Вы находитесь на странице: 1из 1

Generated From A

SYSTEM FLOW DIAGRAM (P & I)

Project: HECTRA Area/Tag No: CAPSULATION Date: 03-Nov-2017 Prepared By: RVR

Internal Latent Load : 1524538 Grs / Hr

Internal Sensible Load : 0 Btu/hr

Return Air DBT RH Abs. Hum.

73.4 °F 20 + 5% 24.4 Gr / lb

Conditioned Room
Return
Damper

Fresh Air

Pre Fine Precool Aftercool Supply


Filter Filter (-) Fan

Wet Air

React Fan Heater (+) Steam Coil (+)

React Air

Filter Model Selected : FLB_25000 + FLB-20000

Process A B B1 C D D1 E E1 F G G1 H I J J1

Airflow cfm 7300 7300 42738 22700 30000 30000 30000 20038 50038 50038 50038
Temp °F 85 55 73.4 73.4 68.9 68.9 105.8 73.4 92.8 56 56
Moisture Grs / lb 162.3 64.6 24.4 24.4 34.2 34.2 7.3 24.4 14.1 14.1 14.1
Pressure ( Pa )

React K K1 L M N O P Q Q1

Airflow cfm 10000 10000 10000 10000 10000


Temp °F 85 85 284 175.3 175.3
Moisture Grs/lb 162.3 162.3 162.3 243.1 243.1
Pressure ( Pa )
Pressure

UTILITIES REQD. Heat Addition by Dehumidifier : 1195560 BTUH

Precool: 710185.7 BTUH 59.18 TR Aftercool: 1988710 BTUH 165.7 TR


208.02 KW 582.52 KW

REACTIVATION

Electric : 629.9 KW OR Steam : 0 Kgs/Hr @0 PSIG


MOTOR DETAILS

Process: 0 KW Reactivation: 0 KW
Electrical Connection(V/Ph/Hz)
Standard Unit Dimension: mm X mm X mm

Dimensions shall increase for Bypass & other options e.g. After / Pre coil , fan etc.

Version : 1.1.0.7(Linric) 01-May-2017