ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 1 OF 36

TEST REPORT FOR LINE DISTANCE PROTECTION RELAY

1. Designation: LINE DISTANCE PROTECTION RELAY


Location: 1x135MW , CONTROL ROOM / OOCHF01/ 220KV LINE PROTECTION PANEL -A

2. Name Plate Details :

Manufacturer :Nanjing Nari – Relays Electric Co.,Ltd. Rated Current : 1.0 A


Type No. : RCS 902 Rated Voltage : 100-110 VAC
Serial No. : 00029703 Rated Freq. : 50/60 Hz
Model No. : RCS 902A Aux. Voltage : 250 VDC

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A

4. Electrical Tests (Tick If Verified) Date : 26.01.2012

1. Function Test
1. Function Test
Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case earthing checked. Yes N/A
4 Indications checked. Yes N/A
5 Alarm contacts checked. Yes N/A
6 Trip contacts checked. Yes N/A
7 Reset of indications checked. Yes N/A
8 Carrier send checked. Yes N/A
9 Carrier receive checked. Yes N/A
11 Blocking inputs checked. Yes N/A
11 Switch onto fault checked. Yes N/A
12 Power swing blocking function checked. Yes N/A
13 Scheme function checked. Yes N/A
14 Week End Infeed Function checked Yes N/A

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 2 OF 36
PROJECT : MAINTENANCE TESTING OF RELAYS AND BREAKERS SHEET : 2 OF 318

5.Setting adopted
Description Parameters Settings Remarks
Line reference Line length 61.07 Km
XIL 7.33 Ω
RIL 1.46 Ω CTR : 600/1 A
X0L 22.72 Ω VTR ; 220000/110 V
R0L 4.95 Ω
IPP InR FD 0.2 A
I ROC FD 0.2 A
Z DPEC 5.97 Ω
Z Telp 18.0 Ω
Z Rev Telp 0.6 Ω
I ROC Telp 1.5 Ω
TChAuto Test 10.0H
Ko 0.7
I PSB OC 1.3 A

Zone -1 ZPG1 5.97


Zone - 2 ZPG2 9.18
tPG2 0.3
Zone - 3 ZPG3 27.17
tPG3 0.8
Zone -1 ZPP1 5.97
Zone - 2 ZPP2 9.18
tPP2 0.3
Zone - 3 ZPP3 27.17
tPP3 0.8
R Blinder 20.7 Ω
Ph.Rech 79.0°
Phio.Rech 78.0°
Phi.Sihift ZPG 0.0°
Phi.Sihift ZPP 0.0°
I ROC2 20.0 A
tROC2 10.0 Sec
IROC3 2.0 A
tROC3 0.5 sec
IROC SOTF 0.2 A
I OC VTS 2.5 A
I ROC VTS 1.6 A
toc/Roc VTS 1.0 sec
T1P AR 10.0 sec
T3P AR 10.0 sec
Ph.AR Syn Chk 30.0°

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 3 OF 36

5. Secondary injection test :

6. Switch On to Fault Function.:


Energize the manual close Binary Input through a switch and simultaneously apply 3 phase current above setting
Amps but without 3phase voltage. The protection should Trip instantaneously.
Measured Time : msecs
7. Fuse Failure function.

Un =49.0 V

Settings Measured Values


Phase
3Uo> 3Io< 3Uo> 3Io<
L1 50% - 47.81 V -
L2 50% - 47.82 V -
L3 50% - 47.82 V -

1. Apply 3 phase voltage to the relay and then remove 1ph voltage and the timer will start simultaneously “ Fuse Failure
Alarm” Appeared in : Appeared insec
Alarm” : 6.00 sec
2. Apply Zone -1 1ph fault within “6 sec” of fuse failure status. Protection triped in :0.035……. msec.
3. Apply Zone-1 1ph fault after 6sec of fuse failure status. Protection should blocked.
4. VT MCB binary input energized “Fuse Failure Indication” appeared.
Apply 3 phase Zone-1 fault and check for Protection blocked

ITEM DESCRIPTION CHECKED


1 Check operation on/off OK
2 Check operation of indication OK
3 Check operation of contacts OK

9.Powerswing test:
PSB blocking function checked :OK

Test Equipment Details


Make : Doble Engineering Company U.S.A
Type: F 6150

8.Timing test
Fault type ZONE1 ZONE2 ZONE3
A-N
B-N
C-N
A-B Refer Page No.
B-C
C-A
A-B-C

for ELSYTEC
F6TesT

Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Location Path VSLP,1x135MW

Test Definition Name Test Definition 1


Tested Date 26/01/2012
Tested By R.kanagaraj Evaluation Pass
Test Definition Description Auto saved Test result were simulated offline.

Relay Under Test General Parameters

Relay Name RCS902


Serial Number 00029703Panel-A
Manufacturer Nari-RelaysElect.Co.Ltd Model RCS 902A
Nominal Ratings: fn 50.000 Hz Max Test Current 250.000% In
Vn 110.00 V (Ph-Ph) Max Test Voltage 120.00% Vn
In 1.000 A Phase Names And Rotation A-B-C
VTR 220000 : 110 CTR 600 : 1
Station Name Substation

Protected Object Parameters

Protected Object Name LINE _1

Protected Object Parameters

Relay Functions

Function Name Impedance Function Type Impedance


Display values in Secondary Inherent Op Time 0 ms
General Tolerances
Absolute Minimum 0.100 Ohm Absolute Minimum Time 20.0 ms

Zone Elements
Zone Name Char Type Fault Characteristic t nom Residual Compensation Z tol t tol
Type Angle [ms]
-% +% -% +%

Zone1 Mho 3-Ph 79.00 35 5.00 5.00 5.00 5.00


Zone1 Mho Ph-Ph 79.00 35 5.00 5.00 5.00 5.00
Zone1 Mho Ph-N 79.00 35 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone2 Mho 3-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-N 79.00 335 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone3 Mho 3-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-N 79.00 835 KN 0.70 -2.00 5.00 5.00 5.00 5.00

Doble Page 1 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Test Configuration
Prefault Voltage 110.00 V
Prefault Current 0.000 A Angle 0 Deg
Test Method Constant Voltage
Desired Test Voltage 50 V Ph-N 50 V Ph-Ph
Max Acceptable Current 8 A
dc transient, fault inception angle
Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Prefault Voltage 110.00 V


Prefault Current 0.000 A Angle 0 Deg
Test Method Constant Voltage
Desired Test Voltage 50 V Ph-N 50 V Ph-Ph
Max Acceptable Current 8 A
dc transient, fault inception angle
Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Test Timing Trigger Selection

Prefault Duration 0.7000 s Fault Type Trigger


Max. Fault Duration 20.0000 s AN LN1 0->1
Max Fault Duration For Faster Zones x Tmax BN LN1 0->1
CN LN1 0->1
CBTripTime 0.0000 s
AB LN1 0->1
Time between shots 0.1000 s
BC LN1 0->1
CA LN1 0->1
ABC LN1 0->1

Doble Page 2 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3383 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8419 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type AN

Doble Page 3 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3382 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8308 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type BN

Doble Page 4 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0347 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3383 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8380 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type CN

Doble Page 5 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AB

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3323 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8284 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type AB

Doble Page 6 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0348 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3320 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8316 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type BC

Doble Page 7 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CA

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0349 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3380 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8431 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type CA

Doble Page 8 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type ABC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
29.257 76.21 55.80 Zone1 0.0350 0.0348 Pass 0.0150 0.0550 50.00 0.987
7.948 60.93 91.10 Zone2 0.3350 0.3327 Pass 0.3150 0.3550 50.00 3.632
21.271 55.27 85.50 Zone3 0.8350 0.8294 Pass 0.7933 0.8768 50.00 1.357
29.378 63.81 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.983
Fault Type ABC

Doble Page 9 of 9
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 13 OF 36

TEST REPORT FOR LINE DISTANCE PROTECTION RELAY

1. Designation: LINE DISTANCE PROTECTION RELAY


Location: 1x135MW , CONTROL ROOM / OOCHG01/ 220KV LINE PROTECTION PANEL -B

2. Name Plate Details :

Manufacturer :Nanjing Nari – Relays Electric Co.,Ltd. Rated Current : 1.0 A


Type No. : RCS 902 Rated Voltage : 100-110 VAC
Serial No. : Rated Freq. : 50/60 Hz
Model No. : RCS 902A Aux. Voltage : 250 VDC

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A

4. Electrical Tests (Tick If Verified) Date : 26.01.2012

1. Function Test
1. Function Test
Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case earthing checked. Yes N/A
4 Indications checked. Yes N/A
5 Alarm contacts checked. Yes N/A
6 Trip contacts checked. Yes N/A
7 Reset of indications checked. Yes N/A
8 Carrier send checked. Yes N/A
9 Carrier receive checked. Yes N/A
11 Blocking inputs checked. Yes N/A
11 Switch onto fault checked. Yes N/A
12 Power swing blocking function checked. Yes N/A
13 Scheme function checked. Yes N/A
14 Week End Infeed Function checked Yes N/A

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 14 OF 36
PROJECT : MAINTENANCE TESTING OF RELAYS AND BREAKERS SHEET : 14 OF 318

5.Setting adopted
Description Parameters Settings Remarks
Line reference Line length 61.07 Km
XIL 7.33 Ω
RIL 1.46 Ω CTR : 600/1 A
X0L 22.72 Ω VTR ; 220000/110 V
R0L 4.95 Ω
IPP InR FD 0.2 A
I ROC FD 0.2 A
Z DPEC 5.97 Ω
Z Telp 18.0 Ω
Z Rev Telp 0.6 Ω
I ROC Telp 1.5 Ω
TChAuto Test 10.0H
Ko 0.7
I PSB OC 1.3 A

Zone -1 ZPG1 5.97


Zone - 2 ZPG2 9.18
tPG2 0.3
Zone - 3 ZPG3 27.17
tPG3 0.8
Zone -1 ZPP1 5.97
Zone - 2 ZPP2 9.18
tPP2 0.3
Zone - 3 ZPP3 27.17
tPP3 0.8
R Blinder 20.7 Ω
Ph.Rech 79.0°
Phio.Rech 78.0°
Phi.Sihift ZPG 0.0°
Phi.Sihift ZPP 0.0°
I ROC2 20.0 A
tROC2 10.0 Sec
IROC3 2.0 A
tROC3 0.5 sec
IROC SOTF 0.2 A
I OC VTS 2.5 A
I ROC VTS 1.6 A
toc/Roc VTS 1.0 sec
T1P AR 10.0 sec
T3P AR 10.0 sec
Ph.AR Syn Chk 30.0°

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 15 OF 36

5. Secondary injection test :

6. Switch On to Fault Function.:


Energize the manual close Binary Input through a switch and simultaneously apply 3 phase current above setting
Amps but without 3phase voltage. The protection should Trip instantaneously.
Measured Time : -------------------msecs
7. Fuse Failure function.

Un =49.0 V

Settings Measured Values


Phase
3Uo> 3Io< 3Uo> 3Io<
L1 50% - 47.81 V -
L2 50% - 47.82 V -
L3 50% - 47.82 V -

1. Apply 3 phase voltage to the relay and then remove 1ph voltage and the timer will start simultaneously “ Fuse Failure
Alarm” Appeared in : Appeared insec
Alarm” : 6.00 sec
2. Apply Zone -1 1ph fault within “6 sec” of fuse failure status. Protection triped in :0.035……. msec.
3. Apply Zone-1 1ph fault after 6sec of fuse failure status. Protection should blocked.
4. VT MCB binary input energized “Fuse Failure Indication” appeared.
Apply 3 phase Zone-1 fault and check for Protection blocked

ITEM DESCRIPTION CHECKED


1 Check operation on/off OK
2 Check operation of indication OK
3 Check operation of contacts OK

9.Powerswing test:
PSB blocking function checked :OK

Test Equipment Details


Make : Doble Engineering Company U.S.A
Type: F 6150

8.Timing test
Fault type ZONE1 ZONE2 ZONE3
A-N
B-N
C-N
A-B Refer Page No.
B-C
C-A
A-B-C

for ELSYTEC
F6TesT

Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Location Path VSLP,1x135MW

Test Definition Name Test Definition 1


Tested Date 26/01/2012
Tested By R.kanagaraj Evaluation Pass
Test Definition Description Auto saved Auto saved Test result were simulated offline.

Relay Under Test General Parameters

Relay Name RCS902


Serial Number 00029703Panel-A
Manufacturer Nari-RelaysElect.Co.Ltd Model RCS 902A
Nominal Ratings: fn 50.000 Hz Max Test Current 250.000% In
Vn 110.00 V (Ph-Ph) Max Test Voltage 120.00% Vn
In 1.000 A Phase Names And Rotation A-B-C
VTR 220000 : 110 CTR 600 : 1
Station Name Substation

Protected Object Parameters

Protected Object Name LINE _2

Protected Object Parameters

Relay Functions

Function Name Impedance Function Type Impedance


Display values in Secondary Inherent Op Time 0 ms
General Tolerances
Absolute Minimum 0.100 Ohm Absolute Minimum Time 20.0 ms

Zone Elements
Zone Name Char Type Fault Characteristic t nom Residual Compensation Z tol t tol
Type Angle [ms]
-% +% -% +%

Zone1 Mho 3-Ph 79.00 35 5.00 5.00 5.00 5.00


Zone1 Mho Ph-Ph 79.00 35 5.00 5.00 5.00 5.00
Zone1 Mho Ph-N 79.00 35 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone2 Mho 3-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-N 79.00 335 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone3 Mho 3-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-N 79.00 835 KN 0.70 -2.00 5.00 5.00 5.00 5.00

Doble Page 1 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Test Configuration
Prefault Voltage 110.00 V
Prefault Current 0.000 A Angle 0 Deg
Test Method Constant Voltage
Desired Test Voltage 50 V Ph-N 50 V Ph-Ph
Max Acceptable Current 8 A
dc transient, fault inception angle
Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Test Timing Trigger Selection

Prefault Duration 0.7000 s Fault Type Trigger


Max. Fault Duration 20.0000 s AN LN1 0->1
Max Fault Duration For Faster Zones x Tmax BN LN1 0->1
CN LN1 0->1
CBTripTime 0.0000 s
AB LN1 0->1
Time between shots 0.1000 s
BC LN1 0->1
CA LN1 0->1
ABC LN1 0->1

Doble Page 2 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3352 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8364 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type AN

Doble Page 3 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0349 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3368 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8269 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type BN

Doble Page 4 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0352 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3364 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8275 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type CN

Doble Page 5 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AB

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0353 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3369 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8329 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type AB

Doble Page 6 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0353 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3320 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8426 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type BC

Doble Page 7 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CA

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0350 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3368 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8276 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type CA

Doble Page 8 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type ABC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
29.257 76.21 55.80 Zone1 0.0350 0.0350 Pass 0.0150 0.0550 50.00 0.987
7.948 60.93 91.10 Zone2 0.3350 0.3336 Pass 0.3150 0.3550 50.00 3.632
21.271 55.27 85.50 Zone3 0.8350 0.8371 Pass 0.7933 0.8768 50.00 1.357
29.378 63.81 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.983
Fault Type ABC

Doble Page 9 of 9
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 25 OF 36

TEST REPORT FOR LINE DISTANCE PROTECTION RELAY

1. Designation: LINE DISTANCE PROTECTION RELAY


Location: 1x135MW , CONTROL ROOM / OOCHI01/ BUS - TIE PROTECTION PANEL

2. Name Plate Details :

Manufacturer :Nanjing Nari – Relays Electric Co.,Ltd. Rated Current : 1.0 A


Type No. : RCS 902 Rated Voltage : 100-110 VAC
Serial No. : Rated Freq. : 50/60 Hz
Model No. : RCS 902A Aux. Voltage : 250 VDC

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A

4. Electrical Tests (Tick If Verified) Date : 26.01.2012

1. Function Test
1. Function Test
Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case earthing checked. Yes N/A
4 Indications checked. Yes N/A
5 Alarm contacts checked. Yes N/A
6 Trip contacts checked. Yes N/A
7 Reset of indications checked. Yes N/A
8 Carrier send checked. Yes N/A
9 Carrier receive checked. Yes N/A
11 Blocking inputs checked. Yes N/A
11 Switch onto fault checked. Yes N/A
12 Power swing blocking function checked. Yes N/A
13 Scheme function checked. Yes N/A
14 Week End Infeed Function checked Yes N/A

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 26 OF 36
PROJECT : MAINTENANCE TESTING OF RELAYS AND BREAKERS SHEET : 26 OF 318

5.Setting adopted
Description Parameters Settings Remarks
Line reference Line length 61.07 Km
XIL 7.33 Ω
RIL 1.46 Ω CTR : 600/1 A
X0L 22.72 Ω VTR ; 220000/110 V
R0L 4.95 Ω
IPP InR FD 0.2 A
I ROC FD 0.2 A
Z DPEC 5.97 Ω
Z Telp 18.0 Ω
Z Rev Telp 0.6 Ω
I ROC Telp 1.5 Ω
TChAuto Test 10.0H
Ko 0.7
I PSB OC 1.3 A

Zone -1 ZPG1 5.97


Zone - 2 ZPG2 9.18
tPG2 0.3
Zone - 3 ZPG3 27.17
tPG3 0.8
Zone -1 ZPP1 5.97
Zone - 2 ZPP2 9.18
tPP2 0.3
Zone - 3 ZPP3 27.17
tPP3 0.8
R Blinder 20.7 Ω
Ph.Rech 79.0°
Phio.Rech 78.0°
Phi.Sihift ZPG 0.0°
Phi.Sihift ZPP 0.0°
I ROC2 20.0 A
tROC2 10.0 Sec
IROC3 2.0 A
tROC3 0.5 sec
IROC SOTF 0.2 A
I OC VTS 2.5 A
I ROC VTS 1.6 A
toc/Roc VTS 1.0 sec
T1P AR 10.0 sec
T3P AR 10.0 sec
Ph.AR Syn Chk 30.0°

for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VS LIGNITE POWER PVT LTD ,BIKANER / OEG INDIA LTD TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF RELAYS SHEET : 27 OF 36

5. Secondary injection test :

6. Switch On to Fault Function.:


Energize the manual close Binary Input through a switch and simultaneously apply 3 phase current above setting
Amps but without 3phase voltage. The protection should Trip instantaneously.
Measured Time : msecs
7. Fuse Failure function.

Un =49.0 V

Settings Measured Values


Phase
3Uo> 3Io< 3Uo> 3Io<
L1 50% - 54.81 V -
L2 50% - 54.82 V -
L3 50% - 54.82 V -

1. Apply 3 phase voltage to the relay and then remove 1ph voltage and the timer will start simultaneously “ Fuse Failure
Alarm” Appeared in : Appeared insec
Alarm” : 6.00 sec
2. Apply Zone -1 1ph fault within “6 sec” of fuse failure status. Protection triped in :0.035……. msec.
3. Apply Zone-1 1ph fault after 6sec of fuse failure status. Protection should blocked.
4. VT MCB binary input energized “Fuse Failure Indication” appeared.
Apply 3 phase Zone-1 fault and check for Protection blocked

ITEM DESCRIPTION CHECKED


1 Check operation on/off OK
2 Check operation of indication OK
3 Check operation of contacts OK

9.powerswing test:
PSB blocking function checked :OK

Test Equipment Details


Make : Doble Engineering Company U.S.A
Type: F 6150

8.Timing test
Fault type ZONE1 ZONE2 ZONE3
A-N
B-N
C-N
A-B Refer Page No.
B-C
C-A
A-B-C

for ELSYTEC
F6TesT

Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Location Path VSLP,1x135MW

Test Definition Name Test Definition 1


Tested Date 26/01/2012
Tested By R.kanagaraj Evaluation Pass
Test Definition Description Auto saved Auto saved Auto saved Test result were simulated offline.

Relay Under Test General Parameters

Relay Name RCS902


Serial Number 00029703Panel-A
Manufacturer Nari-RelaysElect.Co.Ltd Model RCS 902A
Nominal Ratings: fn 50.000 Hz Max Test Current 250.000% In
Vn 110.00 V (Ph-Ph) Max Test Voltage 120.00% Vn
In 1.000 A Phase Names And Rotation A-B-C
VTR 220000 : 110 CTR 600 : 1
Station Name Substation

Protected Object Parameters

Protected Object Name LINE _1

Protected Object Parameters

Relay Functions

Function Name Impedance Function Type Impedance


Display values in Secondary Inherent Op Time 0 ms
General Tolerances
Absolute Minimum 0.100 Ohm Absolute Minimum Time 20.0 ms

Zone Elements
Zone Name Char Type Fault Characteristic t nom Residual Compensation Z tol t tol
Type Angle [ms]
-% +% -% +%

Zone1 Mho 3-Ph 79.00 35 5.00 5.00 5.00 5.00


Zone1 Mho Ph-Ph 79.00 35 5.00 5.00 5.00 5.00
Zone1 Mho Ph-N 79.00 35 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone2 Mho 3-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-Ph 79.00 335 5.00 5.00 5.00 5.00
Zone2 Mho Ph-N 79.00 335 KN 0.70 -2.00 5.00 5.00 5.00 5.00
Zone3 Mho 3-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-Ph 79.00 835 5.00 5.00 5.00 5.00
Zone3 Mho Ph-N 79.00 835 KN 0.70 -2.00 5.00 5.00 5.00 5.00

Doble Page 1 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902

Test Configuration
Prefault Voltage 110.00 V
Prefault Current 0.000 A Angle 0 Deg
Test Method Constant Voltage
Desired Test Voltage 50 V Ph-N 50 V Ph-Ph
Max Acceptable Current 8 A
dc transient, fault inception angle
Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Test Timing Trigger Selection

Prefault Duration 0.7000 s Fault Type Trigger


Max. Fault Duration 20.0000 s AN LN1 0->1
Max Fault Duration For Faster Zones x Tmax BN LN1 0->1
CN LN1 0->1
CBTripTime 0.0000 s
AB LN1 0->1
Time between shots 0.1000 s
BC LN1 0->1
CA LN1 0->1
ABC LN1 0->1

Doble Page 2 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0348 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3335 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8406 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type AN

Doble Page 3 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3383 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8419 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type BN

Doble Page 4 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CN

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.879 66.35 83.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 6.029
7.616 65.81 85.20 Zone2 0.3350 0.3382 Pass 0.3150 0.3550 50.00 3.862
17.885 61.55 69.00 Zone3 0.8350 0.8308 Pass 0.7933 0.8768 50.00 1.645
29.857 85.63 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.985
Fault Type CN

Doble Page 5 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type AB

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0347 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3383 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8380 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type AB

Doble Page 6 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type BC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0351 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3323 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8284 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type BC

Doble Page 7 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type CA

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
4.522 81.26 75.80 Zone1 0.0350 0.0348 Pass 0.0150 0.0550 50.00 5.529
8.025 78.98 87.40 Zone2 0.3350 0.3320 Pass 0.3150 0.3550 50.00 3.115
20.289 62.50 77.90 Zone3 0.8350 0.8316 Pass 0.7933 0.8768 50.00 1.232
29.257 67.79 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.854
Fault Type CA

Doble Page 8 of 9
Impedance Relay Timing Test Report 26-Jan-12

VSLP,1x135MW/RCS902
Fault Type ABC

Z Angle %Zone Zone t exp t act Eval t min t max V I


Test Test
[Ω] [°] [s] [s] [s] [s] [V] [A]
29.257 76.21 55.80 Zone1 0.0350 0.0349 Pass 0.0150 0.0550 50.00 0.987
7.948 60.93 91.10 Zone2 0.3350 0.3380 Pass 0.3150 0.3550 50.00 3.632
21.271 55.27 85.50 Zone3 0.8350 0.8431 Pass 0.7933 0.8768 50.00 1.357
29.378 63.81 0.00 NoOp NoOp Pass NoOp NoOp 50.00 0.983
Fault Type ABC

Doble Page 9 of 9