2 Trip phase 2
TRINL3 Trip phase 3
PSL1 Functional input for phase selection in phase L1
PSL2 Functional input for phase selection in phase L2
PSL3 Functional input for phase selection in phase L3
1PTRZ Zone Trip with a separate phase selection
1PTREF Single phase DEF Trip for separate phase selection
P3PTR Prepare all tripping to be three-phase
SETLKOUT Input for setting the circuit breaker lockout function
RSTLKOUT Input for resetting the circuit breaker lockout function
Table 258: Output signals for the SMPPTRC_94 (TRP1-) function block
Signal Description
TRIP General trip output signal
TRL1 Trip signal from phase L1
TRL2 Trip signal from phase L2
Table continued on next page
Signal Description
TRL3 Trip signal from phase L3
TR1P Tripping single-pole
TR2P Tripping two-pole
TR3P Tripping three-pole
CLLKOUT Circuit breaker lockout output (set until reset)
Table 259: Parameter group settings for the SMPPTRC_94 (TRP1-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
Program 3 phase - 1ph/3ph - Three ph; single or
1ph/3ph three ph; single, two
1ph/2ph/3ph or three ph trip
TripLockout Off - Off - On: activate output
On (CLLKOUT) and trip
latch, Off: only outp
AutoLock Off - Off - On: lockout from input
On (SETLKOUT) and
trip, Off: only inp
tTripMin 0.000 - 60.000 0.001 0.150 s Minimum duration of
trip output signal
13.2.1 Introduction
Twelve trip matrix logic blocks are included in the IED. The function blocks are used
in the configuration of the IED to route trip signals and/or other logical output signals
to the different output relays.
The matrix and the physical outputs will be seen in the PCM 600 engineering tool
and this allows the user to adapt the signals to the physical tripping outputs according
to the specific application needs.
Internal built-in OR logic is made in accordance with the following three rules:
1. when any one of first 16 inputs signals (i.e. INPUT1 to INPUT16) has logical
value 1 (i.e. TRUE) the first output signal (i.e. OUTPUT1) will get logical value
1 (i.e. TRUE). Additional time delays can be introduced for OUTPUT1 via
setting parameters "PulseTime1", "OnDelayTime1" & "OffDelayTime1".
2. when any one of second 16 inputs signals (i.e. INPUT17 to INPUT32) has logical
value 1 (i.e. TRUE) the second output signal (i.e. OUTPUT2) will get logical
value 1 (i.e. TRUE). Additional time delays can be introduced for OUTPUT2
via setting parameters "PulseTime2", "OnDelayTime2" & "OffDelayTime2"
3. when any one of all 32 input signals (i.e. INPUT1 to INPUT32) has logical value
1 (i.e. TRUE) the third output signal (i.e. OUTPUT3) will get logical value 1
(i.e. TRUE). Additional time delays can be introduced for OUTPUT3 via setting
parameters "PulseTime3", "OnDelayTime3" & "OffDelayTime3".
Output signals from this function block are typically connected to other logic blocks
or directly to output contacts from the IED. When used for direct tripping of the circuit
breaker(s) the pulse time delay on that output signal shall be set to approximately
0,150s in order to obtain satisfactory minimum duration of the trip pulse to the circuit
breaker trip coils.
en05000370.vsd
Table 261: Input signals for the TRMGGIO (TR01-) function block
Signal Description
INPUT1 Binary input 1
INPUT2 Binary input 2
INPUT3 Binary input 3
INPUT4 Binary input 4
INPUT5 Binary input 5
INPUT6 Binary input 6
INPUT7 Binary input 7
INPUT8 Binary input 8
INPUT9 Binary input 9
INPUT10 Binary input 10
INPUT11 Binary input 11
INPUT12 Binary input 12
INPUT13 Binary input 13
Table continued on next page
Signal Description
INPUT14 Binary input 14
INPUT15 Binary input 15
INPUT16 Binary input 16
INPUT17 Binary input 17
INPUT18 Binary input 18
INPUT19 Binary input 19
INPUT20 Binary input 20
INPUT21 Binary input 21
INPUT22 Binary input 22
INPUT23 Binary input 23
INPUT24 Binary input 24
INPUT25 Binary input 25
INPUT26 Binary input 26
INPUT27 Binary input 27
INPUT28 Binary input 28
INPUT29 Binary input 29
INPUT30 Binary input 30
INPUT31 Binary input 31
INPUT32 Binary input 32
Table 262: Output signals for the TRMGGIO (TR01-) function block
Signal Description
OUTPUT1 Binary output 1
OUTPUT2 Binary output 2
OUTPUT3 Binary output 3
Table 263: Parameter group settings for the TRMGGIO (TR01-) function
Parameter Range Step Default Unit Description
Operation Off - On - Operation Off / On
On
PulseTime1 0.000 - 60.000 0.001 0.000 s Output pulse time for
output 1
OnDelayTime1 0.000 - 60.000 0.001 0.000 s Output on delay time
for output 1
OffDelayTime1 0.000 - 60.000 0.001 0.000 s Output off delay time
for output 1
Table continued on next page
13.3.1 Introduction
A high number of logic blocks and timers are available for user to adapt the
configuration to the specific application needs.
I001-
INV
INPUT OUT
en04000404.vsd
Table 264: Input signals for the INV (I001-) function block
Signal Description
INPUT Input
Table 265: Output signals for the INV (I001-) function block
Signal Description
OUT Output
O001-
OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6
en04000405.vsd
A001-
AND
INPUT 1 OUT
INPUT 2 NOUT
INPUT 3
INPUT 4N
en04000406.vsd
Table 268: Input signals for the AND (A001-) function block
Signal Description
INPUT1 Input 1
INPUT2 Input 2
INPUT3 Input 3
INPUT4N Input 4 inverted
Table 269: Output signals for the AND (A001-) function block
Signal Description
OUT Output
NOUT Output inverted
T M01-
Timer
INPUT ON
T OFF
en04000378.vsd
Table 270: Input signals for the Timer (TM01-) function block
Signal Description
INPUT Input to timer
Table 271: Output signals for the Timer (TM01-) function block
Signal Description
ON Output from timer , pick-up delayed
OFF Output from timer, drop-out delayed
TP01-
Pulse
INPUT OUT
en04000407.vsd
Table 273: Input signals for the Pulse (TP01-) function block
Signal Description
INPUT Input to pulse timer
Table 274: Output signals for the Pulse (TP01-) function block
Signal Description
OUT Output from pulse timer
XO01-
XOR
INPUT 1 OUT
INPUT 2 NOUT
en04000409.vsd
Table 276: Input signals for the XOR (XO01-) function block
Signal Description
INPUT1 Input 1 to XOR gate
INPUT2 Input 2 to XOR gate
Table 277: Output signals for the XOR (XO01-) function block
Signal Description
OUT Output from XOR gate
NOUT Inverted output from XOR gate
SM01-
SRM
SET OUT
RESET NOUT
en04000408.vsd
Table 278: Input signals for the SRM (SM01-) function block
Signal Description
SET Set input
RESET Reset input
Table 279: Output signals for the SRM (SM01-) function block
Signal Description
OUT Output
NOUT Output inverted
Table 280: Parameter group settings for the SRM (SM01-) function
Parameter Range Step Default Unit Description
Memory Off - Off - Operating mode of
On the memory function
GT 01-
GT
INPUT OUT
en04000410.vsd
TS01-
TimerSet
INPUT ON
OFF
en04000411.vsd
Table 284: Input signals for the TimerSet (TS01-) function block
Signal Description
INPUT Input to timer
Table 285: Output signals for the TimerSet (TS01-) function block
Signal Description
ON Output from timer, pick-up delayed
OFF Output from timer, drop-out delayed
Table 286: Parameter group settings for the TimerSet (TS01-) function
Parameter Range Step Default Unit Description
Operation Off - Off - Operation Off/On
On
t 0.000 - 90000.000 0.001 0.000 s Delay for settable
timer n
13.4.1 Introduction
The fixed signals function block generates a number of pre-set (fixed) signals that
can be used in the configuration of an IED, either for forcing the unused inputs in the
other function blocks to a certain level/value, or for creating a certain logic.
en05000445.vsd
Table 288: Output signals for the FixedSignals (FIXD-) function block
Signal Description
OFF Boolean signal fixed off
ON Boolean signal fixed on
INTZERO Integer signal fixed zero
INTONE Integer signal fixed one
REALZERO Real signal fixed zero
STRNULL String signal with no characters
ZEROSMPL Channel id for zero sample
GRP_OFF Group signal fixed off
Section 14 Monitoring
14.1.1 Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM 600 or to station level (i.e.
IEC61850). The possibility to continuously monitor measured values of active power,
reactive power, currents, voltages, frequency, power factor etc. is vital for efficient
production, transmission and distribution of electrical energy. It provides to the
system operator fast and easy overview of the present status of the power system.
Additionally it can be used during testing and commissioning of protection and
control IEDs in order to verify proper operation and connection of instrument
transformers (i.e. CTs & VTs). During normal service by periodic comparison of the
measured value from the IED with other independent meters the proper operation of
the IED analog measurement chain can be verified. Finally it can be used to verify
proper direction orientation for distance or directional overcurrent protection
function.
All measured values can be supervised with four settable limits, i.e. low-low limit,
low limit, high limit and high-high limit. A zero clamping reduction is also supported,
i.e the measured value below a settable limit is forced to zero which reduces the impact
of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure value
can also be based on periodic reporting.
The measuring function, SVR, provides the following power system quantities:
It is possible to calibrate the measuring function above to get class 0.5 presentation.
This is accomplished by angle and amplitude compensation at 5, 30 and 100% of
rated current and voltage.
The IED can be provided with up to 3 SVR-, 10 CP-, 5 VP-, 3 CSQ- and 3 VSQ-
measurement functions.
The protection, control, and monitoring IEDs have functionality to measure and
further process information for currents and voltages obtained from the pre-
processing blocks. The number of processed alternate measuring quantities depends
on the type of IED and built-in options.
The information on measured quantities is available for the user at different locations:
• Overfunction, when the measured current exceeds the High limit (XHiLim) or
High-high limit (XHiHiLim) pre-set values
• Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.
X_RANGE = 3
High-high limit
X_RANGE= 1 Hysteresis
High limit
X_RANGE=0
X_RANGE=0 t
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
en05000657.vsd
Each analog output has one corresponding supervision level output (X_RANGE).
The output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded,
3: High-high limit exceeded, 2: below Low limit and 4: below Low-low limit). The
output may be connected to a measurement expander block (XP) to get measurement
supervision as binary signals.
The logical value of the functional output signals changes according to figure 273.
The user can set the hysteresis (XLimHyst), which determines the difference between
the operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one
channel.
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
Y
Value Reported Value Reported
Value Reported Value Reported
(1st)
Y3 Value Reported
Y2 Y4
Y1 Y5
t
Value 1
Value 2
Value 3
Value 4
Value 5
en05000500.vsd
(*)Set value for t: XDbRepInt
Value Reported
Y
99000529.vsd
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more than
defined by the ±ΔY set limits.
The last value reported, Y1 in figure 276 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
absolute values of these integral values are added until the pre-set value is exceeded.
This occurs with the value Y2 that is reported and set as a new base for the following
measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with
small variations that can last for relatively long periods.
Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
(1st) Value
Value Reported Y5
A Reported Value
Reported Value
Y1 Reported
t
99000530.vsd
Mode of operation
The measurement function must be connected to three-phase current and three-phase
voltage input in the configuration tool (group signals), but it is capable to measure
and calculate above mentioned quantities in nine different ways depending on the
available VT inputs connected to the IED. The end user can freely select by a
parameter setting, which one of the nine available measuring modes shall be used
within the function. Available options are summarized in the following table:
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
1 L1, L2, L3 Used when
* *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3
*
U = ( U L1 + U L 2 + U L 3 ) / 3 three phase-
to-earth
I = ( I L1 + I L 2 + I L 3 ) / 3 voltages are
available
2 Arone Used when
three two
S = U L1 L 2 × I L1 - U L 2 L 3 × I L 3
* *
U = ( U L1 L 2 + U L 2 L 3 ) / 2
phase-to-
phase
I = ( I L1 + I L 3 ) / 2 voltages are
available
3 PosSeq Used when
only
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq symmetrical
three phase
I = I PosSeq power shall
be measured
4 L1L2 Used when
only UL1L2
S = U L1 L 2 × ( I L1 - I L 2 )
* *
U = U L1 L 2
phase-to-
phase voltage
I = ( I L1 + I L 2 ) / 2 is available
Set value for Formula used for complex, three- Formula used for voltage and Comment
parameter phase power calculation current magnitude calculation
“Mode”
5 L2L3 Used when
only UL2L3
S = U L 2 L3 × ( I L 2 - I L3 )
* *
U = U L2 L3
phase-to-
phase voltage
I = ( I L2 + I L3 ) / 2 is available
7 L1 Used when
only UL1
S = 3 × U L1 × I L1
*
U = 3 × U L1
phase-to-
earth voltage
I = I L1 is available
8 L2 Used when
only UL2
S = 3 ×U L2 × I L2
*
U = 3 × U L2
phase-to-
earth voltage
I = IL2 is available
9 L3 Used when
only UL3
S = 3 ×U L3 × I L3
*
U = 3 × U L3
phase-to-
earth voltage
I = I L3 is available
It shall be noted that only in the first two operating modes (i.e. 1 & 2) the measurement
function calculates exact three-phase power. In other operating modes (i.e. from 3 to
9) it calculates the three-phase power under assumption that the power system is fully
symmetrical. Once the complex apparent power is calculated then the P, Q, S, & PF
are calculated in accordance with the following formulas:
P = Re( S )
(Equation 83)
Q = Im( S )
(Equation 84)
S = S = P +Q
2 2
(Equation 85)
PF = cosj = P
S (Equation 86)
Additionally to the power factor value the two binary output signals from the function
are provided which indicates the angular relationship between current and voltage
phasors. Binary output signal ILAG is set to one when current phasor is lagging
behind voltage phasor. Binary output signal ILEAD is set to one when current phasor
is leading the voltage phasor.
Each analog output has a corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4, see section "Measurement
supervision".
Amplitude
% of Ir compensation
-10
IAmpComp5 Measured
IAmpComp30 current
IAmpComp100
5 30 100 % of Ir
0-5%: Constant
-10 5-30-100%: Linear
>100%: Constant
Degrees Angle
compensation
-10
IAngComp30 Measured
current
IAngComp5
IAngComp100
5 30 100 % of Ir
-10
en05000652.vsd
The first current and voltage phase in the group signals will be used as reference and
the amplitude and angle compensation will be used for related input signals.
X = k × X Old + (1 - k ) × X Calculated
(Equation 87)
where:
X is a new measured value (i.e. P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle
k is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (i.e. without any additional delay). When
k is set to value bigger than 0, the filtering is enabled. Appropriate value of k shall be
determined separately for every application. Some typical value for k =0.14.
Compensation facility
In order to compensate for small magnitude and angular errors in the complete
measurement chain (i.e. CT error, VT error, IED input transformer errors etc.) it is
possible to perform on site calibration of the power measurement. This is achieved
by setting the complex constant which is then internally used within the function to
multiply the calculated complex apparent power S. This constant is set as magnitude
(i.e. setting parameter PowAmpFact, default value 1.000) and angle (i.e. setting
parameter PowAngComp, default value 0.0 degrees). Default values for these two
parameters are done in such way that they do not influence internally calculated value
(i.e. complex constant has default value 1). In this way calibration, for specific
operating range (e.g. around rated power) can be done at site. However to perform
this calibration it is necessary to have external power meter of the high accuracy class
available.
Directionality
In CT earthing parameter is set as described in section "Analog inputs", active and
reactive power will be measured always towards the protected object. This is shown
in the following figure 278.
Busbar
P Q
Protected
Object
en05000373.vsd
That practically means that active and reactive power will have positive values when
they flow from the busbar towards the protected object and they will have negative
values when they flow from the protected object towards the busbar.
In some application, like for example when power is measured on the secondary side
of the power transformer it might be desirable, from the end client point of view, to
have actually opposite directional convention for active and reactive power
measurements. This can be easily achieved by setting parameter PowAngComp to
value of 180.0 degrees. With such setting the active and reactive power will have
positive values when they flow from the protected object towards the busbar.
Frequency
Frequency is actually not calculated within measurement block. It is simply obtained
from the pre-processing block and then just given out from the measurement block
as an output.
Phase currents (amplitude and angle) are available on the outputs and each amplitude
output has a corresponding supervision level output (ILx_RANG). The supervision
output signal is an integer in the interval 0-4, see section "Measurement
supervision".
Phase to phase voltages (amplitude and angle) are available on the outputs and each
amplitude output has a corresponding supervision level output (ULxy_RANG). The
supervision output signal is an integer in the interval 0-4, see section "Measurement
supervision".
Positive, negative and three times zero sequence quantities are available on the
outputs (voltage and current, amplitude and angle). Each amplitude output has a
corresponding supervision level output (XRANGE). The output signal is an integer
in the interval 0-4, see section "Measurement supervision".
SVR1-
CVMMXU
I3P S
U3P S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
en05000772.vsd
CP01-
CMMXU
I3P IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL
en05000699.vsd
VP01-
VMMXU
U3P UL12
UL12RANG
UL23
UL23RANG
UL31
UL31RANG
en05000701.vsd
CSQ1-
CMSQI
I3P 3I0
3I0RANG
I1
I1RANG
I2
I2RANG
en05000703.vsd
VSQ1-
VMSQI
U3P 3U0
3U0RANG
U1
U1RANG
U2
U2RANG
en05000704.vsd
Table 289: Input signals for the CVMMXU (SVR1-) function block
Signal Description
I3P Group signal for current input
U3P Group signal for voltage input
Table 290: Output signals for the CVMMXU (SVR1-) function block
Signal Description
S Apparent Power magnitude of deadband value
S_RANGE Apparent Power range
P Active Power magnitude of deadband value
P_RANGE Active Power range
Q Active Power magnitude of deadband value
Q_RANGE Reactive Power range
PF Power Factor magnitude of deadband value
PF_RANGE Power Factor range
ILAG Current is lagging voltage
ILEAD Current is leading voltage
U Calculate voltage magnitude of deadband value
U_RANGE Calcuate voltage range
I Calculated current magnitude of deadband value
I_RANGE Calculated current range
F System frequency magnitude of deadband value
F_RANGE System frequency range
Table 291: Input signals for the CMMXU (CP01-) function block
Signal Description
I3P Group connection abstract block 1
Table 292: Output signals for the CMMXU (CP01-) function block
Signal Description
IL1 IL1 Amplitude, magnitude of reported value
IL1RANG IL1 Amplitude range
IL2 IL2 Amplitude, magnitude of reported value
IL2RANG IL2 Amplitude range
IL3 IL3 Amplitude, magnitude of reported value
IL3RANG IL3 Amplitude range
Table 293: Input signals for the VMMXU (VP01-) function block
Signal Description
U3P Group connection abstract block 2
Table 294: Output signals for the VMMXU (VP01-) function block
Signal Description
UL12 UL12 Amplitude, magnitude of reported value
UL12RANG UL12 Amplitude range
UL23 UL23 Amplitude, magnitude of reported value
UL23RANG UL23 Amplitude range
UL31 UL31 Amplitude, magnitude of reported value
UL31RANG UL31 Amplitude range
Table 295: Input signals for the CMSQI (CSQ1-) function block
Signal Description
I3P Group connection abstract block 3
Table 296: Output signals for the CMSQI (CSQ1-) function block
Signal Description
3I0 3I0 Amplitude, magnitude of reported value
3I0RANG 3I0 Amplitude range
I1 I1 Amplitude, magnitude of reported value
I1RANG I1 Amplitude range
I2 I2 Amplitude, magnitude of reported value
I2RANG I2 Amplitude range
Table 297: Input signals for the VMSQI (VSQ1-) function block
Signal Description
U3P Group connection abstract block 4
Table 298: Output signals for the VMSQI (VSQ1-) function block
Signal Description
3U0 3U0 Amplitude, magnitude of reported value
3U0RANG 3U0 Amplitude range
U1 U1 Amplitude, magnitude of reported value
U1RANG U1 Amplitude range
U2 U2 Amplitude, magnitude of reported value
U2RANG U2 Amplitude range
14.2.1 Introduction
The function consists of six counters which are used for storing the number of times
each counter has been activated. It is also provided with a common blocking function
for all six counters, to be used for example at testing. Every counter can separately
be set on or off by a parameter setting.
To not risk that the flash memory is worn out due to too many writings, a mechanism
for limiting the number of writings per time period is included in the product. This
however gives as a result that it can take long time, up to several minutes, before a
new value is stored in the flash memory. And if a new CNTGGIO value is not stored
before auxiliary power interruption, it will be lost. The CNTGGIO stored values in
flash memory will however not be lost at an auxiliary power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example be used for blocking the counters at
testing.
14.2.2.1 Reporting
The content of the counters can be read in the local HMI. Refer to “Operators
manual” for procedure.
Reset of counters can be performed in the local HMI and a binary input. Refer to
“Operators manual” for procedure.
Reading of content and resetting of the counters can also be performed remotely, for
example PCM 600 or MicroSkada.
14.2.2.2 Design
The function block has six inputs for increasing the counter values for each of the six
counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked.
The function block has an input RESET. At activation of this input all six counters
are set to 0.
en05000345.vsd
Table 305: Input signals for the CNTGGIO (CNT1-) function block
Signal Description
BLOCK Block of function
COUNTER1 Input for counter1
COUNTER2 Input for counter2
COUNTER3 Input for counter3
COUNTER4 Input for counter4
COUNTER5 Input for counter5
COUNTER6 Input for counter6
RESET Reset of function
14.3.1 Introduction
When using a Substation Automation system with LON or SPA communication,
time-tagged events can be sent at change or cyclically from the IED to the station
level. These events are created from any available signal in the IED that is connected
to the Event function block. The event function block is used for LON and SPA
communication.
Analog and double indication values are also transferred through the event block.
Each event function block has 16 inputs INPUT1 - INPUT16. Each input can be given
a name from the CAP configuration tool. The inputs are normally used to create single
events, but are also intended for double indication events.
The function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical signals
and binary input channels. The internal signals are time-tagged in the main processing
module, while the binary input channels are time-tagged directly on the input module.
The time-tagging of the events that are originated from internal logical signals have
a resolution corresponding to the execution cyclicity of the event function block. The
time-tagging of the events that are originated from binary input signals have a
resolution of 1 ms.
The outputs from the event function block are formed by the reading of status, events
and alarms by the station level on every single input. The user-defined name for each
input is intended to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are treated
commonly for both the LON and SPA communication. The event mask can be set
individually for each input channel. These settings are available:
• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect
It is possible to define which part of the event function block that shall generate events.
This can be performed individually for the LON and SPA communication
respectively. For each communication type these settings are available:
• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16
For LON communication the events normally are sent to station level at change. It is
possibly also to set a time for cyclic sending of the events individually for each input
channel.
To protect the SA system from signals with a high change rate that can easily saturate
the event system or the communication subsystems behind it, a quota limiter is
implemented. If an input creates events at a rate that completely consume the granted
quota then further events from the channel will be blocked. This block will be
removed when the input calms down and the accumulated quota reach 66% of the
maximum burst quota. The maximum burst quota per input channel equals 3 times
the configurable setting MaxEvPerSec.
en05000697.vsd
Table 307: Input signals for the Event (EV01-) function block
Signal Description
BLOCK Block of function
INPUT1 Input 1
INPUT2 Input 2
INPUT3 Input 3
INPUT4 Input 4
INPUT5 Input 5
INPUT6 Input 6
INPUT7 Input 7
INPUT8 Input 8
INPUT9 Input 9
INPUT10 Input 10
INPUT11 Input 11
INPUT12 Input 12
INPUT13 Input 13
Table continued on next page
Signal Description
INPUT14 Input 14
INPUT15 Input 15
INPUT16 Input 16
NAME1 User defined string for input 1
NAME2 User defined string for input 2
NAME3 User defined string for input 3
NAME4 User defined string for input 4
NAME5 User defined string for input 5
NAME6 User defined string for input 6
NAME7 User defined string for input 7
NAME8 User defined string for input 8
NAME9 User defined string for input 9
NAME10 User defined string for input 10
NAME11 User defined string for input 11
NAME12 User defined string for input 12
NAME13 User defined string for input 13
NAME14 User defined string for input 14
NAME15 User defined string for input 15
NAME16 User defined string for input 16
14.4.1 Introduction
The accurate fault locator is an essential component to minimize the outages after a
persistent fault and/or to pin-point a weak spot on the line.
The built-in fault locator is an impedance measuring function giving the distance to
the fault in percent, km or miles. The main advantage is the high accuracy achieved
by compensating for load current and for the mutual zero sequence effect on double
circuit lines.
The compensation includes setting of the remote and local sources and calculation of
the distribution of fault currents from each side. This distribution of fault current,
together with recorded load (pre-fault) currents, is used to exactly calculate the fault
position. The fault can be recalculated with new source data at the actual fault to
further increase the accuracy.
Specially on heavily loaded long lines (where the fault locator is most important)
where the source voltage angles can be up to 35-40 degrees apart the accuracy can
be still maintained with the advanced compensation included in fault locator.
When calculating distance to fault, pre-fault and fault phasors of currents and voltages
are selected from the Trip Value Recorder data, thus the analog signals used by the
fault locator must be among those connected to the disturbance report function. The
analog configuration (channel selection) is performed using the parameter setting tool
within PCM 600.
The calculation algorithm considers the effect of load currents, double-end infeed and
additional fault resistance.
R0L+jX0L
R1L+jX1L
R1A+jX1A R1B+jX1B
Z0m=Z0m+jX0m
R0L+jX0L
R1L+jX1L en05000045.vsd
DRP
FL
Figure 285: Simplified network configuration with network data, required for
settings of the fault location-measuring function.
If source impedance in the near and far end of the protected line have changed in a
significant manner relative to the set values at fault location calculation time (due to
exceptional switching state in the immediate network, power generation out of order
etc.), new values can be entered via the local HMI and a recalculation of the distance
to the fault can be ordered using the algorithm described below. It’s also possible to
change fault loop. In this way, a more accurate location of the fault can be achieved.
The function indicates the distance to the fault as a percentage of the line length, in
kilometers or miles as selected on the local HMI. The fault location is stored as a part
of the disturbance report information (ER, DR, IND, TVR and FL) and managed via
the LHMI or PCM 600.
For transmission lines with voltage sources at both line ends, the effect of double-end
infeed and additional fault resistance must be considered when calculating the
distance to the fault from the currents and voltages at one line end. If this is not done,
the accuracy of the calculated figure will vary with the load flow and the amount of
additional fault resistance.
The calculation algorithm used in the fault locator in compensates for the effect of
double-end infeed, additional fault resistance and load current.
Figure 286 shows a single-line diagram of a single transmission line, that is fed from
both ends with source impedances ZA and ZB. Assume, that the fault occurs at a
distance F from terminal A on a line with the length L and impedance ZL. The fault
resistance is defined as RF. A single-line model is used for better clarification of the
algorithm.
A B
ZA IA pZL IB (1-p).ZL ZB
IF
UA RF
xx01000171.vsd
U A = I A × p × Z L + IF × R F
(Equation 88)
Where:
IA is the line current after the fault, that is, pre-fault current plus current change due to the fault,
IF A
IF = --------
DA
(Equation 89)
Where:
IFA is the change in current at the point of measurement, terminal A and
DA is a fault current-distribution factor, that is, the ratio between the fault current at line end A and
the total fault current.
( 1 – p ) × Z L + ZB
DA = -----------------------------------------
Z A + Z L + ZB
(Equation 90)
Thus, the general fault location equation for a single line is:
I FA
U A = I A × p × Z L + -------
- × RF
DA
(Equation 91)
Table 309: Expressions for UA, IA and IFA for different types of faults
The KN complex quantity for zero-sequence compensation for the single line is equal
to:
Z0L – Z 1L
K N = ------------------------
3 × Z1L
(Equation 98)
DI is the change in current, that is the current after the fault minus the current before
the fault.
In the following, the positive sequence impedance for ZA, ZB and ZL is inserted into
the equations, because this is the value used in the algorithm.
I FA
U A = I A × p × Z 1L + -------- × RF + I 0P × Z 0M
DA
(Equation 99)
Where:
I0P is a zero sequence current of the parallel line,
( 1 – p ) × ( ZA + ZA L + ZB ) + Z B
DA = ----------------------------------------------------------------------------
-
2 × ZA + Z L + 2 × Z B
Z0L – Z 1L Z 0M I 0P
K N = ----------------------- - × -------
- + ----------------
3 × Z1L 3 × Z1L I 0A
(Equation 101)
From these equations it can be seen, that, if Z0m = 0, then the general fault location
equation for a single line is obtained. Only the distribution factor differs in these two
cases.
Where:
UA ZB
K 1 = ---------------
- + --------------------------
-+1
I A × ZL Z L + ZA DD
(Equation 103)
UA ZB
K2 = --------------- × æè --------------------------- + 1öø
IA × Z L Z L + Z A DD
(Equation 104)
IF A æ ZA + ZB
- × --------------------------- + 1ö
K 3 = ---------------
I A × Z L è Z 1 + ZA DD ø
(Equation 105)
and:
For a single line, Z0M = 0 and ZADD = 0. Thus, equation 102 applies to both single
and parallel lines.
– p × Im × ( K1 ) + Im × ( K 2 ) – R F × Im × ( K3 ) = 0
(Equation 107)
If the imaginary part of K3 is not zero, RF can be solved according to equation 107,
and then inserted to equation 106. According to equation 106, the relative distance
to the fault is solved as the root of a quadratic equation.
Equation 106 gives two different values for the relative distance to the fault as a
solution. A simplified load compensated algorithm, that gives an unequivocal figure
for the relative distance to the fault, is used to establish the value that should be
selected.
If the load compensated algorithms according to the above do not give a reliable
solution, a less accurate, non-compensated impedance model is used to calculate the
relative distance to the fault.
In the non-compensated impedance model, IA line current is used instead of IFA fault
current:
U A = p × Z 1 L × IA + R F × IA
(Equation 108)
Where:
IA is according to table 309.
The communication protocol IEC 60870-5-103 may be used to poll fault location
information from the IED to a master (i.e. station HSI). There are two outputs that
must be connected to appropriate inputs on the function block I103StatFltDis,
FLTDISTX gives distance to fault (reactance, according the standard) and
CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX
output.
en05000679.vsd
Table 310: Input signals for the LMBRFLO (FLO1-) function block
Signal Description
PHSELL1 Phase selecton L1
PHSELL2 Phase selecton L2
PHSELL3 Phase selecton L3
CALCDIST Do calculate fault distance (release)
Table 311: Output signals for the LMBRFLO (FLO1-) function block
Signal Description
FLTDISTX Reactive distance to fault
CALCMADE Fault calculation made
Table 313: Parameter group settings for the LMBRFLO (FLO1-) function
Parameter Range Step Default Unit Description
R1A 0.001 - 1500.000 0.001 2.000 ohm/p Source resistance A
(near end)
X1A 0.001 - 1500.000 0.001 12.000 ohm/p Source reactance A
(near end)
R1B 0.001 - 1500.000 0.001 2.000 ohm/p Source resistance B
(far end)
X1B 0.001 - 1500.000 0.001 12.000 ohm/p Source reactance B
(far end)
R1L 0.001 - 1500.000 0.001 2.000 ohm/p Positive sequence
line resistance
X1L 0.001 - 1500.000 0.001 12.500 ohm/p Positive sequence
line reactance
R0L 0.001 - 1500.000 0.001 8.750 ohm/p Zero sequence line
resistance
X0L 0.001 - 1500.000 0.001 50.000 ohm/p Zero sequence line
reactance
R0M 0.000 - 1500.000 0.001 0.000 ohm/p Zero sequence
mutual resistance
X0M 0.000 - 1500.000 0.001 0.000 ohm/p Zero sequence
mutual reactance
LineLength 0.0 - 10000.0 0.1 40.0 km Length of line
14.5.1 Introduction
The functions MMXU (SVR, CP and VP), MSQI (CSQ and VSQ) and MVGGIO
(MV) are provided with measurement supervision functionality. All measured values
can be supervised with four settable limits, i.e. low-low limit, low limit, high limit
and high-high limit. The measure value expander block (XP) has been introduced to
be able to translate the integer output signal from the measuring functions to 5 binary
signals i.e. below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable
logic.
en05000346.vsd
Table 316: Input signals for the RANGE_XP (XP01-) function block
Signal Description
RANGE Measured value range
Table 317: Output signals for the RANGE_XP (XP01-) function block
Signal Description
HIGHHIGH Measured value is above high-high limit
HIGH Measured value is between high and high-high limit
NORMAL Measured value is between high and low limit
LOW Measured value is between low and low-low limit
LOWLOW Measured value is below low-low limit
Function block name: DRP--, DRA1- – DRA4-, IEC 60617 graphical symbol:
DRB1- – DRB6-
ANSI number:
IEC 61850 logical node name:
ABRDRE
14.6.1 Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
The disturbance report, always included in the IED, acquires sampled data of all
selected analogue input and binary signals connected to the function block i.e.
maximum 40 analogue and 96 binary signals.
Every disturbance report recording is saved in the IED in the standard Comtrade
format. The same applies to all events, which are continuously saved in a ring-buffer.
The Local Human Machine Interface (LHMI) is used to get information about the
recordings, but the disturbance report files may be uploaded to the PCM 600
(Protection and Control IED Manager) and further analysis using the disturbance
handling tool.
Figure 289Figure "" shows the relations among Disturbance Report, included
functions and function blocks. EL, ER and IND uses information from the binary
input function blocks (DRB1- 6). TVR uses analog information from the analog input
function blocks (DRA1-3) which is used by FL after estimation by TVR. The DR
function acquires information from both DRAx and DRBx.
DRP- - FL01
A4RADR RDRE FL
Analog signals
Trip Value Rec Fault Locator
DRB1-- 6- Disturbance
Recorder
Event Recorder
Indications
en05000124.vsd
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list function
is working continuously, independent of disturbance triggering, recording time etc.
All information in the disturbance report is stored in non-volatile flash memories.
This implies that no information is lost in case of loss of auxiliary power. Each report
will get an identification number in the interval from 1-65536.
Disturbance report
en05000125.vsd
Number of recordings
100
3,4 s
80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s
6,3 s 50 Hz
40
60 Hz
Total recording time
en05000488.vsd
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local human-machine interface (LHMI). To acquire a
complete disturbance report the use of a PC and PCM600 is required. The PC may
be connected to the IED-front, rear or remotely via the station bus (Ethernet ports).
Indications (IND)
Indications is a list of signals that were activated during the total recording time of
the disturbance (not time-tagged). (See section "Indications (RDRE)" for more
detailed information.)
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
Recording times
The disturbance report (DRP) records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
The disturbance recorder (DR), the event recorder (ER) and indication function
register disturbance data and events during tRecording, the total recording time.
Trig point
TimeLimit
PreFaultRecT PostFaultRecT
1 2 3
en05000487.vsd
PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the operate
time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as any
valid trigger condition, binary or analog, persists (unless limited by TimeLimit the
limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does
not reset within a reasonable time interval. It limits the maximum recording time of
a recording and prevents subsequent overwriting of already stored
disturbances.Use the setting TimeLimit to set this time.
Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for
external analog signals, i.e. signals from the analog input modules (TRM) and line
differential communication module (LDCM) via preprocessing function blocks
(SMAI) and summation block (Sum3Ph). The last 10 channels may be connected to
internally calculated analog signals available as function block output signals (mA
input signals, phase differential currents, bias currents etc.).
PRxx- DRA1-
SMAI A1RADR DRA2-
GRPNAME AI3P A2RADR DRA3-
External analog AI1NAME AI1 INPUT1 A3RADR
signals
AI2NAME AI2 INPUT2
TRM, LDCM AI3NAME AI3 INPUT3
SUxx
AI4NAME AI4 INPUT4
AIN INPUT5
INPUT6
...
A4RADR
INPUT31
Internal analog signals
T2Dx, T3Dx, INPUT32
REFx, HZDx, INPUT33
L3D, L6D,
LT3D, LT6D INPUT34
INPUT35
SVRx, CPxx, VP0x,
CSQx, VSQx, MVxx INPUT36
...
INPUT40
en05000653.vsd
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the DRAx- function block via the PRxx
function block. The information is saved at the Disturbance report base sampling rate
(1000 or 1200 Hz). Internally calculated signals are updated according to the cycle
time of the specific function. If a function is running at lower speed than the base
sampling rate, the Disturbance recorder will use the latest updated sample until a new
updated sample is available.
If the IED is preconfigured the only tool needed for analogue configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (PRxx) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used). PRxx makes the
information available as a group signal output, phase outputs and calculated residual
output (AIN-output). In situations where AI4-input is used as a input signal the
corresponding information is available on the non-calculated output (AI4) on the
PRxx-block. Connect the signals to the DRAx accordingly.
For each of the analog signals, Operation = On means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Off. Both undervoltage and overvoltage can be used
as trigger conditions. The same applies for the current signals.
The analog signals are presented only in the disturbance recording, but they affect
the entire disturbance report when being used as triggers.
Binary signals
Up to 96 binary signals can be selected to be handled by the disturbance report.The
signals can be selected from internal logical and binary input signals. A binary signal
is selected to be recorded when:
The selected signals are presented in the event recorder, event list and the disturbance
recording. But they affect the whole disturbance report when they are used as triggers.
The indications are also selected from these 96 signals with the LHMI
IndicationMask=Show/Hide.
Trigger signals
The trigger conditions affect the entire disturbance report, except the event list, which
runs continuously. As soon as at least one trigger condition is fulfilled, a complete
disturbance report is recorded. On the other hand, if no trigger condition is fulfilled,
there is no disturbance report, no indications, and so on. This implies the importance
of choosing the right signals as trigger conditions.
• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)
Manual trigger
A disturbance report can be manually triggered from the local HMI, from PCM600
or via station bus (IEC61850). When the trigger is activated, the manual trigger signal
is generated. This feature is especially useful for testing. Refer to “Operators
manual” for procedure.
Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a trigger
(Triglevel = Trig on 0/Trig on 1).The binary signal must remain in a steady state for
at least 15 ms to be valid. When a binary signal is selected to generate a trigger from
a logic zero, the selected signal will not be listed in the indications list of the
disturbance report.
Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded
in the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is
found, the absolute average value of these two peak values is calculated. If the average
value is above the threshold level for an overvoltage or overcurrent trigger, this trigger
is indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or
undercurrent trigger, this trigger is indicated with a less than (<) sign with its name.
The procedure is separately performed for each channel.
This method of checking the analog start conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this start is typically in the
range of one cycle, 20 ms for a 50 Hz network.
All under/over trig signal information is available on the LHMI and PCM600, see
table 318.
Post Retrigger
The disturbance report function does not respond to any new trig condition, during a
recording. Under certain circumstances the fault condition may reoccur during the
post-fault recording, for instance by automatic reclosing to a still faulty power line.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not
start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a new
trig occurs during the post-fault period and lasts longer than the proceeding recording
a new complete recording will be fetched.
DRP--
RDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
en05000406.vsd
DRA1-
A1RADR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
NAME1
NAME2
NAME3
NAME4
NAME5
NAME6
NAME7
NAME8
NAME9
NAME10
en05000430.vsd
Figure 295: DRA1 function block, analog inputs, example for DRA1–DRA3
DRA4-
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
INPUT37
INPUT38
INPUT39
INPUT40
NAME31
NAME32
NAME33
NAME34
NAME35
NAME36
NAME37
NAME38
NAME39
NAME40
en05000431.vsd
DRB1-
B1RBDR
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
NAME1
NAME2
NAME3
NAME4
NAME5
NAME6
NAME7
NAME8
NAME9
NAME10
NAME11
NAME12
NAME13
NAME14
NAME15
NAME16
en05000432.vsd
Figure 297: DRB1 function block, binary inputs, example for DRB1–DRB6
Table 318: Output signals for the RDRE (DRP--) function block
Signal Description
DRPOFF Disturbance report function turned off
RECSTART Disturbance recording started
RECMADE Disturbance recording made
CLEARED All disturbances in the disturbance report cleared
MEMUSED More than 80% of memory used
Table 319: Input signals for the A1RADR (DRA1-) function block, example for DRA1–DRA3
Signal Description
INPUT1 Group signal for input 1
INPUT2 Group signal for input 2
INPUT3 Group signal for input 3
INPUT4 Group signal for input 4
INPUT5 Group signal for input 5
Table continued on next page
Signal Description
INPUT6 Group signal for input 6
INPUT7 Group signal for input 7
INPUT8 Group signal for input 8
INPUT9 Group signal for input 9
INPUT10 Group signal for input 10
NAME1 User define string for analogue input 1
NAME2 User define string for analogue input 2
NAME3 User define string for analogue input 3
NAME4 User define string for analogue input 4
NAME5 User define string for analogue input 5
NAME6 User define string for analogue input 6
NAME7 User define string for analogue input 7
NAME8 User define string for analogue input 8
NAME9 User define string for analogue input 9
NAME10 User define string for analogue input 10
Table 320: Input signals for the A4RADR (DRA4-) function block
Signal Description
INPUT31 Analogue channel 31
INPUT32 Analogue channel 32
INPUT33 Analogue channel 33
INPUT34 Analogue channel 34
INPUT35 Analogue channel 35
INPUT36 Analogue channel 36
INPUT37 Analogue channel 37
INPUT38 Analogue channel 38
INPUT39 Analogue channel 39
INPUT40 Analogue channel 40
NAME31 User define string for analogue input 31
NAME32 User define string for analogue input 32
NAME33 User define string for analogue input 33
NAME34 User define string for analogue input 34
NAME35 User define string for analogue input 35
NAME36 User define string for analogue input 36
NAME37 User define string for analogue input 37
NAME38 User define string for analogue input 38
NAME39 User define string for analogue input 39
NAME40 User define string for analogue input 40
Table 321: Input signals for the B1RBDR (DRB1-) function block, example for DRB1–DRB6
Signal Description
INPUT1 Binary channel 1
INPUT2 Binary channel 2
INPUT3 Binary channel 3
INPUT4 Binary channel 4
INPUT5 Binary channel 5
INPUT6 Binary channel 6
INPUT7 Binary channel 7
INPUT8 Binary channel 8
INPUT9 Binary channel 9
INPUT10 Binary channel 10
INPUT11 Binary channel 11
INPUT12 Binary channel 12
INPUT13 Binary channel 13
INPUT14 Binary channel 14
INPUT15 Binary channel 15
INPUT16 Binary channel 16
NAME1 User define string for binary input 1
NAME2 User define string for binary input 2
NAME3 User define string for binary input 3
NAME4 User define string for binary input 4
NAME5 User define string for binary input 5
NAME6 User define string for binary input 6
NAME7 User define string for binary input 7
NAME8 User define string for binary input 8
NAME9 User define string for binary input 9
NAME10 User define string for binary input 10
NAME11 User define string for binary input 11
NAME12 User define string for binary input 12
NAME13 User define string for binary input 13
NAME14 User define string for binary input 14
NAME15 User define string for binary input 15
NAME16 User define string for binary input 16
14.7.1 Introduction
Continuous event-logging is useful for monitoring of the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The event list logs all binary input signals connected to the Disturbance report
function. The list may contain of up to 1000 time-tagged events stored in a ring-buffer.
The event list information is available in the IED and is reported to higher control
systems via the station bus together with other logged events in the IED. In absence
of any software tool the information seeker may use the local HMI to view the event
list.
The list can be configured to show oldest or newest events first with a setting on the
LHMI.
The event list function runs continuously, in contrast to the event recorder function,
which is only active during a disturbance.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when the IED is configured. The same name is used in the
disturbance recorder function (DR), indications (IND) and the event recorder function
(ER).
The event list is stored and managed separate from the disturbance report information
(ER, DR, IND, TVR and FL).
14.8.1 Introduction
To get fast, condensed and reliable information about disturbances in the primary
and/or in the secondary system it is important to know e.g. binary signals that have
changed status during a disturbance. This information is used in the short perspective
to get information via the LHMI in a straightforward way.
There are three LEDs on the LHMI (green, yellow and red), which will display status
information about the IED and the Disturbance Report function (trigged).
The Indication list function shows all selected binary input signals connected to the
Disturbance Report function that have changed status during a disturbance.
The indication information is available for each of the recorded disturbances in the
IED and the user may use the Local Human Machine Interface (LHMI) to get the
information.
Green LED:
Yellow LED:
Red LED:
Indication list:
The possible indicated signals are the same as the ones chosen for the disturbance
report function and disturbance recorder
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
Indications are selected with the indication mask (IndicationMask) when configuring
the binary inputs.
The name of the binary input signal that appears in the Indication function is the user-
defined name assigned at configuration of the IED. The same name is used in
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).
14.9.1 Introduction
Quick, complete and reliable information about disturbances in the primary and/or in
the secondary system is vital e.g. time tagged events logged during disturbances. This
information is used for different purposes in the short term (e.g. corrective actions)
and in the long term (e.g. Functional Analysis).
The event recorder logs all selected binary input signals connected to the Disturbance
Report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
The information may be uploaded to the PCM 600 (Protection and Control IED
Manager) and further analysed using the Disturbance Handling tool.
The name of the binary input signal that appears in the event recording is the user-
defined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder function
(ER).
The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the LHMI or PCM 600.
14.10.1 Introduction
Information about the pre-fault and fault values for currents and voltages are vital for
the disturbance evaluation.
The Trip value recorder calculates the values of all selected analogue input signals
connected to the Disturbance report function. The result is magnitude and phase angle
before and during the fault for each analogue input signal.
The trip value recorder information is available for the disturbances locally in the
IED.
The information may be uploaded to the PCM 600 (Protection and Control IED
Manager) and further analysed using the Disturbance Handling tool.
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).
When the disturbance report function is triggered the sample for the fault interception
is searched for, by checking the non-periodic changes in the analog input signals. The
channel search order is consecutive, starting with the analog input with the lowest
number.
When a starting point is found, the Fourier estimation of the pre-fault values of the
complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated using
the Recursive Least Squares (RLS) method. The calculation starts a few samples after
the fault sample and uses samples during 1/2 - 2 cycles depending on the shape of the
signals.
If no starting point is found in the recording, the disturbance report trig sample is used
as the start sample for the Fourier estimation. The estimation uses samples during one
cycle before the trig sample. In this case the calculated values are used both as pre-
fault and fault values.
The name of the analog input signal that appears in the Trip value recorder function
is the user-defined name assigned when the IED is configured. The same name is
used in the Disturbance recorder function (DR).
The trip value record is stored as a part of the disturbance report information (ER,
DR, IND, TVR and FLOC) and managed in via the LHMI or PCM 600.
14.11.1 Introduction
The Disturbance Recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system behavior
and related primary and secondary equipment during and after a disturbance.
Recorded information is used for different purposes in the short perspective (e.g.
corrective actions) and long perspective (e.g. Functional Analysis).
The Disturbance Recorder acquires sampled data from all selected analogue input
and binary signals connected to the Disturbance Report function (maximum 40 analog
and 96 binary signals). The binary signals are the same signals as available under the
event recorder function.
The function is characterized by great flexibility and is not dependent on the operation
of protection functions. It can record disturbances not detected by protection
functions.
The disturbance recorder information for the last 100 disturbances are saved in the
IED and the Local Human Machine Interface (LHMI) is used to view the list of
recordings.
The disturbance recording information can be uploaded to the PCM 600 (Protection
and Control IED Manager) and further analysed using the Disturbance Handling tool.
DR collects analog values and binary signals continuously, in a cyclic buffer. The
pre-fault buffer operates according to the FIFO principle; old data will continuously
be overwritten as new data arrives when the buffer is full. The size of this buffer is
determined by the set pre-fault recording time.
Upon detection of a fault condition (triggering), the disturbance is time tagged and
the data storage continues in a post-fault buffer. The storage process continues as long
as the fault condition prevails - plus a certain additional time. This is called the post-
fault time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. The last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from
analog inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common for
all functions within the disturbance report functionality.
• Saving the data for analog channels with corresponding data for binary signals
• Add relevant data to be used by the Disturbance Handling tool (part of PCM 600)
• Compression of the data, which is performed without losing any data accuracy
• Storing the compressed data in a non-volatile memory (flash memory)
The recording files comply with the Comtrade standard IEC 60255-24 and are divided
into three files; a header file (HDR), a configuration file (CFG) and a data file (DAT).
The header file (optional in the standard) contains basic information about the
disturbance i.e. information from the Disturbance Report functions (ER, TVR and
FL). The Disturbance Handling tool use this information and present the recording
in a user-friendly way.
General:
Analog:
Binary:
• Signal names
• Status of binary input signals
The data file, which also is mandatory, containing values for each input channel for
each sample in the record (scaled value). The data file also contains a sequence
number and time stamp for each set of samples.
The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).
To be able to report 40 analog channels from the IED using IEC 60870-5-103 the first
8 channels are placed in the public range and the next 32 are placed in the private
range. To comply the standard the first 8 must be configured according to
table 331.
The binary signals connected to DRB1-DRB6 are reported by polling. The function
blocks include function type and information number.
Section 15 Metering
15.1.1 Introduction
The pulse counter logic function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then
read by the pulse counter function. A scaled service value is available over the station
bus. The special Binary input module with enhanced pulse counting capabilities must
be ordered to achieve this functionality.
The integration time period can be set in the range from 30 seconds to 60 minutes
and is synchronized with absolute system time. Interrogation of additional pulse
counter values can be done with a command (intermediate reading) for a single
counter. All active counters can also be read by the LON General Interrogation
command (GI).
The reported value to station HMI over the LON bus contains Identity, Value, Time,
and Pulse Counter Quality. The Pulse Counter Quality consists of:
The transmission of the counter value by SPA can be done as a service value, that is,
the value frozen in the last integration cycle is read by the station HMI from the
database. The pulse counter function updates the value in the database when an
integration cycle is finished and activates the NEW_VAL signal in the function block.
This signal can be connected to an Event function block, be time tagged, and
transmitted to the station HMI. This time corresponds to the time when the value was
frozen by the function.
The pulse counter function requires an binary input card, BIMp, that
is specially adapted to the pulse counter function.
Figure 298 shows the pulse counter function block with connections of the inputs and
outputs.
The BLOCK and READ_VAL inputs can be connected to Single Command blocks,
which are intended to be controlled either from the station HMI or/and the local HMI.
As long as the BLOCK signal is set, the pulse counter is blocked. The signal connected
to READ_VAL performs one additional reading per positive flank. The signal must
be a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
Each pulse counter function block has four binary output signals that can be connected
to an Event function block for event recording: INVALID, RESTART, BLOCKED
and NEW_VAL. The SCAL_VAL signal can be connected to the IEC Event function
block.
The INVALID signal is a steady signal and is set if the Binary Input Module, where
the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-
up, in the first message after deblocking, and after the counter has wrapped around
during last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked. There
are two reasons why the counter is blocked:
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
en05000709.vsd
Table 333: Input signals for the PCGGIO (PC01-) function block
Signal Description
BLOCK Block pulse counter function
READ_VAL Initiates an additional pulse counter reading
BI_PULSE Connect binary input channel for metering
RS_CNT Resets pulse counter value
Table 334: Output signals for the PCGGIO (PC01-) function block
Signal Description
INVALID The pulse counter value is invalid
RESTART The reported value not comprise a complete integration
cycle
BLOCKED The pulse counter function is blocked
NEW_VAL A new pulse counter value is generated
NAME User defined string for pulse counter
SCAL_VAL Scaled value with time and status information
16.1 Overview
16.2.1 Introduction
Single or double optical Ethernet ports for the new substation communication
standard IEC61850-8-1 for the station bus are provided. IEC61850-8-1 allows
intelligent devices (IEDs) from different vendors to exchange information and
simplifies SA engineering. Peer- to peer communication according to GOOSE is part
of the standard. Disturbance files uploading is provided.
When double Ethernet ports are activated, make sure that the two ports
are connected to different subnets. For example: Port 1 has IP-address
138.227.102.10 with subnet mask 255.255.255.0 and port 2 has IP-
address 138.227.103.10 with subnet mask 255.255.255.0
16.2.2.1 Introduction
The SPGGIO function block is used to send one single logical signal to other systems
or equipment in the substation.
Upon receiving a signal at its input, the SPGGIO function block will send the signal
over IEC 61850-8-1 (via its non-transparent-to-CAP user output) to the equipment
or system that requests this signal. To be able to get the signal, one must use other
tools, described in the Application Manual, Chapter 2: “Engineering of the IED” and
define which function block in which equipment or system should receive this
information.
en05000409.vsd
MP01-
SP16GGIO
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
en06000632.vsd
Table 337: Input signals for the SPGGIO (SP01-) function block
Signal Description
IN Input status
Table 338: Input signals for the SP16GGIO (MP01-) function block
Signal Description
BLOCK Block of function
IN1 Input 1 status
IN2 Input 2 status
IN3 Input 3 status
IN4 Input 4 status
IN5 Input 5 status
IN6 Input 6 status
IN7 Input 7 status
IN8 Input 8 status
IN9 Input 9 status
IN10 Input 10 status
IN11 Input 11 status
IN12 Input 12 status
IN13 Input 13 status
IN14 Input 14 status
IN15 Input 15 status
IN16 Input 16 status
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM 600)
16.2.3.1 Introduction
The MVGGIO function block is used to send the instantaneous value of an analog
output to other systems or equipment in the substation. It can also be used inside the
same IED, to attach a “RANGE” aspect to an analog value and to permit measurement
supervision on that value.
Upon receiving an analog signal at its input, the MVGGIO block will give the
instantaneous value of the signal and the range, as output values. In the same time, it
will send over IEC61850-8-1 (through two not-visible-to-CAP user outputs) the value
and the deadband, to other equipment or systems in the substation.
en05000408.vsd
Table 339: Input signals for the MVGGIO (MV01-) function block
Signal Description
IN Analogue input value
Table 340: Output signals for the MVGGIO (MV01-) function block
Signal Description
VALUE Magnitude of deadband value
RANGE Range
16.3.1 Introduction
An optical network can be used within the Substation Automation system. This
enables communication with the IED through the LON bus from the operator’s
workplace, from the control center and also from other terminals.
In this document the most common addresses for commands and events are available.
Other addresses can be found in a separate document, refer to section "Related
documents".
It is assumed that the reader is familiar with the LON communication protocol in
general.
The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent
to the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for example,
interlocking information among the terminals without the need of a bus master.
The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short messages,
such as measuring values, status information, and interlocking/blocking signals.
Explicit messages are used to transfer longer pieces of information, such as events
and explicit read and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for
multi-master implementations. The LON bus also has an open concept, so that the
terminals can communicate with external devices using the same standard of network
variables.
LON protocol
Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a LonWorks
network is easily accessible on a single tool program. For details see the “Operators
manual”.
Activate LONCommunication
Activate LON communication in the PST Parameter Setting Tool under Settings ->
General settings – > Communication – > SLM configuration – > Rear optical LON,
where ADE should be set to ON.
Vertical communication
Vertical communication describes communication between the monitoring devices
and protection and control IEDs. This communication includes sending of changed
process data to monitoring devices as events and transfer of commands, parameter
data and disturbance recorder files. This communication is implemented using
explicit messages.
Binary events
Binary events are generated in event function blocks EV01 to EV20 in the 670IEDs.
The event function blocks have predefined LON addresses. table 343 shows the LON
addresses to the first input on the event function blocks. The addresses to the other
inputs on the event function block are consecutive after the first input. For example,
input 15 on event block EV17 has the address 1280 + 14 (15-1) = 1294.
For double indications only the first eight inputs 1–8 must be used. Inputs 9–16 can
be used for other type of events at the same event block.
As basic, 3 event function blocks EV01-EV03 running with a fast loop time (3 ms)
is available in the 670IEDS. The remaining event function blocks EV04-EV09 runs
with a loop time on 8 ms and EV10-EV20 runs with a loop time on 100 ms. The event
blocks are used to send binary signals, integers, real time values like analogue data
from measuring functions and mA input modules as well as pulse counter signals.
16 pulse counter value function blocks PC01 to PC16 and 24 mA input service values
function blocks SMMI1_In1 to 6 – SMMI4_In1 to 6 are available in the 670IEDs.
The first LON address in every event function block is found in table 343
Event masks
The event mask for each input can be set individually from the Parameter Setting
Tool (PST) Under: Settings – > General Settings –> Monitoring –> Event function
as.
• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, event system itself make the reporting decision, (reporting criteria
for integers has no semantic, prefer to be set by the user)
The following type of signals from application functions can be connected to the event
function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is always
reported on change, no changed detection is done in the event function block. Other
Boolean signals, for example a start or a trip signal from a protection function is event
masked in the event function block.
Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for
the first 8 inputs on an event function block.
Analog value
All analog values are reported cyclic, the reporting interval is taken from the
connected function if there is a limit supervised signal, otherwise it is taken from the
event function block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent
SPA-bus message is an explicit LON message, which contains an ASCII character
message following the coding rules of the SPA-bus protocol. The message is sent
using explicit messages with message code 41H and using acknowledged transport
service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or N)
are sent using the same message code. It is mandatory that one device sends out only
one SPA-bus message at a time to one node and waits for the reply before sending
the next message.
For commands from the operator workplace to the IED for apparatus control, i.e. the
function blocks type SCSWI 1 to 32, SXCBR 1 to 18and SXSWI 1 to 28; the SPA
addresses are according to table 344
Horizontal communication
Network variables are used for communication between REx 5xx and 670IEDs. The
supported network variable type is SNVT_state (NV type 83). SNVT_state is used
to communicate the state of a set of 1 to 16 Boolean values.
The multiple command send function block (MTxx) is used to pack the information
to one value. This value is transmitted to the receiving node and presented for the
application by a multiple command function block (CMxx). At horizontal
communication the input BOUND on the event function block (MTxx) must be set
to 1. There are 10 MT and 60 CM function blocks available. The MT and CM function
blocks are connected using Lon Network Tool (LNT 505). This tool also defines the
service and addressing on LON.
This is an overview description how to configure the network variables for 670IEDs.
LON
en05000718.vsd
The network variable connections are done from the NV Connection window. From
LNT window select Connections -> NVConnections -> New
en05000719.vsd
There are two ways of downloading NV connections. Either you use the drag-and-
drop method where you select all nodes in the device window, drag them to the
Download area in the bottom of the program window and drop them there. Or the
traditional menu selection, Configuration -> Download...
en05000720.vsd
Communication ports
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on the
Main Processing Module (NUM). The serial communication module can have
connectors for two plastic fiber cables (snap-in) or two glass fiber cables (ST,
bayonet) or a combination of plastic and glass fiber. Three different types are available
depending on type of fiber. The incoming optical fiber is connected to the RX receiver
input, and the outgoing optical fiber to the TX transmitter output. When the fiber optic
cables are laid out, pay special attention to the instructions concerning the handling,
connection, etc. of the optical fibers. The module is identified with a number on the
label on the module.
Table 344: SPA addresses for commands from the operator workplace to the IED for apparatus
control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block command
BL_CMD SCSWI05 1 I 5210 SPA parameters for block command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block command
BL_CMD SCSWI07 1 I 5258 SPA parameters for block command
BL_CMD SCSWI08 1 I 5283 SPA parameters for block command
BL_CMD SCSWI09 1 I 5307 SPA parameters for block command
Table continued on next page
16.4.1 Introduction
In this section the most common addresses for commands and events are available.
Other addresses can be found in a separate document, refer to section "Related
documents".
It is assumed that the reader is familiar with the SPA communication protocol in
general.
The master requests slave information using request messages and sends information
to the slave in write messages. Furthermore, the master can send all slaves in common
a broadcast message containing time or other data. The inactive state of bus transmit
and receive lines is a logical "1".
SPA protocol
The tables below specify the SPA addresses for reading data from and writing data
to an IED 670 with the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MI03-MI16) are found in
table348
The SPA addresses for the pulse counter values PC01 – PC16 are found in table 349
I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function
block are used, i.e. the addresses for BI1 – BI16. The SPA addresses are found in a
separate document, refer to section "Related documents".
One example is for the limits of the mA-input modules (MIxx), where 0 value must
be written to the 10V43 address. Addresses for other settings that must be stored on
The single command function consists of three function blocks; CD01 – CD03 for
16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. The SPA addresses for the single
command function (CD) are shown in Table 3. For the single command function
block, CD01 to CD03, the address is for the first output. The other outputs follow
consecutively after the first one. For example, output 7 on the CD02 function block
has the 70O718 address.
The SPA addresses for the single command functions CD01 – CD03 are found in
table 350
Table 350 SPA addresses for the controllable signals on the single command functions
Figure 307 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection
terminal for control of a circuit breaker.
A pulse via the binary outputs of the terminal normally performs this type of command
control. The SPA addresses to control the outputs OUT1 – OUT16 in CD01 are shown
in table 350
Figure 307: Application example showing a simplified logic diagram for control of
a circuit breaker.
The MODE input defines if the output signals from CD01 shall be steady or pulsed
signals (1 = steady, 2 = pulsed).
Event function
This event function is intended to send time-tagged events to the station level (e.g.
operator workplace) over the station bus. The events are there presented in an event
list. The events can be created from both internal logical signals and binary input
channels, and all of them must be tied to the 6 DR function blocks. All internal signals
are time tagged in the main processing module, while the binary input channels are
time tagged directly on each I/O module. The events are produced according to the
set event masks. The event masks are treated commonly for both the LON and SPA
channels. All events according to the event mask are stored in a buffer, which contains
up to 1000 events. If new events appear before the oldest event in the buffer is read,
the oldest event is overwritten and an overflow alarm appears.
Two special signals for event registration purposes are available in the terminal,
Terminal Restarted (0E50) and Event buffer overflow (0E51).
The input parameters can be set individually from the Parameter Setting Tool (PST)
under EVENT MASKS/Binary Events as:
Double indications are used to handle a combination of two inputs at a time, for
example, one input for the open and one for the close position of a circuit breaker or
disconnector. The double indication consists of an odd and an even input number.
When the odd input is defined as a double indication, the next even input is considered
to be the other input. The odd inputs has a suppression timer to suppress events at 00
states. To be used as double indications the odd inputs are individually set from the
PST under EVENT MASKS/Binary Events as:
Here, the settings of the corresponding even inputs have no meaning. These states of
the inputs generate events.
The status is read by the station HMI on the status indication for the odd input:
The Status and event codes for the Event functions are found in table 351
22
E2
3
22
E2
7
22
E3
1
EV02 230.. 23E.. 23E.. 23E.. 23E.. 23E.. 23
EV03 240.. 24E.. 24E.. 24E.. 23E.. 24E.. E..
- - - - - - - 24
- - - - - - - E..
- - - - - - - -
EV20 410.. 41E.. 41E.. 41E.. 41E.. 41E.. -
-
41
E..
3) This status value contains a value with all the 16 inputs combined to a hex-value
(0-FFF).
Example
The master requests the slave (no. 2) for latest events by addressing data category
L:>2RL:CCcr
The slave sends the recent events from the buffer starting from the oldest event. If all
recent events do not fit into one message, rest of recent events will not be sent until
during the next request.
When events are requested from the slave and the buffer of the slave is empty, the
slave responds with an empty data message: If<2D::CCcrlf.
Note that corresponding Event mask must be set to an applicable value via the
Parameter Setting Tool (PST).
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on the
Analog/Digital conversion module (ADM). The serial communication module can
have connectors for two plastic fiber cables (snap-in) or two glass fiber cables (ST,
bayonet) or a combination of plastic and glass fiber. Three different types are available
depending on type of fiber.
The incoming optical fiber is connected to the RX receiver input, and the outgoing
optical fiber to the TX transmitter output. When the fiber optic cables are laid out,
pay special attention to the instructions concerning the handling, connection, etc. of
the optical fibers. The module is identified with a number on the label on the module.
The procedure to set the transfer rate and slave number can be found in the Installation
and commissioning manual for respective IED.
16.4.3 Design
When communicating locally with a Personal Computer (PC) in the station, using the
rear SPA port, the only hardware needed for a station monitoring system is:
• Optical fibres
• Opto/electrical converter for the PC
• PC
When communicating remotely with a PC using the rear SPA port, the same hardware
is needed plus telephone modems.
The software needed in the PC, either local or remote, is PCM 600.
When communicating between the LHMI and a PC, the only hardware required is a
front-connection cable.
16.5.1 Introduction
The IEC 60870-5-103 communication protocol is mainly used when a protection
terminal communicates with a third party control or monitoring system. This system
must have software that can interpret the IEC 60870-5-103 communication messages.
16.5.2.1 General
principle. The master must have software that can interpret the IEC 60870-5-103
communication messages.
• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling
• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC60870 standard part
5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
IEC 60870-5-103
The tables in the following sections specify the information types supported by the
IED 670 products with the communication protocol IEC 60870-5-103 implemented.
Number of instances: 1
Number of instances: 1
Number of instances: 4
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 1 - 4. One for each instance.
INFORMATION NUMBER is required for each output signal. Default values are 1
- 8.
Info. no. Message Supported
1 Output signal 01 Yes
2 Output signal 02 Yes
3 Output signal 03 Yes
4 Output signal 04 Yes
5 Output signal 05 Yes
6 Output signal 06 Yes
7 Output signal 07 Yes
8 Output signal 08 Yes
Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined terminal functions.
Number of instances: 1
Number of instances: 20
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 5 - 24. One for each instance.
INFORMATION NUMBER is required for each input signal. Default values are
defined in range 1 - 8
Info. no. Message Supported
1 Input signal 01 Yes
2 Input signal 02 Yes
3 Input signal 03 Yes
4 Input signal 04 Yes
5 Input signal 05 Yes
6 Input signal 06 Yes
7 Input signal 07 Yes
8 Input signal 08 Yes
Number of instances: 1
Number of instances: 1
Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
78 Zone 1 Yes
79 Zone 2 Yes
80 Zone 3 Yes
81 Zone 4 Yes
82 Zone 5 Yes
76 Signal transmitted Yes
77 Signal received Yes
73 SCL, Fault location in ohm Yes
The instance type is suitable for linediff, transformerdiff, overcurrent and earthfault
protection functions.
Number of instances: 1
Info. no. Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
85 Breaker failure Yes
86 Trip measuring system L1 Yes
87 Trip measuring system L2 Yes
88 Trip measuring system L3 Yes
89 Trip measuring system N Yes
90 Over current trip I> Yes
91 Over current trip I>> Yes
92 Earth fault trip IN> Yes
93 Earth fault trip IN>> Yes
Number of instances: 1
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXU.
The IED will report all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no. Message Supported
148 IL1 Yes
144, 145, IL2 Yes
148
148 IL3 Yes
147 IN, Neutral current Yes
148 UL1 Yes
148 UL2 Yes
148 UL3 Yes
145, 146 UL1-UL2 Yes
147 UN, Neutral voltage Yes
146, 148 P, active power Yes
146, 148 Q, reactive power Yes
148 f, frequency Yes
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 25 – 27. One for each instance.
Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be specified.
Channels used in the public range are 1 to 8 and with:
Channel number used for the remaining 32 analog signals are numbers in the private
range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
Disturbance Upload
All analog and binary signals that are recorded with disturbance recorder will be
reported to the master. The last eight disturbances that are recorded are available for
transfer to the master. A successfully transferred disturbance (acknowledged by the
master) will not be reported to the master again.
This section describes all data that is not exactly as specified in the standard.
ASDU23
• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or
test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event
than start/pick-up
The only information that is easily available is test-mode status. The other information
is always set (hard coded) to:
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number should indicate fault
number in the power system, i.e. a fault in the power system with several trip and
auto-reclosing has the same NOF (while the FAN should be incremented). NOF is in
Rex67x, just as FAN, equal to disturbance number.
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever
he connects to the corresponding input.
Supported
ASDU Yes
6 Time synchronization Yes
7 General interrogation Yes
10 Generic data No
20 General command Yes
21 Generic command No
24 Order for disturbance data transmission Yes
25 Acknowledgement for distance data transmission Yes
Selection of basic application functions
Test mode No
Blocking of monitoring direction Yes
Disturbance data Yes
Private data Yes
Generic services No
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. This module is a mezzanine module, and can be placed on the
Analog/Digital conversion module (ADM). The serial communication module can
have connectors for two plastic fiber cables (snap-in) or two glass fiber cables (ST,
bayonet) or a combination of plastic and glass fiber. Three different types are available
depending on type of fiber.
The incoming optical fiber is connected to the RX receiver input, and the outgoing
optical fiber to the TX transmitter output. When the fiber optic cables are laid out,
pay special attention to the instructions concerning the handling, connection, etc. of
the optical fibers. The module is identified with a number on the label on the module.
en05000689.vsd
ICMD-
I103CMD
BLOCK 16-AR
17-DIFF
18-PROT
en05000684.vsd
ICM1-
I103UserCMD
BLOCK OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
en05000693.vsd
IEV1-
I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
en05000688.vsd
IS01-
I103UsrDef
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
en05000694.vsd
ISU1-
I103Superv
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
en05000692.vsd
ISEF-
I103EF
BLOCK
51_EFFW
52_EFREV
en05000685.vsd
IZ01-
I103FltDis
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
en05000686.vsd
IFL1-
I103FltStd
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
en05000687.vsd
IAR1-
I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
en05000683.vsd
IMM1-
I103Meas
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
en05000690.vsd
IMU1-
I103MeasUsr
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
en05000691.vsd
Table 357: Input signals for the I103IEDCMD (ICMA-) function block
Signal Description
BLOCK Block of commands
Table 358: Input signals for the I103FuncCMD (ICMD-) function block
Signal Description
BLOCK Block of commands
Table 359: Input signals for the I103IED (IEV1-) function block
Signal Description
BLOCK Block of status reporting
19_LEDRS Information number 19, reset LEDs
23_GRP1 Information number 23, setting group 1 is active
Table continued on next page
Signal Description
24_GRP2 Information number 24, setting group 2 is active
25_GRP3 Information number 25, setting group 3 is active
26_GRP4 Information number 26, setting group 4 is active
21_TESTM Information number 21, test mode is active
Table 360: Input signals for the I103FuncUserCM (ICM1-) function block
Signal Description
BLOCK Block of commands
Table 361: Input signals for the I103UsrDef (IS01-) function block
Signal Description
BLOCK Block of status reporting
INPUT1 Binary signal Input 1
INPUT2 Binary signal input 2
INPUT3 Binary signal input 3
INPUT4 Binary signal input 4
INPUT5 Binary signal input 5
INPUT6 Binary signal input 6
INPUT7 Binary signal input 7
INPUT8 Binary signal input 8
Table 362: Input signals for the I103Superv (ISU1-) function block
Signal Description
BLOCK Block of status reporting
32_MEASI Information number 32, measurand supervision of I
33_MEASU Information number 33, measurand supervision of U
37_IBKUP Information number 37, I high-high back-up protection
38_VTFF Information number 38, fuse failure VT
46_GRWA Information number 46, group warning
47_GRAL Information number 47, group alarm
Table 363: Input signals for the I103StatEF (ISEF-) function block
Signal Description
BLOCK Block of status reporting
51_EFFW Information number 51, earth-fault forward
52_EFREV Information number 52, earth-fault reverse
Table 364: Input signals for the I103StatFltDis (IZ01-) function block
Signal Description
BLOCK Block of status reporting
64_STL1 Information number 64, start phase L1
65_STL2 Information number 65, start phase L2
66_STL3 Information number 66, start phase L3
67_STIN Information number 67, start residual current IN
84_STGEN Information number 84, start general
69_TRL1 Information number 69, trip phase L1
70_TRL2 Information number 70, trip phase L2
71_TRL3 Information number 71, trip phase L3
68_TRGEN Information number 68, trip general
74_FW Information number 74, forward/line
75_REV Information number 75, reverse/bus
78_ZONE1 Information number 78, zone 1
79_ZONE2 Information number 79, zone 2
80_ZONE3 Information number 79, zone 3
81_ZONE4 Information number 79, zone 4
82_ZONE5 Information number 79, zone 5
76_TRANS Information number 76, signal transmitted
77_RECEV Information number 77, signal recevied
73_SCL Information number 73, fault location in ohm
FLTLOC Faultlocator faultlocation valid (LMBRFLO-CALCMADE)
ARINPROG Autorecloser in progress (SMBRREC- INPROGR)
Table 365: Input signals for the I103StatFltStd (IFL1-) function block
Signal Description
BLOCK Block of status reporting
64_STL1 Information number 64, start phase L1
65_STL2 Information number 65, start phase L2
66_STL3 Information number 66, start phase L3
67_STIN Information number 67, start residual curent IN
84_STGEN Information number 84, start general
69_TRL1 Information number 69, trip phase L1
70_TRL2 Information number 70, trip phase L2
71_TRL3 Information number 71, trip phase L3
68_TRGEN Information number 68, trip general
74_FW Information number 74, forward/line
75_REV Information number 75, reverse/bus
85_BFP Information number 85, breaker failure
Table continued on next page
Signal Description
86_MTRL1 Information number 86, trip measuring system phase L1
87_MTRL2 Information number 87, trip measuring system phase L2
88_MTRL3 Information number 88, trip measuring system phase L3
89_MTRN Information number 89, trip measuring system neutral N
90_IOC Information number 90, over current trip, stage low
91_IOC Information number 91, over current trip, stage high
92_IEF Information number 92, earth-fault trip, stage low
93_IEF Information number 93, earth-fault trip, stage high
ARINPROG Autorecloser in progress (SMBRREC- INPROGR)
Table 366: Input signals for the I103MeasUsr (IMU1-) function block
Signal Description
BLOCK Block of service value reporting
INPUT1 Service value for measurement on input 1
INPUT2 Service value for measurement on input 2
INPUT3 Service value for measurement on input 3
INPUT4 Service value for measurement on input 4
INPUT5 Service value for measurement on input 5
INPUT6 Service value for measurement on input 6
INPUT7 Service value for measurement on input 7
INPUT8 Service value for measurement on input 8
INPUT9 Service value for measurement on input 9
Table 367: Input signals for the I103Meas (IMM1-) function block
Signal Description
BLOCK Block of service value reporting
IL1 Service value for current phase L1
IL2 Service value for current phase L2
IL3 Service value for current phase L3
IN Service value for residual current IN
UL1 Service value for voltage phase L1
UL2 Service value for voltage phase L2
UL3 Service value for voltage phase L3
UL1L2 Service value for voltage phase-phase L1-L2
UN Service value for residual voltage UN
P Service value for active power
Q Service value for reactive power
F Service value for system frequency
Table 368: Output signals for the I103FuncCMD (ICMD-) function block
Signal Description
16-AR Information number 16, block of autorecloser
17-DIFF Information number 17, block of differential protection
18-PROT Information number 18, block of protection
Table 369: Output signals for the I103IEDCMD (ICMA-) function block
Signal Description
19-LEDRS Information number 19, reset LEDs
23-GRP1 Information number 23, activate setting group 1
24-GRP2 Information number 24, activate setting group 2
25-GRP3 Information number 25, activate setting group 3
26-GRP4 Information number 26, activate setting group 4
Table 370: Output signals for the I103FuncUserCM (ICM1-) function block
Signal Description
OUTPUT1 Command output 1
OUTPUT2 Command output 2
OUTPUT3 Command output 3
OUTPUT4 Command output 4
OUTPUT5 Command output 5
OUTPUT6 Command output 6
OUTPUT7 Command output 7
OUTPUT8 Command output 8
16.6.1 Introduction
The IEDs can receive commands either from a substation automation system or from
the local human-machine interface, LHMI. The command function block has outputs
that can be used, for example, to control high voltage apparatuses or for other user
defined functionality.
The output signals can be of the types Off, Steady, or Pulse. This configuration setting
is done via the LHMI or PCM 600 and is common for the whole function block. The
length of the output pulses are 100 ms. In steady mode the function block has a
memory to remember the output values at power interruption of the IED. Also a
BLOCK input is available used to block the updating of the outputs.
The output signals, here OUT1 to OUT16, are then available for configuration to
built-in functions or via the configuration logic circuits to the binary outputs of the
IED.
en05000698.vsd
Table 384: Output signals for the SingleCmd (CD01-) function block
Signal Description
OUT1 Single command output 1
OUT2 Single command output 2
OUT3 Single command output 3
OUT4 Single command output 4
OUT5 Single command output 5
OUT6 Single command output 6
OUT7 Single command output 7
OUT8 Single command output 8
OUT9 Single command output 9
OUT10 Single command output 10
OUT11 Single command output 11
OUT12 Single command output 12
OUT13 Single command output 13
OUT14 Single command output 14
Table continued on next page
Signal Description
OUT15 Single command output 15
OUT16 Single command output 16
NAME1 User defined string for single command output 1
NAME2 User defined string for single command output 2
NAME3 User defined string for single command output 3
NAME4 User defined string for single command output 4
NAME5 User defined string for single command output 5
NAME6 User defined string for single command output 6
NAME7 User defined string for single command output 7
NAME8 User defined string for single command output 8
NAME9 User defined string for single command output 9
NAME10 User defined string for single command output 10
NAME11 User defined string for single command output 11
NAME12 User defined string for single command output 12
NAME13 User defined string for single command output 13
NAME14 User defined string for single command output 14
NAME15 User defined string for single command output 15
NAME16 User defined string for single command output 16
Table 385: Input signals for the SingleCmd (CD01-) function block
Signal Description
BLOCK Block single command function
16.7.1 Introduction
The IED may be provided with a function to send and receive signals to and from
other IEDs via the interbay bus. The send and receive function blocks has 16 outputs/
inputs that can be used, together with the configuration logic circuits, for control
purposes within the IED or via binary outputs. When it is used to communicate with
other IEDs, these IEDs have a corresponding Multiple transmit function block with
16 outputs to send the information received by the command block.
Sixteen signals can be connected and they will then be sent to the multiple command
block in the other IED. The connections are set with the LON Network Tool (LNT).
Twelve multiple command function block CM12 with fast execution time and 48
multiple command function blocks CM13-CM60 with slower execution time are
available in the IED 670s.
The multiple command function block has 16 outputs combined in one block, which
can be controlled from other IEDs.
The output signals, here OUT1 to OUT16, are then available for configuration to
built-in functions or via the configuration logic circuits to the binary outputs of the
terminal.
The command function also has a supervision function, which sets the output VALID
to 0 if the block did not receive data within set maximum time.
16.7.3 Design
16.7.3.1 General
The output signals can be of the types Off, Steady, or Pulse. The setting is done on
the MODE settings, common for the whole block, from the PCM 600 setting tool.
• 0 = Off sets all outputs to 0, independent of the values sent from the station level,
that is, the operator station or remote-control gateway.
• 1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
• 2 = Pulse gives a pulse with one execution cycle duration, if a value sent from
the station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer
than the execution cycle time for the command function block.
CM01-
MultiCmd
BLOCK ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
en06000007.vsd
MT01-
MultiTransm
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
en06000008.vsd
Table 387: Input signals for the MultiCmd (CM01-) function block
Signal Description
BLOCK Block of function
Table 388: Input signals for the MultiTransm (MT01-) function block
Signal Description
BLOCK Block of function
INPUT1 Input 1
INPUT2 Input 2
INPUT3 Input 3
INPUT4 Input 4
INPUT5 Input 5
INPUT6 Input 6
INPUT7 Input 7
INPUT8 Input 8
INPUT9 Input 9
INPUT10 Input 10
INPUT11 Input 11
INPUT12 Input 12
INPUT13 Input 13
INPUT14 Input 14
INPUT15 Input 15
INPUT16 Input 16
Table 389: Output signals for the MultiCmd (CM01-) function block
Signal Description
ERROR MultiReceive error
NEWDATA New data is received
OUTPUT1 Output 1
OUTPUT2 Output 2
OUTPUT3 Output 3
OUTPUT4 Output 4
OUTPUT5 Output 5
OUTPUT6 Output 6
OUTPUT7 Output 7
OUTPUT8 Output 8
OUTPUT9 Output 9
OUTPUT10 Output 10
OUTPUT11 Output 11
OUTPUT12 Output 12
OUTPUT13 Output 13
OUTPUT14 Output 14
Table continued on next page
Signal Description
OUTPUT15 Output 15
OUTPUT16 Output 16
VALID Output data is valid
Table 390: Output signals for the MultiTransm (MT01-) function block
Signal Description
ERROR MultiSend error
17.1.1 Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection in
RED670, or for transmission of only binary signals, up to 192 signals, in the other
600 series IEDs. The binary signals are freely configurable and can thus be used for
any purpose e.g. communication scheme related signals, transfer trip and/or other
binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with an
LDCMs (Line Data Communication Module). The LDCMs are then interfaces to a
64 kbit/s communication channel for duplex communication between the IEDs.
Each IED can be equipped with up to four LDCMs, thus enabling communication
with four remote IEDs.
Start Stop
Information CRC
flag flag
The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in the
HDLC standard. The CRC is designed according to the standard CRC16 definition.
The optional address field in the HDLC frame is not used instead a separate addressing
is included in the data field.
The address field is used for checking that the received message originates from the
correct equipment. There is always a risk that multiplexers occasionally mixe the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC function
detects a faulty message, the message is thrown away and not used in the evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and eight
binary signals which can be used for any purpose. The three currents are represented
as sampled values.
When the communication is used exclusively for binary signals, the full data capacity
of the communication channel is used for the binary signal purpose which gives the
capacity of 192 signals.
CRM1-
LDCMRecBinStat
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
en07000043.vsd
CRM2-
LDCMRecBinStat
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
en07000044.vsd
CRB1-
LDCMRecBinStat
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGT HERR
CRCERROR
REMCOMF
LOWLEVEL
en05000451.vsd
Table 393: Output signals for the LDCMRecBinStat (CRM1-) function block
Signal Description
COMFAIL Detected error in the differential communication
YBIT Detected error in remote end with incoming message
NOCARR No carrier is detected in the incoming message
NOMESS No start and stop flags identified for the incoming message
ADDRERR Incoming message from a wrong terminal
Table continued on next page
Signal Description
LNGTHERR Wrong length of the incoming message
CRCERROR Identified error by CRC check in incoming message
TRDELERR Transmission time is longer than permitted
SYNCERR Indicates when echo synchronication is used
REMCOMF Remote terminal indicates problem with received message
REMGPSER Remote terminal indicates problem with GPS synchronization
SUBSTITU Link error, values are substituted
LOWLEVEL Low signal level on the receive link
Table 394: Output signals for the LDCMRecBinStat (CRM2-) function block
Signal Description
COMFAIL Detected error in the differential communication
YBIT Detected error in remote end with incoming message
NOCARR No carrier is detected in the incoming message
NOMESS No start and stop flags identified for the incoming message
ADDRERR Incoming message from a wrong terminal
LNGTHERR Wrong length of the incoming message
CRCERROR Identified error by CRC check in incoming message
TRDELERR Transmission time is longer than permitted
SYNCERR Indicates when echo synchronication is used
REMCOMF Remote terminal indicates problem with received message
REMGPSER Remote terminal indicates problem with GPS synchronization
SUBSTITU Link error, values are substituted
LOWLEVEL Low signal level on the receive link
Table 395: Output signals for the LDCMRecBinStat (CRB1-) function block
Signal Description
COMFAIL Detected error in the differential communication
YBIT Detected error in remote end with incoming message
NOCARR No carrier is detected in the incoming message
NOMESS No start and stop flags identified for the incoming message
ADDRERR Incoming message from a wrong terminal
LNGTHERR Wrong length of the incoming message
CRCERROR Identified error by CRC check in incoming message
REMCOMF Remote terminal indicates problem with received message
LOWLEVEL Low signal level on the receive link
Table 396: Basic general settings for the LDCMRecBinStat (CRM1-) function
Parameter Range Step Default Unit Description
ChannelMode Off - On - Channel mode of
On LDCM, 0=OFF,
OutOfService 1=ON,
2=OutOfService
TerminalNo 0 1 0 - 255 - Terminal number
used for line
differential
communication
RemoteTermNo 0 1 0 - 255 - Terminal number on
remote terminal
DiffSync Echo - Echo - Diff Synchronization
GPS mode of LDCM,
0=ECHO, 1=GPS
GPSSyncErr Block - Block - Operation mode
Echo when GPS
synchroniation signal
is lost
CommSync Slave - Slave - Com Synchronization
Master mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower - LowPower - Transmission power
HighPower for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1 - CT-GRP1 - Summation mode for
CT-GRP2 transmitted current
CT-SUM values
CT-DIFF1
CT-DIFF2
ComFailAlrmDel 5 - 500 5 100 ms Time delay before
communication error
signal is activated
ComFailResDel 5 - 500 5 100 ms Reset delay before
communication error
signal is reset
RedChSwTime 5 - 500 5 5 ms Time delay before
switching in
redundant channel
RedChRturnTime 5 - 500 5 100 ms Time delay before
switching back from
redundant channel
AsymDelay -20.00 - 20.00 0.01 0.00 ms Asymmetric delay
when communication
use echo synch.
MaxTransmDelay 0 - 40 1 20 ms Max allowed
transmission delay
CompRange 0-10kA - 0-25kA - Compression range
0-25kA
0-50kA
0-150kA
Table continued on next page
Table 397: Basic general settings for the LDCMRecBinStat (CRM2-) function
Parameter Range Step Default Unit Description
ChannelMode Off - On - Channel mode of
On LDCM, 0=OFF,
OutOfService 1=ON,
2=OutOfService
TerminalNo 0 1 0 - 255 - Terminal number
used for line
differential
communication
RemoteTermNo 0 1 0 - 255 - Terminal number on
remote terminal
DiffSync Echo - Echo - Diff Synchronization
GPS mode of LDCM,
0=ECHO, 1=GPS
GPSSyncErr Block - Block - Operation mode
Echo when GPS
synchroniation signal
is lost
CommSync Slave - Slave - Com Synchronization
Master mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower - LowPower - Transmission power
HighPower for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1 - CT-GRP1 - Summation mode for
CT-GRP2 transmitted current
CT-SUM values
CT-DIFF1
CT-DIFF2
RedundantChann
el
ComFailAlrmDel 5 - 500 5 100 ms Time delay before
communication error
signal is activated
ComFailResDel 5 - 500 5 100 ms Reset delay before
communication error
signal is reset
RedChSwTime 5 - 500 5 5 ms Time delay before
switching in
redundant channel
RedChRturnTime 5 - 500 5 100 ms Time delay before
switching back from
redundant channel
Table continued on next page
Table 398: Basic general settings for the LDCMRecBinStat (CRB1-) function
Parameter Range Step Default Unit Description
ChannelMode Off - On - Channel mode of
On LDCM, 0=OFF,
OutOfService 1=ON,
2=OutOfService
TerminalNo 0 1 0 - 255 - Terminal number
used for line
differential
communication
RemoteTermNo 0 1 0 - 255 - Terminal number on
remote terminal
CommSync Slave - Slave - Com Synchronization
Master mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower - LowPower - Transmission power
HighPower for LDCM, 0=Low,
1=High
ComFailAlrmDel 5 - 500 5 100 ms Time delay before
communication error
signal is activated
ComFailResDel 5 - 500 5 100 ms Reset delay before
communication error
signal is reset
InvertPolX21 Off - Off - Invert polarization for
On X21 communication
Section 18 Hardware
18.1 Overview
xx04000458.eps
xx04000459.eps
xx05000763.eps
xx04000460.eps
xx04000461.eps
Table 399: Designations for 1/2 x 19” casing with 1 TRM slot
Table 400: Designations for 3/4 x 19” casing with 1 TRM slot
Table 401: Designations for 3/4 x 19” casing with 2TRM slot
Table 402: Designations for 1/1 x 19” casing with 1 TRM slot
Table 403: Designations for 1/1 x 19” casing with 2 TRM slots
18.2.1 Overview
Table 404: Basic modules, always included
Module Description
Combined backplane module (CBM) A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM is not
connected directly to this board.
Universal backplane module (UBM) A backplane PCB that forms part of the IED
backplane with connectors for TRM, ADM etc.
Power supply module (PSM) Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.
18.2.2.1 Introduction
The combined backplane module (CBM) carries signals between modules in an IED.
18.2.2.2 Functionality
The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The CBM
backplane and connected modules are 5V PCI-compatible.
Some pins on the Compact PCI connector are connected to the CAN bus, to be able
to communicate with CAN based modules.
If a modules self test discovers an error it informs other modules using the Internal
Fail signal IRF.
18.2.2.3 Design
used by other PCI modules, for example two ADMs in IEDs with two TRMs.
See figure 321
• with 2 Compact PCI connectors and a number of euro connectors depending on
the IED case size. One Compact PCI connector is used by NUM and one is used
by for example an ADM in IEDs with one TRM. See figure 320
Each PCI connector consists of 2 compact PCI receptacles. The euro connectors are
connected to the CAN bus and used for I/O modules and power supply.
1 2
en05000516.vsd
1 2
en05000755.vsd
2 CPCI slots
en05000756.vsd
18.2.3.1 Introduction
The Universal Backplane Module (UBM) is part of the IED backplane and is mounted
above the CBM. It connects the Transformer input module (TRM) to the Analog
digital conversion module (ADM) and the Numerical module (NUM).
18.2.3.2 Functionality
The Universal Backplane Module connects the CT and VT analogue signals from the
transformer input module to the analogue digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on
the front panel as well as the internal ethernet and D-sub contacts are connected to
the UBM which provides the signal path to the NUM board.
18.2.3.3 Design
It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).
• for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and
one 96 pin euro connector, see figure 324
• for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and
one 96 pin euro connector, see figure 325.
The 96 pin euro connector is used to connect the NUM board to the backplane. The
48 pin connectors are used to connect the TRM and ADM.
TRM ADM
NUM
AD Data
X1 X2
X3 X4
RS485
X10 X10
Front Ethernet
LHMI connection
port
Ethernet X5
en05000489.vsd
en05000757.vsd
en05000758.vsd
en05000759.vsd
18.2.4.1 Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output
is available.
18.2.4.2 Design
There are two types of the power supply module. They are designed for different DC
input voltage ranges see table 406. The power supply module contains a built-in, self-
regulated DC/DC converter that provides full isolation between the terminal and the
external battery system.
Block diagram
Input connector
Power
Filter supply
Backplane connector
Supervision
99000516.vsd
18.2.5.1 Introduction
The Numeric processing module (NUM), is a CPU-module that handles all protection
functions and logic.
For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM is
the compact PCI system card i.e. it controls bus mastering, clock distribution and
receives interrupts.
18.2.5.2 Functionality
The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PCMIP slots
onto which mezzanine cards such as OEM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC slot and external PCI accesses
through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a flash
file system. During power up the application code is moved to and then executed from
the DRAM. The code is stored in the flash memory because it is nonvolatile and
executed in DRAM because of the higher performance of DRAM.
The NUM is equipped with a real time clock. It uses a capacitor for power backup of
the real time clock.
No forced cooling is used on this standard module because of the low power
dissipation.
Compact
Flash Logic
PMC
connector
PC-MIP
connector
UBM
Memory Ethernet
North
bridge
Backplane
PCI-PCI-
connector
bridge
CPU
en04000473.vsd
18.2.7.1 Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The
module has twelve inputs in different combinations.
18.2.7.2 Design
The transformer module has 12 input transformers. There are several versions of the
module, each with a different combination of voltage and current input transformers.
Basic versions:
The TRM is connected to the ADM and NUM via the UBM.
Configuration of the input and output signals, please refer to section "Signal matrix
for analog inputs (SMAI)".
18.2.8.1 Introduction
The Analog/Digital module has twelve analogue inputs, 2 PCMIP slots and 1 PMC
slot. The PCMIP slot is used for the LDCM card and the PMC slot for the SLM and
OEM modules. The OEM card should always be mounted on the NUM board if only
one card is needed. In cases where two cards are needed then the PCM slot on the
ADM may be used for the second OEM. The UBM connects the ADM to the
transformer input module (TRM).
18.2.8.2 Design
The Analog digital conversion module input signals are voltage and current from the
transformer module. Shunts are used to adapt the current signals to the electronic
voltage level. To gain dynamic range for the current inputs, two shunts with separate
A\D channels are used for each input current. In this way a 20 bit dynamic range is
obtained with a 16 bit A\D converter.
The A\D converted signals go through a filter with a cut off frequency of 500 Hz and
are reported to the numerical module (NUM) with 1 kHz at 50 Hz system frequency
and 1,2 kHz at 60 Hz system frequency.
Channel 1
AD1 Channel 2
Channel 3
Channel 4
AD2
Channel 5
1.2v Channel 6
AD3 Channel 7
Channel 8
Channel 9
AD4 Channel 10
Channel 11
Channel 12
PMC
level shift
PC-MIP
2.5v
PCI to PCI
PC-MIP
en05000474.vsd
18.2.9.1 Introduction
The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the inputs
to be used with the pulse counter function. The binary inputs are freely programmable
and can be used for the input of logical signals to any of the functions. They can also
be included in the disturbance recording and event-recording functions. This enables
extensive monitoring and evaluation of operation of the IED and for all associated
electrical circuits.
18.2.9.2 Design
The Binary input module contains 16 optical isolated binary inputs. The voltage level
of the binary input is selected at order.
For configuration of the input signals, please refer to section "Signal matrix for binary
inputs (SMBI)".
Figure 330 shows the operating characteristics of the binary inputs of the four voltage
levels.
[V]
300
176
144
88
72
38
32
19
18
Guaranteed operation
Operation uncertain
No operation
This binary input module communicates with the Numerical module (NUM) via the
CAN-bus on the backplane.
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 331 and 332.
[mA]
30
1
35 70 [ms]
en03000108.vsd
Figure 331: Approximate binary input inrush current for the standard version of
BIM.
[mA]
30
1
3.5 7.0 [ms]
en05000455.vsd
Figure 332: Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.
Process connector
Opto isolated input
Backplane connector
Process connector
CAN
Opto isolated input
99000503.vsd
Table 409: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL RL24 (24/40) V RL ± 20%
RL48 (48/60) V RL ± 20%
RL110 (110/125) V RL ± 20%
RL220 (220/250) V RL ± 20%
Power consumption
RL24 = (24/40) V max. 0.05 W/input -
RL48 = (48/60) V max. 0.1 W/input
RL110 = (110/125) V max. 0.2 W/input
RL220 = (220/250) V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
18.2.10.1 Introduction
The binary output module has 24 independent output relays and is used for trip output
or any signalling purpose.
18.2.10.2 Design
The binary output module (BOM) has 24 software supervised output relays. Each
pair of relays have a common power source input to the contacts, see figure 334. This
should be considered when connecting the wiring to the connection terminal on the
back of the IED.
The high closing and carrying current capability allows connection directly to breaker
trip and closing coils. If breaking capability is required to manage fail of the breaker
auxiliary contacts normally breaking the trip coil current, a parallel reinforcement is
required.
For configuration of the output signals, please refer to section "Signal matrix for
binary outputs (SMBO)".
Output module
xx00000299.vsd
Relay
Relay
Relay
Relay
Relay
Process connector
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Backplane connector
Process connector
Relay Micro-
controller
Relay
Relay
CAN
Relay
Relay Memory
Relay
Relay
99000505.vsd
Table 410: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Continuous 8A
1s 10 A
Table continued on next page
18.2.11.1 Introduction
The binary input/output module is used when only a few input and output channels
are needed. The ten standard output channels are used for trip output or any signalling
purpose. The two high speed signal output channels are used for applications where
short operating time is essential. Eight optically isolated binary inputs cater for
required binary input information.
18.2.11.2 Design
Inputs are designed to allow oxide burn-off from connected contacts, and increase
the disturbance immunity during normal protection operate times. This is achieved
with a high peak inrush current while having a low steady-state current, see figure
331. Inputs are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply earth faults, see figure 330.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output relays.
One of the outputs has a change-over contact. The nine remaining output contacts are
connected in two groups. One group has five contacts with a common and the other
group has four contacts with a common, to be used as single-output channels, see
figure 336.
The binary I/O module also has two high speed output channels where a reed relay
is connected in parallel to the standard output relay.
For configuration of the input and output signals, please refer to sections "Signal
matrix for binary inputs (SMBI)" and "Signal matrix for binary outputs (SMBO)".
Figure 336: Binary in/out module (IOM), input contacts named XA corresponds
to rear position X31, X41, etc. and output contacts named XB to rear
position X32, X42, etc.
Table 412: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel reed
relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V AC, DC
Test voltage across open contact, 1000 V rms 800 V DC
1 min
Current carrying capacity
Continuous 8A 8A
1s 10 A 10 A
Making capacity at inductive load
with L/R>10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Breaking capacity for AC, cos φ > 250 V/8.0 A 250 V/8.0 A
0.4
Breaking capacity for DC with L/R 48 V/1 A 48 V/1 A
< 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
18.2.12.1 Introduction
The line data communication module (LDCM) is used for communication between
the IEDs or from the IED to optical to electrical converter with G.703 interface located
on a distances <3 km away. The LDCM module sends and receives data, to and from
another LDCM module. The IEEE/ANSI C37.94 standard format is used.
The line data communication module is used for binary signal transfer. Each module
has one optical port, one for each remote end to which the IED communicates.
Alternative cards for Long range (1550 nm single mode), Medium range (1310 nm
single mode) and Short range (900 nm multi mode) are available.
18.2.12.2 Design
The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:
• the ADM
• the NUM
ID
ST
16.000
IO-connector
MHz
32,768
MHz
ST
en05000473.vsd
Figure 337: The SR-LDCM layout. PCMIP type II single width format with two PCI
connectors and one I/O ST type connector
X1
C
ADN 2.5V
ID
2841
PCI9054
FPGA TQ176
DS DS
256 FBGA
3904 3904
MAX
3645
3
2
en06000393.vsd
Figure 338: The MR-LDCM and LR-LDCM layout. PCMIP type II single width
format with two PCI connectors and one I/O FC/PC type connector
18.2.13.1 Introduction
The serial communication module (SLM) is used for SPA or IEC 60870-5-103 and
LON communication. The module has two communication ports, one for serial
communication and one dedicated for LON communication.
18.2.13.2 Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the NUM
module. Three variants of the SLM is available with different combinations of optical
fibre connectors, see figure 339. The plastic fibre connectors are of snap-in type and
the glass fibre connectors are of ST type.
1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103
4 Transmitter, SPA/IEC 60870-5-103
18.2.14.1 Introduction
18.2.14.2 Functionality
The Optical Ethernet module (OEM) is used when communication systems according
to IEC61850–8–1 have been implemented. Refer to section "Line data
communication module (LDCM)" for further information.
18.2.14.3 Design
The Optical Ethernet module (OEM) is a PCM card and mounted as a mezzanine card
on the NUM. If a second OEM is needed it is mounted on the NUM. The OEM is a
100base Fx module and available as a single channel or double channel unit.
100Base-FX
Transmitter
ID chip ST fiber optic
Ethernet Controller
connectors
100Base-FX
EEPROM
IO - bus Connector Receiver
en04000472.vsd
ID chip
Receiver
IO bus
LED
Ethernet cont.
25MHz oscillator
Transmitter
Receiver
LED
PCI bus
Ethernet cont. PCI to PCI
bridge
25MHz oscillator
Transmitter
en05000472.vsd
18.2.15.1 Introduction
The milli-ampere input module is used to interface transducer signals in the –20 to
+20 mA range from for example OLTC position, temperature or pressure
transducers.The module has six independent, galvanically separated channels.
18.2.15.2 Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, please refer to section "Signal matrix for mA
inputs (SMMI)".
The analog inputs measure DC and low frequency currents in the range of +/- 20mA.
The A/D converter has a digital filter with selectable filter frequency. All inputs are
calibrated separately The filter parameters and the calibration factors are stored in a
non-volatile memory on the module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The module
communicates, like the other I/O-modules on the serial CAN-bus.
Process connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC
Backplane connector
A/D Converter Opto-
Protection isolation
& filter
Volt-ref DC/DC
CAN
Memory Micro-
controller
99000504.vsd
Power consumption -
each mA-board £4W
each mA input £ 0.1 W
18.2.16.1 Introduction
This module includes the GPS receiver used for time synchronization. The GPS has
one SMA contact for connection to an antenna.
18.2.16.2 Design
The GPS time synchronization module is 6U high and occupies one slot. The slot
closest to the NUM shall always be used.
The CCM is a carrier board for the GCM mezzanine PCM card and GPS unit, see
figure 345. There is a cable between the external antenna input on the back of the
GCM and the GPS-receiver. This is a galvanic connection vulnerable to electro-
magnetic interference. The connector is shielded and directly attached to a grounded
plate to reduce the risk. The second cable is a flat cable that connects the GPS and
the GCM. It is used for communication between the GCM and the GPS-receiver. All
communication between the GCM and the NUM is via the CAN-bus.
The CMPPS signal is sent from the GCM to the rest of the time system to provide
1µs accuracy at sampling level.
PMC
GPS GPS clock
GPS antenna
receiver module
CMPPS
Backplane CAN
CAN
connector
controller CAN
en05000675.vsd
xx05000471.vsd
Figure 345: A CCM with the GCM and GPS mounted with cables
1 GPS receiver
2 GPS Clock module (GCM)
3 CAN carrier module (CCM)
4 Antenna connector
18.2.17.1 Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.
18.2.17.2 Design
The antenna with a console for mounting on a horizontal or vertical flat surface or on
an antenna mast. See figure 346
1 6
4 7
xx04000155.vsd
where:
1 GPS antenna
2 TNC connector
3 Console, 78x150 mm
4 Mounting holes 5.5 mm
5 Tab for securing of antenna cable
6 Vertical mounting position
7 Horizontal mounting position
Always position the antenna and its console so that a continuous clear line-of-sight
visibility to all directions is obtained, preferably more than 75%. A minimum of 50%
clear line-of-sight visibility is required for un-interrupted operation.
99001046.vsd
Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a male
SMA connector in the receiver end to connect the antenna to GSM. Choose cable
type and length so that the total attenuation is max. 26 dB at 1.6 GHz.
Make sure that the antenna cable is not charged when connected to
the antenna or to the receiver. Short-circuit the end of the antenna
cable with some metal device, when first connected to the antenna.
When the antenna is connected to the cable, connect the cable to the
receiver. REx670 must be switched off when the antenna cable is
connected.
E
K
D
A F
B C
G J
xx04000448.vsd H
Case size A B C D E F G H J K
6U, 1/2 x 19” 265.9 223.7 201.1 252.9 205.7 190.5 203.7 - 187.6 -
6U, 3/4 x 19” 265.9 336.0 201.1 252.9 318.0 190.5 316.0 - 187.6 -
6U, 1/1 x 19” 265.9 448.3 201.1 252.9 430.3 190.5 428.3 465.1 187.6 482.6
(mm)
The H and K dimensions are defined by the 19” rack mounting kit
D F
J
B G
C H xx05000502.vsd
xx05000501.vsd
xx05000503.vsd
Case size A B C D E F G H J K
6U, 1/2 x 19” 265.9 223.7 242.1 255.8 205.7 190.5 203.7 - 228.6 -
6U, 3/4 x 19” 265.9 336.0 242.1 255.8 318.0 190.5 316.0 - 228.6 -
6U, 1/1 x 19” 265.9 448.3 242.1 255.8 430.3 190.5 428.3 465.1 228.6 482.6
The H and K dimensions are defined by the 19” rack mounting kit. All dimensions are in millimeters.
A C
E
D
xx04000465.vsd
Cut-out
Case size dimensions (mm)
Tolerance
A B C D
+/-1 +/-1
6U, 1/2 x 19” 210.1 254.3 4.0-10.0 12.5
6U, 3/4 x 19” 322.4 254.3 4.0-10.0 12.5
6U, 1/1 x 19” 434.7 254.3 4.0-10.0 12.5
E = 188.6 mm without rear protection cover, 229.6 mm with rear protection cover
xx06000182.vsd
Figure 354: A 1/2 x 19” size IED 670 side-by-side with RHGS6.
G
D
B
E
F
C
xx05000505.vsd
Case size A B C D E F G
(mm) ±1 ±1 ±1 ±1 ±1 ±1 ±1
Tolerance
6U, 1/2 x 214.0 259.3 240.4 190.5 34.4 13.2 6.4 diam
19”
6U, 3/4 x 326.4 259.3 352.8 190.5 34.4 13.2 6.4 diam
19”
6U, 1/1 x 438.7 259.3 465.1 190.5 34.4 13.2 6.4 diam
19”
B
E
C
D
en04000471.vsd
[4.02]
Dimension
mm [inches] xx06000232.eps
[7.50]
en06000234.eps
[inches]
Figure 358: Dimension drawing of a three phase high impedance resistor unit
18.4.1.1 Overview
All IED sizes, 1/2 x 19”, 3/4 x 19” and 1/1 x 19” and RHGS6 6U 1/4 x 19”, cases,
can be flush mounted. Only a single case can be mounted in each cut-out on the cubicle
panel, for class IP54 protection.
The flush mounting kit are utilized for IEDs of sizes: 1/2 x 19”, 3/4 x 19” and 1/1 x
19” and are also suitable for mounting of RHGS6, 6U 1/4 x 19” cases.
1
7
2
6
5
3
xx06000246.vsd
18.4.2.1 Overview
All IED sizes can be mounted in a standard 19” cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening screws
for the angles. The mounting angles are reversible which enables mounting of IED
size 1/2 x 19” or 3/4 x 19” either to the left or right side of the cubicle.
Please note that the separately ordered rack mounting kit for side-by-
side mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19”.
1a
1b
xx04000452.vs d
18.4.3.1 Overview
All case sizes, 1/2 x 19”, 3/4 x 19” and 1/1 x 19”, can be wall mounted. It is also
possible to mount the IED on a panel or in a cubicle.
When mounting the side plates, be sure to use screws that follows the
recommended dimensions. Using screws with other dimensions than
the original may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication modules
with fiber connection; Serial SPA/IEC 60870-5-103 and LON
communication module (SLM), Optical Ethernet module (OEM) and
Line data communication module (LDCM).
3
4
2
6
xx04000453.vs d
The IED can be equipped with a rear protection cover which is recommended to use
with this type of mounting. See figure 362.
To reach the rear side of the IED, a free space of 80 mm is required on the unhinged
side.
3
1
80 mm 2
en06000135.vsd
Figure 362: How to reach the connectors on the rear side of the IED.
18.4.4.1 Overview
IED case sizes, 1/2 x 19” or 3/4 x 19” and RHGS cases, can be mounted side-by-side
up to a maximum size of 19”. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19” rack panel mounting kit must be used. The
mounting kit has to be ordered separately.
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws with
other dimensions than the original may damage the PCBs inside the
IED.
2
1
xx04000456.vsd
An 1/2 x 19” or 3/4 x 19” size IED can be mounted with a RHGS (6 or 12 depending
on IED size) case. The RHGS case can be used for mounting a test switch of type
RTXP 24. It also has enough space for a terminal base of RX 2 type for mounting of,
for example, a DC-switch or two trip relays.
1 2
1 2 1 2
1 1 1 1
2 2 2 2
3 3 3 3
4 4 4 4
5 5 5 5
6 6 6 6
7 7 7 7
8 8 8 8
xx06000180.vsd
Figure 364: IED 670 (1/2 x 19”) mounted with a RHGS6 case containing a test
switch module equipped with only a test switch and a RX2 terminal
base.
18.4.5.1 Overview
It is not recommended to flush mount side by side mounted cases if IP54 is required.
If your application demands side-by-side flush mounting, the side-by-side mounting
details kit and the 19” panel rack mounting kit must be used. The mounting kit has
to be ordered separately. The maximum size of the panel cut out is 19”.
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws with
other dimensions than the original may damage the PCBs inside the
IED.
1 2
xx06000181.vsd
Figure 365: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x
19” IED).
18.5.1 Enclosure
Table 420: Water and dust protection level according to IEC 60529
Section 19 Labels
2
3
6
6 5
7
xx06000574.eps
4
en06000573.eps
1 Warning label
2 Caution label
3 Class 1 laser product label
4 Warning label
This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.
21.1 Application
Stage 3
Time
Stage 2 Stage 2
Fault point
position
en05000130.vsd
Time
Fault point
position
en05000131.vsd
The inverse time characteristic makes it possible to minimize the fault clearance time
and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of following
factors, in a simple case with two protections in series:
A1 B1
Feeder
I> I>
Time axis
en05000132.vsd
where:
t=0 is The fault occurs
t=t1 is Protection B1 trips
In the case protection B1 shall operate without any intentional delay (instantaneous).
When the fault occurs the protections start to detect the fault current. After the time
t1 the protection B1 send a trip signal to the circuit breaker. The protection A1 starts
its delay timer at the same time, with some deviation in time due to differences
between the two protections. There is a possibility that A1 will start before the trip is
sent to the B1 circuit breaker.
At the time t2 the circuit breaker B1 has opened its primary contacts and thus the fault
current is interrupted. The breaker time (t2 - t1) can differ between different faults.
The maximum opening time can be given from manuals and test protocols. Still at
t2 the timer of protection A1 is active.
In most applications it is required that the delay times shall reset as fast as possible
when the current fed to the protection drops below the set current level, the reset time
shall be minimized. In some applications it is however beneficial to have some type
of delayed reset time of the overcurrent function. This can be the case in the following
applications:
• If there is a risk of intermittent faults. If the current relay, close to the faults, starts
and resets there is a risk of unselective trip from other protections in the system.
• Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for other
protection functions. It can often be valuable to have a reset delay to assure the
release function.
If current in any phase exceeds the set start current value (here internal signal
startValue), a timer, according to the selected operate mode, is started. The component
always uses the maximum of the three phase current values as the current level used
in timing calculations.
In case of definite time the timer will run constantly until the trip time is reached or
until the current drops below the reset value (start value minus the hysteresis) and the
reset time has elapsed.
For definite time delay curve index no 5 (ANSI/IEEE Definite time) or 15 (IEC
Definite time) are chosen.
The general expression for inverse time curves is according to equation 109.
æ ö
ç A
÷
t[ s ] = ç + B÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø (Equation 109)
where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.
For inverse time characteristics a time will be initiated when the current reaches the
set start level. From the general expression of the characteristic the following can be
seen:
ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø (Equation 110)
where:
top is the operation time of the protection
The time elapsed to the moment of trip is reached when the integral fulfils according
to equation 111, in addition to the constant time delay:
t
ææ i öp ö
ò ç çè in > ÷ø - C ÷ × dt ³ A × k
0 è ø (Equation 111)
For the numerical protection the sum below must fulfil the equation for trip.
n æ æ i( j ) ö p ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø (Equation 112)
where:
j=1 is the first protection execution cycle when a fault has been detected, i.e. when
i
>1
in >
Dt is the time interval between two consecutive executions of the protection algorithm,
n is the number of the execution of the algorithm when the trip time equation is fulfilled, i.e. when
a trip is given and
i (j) is the fault current at time j
For inverse time operation, the inverse-time characteristic is selectable. Both the IEC
and ANSI/IEEE standardized inverse-time characteristics are supported. The list of
characteristics in table 432 matches the list in the IEC 61850-7-4 spec.
For the ANSI/IEEE characteristics the inverse time curves are defined according to
table 433:
For the IEC characteristics the inverse time curves are defined according to
table 434:
For the IEC curves there is also a setting of the minimum time delay of operation, see
figure 370.
Operate
time
tnMin
Current
en05000133.vsd
Figure 370: Minimum time delay operation for the IEC curves
In addition to the ANSI and IEC standardized characteristics, there are also two
additional curves available; the 18 = RI time inverse and the 19 = RD time inverse.
æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø (Equation 114)
where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.
The 19 = RD time inverse curve gives a logarithmic delay, as used in the Combiflex
protection RXIDG. The curve enables a high degree of selectivity required for
sensitive residual earth fault current protection, with ability to detect high resistive
earth faults. The curve is described by equation 115:
æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø (Equation 115)
where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current
If the curve type is chosen as 17 the user can make a tailor made inverse time curve
according to the general equation 116.
æ ö
ç A
÷
t[ s ] = ç + B÷×k
çæ i ö p
÷
çç ÷ -C ÷
è è in > ø ø (Equation 116)
Also the reset time of the delayed function can be controlled. We have the possibility
to choose between three different reset type delays. Available alternatives are listed
in table 435.
If instantaneous reset is chosen the timer will be reset directly when the current drops
below the set start current level minus the hysteresis.
If IEC reset is chosen the timer is reset the timer will be reset after a set constant time
when the current drops below the set start current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after fault
clearance (when the current drops below the start current level minus the hysteresis).
The timer will reset according to equation 117.
æ ö
ç tr
÷
t[ s ] = ç ÷
ç æ i ö2 ÷
çç ÷ -1 ÷
è è in > ø ø (Equation 117)
where:
The set value tr is the reset time in case of zero current after fault clearance.
For the independent time delay characteristics (type 5 and 15) the possible delay time
settings are instantaneous (1) and IEC (2 = set constant time reset).
For ANSI inverse time delay characteristics (type 1 - 4 and 6 - 8) all three types of
reset time characteristics are available; instantaneous (1), IEC (2 = set constant time
reset) and ANSI (3 = current dependent reset time).
For IEC inverse time delay characteristics (type 9 - 14) the possible delay time settings
are instantaneous (1) and IEC (2 = set constant time reset).
For the customer tailor made inverse time delay characteristics (type 17) all three
types of reset time characteristics are available; instantaneous (1), IEC (2 = set
constant time reset) and ANSI (3 = current dependent reset time). If the current
dependent type is used settings pr, tr and cr must be given, see equation 118:
æ ö
ç tr
÷
t[ s ] = ç ÷
ç æ i ö pr ÷
çç ÷ - cr ÷
è è in > ø ø (Equation 118)
For RI and RD inverse time delay characteristics (type 18 and 19) the possible delay
time settings are instantaneous (1) and IEC (2 = set constant time reset).
Reset characteristic:
tr
t = ×k
(I 2
)
-1
I = Imeasured/Iset
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
IEC Normal Inverse no 9 A=0.14, P=0.02 IEC 60255-3, class 5 + 40 ms
IEC Very inverse no 10 A=13.5, P=1.0
IEC Inverse no 11 A=0.14, P=0.02
IEC Extremely inverse no 12 A=80.0, P=2.0
IEC Short-time inverse no 13 A=0.05, P=0.04
IEC Long-time inverse no 14 A=120, P=1.0
Table continued on next page
I = Imeasured/Iset
I = Imeasured/Iset
Table 438: Inverse time characteristics for Two step undervoltage protection (PUVM, 27)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms
0.01
k
t =
æ U < -U
ö
ç ÷
è U< ø
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
Table 439: Inverse time characteristics for Two step overvoltage protection (POVM, 59)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms
0.01
k
t =
æU -U >ö
ç ÷
è U> ø
U> = Uset
U = Umeasured
Table 440: Inverse time characteristics for Two step residual overvoltage protection (POVM, 59N)
Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms
0.01
k
t =
æU -U >ö
ç ÷
è U> ø
U> = Uset
U = Umeasured
100
10
k=
15
10
7
1
5
3
2
1
0.1
0.5
0.01
1 10 100 I/I>
xx05000764.vsd
100
10
k=
15
10
1 7
5
3
2
1
0.1
0.5
0.01
1 10 100 I/I>
xx05000765.vsd
100
10
k=
15
10
1 7
5
3
2
1
0.1
0.5
0.01
1 10 100 I/I>
xx05000766.vsd
100
k=
15
10
10
7
5
1
1
0.5
0.1
0.01
1 10 100 I/I>
xx05000767.vsd
100
10
k=
1.1
0.9
0.7
1 0.5
0.3
0.2
0.1
0.1 0.05
0.01
1 10 100 I/I>
xx05000768.vsd
100
10
1
k=
1.1
0.9
0.7
0.5
0.3
0.1 0.2
0.1
0.05
0.01
1 10 100 I/I>
xx05000769.vsd
100
10
k=
0.1 1.1
0.9
0.7
0.5
0.3
0.2
0.01 0.1
1 10 100 I/I>
0.05 xx05000770.vsd
Section 22 Glossary
22.1 Glossary
AC Alternating current
A/D converter Analog to digital converter
ADBS Amplitude dead -band supervision
ADM Analog digital conversion module, with time synchronization
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BIM Binary input module
BOM Binary output module
BR External bi-stable relay
BS British standard
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CAP 531 Configuration and programming tool
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and
Telephony. A United Nations sponsored standards body
within the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined mega pulses per second
CO cycle Close-open cycle
Co-directional Way of transmitting G.703 over a balanced line. Involves two
twisted pairs making it possible to transmit information in both
directions
COMTRADE Standard format according to IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four
twisted pairs of with two are used for transmitting data in both
directions, and two pairs for transmitting clock signals
CPU Central processor unit
CR Carrier receive
CRC Cyclic redundancy check
CS Carrier send
CT Current transformer
CVT Capacitive voltage transformer
DAR Delayed auto-reclosing
DARPA Defense Advanced Research Projects Agency (The US
developer of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFT Discrete Fourier transform
DIP-switch Small switch mounted on a printed circuit board
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE/ANSI Std.
1379-2000
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler