Вы находитесь на странице: 1из 56

Previous

iv

Reference Guide

Guidelines for Smoke Control

Smoke Control System

Control Systems
International TCON120.–.10/96
We at Control Systems International (CSI) have tried to make the information contained in this manual as accurate and reliable
as possible. Nevertheless, CSI disclaims any warranty of any kind, whether express or implied, as to any matter whatsoever
relating to this manual, including without limitation the merchantability or fitness for any particular purpose.
CSI will, from time to time, revise the software described in this manual and reserves the right to make such changes without
obligation to notify the purchaser. In no event shall CSI be liable for any indirect, special, incidental, or consequential damages
arising out of purchase or use of this manual or the information contained herein.
 1994, 1996 by Control Systems International. All rights reserved.
Printed in the United States of America.
Document Number: TCON120–10/96
I/NET, Control Systems International, and the Control Systems International logo are registered trademarks of Control Systems
International.
Hayes is a registered trademark and Smartmodem 2400 is a trademark of Hayes Microcomputer Products, Inc. FrameMaker is
a registered trademark of Frame Technology Corporation. Minion is a trademark of Adobe Systems Incorporated. Canvas is a
trademark of Deneba Software. All other trademarks mentioned belong to their respective owners.

About this manual:


This book was written and produced using FrameMaker workstation publishing software and the Minion font from Adobe.
Illustrations were created or modified using Canvas.
Contents
FCC Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
AHU Type 1 - Sequence of Operation - Smoke Control . . . . . . . . . 8
AHU Type 2 - Sequence of Operation - Smoke Control . . . . . . . . . 10
AHU Type 3 - Sequence of Operation - Smoke Control . . . . . . . . . 12
AHU Type 4 - Sequence of Operation - Smoke Control . . . . . . . . . 13
AHU Type 5 (Stairwell) - Sequence of Operation - Smoke Control . 14
System Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Appendix B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Appendix C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Guidelines for Smoke Control iii


Contents Reference Guide

FCC Warning

The Federal Communications Commission (FCC) requirements prescribe certification of personal computers and any intercon-
nected peripherals in the FCC rules and regulations.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: this device may not
cause harmful interference, and this device must accept any interference received, including interference that may cause undes-
ired operation.
This equipment generates and uses radio frequency (rf) energy for its operation and, if not installed and used in accordance with
the installation and operation manual, may cause interference to radio and television reception. It has been found to comply
with the limits for a Class A computing device pursuant to the aforementioned regulations. These are designed to provide
reasonable protection against such interference when operated in a residential area. Only peripherals (computer input/output
devices) certified to comply with the Class A limits may be connected to this device. Operation with noncertified computer
peripherals is likely to result in interference with radio and television reception. If this equipment does cause interference to
radio or television reception, the user is encouraged to correct the situation by one or more of the following measures.
• Relocate the receiver with respect to the computer.
• Move the computer away from the receiver.
• Plug the equipment into a different outlet, so that the computing device and receiver are on different branch circuits.
• Disconnect and remove any unused cables that may be acting as a transmission source.
• Make certain that the computing device is plugged into a grounded outlet receptacle.
If necessary, contact CSI for additional suggestions.

iv Guidelines for Smoke Control


Definition

The purpose of a smoke control system is to contain or direct the flow of smoke in
burning buildings to minimize property damage and danger to human life. The smoke
is directed by pressurizing or depressurizing separate areas or zones of the building with
air handler units and exhaust fans. A positive pressure is used to push the smoke from
the zone to an exhaust duct, or prevent it from entering the zone from an adjacent
smoke-filled zone. Negative pressure is used to prevent the smoke from leaving the zone.
Airflow may be used to stop the movement of smoke through open doorways, but is
usually impractical because of the quantities of air required to maintain an air velocity
high enough to prevent smoke movement. A tenable environment can be maintained in
an area such as a stairwell by pressurizing to allow the occupants to leave the building
and allow emergency response personnel access to the building for fire fighting and
conducting search and rescue. Adjacent zones near the smoke zones should be pressur-
ized to prevent smoke from entering through cracks around doors and around utilities
entering the zone. The zone that contains the smoke should be controlled to a negative
pressure with respect to the surrounding zones to prevent the smoke from spreading to
other areas of the building and to facilitate exhausting the smoke to the building exterior.
The ability to create a pressure difference or air flow velocity across openings to adjacent
zones is one criterion that defines a zone. Small openings such as cracks and door gaps
will need to have sufficient pressure differences across them to control smoke movement.
The pressure difference should be great enough to prevent smoke leakage and not be
overcome by the effects of wind, stack effect, and the buoyancy of hot smoke, but should
not be so high that a force greater than 30 pounds is required to begin opening a door to
adjacent zones. Large openings such as open doors must have a sufficient air velocity
through the opening to prevent smoke movement. Similar variables are used to deter-
mine minimum air velocities (refer to NFPA-92A and ASHRAE’s Design of Smoke
Management Systems for additional information).
The number of open doors is another design criterion for defining zones. The occupancy
of the building will determine how many doors are open simultaneously and will affect
the pressure difference. Some doors may only be open for a short period of time creating
negligible smoke leakage.
The size of the zone should be considered during design. It should be small enough to
allow for the evacuation or pressurization of the air in the zone within a reasonable
amount of time. It should also be large enough to be able to dilute the heat buildup from
the fire with surrounding air so that components of the smoke control system do not fail.
The zone should also be designed to match the alarm zone and the HVAC equipment to
avoid activating the wrong smoke control equipment. An AHU should be completely
contained within one zone in order to create pressure differences or air velocities
between adjacent zones. In multi-story buildings, one floor is usually one or more zones
if it is served exclusively by one or more AHUs. An AHU that serves more than one floor
will define a zone that covers all or parts of each floor. Floors that have one or more
AHUs may still be lumped together in one zone if they are too small, or it is not possible
to generate sufficient air pressure between them. A single story building or a single floor

Guidelines for Smoke Control 1


Definition Reference Guide

within a multi-story building may be defined as more than one zone if served by more
than one AHU and there is sufficient partitioning to create the required pressure differ-
ences or air velocities between zones.
A system for smoke control may be a dedicated system that has separate air moving and
control equipment and operates only during emergency situations, or it may be a
nondedicated system that has shared equipment and functions (such as controlling the
HVAC during normal conditions, and switching to smoke control during emergency
conditions). Dedicated systems are easier to operate and modify because they have only
one function to perform, but they require additional building space and cost more than
nondedicated systems because of the duplication of equipment. They also require
frequent testing since the equipment is not used on a daily basis. Nondedicated systems
are more elaborate in their control strategies because they have more than one function
to perform and are more difficult to modify, but the cost is less and since the equipment
is used constantly, malfunctions are less likely to go undetected for long periods of time.
An existing HVAC control system that controls fans and dampers can usually be easily
modified to perform smoke control as well. This document discusses the use of UUKL
Listed CSI equipment and controllers to implement a nondedicated HVAC/smoke
management system.
The need to interface with life safety systems is often present. The smoke control system
must receive its inputs indicating the area of the smoke or fire from a Listed fire alarm
control panel. The fire alarm control panel and smoke control input circuits (typically
7716U8 PCU or 7700U8 DCU) must be mounted adjacent to, and connected by conduit
with each other and have access restricted to qualified personnel (see NFPA-92A and
UL864 for additional requirements). These fire alarm control panels provide dry contact
outputs for other systems to use as inputs to indicate alarm conditions. The smoke
control system must be designed with these other systems in mind if monitored alarm
circuits are required. It is preferable and often necessary to have a separate dry contact
for every alarm circuit (zone) as opposed to one, or a few combined alarms.
A Firefighter's Smoke Control Station (FSCS) is required for firefighters to monitor and
manually override the equipment used for smoke control. The FSCS should have the
highest priority control over all smoke control equipment. Check with local building
codes and fire authorities to determine how the FSCS must be implemented for the
particular application. The FSCS shall be provided using the (UUKL Listed) Space Age
Electronics XL8 series Annunciator panel with related building diagram showing the
type and location of all smoke control equipment. Typical systems might consist of
7716U8 PCUs or 7700U8 DCUs controlling the large air handler units (AHU) with one
or two air handlers per controller, depending on the number of hardware points required
to monitor and control. 7760U8 UCIs and 7270U8 or 7261U8 UCs may be used to
control variable air volume (VAV) boxes or small fans or AHUs. The 7261U8 UC would
also be an appropriate controller for a stairwell smoke control application. The ACT02
and 03 damper actuators are used with the VAV UC. The 4AOC1 is used with the 7700U8
DCU for 4-20 mA output to devices such as electric actuators for dampers or valves, for
variable frequency motor drives, or for transducers requiring 4-20 mA input. The IP1,
PWMP1, PWMV1, PWMC1, and PWMC2 are transducers used with the controllers for
similar electric or pneumatic devices. Refer to Appendix B for a complete list of CSI
equipment that can be used for HVAC and nondedicated smoke management systems.
All DCU, PCU, and UCI controllers communicate through a twisted, shielded pair Local
Area Network (LAN). The UCs communicate with the UCI on a similar UC LAN.
Although the controllers are distributed processors and can stand alone, they most likely

2 Guidelines for Smoke Control


Reference Guide Definition

will require information from another controller via the LAN, such as an indication of a
smoke alarm in an adjacent zone. Therefore, the LAN should be located so that it has
maximum protection during a fire and the application software should be designed so
that if communications fail, the controller maintains the equipment in the last mode
before the loss of communications occurred.
See the User/Installation Guide or Specification Sheet with each piece of equipment for
more details about the hardware. See the I/NET 7700 Operator Guide for more informa-
tion about system configurations and programming.
The CSI equipment may be used in a wide variety of applications for smoke control from
controlling air handler units and exhaust fans in multi-story high-rise office towers, to a
single story building with one air handler. The control strategies are similar for each zone
with the basic differences being for the type of air handler under control. Appendix B
provides a list of UUKL Listed CSI equipment which can be used in the design and
construction of non-dedicated smoke control systems that comply with UUKL Smoke
Control System requirements. It is essential that the basic principles of smoke control,
system design goals, and local building code and inspection requirements be understood
before the design of the overall smoke control system is undertaken.

Guidelines for Smoke Control 3


Design Reference Guide

Design

Hardware
After addressing and understanding the requirements of local building codes and rele-
vant governing regulatory agencies, the building or buildings that are to have a smoke
control system installed should be examined. It is important that the design of the smoke
system address the required design parameters (leakage, weather, pressure differences,
etc.) specifically to create the most effective smoke management system. The smoke
control system should minimize the migration of smoke from a fire zone and should
maintain a tenable environment during evacuation in case of a fire. The system should
also provide conditions outside the fire zone conducive to search and rescue operations
as well as firefighting by emergency personnel. It is important that the smoke zones
defined within the building are properly matched with appropriate HVAC equipment
(AHUs, fans, smoke dampers, etc.) which will be capable of generating and maintaining
the required pressure differentials and airflows to achieve proper smoke management.
CSI controllers can then be selected for the proper control of this equipment for both
normal HVAC and smoke control modes.
After the HVAC equipment has been selected and installed, create a sequence of opera-
tion that defines the operation of the equipment in all modes. For HVAC equipment, the
control for the smoke control modes of operation will be merged with normal HVAC
mode control and will override that mode. Define the sequence of operation in detail,
indicating all hardware points and all parameters (such as time delays, setpoints, posi-
tions, etc.).
Create a list to describe the hardware points to be monitored and controlled. To each
point assign a name and point type such as analog input (AI), discrete input (DI), analog
output (AO), or discrete output (DO) and select an address to wire each point to. Pulse
width points are programed as AO points but on the 7700U8 DCU they are wired at a
DO address. Label them as AO but remember to locate them at a DO address for the
7700U8 DCU. Sort the points list by equipment such as AHU 1, AHU 2, etc., and select
the type of controller to use. This list can be used as a guide to installation as well as
programming. Refer to the specific controller Installation Guide for information on the
number of inputs and outputs and expansion capabilities.
Try to keep all points for each piece of controlled equipment together on the same
DCU/PCU to minimize LAN communication for more accurate control should the
controller be separated from the LAN in a fire. Keep in mind that each controller will be
wired to the LAN on a shielded, twisted pair cable. It is desirable to run the LAN in
conduit and in a location that will protect it from fire. This may influence your decision
about the location and quantity of controllers. It may be more cost effective to purchase
an additional controller than to pull multiple cables from a remote AHU to another
controller with enough spare points.
After grouping the points by controller, assign a station address from 0 to 63 to each
controller. Assign one station address for each Tap on the LAN used for a PC host (or
interface to phone lines). If more than 32 stations are required, refer to the Taps and

4 Guidelines for Smoke Control


Reference Guide Design

Repeater Model 7800 Installation Guide for information about repeaters. If more than 64
stations are required, refer to the Taps and Repeater Model 7800 Installation Guide for
information about creating multiple LANs and host LANs. The wiring for UC to UCI
communication is similar to LAN wiring, except that no more than 32 UCs may be tied
to each UCI. The UCI takes up one station address on the LAN.
Typical field devices are used to monitor and control HVAC for smoke control systems
as well as non-smoke control systems with a few exceptions. The obvious exception is the
smoke or fire detector itself. It should be NFPA and UL Listed, and wired to a Listed fire
alarm control panel. The fire alarm control panel should provide a dry contact output to
wire to a DI point. A means for periodic testing of the sensor should be available, since
this device is not in constant use. The interconnection between the Listed control panel
and the controller shall be through conduit, and the two shall be mounted adjacent to
each other.
Fan status DI points for fans greater than 2,000 CFM that are used for smoke control
purposes must be from a differential pressure switch across the fan in order to provide
positive proof of airflow from the fan. A motor starter auxiliary contact, control relay
contact, or air flow switch does not give positive proof of airflow from the fan.
Dampers used to control the flow of smoke such as return air, outside air, relief air, and
inlet vane dampers, require end switches to indicate the positive proof of damper posi-
tion. An end switch must be installed and wired to a DI point to verify that the damper
is fully open or closed for that damper position in a smoke control mode. If separate
smoke dampers are used, they will also require end switches to indicate the closed posi-
tion.
Each system must also provide a Firefighter's Smoke Control Station (FSCS). This FSCS
is implemented using CSI Model 7716U8 PCU controllers that are mounted adjacent to
the FSCS panel. These PCUs monitor the switches and drive the indicator lights on the
FSCS and connect to zone outputs of a U.L. Listed fire alarm control unit. The 7716U8
PCUs used (for FSCS control) must be mounted adjacent to the fire alarm control unit
with the zone output interconnect wiring run in conduit.

Software
The first step in programming a controller is to enter the station address for the DCU or
PCU using the hand-held console. Refer to the Installation Guide for the hand-held
console for instructions. Next, program the station parameters that will be used with the
points in the program; state descriptions, control descriptions and commands, conver-
sion coefficients and engineering units. The use and programming of station parameters
is described in detail in the I/NET 7700 Operator Guide. Program the resident I/O points
using the points list created earlier. Add internal points such as pressurize, exhaust and
trouble modes to the list as well. Any discrete input points that need to create an alarm
in one state should be programed as discrete alarm (DA) points. These points will turn
red and flash on a graphic page when in the alarm state. They can also trigger an audible
alarm from the PC.
Keep all point scan times at 10 seconds or less to allow for an adequate response time.

Guidelines for Smoke Control 5


Design Reference Guide

The controlling software will be written from the sequence of operation using calcula-
tions, direct digital control modules, time schedules, and/or other editors of the I/NET
software. Password protection is supported within the INET software to provide
different levels of access to the smoke control system. Minimal access would be provided
for acknowledgment of incoming signals and checking of system status only. Higher
levels of access would allow individual devices to be controlled and tested. The highest
(system) level password would allow modification of the operating program as well as
any lower access level functions. Refer to the INET 7700 Operator Guide for information
concerning the generation of system and controller password protection.
There are three primary modes of operation for an AHU for smoke control; pressurize,
exhaust and trouble. The level of priority for these three modes is from low to high
respectively with the higher modes overriding the lower modes. The software will switch
automatically from the normal HVAC control to the appropriate smoke mode automat-
ically. Once the system has responded to a (smoke) alarm, each affected zone will “lock”
into the appropriate smoke mode. Additional subsequent alarms will not produce addi-
tional responses from the system. This prevents the AHU from reacting to multiple
alarms and keeps it in the safest mode possible until manually reset or overridden. Two
additional modes of operation, purge (also called dilution) and isolate, may be required
depending on local building codes and requirements. The purge mode, consisting of
equal air supply and exhaust rates, is used to clear smoke infiltrating from other remote
zones or to clear smoke from a smoke zone after a fire has been extinguished. Purging is
generally not used in a zone where a large fire is located since significant reductions of
smoke cannot be achieved with typical HVAC system equipment. The isolate mode is
used to minimize airflow within a zone or zones and to isolate the zone from the outside
air supply and exhaust ducts. These two modes are typically not automatic modes, as are
the pressurize, exhaust, and trouble modes, and can only be manually initiated from the
FSCS controls. All five smoke modes are discussed below.
The pressurize mode is used to prevent smoke from entering the controlled zone. Pres-
surization is accomplished by turning on the supply air fan and opening the outside air
damper to maximize the outside air and closing off the relief air damper (relief fan off).
The return air damper is closed.
The purpose of the exhaust mode is to create a lower air pressure within the controlled
zone with respect to adjacent (pressurized) zones. Smoke within the zone will also be
exhausted. To exhaust a zone, the relief air damper is opened (relief fan on) and the
outside air damper is opened (but the supply air fan is turned off). The return air
damper is closed.
The purge mode maximizes the flow of outside air through the controlled zone. This
facilitates the removal of smoke within the zone after a fire has been extinguished. Purge
mode control is similar to a pressurize control mode except that the relief damper is
opened and the relief fan is turned on.
The isolate mode minimizes the flow of air into or through the zone. All dampers are
closed and all fans are turned off.
The trouble mode is triggered by a hardware malfunction such as a damper not opening
or closing, or a fan not starting or stopping. Smoke control system equipment is required
to verify that a fan or damper has achieved its required end function. This end-process
verification is achieved by monitoring fans with pressure differential switches and
dampers with degree-of-opening switches. These switches are connected to an input
point of the Smoke Control System equipment for monitoring. The state of the switch,

6 Guidelines for Smoke Control


Reference Guide Design

or verification sensor, must agree with the expected controlled state of the mechanical
device after appropriate delays for damper movement and fan startup or shutdown. If,
after the proper delay, the state of the end verification switch (or sensor) does not match
the controlled state, an audible and visual trouble signal must be energized. This trouble
signal may be stopped by an FSCS Reset, but the trouble indicator light will remain lit
until the trouble condition has been corrected and then reset. When the trouble mode
for a zone is activated, the equipment in that zone is placed in the least dangerous config-
uration, which is usually all fans off and outside and relief air open. The exact hardware
configuration for each mode will vary depending on the HVAC equipment but the prin-
ciples are the same.

Guidelines for Smoke Control 7


Operation Reference Guide

Operation

The following sequence of operation and corresponding schematics shown in Figures 1-


5 are for five typical AHU configurations. The FSCS is shown as hardware points in
another station but may be internal points instead. A flow diagram (Figure8, “DDC Flow
Diagram Example for AHU Types 1-4”) and an explanation of the direct digital control
(DDC) modules used to accomplish the sequence of operation for examples 1 through 4
follows. Calculations and events should be used when possible to save DDC modules for
the normal HVAC applications; although DDC modules facilitate the use of time delays
much better when checking for trouble conditions and end-process verification.
Example 5 was programmed with calculations and events, which are described later.

AHU Type 1 - Sequence of Operation - Smoke Control


Normal: Outside air, return air, and relief dampers are modulated based on mixed air
temperature when the outside air temperature is less than the return air temperature,
otherwise the outside air and relief dampers are at a minimum position of 10% for venti-
lation. A position switch on the relief damper will start the relief fan when the damper is
30% open. The supply fan will start and stop based on time schedules.
Pressurize: If an adjacent zone smoke detector goes to the alarm state or if a manual
command to pressurize is received from the FSCS, the supply fan will start and the
outside air damper will open to 100%. The return air damper will close. The relief fan
will stop and the relief damper will close. The maximum response time for the supply
fan to turn on and the relief fan to stop (as indicated by the end-verification device) is 60
seconds. The outside air and relief air dampers are allowed a maximum of 75 seconds to
open to 100% and to completely close respectively (as indicated by the end-verification
device). If any of the controlled devices fail to reach the proper state, the trouble condi-
tion will be activated.
Exhaust: If this AHUs smoke detector goes to the alarm state or if a manual command to
exhaust is received from the FSCS, the supply fan will stop, the outside air and relief
dampers will open to 100%, and the return damper will close. The relief fan will start
when the relief damper opens. If, after the maximum response times mentioned above,
the outside or relief dampers fail to open to 100% or the return damper fails to close or
the supply fan fails to stop, the trouble condition will be activated.
Trouble: If the trouble condition is activated, the supply and relief fan will be controlled
to stop and the outside air and relief dampers will be controlled to open. The AHU will
not be allowed to start again until after the reset is activated.

Note: The firefighter's smoke-control, station-override switch for pressurize and exhaust (or
discrete device control, depending on implementation) will manually override any auto-
matic response. In the Auto position, a zone that has been controlled to a smoke control
mode will remain in that mode until manually controlled to a different mode at the FSCS
(or manually reset at the FSCS).

8 Guidelines for Smoke Control


Reference Guide Operation

Fan Starter

DP Differential Pressure Switch

SD Smoke / Fire Detector

DM Damper Motor

ES Damper End Switch

TD Output Transducer

SP Static Pressure Sensor

A P E FSCS Override Switch - SP3T


Auto - Pressurize - Exhaust

FA Fire Alarm Control Unit/Panel


CU
FSCS Firefighter's Smoke Control Station

TA Trouble Alarm

PB Reset Momentary Pushbutton

Z N-1
Adjacent Zone Smoke Detectors
Z N+1
NO Normally Open
NC Normally Closed
DI Discrete Input, Normally Open
DO Discrete Output, Normally Open
AO Analog Output

R Indicator Light, Red

G Indicator Light, Green

Figure 1. AHU Types 1-5 Legend

Guidelines for Smoke Control 9


Operation Reference Guide

DO G SUPPLY FAN
STATUS

To Relief Fan FA DO TA TROUBLE ALARM


RELIEF AIR Starter DI SD ZONE N - 1
CU

DI PB RESET
FA ZONE N + 1
ES DI CU SD
A P E AUTO
PRESSURIZE R DO
DI
NC OVERRIDE
ES DM
DI EXHAUST
OPEN DI OVERRIDE R DO

RETURN AIR

IP SD FA DI
CU DI
AO TD DM ZONE
N
NO

DP
ES DI CLOSE

DM

OUTSIDE
AIR
COOLING
HEATING

NC
COIL

COIL

SUPPLYFAN
ES

AHU TYPE 1
• Single Zone
• Economy Cycle DO
DI OPEN

Figure 2. AHU Type 1

AHU Type 2 - Sequence of Operation - Smoke Control


Normal: Outside air and return air dampers are modulated based on mixed air temper-
ature when the outside air temperature is less than the return air temperature, otherwise
the outside air dampers are at a minimum position of 10% for ventilation. The relief
damper will be controlled based on a static-pressure sensor monitoring the space pres-
sure. A position switch on the relief damper will start the relief fan when the damper is
30% open. The supply fan will start and stop based on time schedules.
Pressurize: If an adjacent zone smoke detector goes to the alarm state or if a manual
command to pressurize is received from the FSCS, the supply fan will start and the
outside air damper will open to 100%. The return air and relief dampers will close. The
relief fan will stop when the relief damper closes. The maximum response time for the
supply fan to start and the relief fan to stop (as indicated by the end-verification devices)
is 60 seconds. The outside air, return, and relief dampers are allowed a maximum of 75
seconds to reach the proper controlled state. If, after the maximum response times, any
of the controlled devices fail to reach the proper state, the trouble condition will be acti-
vated.

10 Guidelines for Smoke Control


Reference Guide Operation

Exhaust: If this AHUs smoke detector goes to the alarm state, or if a manual command
to exhaust is received from the FSCS, the supply fan will stop, the outside air and relief
dampers will open to 100% and the return damper will close. The relief fan will start
when the relief damper opens. If, after the maximum response times mentioned above,
the relief dampers fail to open to 100%, or the return damper fails to close, or the supply
fan fails to stop, the trouble condition will be activated.
Trouble: If the trouble condition is activated, the supply and relief fans will be controlled
to stop and the outside air and relief dampers will be controlled to open. The AHU will
not be allowed to start again until after the reset is activated.

Note: The firefighter's smoke control station override switch for pressurize and exhaust (or
discrete device control, depending on implementation) will manually override any auto-
matic response. In the Auto position, a zone that has been controlled to a smoke control
mode will remain in that mode until manually controlled to a different mode at the FSCS
(or manually reset at the FSCS)

FS CS

DO G SUPPLY FAN S TATUS

TO FA
REL IEF A IR RELIE F RD DI SD ZONE N - 1 DO TA TROUBLE ALARM
CU
F AN STA RTE R SP
L H DI FA SD ZONE N + 1 DI PB RESET
ES CU
AUTO
REF. SPA CE A P E DO
CLOSED D I DI PRESS URIZE R
NC OVE RRIDE
ES DM DI EX HAUST
OVE RRIDE R DO
OPEN DI

PWMVI RETURN
AIR
AO TD
SD FA DI DI
CU
AO TD DM ZONE
PWMP NO N

DP
ES D I CL OSE

DM

OUTSI DE
AI R
NC HEATING COOLING
COIL COIL

SUPPLY
ES FAN
AHU TYPE 2
• Single Zone
• Economy Cycle DO
DI
• Static Pressure Control
OPEN

Figure 3. AHU Type 2

Guidelines for Smoke Control 11


Operation Reference Guide

AHU Type 3 - Sequence of Operation - Smoke Control


Normal: Outside air, return air, and relief dampers are modulated based on mixed air
temperature when the outside air temperature is less than the return air temperature,
otherwise the outside air and relief dampers are at a minimum position of 10% for venti-
lation. The supply and return-relief fans will start and stop together, based on time
schedules.
Pressurize: If an adjacent zone smoke detector goes to the alarm state or if a manual
command to pressurize is received from the FSCS, the supply fan will start, the return-
relief fan will stop, and the outside air damper will open to 100%. The return and relief
air dampers will close. The maximum response time for the supply fan to start and the
relief fan to stop (as indicated by the end-verification devices) is 60 seconds. The outside
air, return, and relief dampers are allowed a maximum of 75 seconds to reach the proper
controlled state. If, after the maximum response times, the outside air damper fails to
open to 100% or the return or relief dampers fail to close or the supply fan fails to start
or the return-relief fan fails to stop, the trouble condition will be activated.

F S CS

DI
FA
DI SD ZO NE N - 1 DO G S UPPLY FAN STATUS
CU

FA ZONE N + 1 DO
OPEN DI SD DP G RE TURN -RE LIE F FAN S T A T US
CU
DI
FA A U TO SD
DO
DI P
CU A
E
DI
ES P R E SSURI ZE
ZONE N SD R
O V E RRIDE
DI

E X H AUS T
R
O V E RRIDE
RELIEF
AIR
NC DO TA T RO UBL E DO
SD
A L AR M

RETURN DI PB RE S ET
AIR

DM RETURN-
RELIEF
IP FAN
AO TD DM

NO
DO
DI
ES DI CLOSE

DM
DP

OUT SID E
AIR
NC HEATING COOLING
COIL COIL

SUPPLY
FAN
ES
AHU TYPE 3
• Single Zone
DI • Economy Cycle
DO
O PEN • Return-Relief Fan

Figure 4. AHU Type 3

Exhaust: If this AHUs smoke detector goes to the alarm state or if a manual command to
exhaust is received from the FSCS, the supply fan will stop, the return-relief fan will start,
the outside air and relief dampers will open to 100% and the return damper will close.

12 Guidelines for Smoke Control


Reference Guide Operation

If, after the maximum response times, the outside or relief dampers fail to open to 100%
or the return damper fails to close or the supply fan fails to stop or the return-relief fan
fails to start, the trouble condition will be activated.
Trouble: If the trouble condition is activated, the supply and return-relief fans will be
controlled to stop and the outside air and relief dampers will be controlled to open. The
AHU will not be allowed to start again until after the reset is activated.

Note: The firefighter's smoke control station override switch for pressurize and exhaust (or
discrete device control depending on implementation) will manually override any auto-
matic response. In the Auto position, a zone which has been controlled to a smoke control
mode will remain in that mode until manually controlled to a different mode at the FSCS
(or manually reset at the FSCS).

AHU Type 4 - Sequence of Operation - Smoke Control


Normal: Outside air, return air, and relief dampers are modulated based on mixed air
temperature when the outside air temperature is less than the return air temperature,
otherwise the outside air and relief dampers are at a minimum position of 10% for venti-
lation. A position switch on the relief damper will start the relief fan when the damper is
30% open. The supply fan will start and stop based on time schedules. The supply fan
inlet vane damper will be controlled, based on a static-pressure sensor measuring supply
duct pressure. VAV box dampers will be controlled based on a CFM sensor in the box
with the CFM setpoint being reset, based on a temperature sensor in the space.
Pressurize: If an adjacent zone smoke detector goes to the alarm state or if a manual
command to pressurize is received from the FSCS, the supply fan will start, and the
supply fan inlet vane and outside air dampers will open to 100%. The return air damper
will close. The relief fan will stop when the relief damper closes. The VAV box fans will
start and the dampers will open to 100%. The maximum response time for the supply
and VAV fans to start (as indicated by the end-verification devices) is 60 seconds. The
outside air, return, relief, and VAV dampers are allowed a maximum of 75 seconds to
reach the proper controlled state. If, after the maximum response times, the outside or
supply inlet vane dampers fail to open to 100%, or the return or relief dampers fail to
close, or the supply fan fails to start, or the relief fan fails to stop, then the trouble condi-
tion will be activated.
Exhaust: If this AHU’s zone smoke detector goes to the alarm state, or if a manual
command to exhaust is received from the FSCS, the supply fan will stop, the supply fan
inlet vane will close, and the outside air and relief air dampers will open to 100%. The
return air damper will close. The relief fan will start when the relief damper opens. The
VAV box fans will stop and the dampers will open to 100%. If, after the maximum
response times mentioned above, the outside or relief dampers fail to open to 100%, or
the return or supply inlet vane dampers fail to close, or the supply fan fails to stop, then
the trouble condition will be activated.
Trouble: If the trouble condition is activated, the supply and relief fan will be controlled
to stop and the outside air and relief dampers will be controlled to open. The inlet vane
damper will be controlled to close. The VAV box fans will stop and the dampers will be
controlled to close. The AHU will not be allowed to start again until after the FSCS reset
is activated.

Guidelines for Smoke Control 13


Operation Reference Guide

DO G SUPPLY FAN STATUS


RELIEF
AIR
FA
D I CU SD ZONE N - 1 DO TA TROUBLE ALARM

TO
RELIEF FA D I RESET
FAN STARTER DI SD ZONE N + 1 PB
CU
A P E AUTO
PRESSURIZE R DO
SD
DI
ES ES OVERRIDE
DI EXHAUST
OPEN DI OVERRIDE R DO
SD

DM
RETURN DO
AIR

SD FA DI DI
PWMCI CU
AO TD DM
ZONE N PWM
NO CZ TD

DP
ES CLOSE OPEN

DO DO
DM SF FAN

DI CLOSE DM SP DO DM

L
H
OUTSIDE CLOSE
AIR
NC HEATING COOLING OPEN
COIL COIL

ES
VAV
(Typical)

SUPPLY
DO FAN D I
ES AHU TYPE 4
• Multizone OPEN
• Economy Cycle
D I • Variable Air Volume VAV

OPEN

Figure 5. AHU Type 4

Note: The firefighter's smoke-control, station-override switch for pressurize and exhaust (or
discrete device control, depending on implementation) will manually override any auto-
matic response. In the Auto position, a zone that has been controlled to a smoke control
mode will remain in that mode until manually controlled to a different mode at the FSCS
(or manually reset at the FSCS)

AHU Type 5 (Stairwell) - Sequence of Operation - Smoke Control


Normal: The outside air damper will be closed and the supply fan will be off.
Pressurize: If a fire alarm signal is received from the fire alarm control panel, if any zone
goes into an exhaust mode, or if a manual command to pressurize is received from the
FSCS, all stairwells should be controlled to the pressurized state. The stairwell outside air
damper will open to 100%. A position switch on the outside air damper will start the
supply fan when the damper is 90% open. The supply fan inlet vane damper will modu-
late based on a stairwell static pressure sensor. If, after 60 seconds, the supply fan fails to
start, the trouble condition will be activated.
A smoke detector should be provided in the stairwell pressurization air supply. Upon
detection of smoke, the stairwell supply fan(s) should be stopped. The FSCS must have
the capability to override or restart the fans by manual control.

14 Guidelines for Smoke Control


Reference Guide Operation

Trouble: If the trouble condition is activated, the outside air damper will be controlled to
close and the supply fan will stop. The inlet vane damper will be controlled to close. The
AHU will not be allowed to start again until after the reset is activated.

Note: The firefighter's smoke control, station-override switch for pressurize will manually over-
ride any automatic mode. In the Auto position, the mode of the stairwell that has been
controlled to the pressurize mode (smoke mode) will remain in that mode unless stopped by
the stairwell smoke detector, manually controlled to a different mode by the FSCS (or
manually reset at the FSCS).

FSCS

DO G SUPPLY FAN STATUS

FA
DI CU SD ZONE 1
DO TA TROUBLE ALARM

DI PB RESET
FA
DI CU SD ZONE N A AUTO
P
DI PRESSURIZE
R S
DO
OVERRIDE D

DI

DP SF

SP

PWMP
DM TD AO L
REF. H

OUTSIDE
AIR

SUPPLY FAN STAIRWELL


DM ES

DO

AHU TYPE 5
• Stairwell Pressurization Fan

Figure 6. AHU Type 5 (Stairwell)

Guidelines for Smoke Control 15


Operation Reference Guide

The following descriptions explain the purpose of each module. The example modules
shown in Figure8, “DDC Flow Diagram Example for AHU Types 1-4” are used to create
the pressurize and exhaust modes for AHU types 1-4. They also lock out the lower
priority modes and allow for manual reset or override.

R - Relay Module
S - Discrete Input
0 - DI=0 Input
1 - DI=1 Input
IT - Interval Timer
DBM - Delay Before Make
H/L - High/Low Module

Notes: Module numbers shown in the upper left corner of the module are for
reference only. Your numbers may be different.

A line is an output from one module that goes directly into the input of
one or more modules. It is easier to program if the line numbers are the
same as the module numbers (as they are in this example).

All state descriptions are written with the 0 state on the left and the 1 state
on the right. Ex.: NRML/ALRM- the normal state is 0 (the contact is
open) and the alarm state is 1 (the contact is closed).

All control descriptions are written with the description that a 0 will go to
the first of the pair on the left and the description that a 1 will go to the
second of the pair on the right. This may or may not correspond with the
control commands.
Figure 7. Legend for DDC Flow Diagrams

Module 1 - Checks if two adjacent zone's smoke detectors, zone N-1 or zone N+1, are in
alarm condition.
Module 2 - Unlatches the pressurize mode if the reset is pressed.
Module 3 - Latches the pressurize mode if an alarm is received.
Module 4 - Turns off the pressurize mode if the exhaust or trouble mode is activated.
Module 5 - Turns off the pressurize mode if the FSCS activates the exhaust mode.
Module 6 - Turns on the pressurize mode if the FSCS activates the pressurize mode.
Module 7 - Unlatches the exhaust mode if the reset is pressed.
Module 8 - Latches the exhaust mode if an alarm is received.
Module 27 - Checks the exhaust or trouble modes for module 4.
Module 28 - Turns off the exhaust mode if the trouble mode is activated.
Module 9 - Turns off the exhaust mode if the FSCS activates the pressurize mode.
Module 10 - Turns on the exhaust mode if the FSCS activates the exhaust mode.
Module 11 - Unlatches the trouble mode if the reset is pressed.

16 Guidelines for Smoke Control


Reference Guide Operation

DA DA DI
Z N-1 Z N+1 AHU
RESET
NRML/ALRM NRML/ALRM OFF/RSET

1 H/L 7 R 11 R
1 IT-10 IT-10
2 S S
3 0 0
4 0 1 1 0
N OUT OUT OUT

2 R 8 R 12 R
IT-10 DA
S AHU S S From
0 SMOKE DET 0 0 19
1 0 NRML/ALRM 1 1 1 1
OUT OUT OUT

3 R 27 H/L DA
1 AHU –
S 2 TROUBLE
0 3 NRML/TRBL
1 1 4
OUT H OUT

4 R 28 R

S S
0 0
1 0 0 1
OUT OUT

5 R DI 9 R
FSCS DI
S EXH FSCS S
0 OFF/EXH PRESS 0
1 0 OFF/PRESS 0 1
OUT OUT

10 R
6 R S
0
S 1 1
0 OUT
1 1
OUT

DI DI
AHU AHU
PRESSURIZE EXH
OFF/PRESS OFF/EXH

TYPE 1, 2, 3 & 4
Normal, Pressurize and Exhuast Control
Modes and FSCS Overrides and Reset

Figure 8. DDC Flow Diagram Example for AHU Types 1-4

Module 12 - Latches the trouble mode if an alarm is received.


The example modules shown in Figure9, “DDC Flow Diagram Example for AHU Types
1–4” check equipment status in the pressurize and exhaust modes to create the trouble
mode for AHU type 1. Other types are similar with slight modifications for checking the
input points depending on the hardware configuration for each AHU.

Guidelines for Smoke Control 17


Operation Reference Guide

DI DI DI DI
AHU OA AHU RL AHU RA AHU
DAMP ES DAMP ES DAMP ES S F STATUS
MOD/OPEN MOD/OPEN MOD/CLSD OFF/ON

15 R

S
1 0
0 1
OUT

13 H/L 16 H/L
1 1
2 2
3 3
4 4
L OUT L OUT

DI DI
AHU AHU
PRESSURIZE EXH
OFF/PRES OFF/EXH

14 R 17 R
DBM-30 DBM-30
S S
0 1 1 0
1 1
OUT OUT

18 H/L
1
2
3
4
L OUT

19 R

S
0 1
1 0
OUT TO
12
TYPE 1, 2, 3 & 4
Trouble Detector

Figure 9. DDC Flow Diagram Example for AHU Types 1–4

Module 13 - Checks outside air, relief and return-air, damper-end switches and fan status
for the proper status in the pressurize mode.
Module 14 - Checks the equipment status 30 seconds after activating the pressurize
mode.
Module 15 - Reverses the fan status.
Module 16 - Checks outside air, relief and return air damper end switches and fan status
for the proper status in the exhaust mode.
Module 17 - Checks the equipment status 30 seconds after activating the exhaust mode.
Module 18 - Checks the equipment status for trouble in either the pressurize or exhaust
modes.
Module 19 - Reverses module 18 results for compatibility with module 12.

18 Guidelines for Smoke Control


Reference Guide Operation

The example modules shown in Figure10, “DDC Flow Diagram Example for AHU Types
1–4”control the outside air damper and the supply fan for the normal, pressurize,
exhaust, and trouble modes of AHU types 1-4.

DM AI DI
AHU SF AHU AHU
STATUS OA MOD TIME SCHED
OFF/ON %
OFF/ON

20 R 23 R

S S
0 0 1 0
1 0 1
OUT To 33 OUT
TYPE 3

21 H/L DI 24 R
1 AHU
2 PRESSURIZE S
3 OFF/PRES 0
4 0 1
H OUT OUT
DI
AHU
EXH 25 H/L
22 R
OFF/EXH 1
S 2
0 3
1 1 DA 4
OUT AHU H OUT
TROUBLE
NRML/TRBL
AO 26 R
AHU OA
DAMP CTRL S
% 0
1 1
OUT
TYPE 1, 2, 3 & 4
Supply Fan and
DC
OA Damper Control
AHU
SF CTRL
STRT/STOP

Figure 10. DDC Flow Diagram Example for AHU Types 1–4

Module 20 - Closes the outside air damper if the supply fan is off.
Module 21 - Checks if the pressurize, exhaust or trouble modes are on.
Module 22 - Opens the outside air damper if the pressurize, exhaust or trouble modes
are on.
Module 23 - Reverses the time schedule signal to start or stop the supply fan and for type
3 AHUs the return-relief fan also.
Module 24 - Starts the supply fan if the pressurize mode is on.
Module 25 - Checks if the exhaust or trouble modes are on.
Module 26 - Stops the supply fan if the exhaust or trouble modes are on.
The example modules shown in Figure11, “DDC Flow Diagram Example for AHU Type
2” control the relief damper for normal, pressurize, exhaust, and trouble modes of AHU
type 2.
Module 29 - Closes the relief damper if the supply fan is off.

Guidelines for Smoke Control 19


Operation Reference Guide

DM AI
AHU SF AHU RL
STATUS DAMP MOD
OFF/ON %

29 R

S
0 0
1
OUT

30 R DI
AHU
S PRESSURIZE
0 OFF/PRES
1 0
OUT
DI
AHU
31 H/L EXH
1 OFF/EXH
2
3
4 DA
H OUT AHU
TROUBLE
NRML/TRBL
32 R

S
0
1 100
OUT

AO
AHU
RL DAMP
CTRL
%

TYPE 2
Relief Damper Control

Figure 11. DDC Flow Diagram Example for AHU Type 2

Module 30 - Closes the relief damper if the pressurize mode is on.


Module 31 - Checks if the exhaust or trouble modes are on.
Module 32 - Opens the relief damper if the exhaust or trouble modes are
The example modules shown in Figure12, “DDC Flow Diagram Example for AHU Type
3” control the return-relief fan in the pressurize exhaust and trouble modes for AHU
type 3.
Module 32 - Checks if the pressurize or trouble modes are on.
Module 33 - Stops the return-relief fan if the pressurize or trouble modes are on.
Module 34 - Starts the return-relief fan if the exhaust mode is on.
The example modules shown in Figure13, “DDC Flow Diagram Example for AHU Type
4” control the supply fan inlet vanes, the VAV box mode and the VAV box dampers in the
pressurize, exhaust, and trouble modes for AHU type 4.
Module 29 - Closes the supply fan inlet vanes if the supply fan is off.
Module 30 - Checks if the pressurize or exhaust modes are on.

20 Guidelines for Smoke Control


Reference Guide Operation

DI DA
AHU AHU
PRESSURIZE TROUBLE
OFF/PRES NRML/TRBL

32 H/L
1
2
3
4
H OUT

33 R

S FROM
0 23
1 1
OUT

34 R DI
AHU
S EXH
0 OFF/EXH
1 0
OUT

DC
AHU
RF CTRL
STRT/STOP

TYPE 3
Return-Relief Fan Control

Figure 12. DDC Flow Diagram Example for AHU Type 3

Module 31 - Opens the supply fan inlet vanes if the pressurize or exhaust modes are on.
Module 32 - Closes the supply fan inlet vanes if the trouble mode is on.
Module 35 - Turns on the VAV boxes if the pressurize mode is on.
Module 36 - Checks if the exhaust or trouble modes are on.
Module 37 - Turns off the VAV boxes if the exhaust or trouble modes are on.
Module 38 - Checks if the pressurize or exhaust modes are on.
Module 39 - Opens the VAV box dampers if the pressurize or exhaust modes are on.
Allows the damper to close if the trouble mode is on.
The logic for AHU type 5 can be created with the following calculations and event
sequences. See the I/NET 7700 Operator Guide for details on calculation and event
editors.
Latch Alarm DI: (~P0*P1+P0)*~P2
NRML/ALRM P0 - Latch Alarm DI NRML/ALRM
P1 - Fire Alarm DI NRML/ALRM
P2 - AHU 5 Reset DI OFF/RSET

Guidelines for Smoke Control 21


Operation Reference Guide

DM AI DI DC DI DI
AHU SF VANE AHU AHU SF AHU AHU
SF STATUS MOD PRESSURIZE CTRL PRESSURIZE EXH
OFF/ON % OFF/PRES OFF/ON OFF/PRES OFF/EXH

29 R 35 R 38 H/L
1
S S 2
0 0 0 3
1 1 1 4
OUT OUT H OUT

DI
30 H/L 36 H/L AHU
DI 39 R DA
1 1 EXH AHU
AHU
2 2 OFF/EXH TROUBLE
PRESSURIZE S
3 OFF/PRES 3 0 NRML/TRBL
4 4 1 0
H OUT H OUT DA OUT
DI AHU
AHU TROUBLE
EXH 37 R NRML/TRBL
31 R DI
OFF/EXH OPEN
S S VAV DAMP
0
0 MOD/OPEN
1
1 100 0
OUT
OUT

32 R DA DI
AHU VAV FAN
S TROUBLE CTRL
0 NRML/TRBL OFF/ON
1 0
OUT

TYPE 4
AO Supply Fan VAV,
AHU SF VAV Box Initiate,
VANE CTRL VAV Box Damper Override
%

Figure 13. DDC Flow Diagram Example for AHU Type 4

Fire Alarm DI: P0|P1|P2|P3


NRML/ALRM P0 - Zone 1 Smoke Det NRML/ALRM
P1 - Zone 2 Smoke Det NRML/ALRM
P2 - Zone 3 Smoke Det NRML/ALRM
P3 - Zone 4 Smoke Det NRML/ALRM
Add more zones as required
AHU 5 Pressurize DI: P0|P1
OFF/PRES P0 - Latch Alarm DI NRML/ALRM
P1 - FSCS Pressurize DI OFF/PRES
AHU 5 OA Damper Ctrl DC: ~P0
OPEN/CLOS P0 - AHU 5 Pressurize DI OFF/PRES
AHU 5 SF Vane Ctrl AO: P0*P1+~P0*C0
% P0 - AHU 5 SF Status DM OFF/ON
P1 - AHU 5 SF Vane Mod AI%
C0 - 0%

22 Guidelines for Smoke Control


Reference Guide Operation

AHU 5 SF Status DM: Event on Alarm


OFF/ON Sequence 1
Sequence 1 - Stop/l AHU 5 OA Damper Ctrl DC
OPEN/CLOS
AHU 5 Reset DI: Event on specified state of 1
OFF/RSET Sequence 2
Sequence 2 - Stop AHU 5 OA Damper Ctrl DC
OPEN/CLOS
The Firefighter’s Smoke Control Stations in the examples for AHU types 1 through 5 are
shown as hardware points that are no more than DIs that monitor the switches and DOs
that activate lights and audible alarms in the Space Age Electronics XL8 Annunciator. For
testing and installation purposes, these points can be displayed and controlled from a
graphics page or pages that give a more complete indication of the status of the entire
building and individual AHUs. These graphic pages can be dynamic, that is, they can
change based on the status of the equipment. Discrete points with two states such as fan
status, damper end switches, smoke detectors, and fan control can be represented on a
graphics page with user defined library symbols for each state, as well as the ASCII char-
acter state description. For example, a type 1 AHU might be shown on a graphics page
exactly as drawn in Figure2, “AHU Type 1”, with the FSCS represented with internal
points. The same points could also be shown on another page along with many other
AHUs to allow for a summary of AHUs at a glance. Fan status could be shown as a
squirrel cage with an empty center for the fan off, and a squirrel cage with the center
filled with color for the fan on. Or arrows might be used to show air flow when the fan
is on. Dampers can be shown as half open for modulating, and fully open or closed when
the end switch closes. Internal points can also be displayed with either ASCII characters
or graphic symbols such as buttons, switches, lights or alarm horns. Colors should corre-
spond with already established standards for FSCS indicators as follows:
✦ Equipment operating or ON - Green
✦ Dampers OPEN - Green
✦ Dampers CLOSED - Yellow
✦ Faults or Alarms - Amber or Orange
A floor plan page or pages can be created with an exact floor plan of the building showing
equipment locations and modes for the equipment and zones. The operator can “zoom
in” on an AHU by placing the cursor on the desired unit and selecting that AHU page if
page icons are used when creating the floor plan. This allows the operator to bring up
another page that shows more detail on the AHU and then switch back to the floor plan.
Graphic pages such as these are usually part of an HVAC control system and adding
points for smoke control would be a natural extension for a non-dedicated system.
The normal, non-fire/smoke mode of the HVAC equipment will vary with the require-
ments for the building, but most likely the AHUs would be controlled automatically,
starting and stopping based on time schedules and modulating dampers to maintain a
constant space temperature. Low and high alarm limits should be programmed on all
analog input points to create an alarm if temperatures or pressures are not maintained.
The operator should acknowledge any alarm conditions and check the equipment to
determine the cause of the alarm. Repairs should be made as soon as possible. A

Guidelines for Smoke Control 23


Operation Reference Guide

malfunction such as a stuck damper can have serious consequences in a smoke control
mode. Normal daily operation of the equipment will uncover many malfunctions if
reasonable alarm limits are set.
Emergency fire or smoke conditions will cause the equipment to automatically enter the
pressurize or exhaust modes as described in the previous examples. Automatic activation
of the smoke modes will be initiated only when a fire alarm signal is received from the
fire control panel. This fire alarm signal will initiate the automatic smoke mode for this
zone (exhaust) and the surrounding zones will respond by pressurizing. It is important
that the smoke zones and the fire zones (as defined in the fire control panel) correspond.
A fire alarm output point from the fire control panel (dry contact output) must identify
the affected fire zone to the smoke control system so that the correct automatic response
is initiated. These points will go into alarm if programed as DA points and should be
acknowledged by the operator (refer to the I/NET 7700 User's Guide).
Smoke Control modes will latch in to prevent the AHU from reacting to multiple alarms,
therefore it is necessary to reset the software (using the FSCS reset) when it is desired to
revert back to a lower priority mode. The modes can be manually overridden by the
FSCS. With the FSCS implemented, using the Space Age Electronics XL8 Annunciator,
all manual override is controlled directly through the switches on the Annunciator. If a
device is placed into manual override, the normal mode of operation of that device will
not be resumed until the override switch is returned to the Auto position. If the smoke
control equipment of the zones is controlled collectively (smoke modes exhaust, pres-
surize, isolate and purge), all smoke related equipment in the zone is controlled collec-
tively. Returning the FSCS switch to Auto allows all of these devices to return to a normal
mode of operation. If a device has not responded properly and a Trouble signal has been
generated, then the problem must be fixed, the FSCS Reset switch activated, and the
override switch returned to Auto before the zone will return to normal operation.
Testing is necessary to make sure that all hardware and software is working correctly (as
well as the related mechanical fans and dampers in the system). In addition, the testing
should include full system activation and response tests to verify operational efficiency
and integrity as a whole. All automatic response modes and all manual override (FSCS)
control should be checked and proper operation verified. These tests should be
conducted annually for non-dedicated systems. If the controllers are on standby power,
the test should be conducted on standby power. Exercise all modes of the smoke control
sequence of operation by changing the inputs that activate those modes and observe the
system to see if the change in inputs were received and the appropriate change in outputs
were executed. Refer to NFPA-92A for testing and verification requirements and
methods.

24 Guidelines for Smoke Control


Reference Guide System Examples

System Examples

A typical example for an entire system might be a 20-story office tower with one AHU
per floor that is the same as AHU type 4 in Figure6, “AHU Type 5 (Stairwell)”. Each floor
has 15 VAV boxes on each AHU. In addition there is a common stairwell with one AHU
type 5 as in Figure7, “Legend for DDC Flow Diagrams”. Each floor is one zone and the
stairwell is one zone. Controlling each AHU is a 7700U8 DCU or 7716BU8 PCU and
there are 15 7261U8 VAV UCs connected to a 7760U8 UCI on each floor for the fan
powered VAV boxes. On the top floor, a 16th 7270U8 Universal UC is used to control the
stairwell fan. Each controller is given a station address beginning with 1 from floor 1.
Therefore, the DCU or PCU on the first floor will have station address 1 and the UCI will
have station address 2 and the DCU or PCU on the 20th floor will have station address
39 and the UCI will have station address 40. A LAN for the controllers will be run up
through the floors and a LAN on each floor for the UCs will be run to connect each VAV
box UC. See Figure14, “Typical LAN Wiring” for typical LAN wiring.

DCU PCU UCI

TB3
1
2
3
TB7 Port A Port B
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

Controller LAN
Note: Connect shield drain to earth
TAP Splice shield drain wire for each LAN cable ground at one location per
segment together to maintain continuity. LAN only.

5
4 UNIV-UC II VAV-UC II
Port B 3
2
1

Modem TB1
TB5 3
Port A RS232 or 2
1 2 3
1
PC (Com1 or Com 2)

UC LAN
Figure 14. Typical LAN Wiring

Zone N-1 is the floor below and Zone N+1 is the floor above, where N is the floor or zone
number. The sequence of operation and control software will be as described for AHU
type 4 for the floor AHUs and type 5 for the stairwell fan. When one floor's smoke

Guidelines for Smoke Control 25


System Examples Reference Guide

detector goes into alarm, the stairwell and the floors above and below will pressurize.
Figure15, “Example AHU Type 4 Points” and Figure16, “Example AHU Type 5 Points”
show the points used for type 4 and 5 AHUs respectively.

Figure 15. Example AHU Type 4 Points

Type Class Name

DC External AHU 4 FAN CTRL


AO External AHU 4 OA DP CTRL
AO External AHU 4 SF VN CTRL
DO Internal AHU 4 TIME SCHED
DA * External AHU 4 SMOKE DET
DI External AHU 4 RL DAMP ES
DI External AHU 4 SF VN ES
DI External AHU 4 RA DAMP ES
DM External AHU 4 FAN STATUS
DA Internal AHU 4 TROUBLE
DI Internal FSCS PRESS
DI Internal FSCS EXH
DI Internal AHU 4 PRESSURIZE
DI Internal AHU 4 EXH
DI Internal AHU 4 RESET
DI Internal AHU 4 OPEN VAV
DI Internal AHU 4 VAV CTRL
AI Internal AHU 4 OA MOD
AI Internal AHU 4 SF VN MOD
DI Indirect AHU 4 Z N-1 SD
DI Indirect AHU 4 Z N+1 SD
DI Indirect OPEN VAV
DI Indirect PARENT CTRL
DO Internal VAV PARENT
AO Internal VAV CFM SETPT
DO External VAV FAN
AO Internal VAV SPACE TMP SP
AO Internal VAV TEMP PID OUT
AI External VAV SPACE TEMP
AI External VAV AIRFLOW
* From Fire Alarm Control Panel

When programming the VAV box UCs, the software should be set up as described in the
I/NET 7700 Operator Guide with one exception. The output of the PID loop controlling
space temperature should go to an internal AO called VAV TEMP PID OUT, and the
setpoint of the PID loop controlling CFM should be another internal AO called VAV
CFM SETPT. Add the following calculation to this point to allow the damper to be forced
open with the fan off:

26 Guidelines for Smoke Control


Reference Guide System Examples

Figure 16. Example AHU Type 5 Points

Type Class Name

DO Internal AH5 TROUBLE


DA Internal AH 5 TROUBLE
DI Internal FIRE ALARM
DI Internal AH5 RESET
DI Internal FSCS PRESS
DI Internal AHU 5 PRESSURIZE
AI Internal AH5 SF VANE MOD
DI Internal LATCH ALARM
DC External AHU 5 OA DP CTRL
AO External AHU 5 SF VN CTRL
DM External AHU 5 SF STATUS
DA * External FIRE ALARM
* From Fire Alarm Control Panel

~P0*P1+P0*C0
where,
P0 = Open VAV
P1 = VAV Temp PID Out
C0 = A constant that is greater than the normal CFM setpoint but less than the high limit
in the CFM PID loop.
Another typical example is a two-story building that is divided into four equal quadrants
per floor, with each quadrant being one zone and no stairwell fan. Each zone is served by
a type 3 AHU. Eight controllers with station numbers 1 through 8 are used, one per
AHU. When one zone smoke detector goes into alarm, the other two adjacent zones on
the same floor and the adjacent zone above or below will go into the pressurize mode.
The sequence of operation is the same as described earlier for type 3 AHUs except now
there are three adjacent zones instead of two to cause the AHU to enter the pressurize
mode. A third adjacent zone would be added to module 1, the high/low selector, shown
in Figure8, “DDC Flow Diagram Example for AHU Types 1-4”. See Figure17, “Example
AHU Type 3 Points” for a points list.

Figure 17. Example AHU Type 3 Points

Type Class Name

DC External AHU 3 SF CTRL


DA Internal AHU 3 TROUBLE
DI Internal FSCS PRESS
DI Internal FSCS EXH
DI Internal AHU 3 PRESSURIZE
DI Internal AHU 3 EXH
DI Internal AHU 3 RESET
* From Fire Alarm Control Panel

Guidelines for Smoke Control 27


System Examples Reference Guide

Figure 17. Example AHU Type 3 Points (Continued)

Type Class Name

AO External AHU 3 OA DP CTRL


AI Internal AHU 3 OA DP MOD
DC External AHU 3 RF CTRL
DI Indirect Z N-1 SD
DI Indirect Z N+1 SD
DI Indirect Z N+2 SD
DO Internal AHU 3 TIME SCHED
DA * External AHU 3 SMOKE DET
DI External AHU 3 OA DAMP ES
DI External AHU 3 RL DAMP ES
DI External AHU 3 RA DAMP ES
DM External AHU 3 SF STATUS
DM External AHU 3 RF STATUS
* From Fire Alarm Control Panel

A single story building that is divided into four equal quadrants with each quadrant
being one zone is another typical building. Each zone is served by a type 1 AHU. Four
controllers with station numbers 1 through 4 are used, one per AHU. The sequence of
operation is the same as described for type 2 AHUs. When a zone smoke detector goes
into alarm, the two adjacent zones go into the pressurize mode. See Figure18, “Example
AHU Type 1 Points” for AHU type 1 points.

Figure 18. Example AHU Type 1 Points

Type Class Name

DC External AHU 1 FAN CTRL


DA Internal AHU 1 TROUBLE
DI Internal FSCS PRESS
DI Internal FSCS EXH
DI Internal AHU 1 PRESSURIZE
DI Internal AHU 1 EXH
DI Internal AHU 1 RESET
AI Internal AHU 1 OA DP MOD
DI Indirect Z N-1 SD
DI Indirect Z N+1 SD
AO External AHU 1 OA DAMP CTRL
DO Internal AHU 1 TIME SCHED
DA * External AHU 1 SMOKE DET
DI External AHU 1 OA DAMP ES
DI External AHU 1 RL DAMP ES
* From Fire Alarm Control Panel

28 Guidelines for Smoke Control


Reference Guide System Examples

Figure 18. Example AHU Type 1 Points (Continued)

Type Class Name

DI External AHU 1 RA DAMP ES


DM External AHU 1 FAN STATUS
* From Fire Alarm Control Panel

Guidelines for Smoke Control 29


Reference Reference Guide

Reference

Refer to the following documents for additional information:


✦ NFPA 92-A, Recommended Practice for Smoke Control Systems
✦ NFPA 101, Life Safety Code
✦ UL 864, Standard for Control Units for Fire-Protective Signaling Systems
✦ ASHRAE publication, Design of Smoke Management Systems, 1992
✦ Local building codes and regulations
✦ Control Systems International documents:
✧ TCON094, I/NET 7700 Operator Guide
✧ TCON145, I/NET Technical Reference Guide
✧ TCON151, I/NET Docutrend Reference Guide
✦ Control Systems International User Guide or Installation Guide (delivered with
each CSI hardware item):

Document Title TCON Number Revision

Model 7200 User Guide TCON069 01/92 or later


I/NET 7700 Operator Guide TCON094 01/93 or later
Model 7700 DCU User Guide TCON095 10/92 or later
Model 7716 PCU Installation Guide TCON096 01/93 or later
Model 7740 DCU User Guide TCON097 10/92 or later
Model 7760 UCI User Guide TCON099 06/92 or later
Model 7800 Series Taps and Repeater
TCON101 04/93 or later
Installation Guide
Model HC7410 User Guide TCON073 08/91 or later

30 Guidelines for Smoke Control


Reference Guide Appendix A

Appendix A
Definition Of Terms
Alarm (Smoke) Signal - An input signal to the smoke control system indicating an emer-
gency fire condition requiring immediate action, such as the alarm initiated from a UL
listed fire alarm control panel.
Firefighter's Smoke Control Station - The Firefighter's Smoke Control Station (FSCS)
includes monitoring and overriding capability over smoke control systems and equip-
ment provided at a designated location within the building for use by qualified personnel
(typically fire department personnel).
Indicating Device - Any audible or visual signal employed to indicate a fire, supervisory,
or trouble condition. Examples of audible signal appliances are bells, horns, sirens, elec-
tronic horns, buzzers, and chimes. A visual indicator consists of a lamp, target, meter
deflection, or the equivalent.
Pressurized Stairwells - A type of smoke control system in which stair shafts are
mechanically pressurized with outdoor air to keep smoke from contaminating them
during a fire.
Smoke - The airborne solid and liquid particulates and gases evolved when a material
undergoes pyrolysis or combustion, together with the quantity of air that is entrained or
otherwise mixed into the mass.
Smoke Barrier - A membrane, either vertical or horizontal, such as a wall, floor, or
ceiling assembly, that is designed and constructed to restrict the movement of smoke. A
smoke barrier may or may not have a fire resistance rating. Smoke barriers may have
openings protected by closing devices or adequate air flows.
Smoke Control Mode - A predefined operational configuration of a system or device
used for the purpose of smoke control.
Smoke Control System - An engineered system that uses mechanical fans to produce
airflows and pressure differences across smoke barriers to limit and direct smoke move-
ment.
Smoke Control Zone - A space within a building enclosed by smoke barriers, including
the top and bottom, that is part of a zoned smoke control system.
Smoke Damper - A device that meets the requirements of UL 555S, Standard for Leakage
Rated Dampers for use in Smoke Control Systems, designed to resist the passage of air
or smoke.
Smoke Exhaust System - A mechanical or gravitational system intended to move smoke
from the smoke zone to the exterior of the building, including smoke removal, purging,
and venting systems, as well as the function of exhaust fans utilized to reduce the pres-
sure in a smoke zone. Maintenance of a tenable environment in the smoke zone is not
within the capability of these systems.
Smoke Zone - The smoke control zone in which the fire is located.
Stack Effect - The vertical airflow within buildings caused by the temperature difference
between the building's interior and exterior.

Guidelines for Smoke Control 31


Appendix A Reference Guide

Tenable Environment - An environment in which the quantity and location of smoke is


limited or otherwise restricted, to allow for ready evacuation through the space.
Zoned Smoke Control - A smoke control system that includes smoke exhaust for the
smoke zone and pressurization for all contiguous smoke control zones. The remaining
smoke control zones in the building also may be pressurized.

Note: The above are terms as defined in UL864 Control Units for Fire-Protective Signaling
Systems and NFPA-92A Smoke Control Systems (1988 Edition).

32 Guidelines for Smoke Control


Reference Guide Appendix B

Appendix B
UUKL Listed CSI Equipment
The following UUKL Listed CSI equipment may be used for smoke control systems:
✦ 7700U8 DCU
✧ 4AOC1 AO Expansion Card, 4-20 mA
✧ 4AOC3 AO Expansion Card, 4-20 mA
✧ 4AOV1 AO Expansion Card, 0-10 V
✧ 4AOV3 AO Expansion Card, 0 -10 V
✧ 8DIPI 8 Point Input Expansion Card
✧ 8DO 8 Point Discrete Output Expansion Card
✧ 12AIF 12 Point AI Expansion Card
✦ 7716U8 PCU
✧ P8UI4AOC 8 Point Universal Input/ 4 Point AO (4-20 mA) Expansion Card
✧ P8UI4AOV 8 Point Universal Input/ 4 Point AO (0-10 V) Expansion Card
✧ P8UI8DO 8 Point Universal Input/ 8 Point Discrete Output Card
✧ P8DO 8 Point Discrete Output Expansion Card
✧ P8UI 8 Point Universal Input Card
✧ P4UI4DO 4 Point Universal Input/ 4 Point Discrete Output card
✧ RS232 I/F Serial Communications Board
✦ B7760U8 UCI
✦ 7270U8 Multi-purpose UC
✦ 7261U8 VAV UC
✦ XFRMR6 Unitary Controller Transformer (120/24 VAC)
✦ ENCL2216 Universal Enclosure
✦ Taps
The following CSI communications Taps may not provide any of the smoke control
functionality, but may be connected for monitoring and data collection purposes.
✧ 78010A Host Tap
✦ Actuators and Dampers
The following actuators and dampers are not UUKL Listed but may be used in the
configuration of UUKL smoke control systems.
✧ ACT02 VAV damper actuator
✧ ACT03 VAV damper actuator
✧ IP1 Current to pneumatic transducer, 3-18 psi
✧ PWMP1 Pulse width to pneumatic transducer, 3-18 psi
✧ PWMV1 Pulse width to voltage transducer, 0-10 V
✧ PWMC1 Pulse width to current transducer, 4-20 mA
✧ PWMC2 Pulse width to current transducer, 0-20 mA

Guidelines for Smoke Control 33


Appendix C Reference Guide

Appendix C
Connections and Restrictions for
CSI UUKL-Listed Equipment
Figure 19. Wiring Illustration – 7700U8 in Enclosure
Figure 20. 7700U8 DCU Board
Figure 21. 7700U8 DCU Expansion Boards
Figure 22. 7700U8 DCU Expansion Boards
Figure 23. 7716U8 PCU
Figure 24. 7716U8 PCU Expansion Boards
Figure 25. 7760U8 Unitary Controller Interface
Figure 26. 7261U8 VAV Unitary Controller II
Figure 27. 7270U8 Universal Unitary Controller
Figure 28. Model IRB8 Interface Relay Board
Figure 29. Firefighter’s Smoke Control Station To 7716U8 DCU Connections
Figure 30. Fire Control Panel To Smoke System Connections

34 Guidelines for Smoke Control


Reference Guide Appendix C

7700U8 DCU

Option Boards
(shown for reference only)

HHC

Power LAN

CSI Transformer
P/N 605601–0001 Splice
(behind cover)

120 VAC Power input is not limited and must


remain segregated in the transformer compartment
not routed with any power-limited (I/O) wiring. Typical knockout for
Utilize provided knockout for wire egress. I/O wire routing.

Figure 19. Wiring Illustration – 7700U8 in Enclosure

Guidelines for Smoke Control 35


Appendix C Reference Guide

POWER
SUPPLY

TB5 TB4 (5–24VDC)


See Note 2
For connection of 12AIF

CHASSIS

 Not +15V
CHASSIS
used

 COMMON
 AI-8
 AI-6
AI-7

 AI-5
 AI-3
AI-4

 AI-1
AI-2
Not used
– +

expansion board only +15v
COMMON +
 AI-8 –

AI-7
AI-6

 AI-5
AI-4
Analog Sensors

P4  AI-3


AI-2
AI-1
ANALOG INPUTS
For connection of 4AOC, 1–5V or 4–20mA Shield
4AOV, or 8DIPI board POWER
only SUPPLY
TB3 (5–24VDC)
See Note 2
 GND
COMMON
– +
 COMMON


COMMON
P3 DI/PI-8


DISCRETE/PULSE DI/PI-7
DI/PI-6
INPUTS
For connection of 4AOC,  DI/PI-5
DI/PI-4
4AOV, or 8DIPI board
 DI/PI-3


only DI/PI-2
DI/PI-1

TB2 Shield

 GND


COMMON
P2  COMMON

 Rating and connections


COMMON
 DO-16


DO-15
DO-14  same as for TB1
For connection of 8DOPO
or 8DIPI board only 
DO-13


DO-12

 DO-11


DO-10
DISCRETE/PULSE  DO-9 POWER
SUPPLY
OUTPUTS  TB1 (5–24VDC)

P1
0.25 amp load (@ 24VDC)  GND
See Note 2
max. each output
 – +
COMMON
COMMON

 COMMON
DO-8 Load
 DO-7


DO-6
DO-5


DO-4
DO-3

 DO-2
DO-1 Load
CONSOLE Shield
For CSI DCU/PCU LAN
POWER Connection only
TB6 TB7 Notes:
1. All I/O connections are power-limited.
LAN + 2. External power supplies should be
For plug-in test/setup LAN –
power-limited or Class II Listed for
Shield
connection of model Fire Protective Signaling Service.
Splice
HC7410 HHC only.
3. Connect controller LAN shield drain
See Note 3 to earth ground at one location per
LAN only.
Figure 20. 7700U8 DCU Board

36 Guidelines for Smoke Control


Reference Guide Appendix C

TBX4 POWER
TBX5
12 SUPPLY See Note 2
CHASSIS
P1

NU

NU
NU
NU
NU
+15V

AI-28
AI-27
AI-26
AI-25
COMMON
CHASSIS
NU (5–24 VDC)
+15V – +
COMMON
AI-24
AI-23
AI-22
ANALOG INPUTS AI-21
Analog Sensors
(4–20 mA or 1–5 volt) AI-20
AI-19
For plug-in connection to 7700U8 DCU AI-18
AI-17 1
P4 expansion port only
Shield

Model 12AIF (Fault Tolerant Analog Input Expansion)

TBX–
12
CHASSIS
NU
P1 NU
ANALOG OUTPUTS NU
Model 4AOC3 – 0–20 mA AO-4/8 COM
AO-3/7 COM
Model 4AOV3 – 1–5 volt
AO-2/6 COM
AO-1/5 COM
AO -4/8 Load
For plug-in connection to 7700U8 DCU
AO -3/7 Load
P2 expansion port – AOs 1–4 Load
AO -2/6
or AO -1/5 Load
1
P3 expansion port – AOs 5–8
Shield

Model 4AOC3/4AOV3 Analog Output Expansion

Notes:
1. All I/O connections are power-limited.
2. External power supplies should be power-limited or
Class II Listed for Fire Protective Signaling Service.

Figure 21. 7700U8 DCU Expansion Boards

Guidelines for Smoke Control 37


Appendix C Reference Guide

POWER
TBXX SUPPLY
12
(5–24 VDC)
CHASSIS
P1 COMMON
See Note 2

COMMON – +
COMMON
DO/PO - 24 LOAD
8 DISCRETE/PULSE OUTPUTS DO/PO - 23
DO/PO - 22
(4-20 mA or 1-5 volt)
DO/PO - 21
DO/PO - 20
DO/PO - 19
DO/PO - 18
For Plug-In Connection to 7700U8 DCU DO/PO - 17 1 LOAD
P1 Expansion Port Only (DO/PO 17-24)
Shield

Model 8DO/PO Expansion Board

POWER
TBXX SUPPLY
12
CHASSIS (5–24 VDC)
COMMON See Note 2

P1 COMMON – +
8 DISCRETE/PULSE INPUTS COMMON
DI/PI - 16/24/32
DI/PI - 15/23/31
For Plug-In Connection to 7700U8 DCU DI/PI - 14/22/30 Discrete
P1Expansion Port - DI/PI 25-32 DI/PI - 13/21/29
Contact
and/or DI/PI - 12/20/28
Input
P2 Expansion Port - DI/PI 17-24 DI/PI - 11/19/27
and/or DI/PI - 10/18/26
P3 Expansion Port - DI/PI 9-16 DI/PI - 9/17/25 1

Shield
Model 8DI/PI Expansion Board

Notes:
1. All I/O connections are power-limited.
2. External power supplies should be power-limited or
Class II Listed for Fire Protective Signaling Service.

Figure 22. 7700U8 DCU Expansion Boards

38 Guidelines for Smoke Control


Reference Guide Appendix C

TB1 TB7
1 N.C.
Typical Discrete GND COM8
Contact Sensing Connection +V N.O.
2 N.C.
GND COM7
+V N.O.
3 N.C.
GND COM6
+V N.O.
4 N.C.
GND COM5
8 OUTPUTS N.O.
+V 8 UNIVERSAL INPUTS
FORM C RELAY
(0-5v, 0-20mA, or TB6
TB2 (Max 0.5 amp
0-5 volt or Sensor Output Discrete Contact Sensing)
5 @ 24VAC/DC N.C.
Ground GND COM4
0 -20mA
Sensor Power +V N.O.
Sensor N.C.
6 0.5 amp max load
Typical Analog Sensor GND COM3
+V N.O. @ 24VAC/DC
Connection
7 N.C.
GND COM2 Typical Load Connection
+V N.O.
N.C. (Normally Closed
8
GND COM1 Connection Shown)
+V N.O.

TB3

Splice DATA +
DATA -

See Note 3
For Connection of
Standard RS232C
For CSI DCU/PCU P2 Device Using CSI
P1 For Connection of Optional
Connection Only Cable 606105-0036
PRS232 Board (#330380) Only
or -0037 Only

For Plug-in Connection of P4


HC7410 HHC
(Test/Setup Use Only)

TB4
24VAC (Use CSI 24VAC
Transformer 24VAC
EGND P3
#605601- 0007)

For Plug-in Connection of CSI Expansion Boards


P8UI8DO, P8UI, P8DO, P4UI4DO, P8UI4AOC, P8UI4AOV,
P4AOC, or P4AOV Only

(Refer to TCON096, Model 7716 PCU Installation Guide)

Notes:
1. Relay Contact outputs (TB6 & TB7) are for connection
to a power-limited or Class II supply listed for Fire
Protective Signaling Service.
2. All other I/O connections are power-limited.
3. Connect controller LAN shield drain to earth ground at
one location per LAN only.

Figure 23. 7716U8 PCU

Guidelines for Smoke Control 39


Appendix C Reference Guide

TBX1 TBX4
P1
1 +V
GND For Plug-In Connection to Model 7716U8 Expansion GND
+V Connector P3 Only 8
2 +V
GND 8 Universal Inputs (Same Ratings & Connections GND
+V as 7716U8 PCU TB1 & TB2 Inputs) 7
3 +V
8 DISCRETE FORM C RELAY OUTPUTS
GND (Same Ratings & Connections GND
+V as 7716U8 PCU TB6 & TB7 Outputs) 6
4 +V
GND GND
+V 5

COM -5

COM -7
COM -4

COM -6

COM -8
COM -1

COM -2

COM -3
N.O.

N.O.

N.O.

N.O.
N.O.
N.C.

N.C.

N.C.

N.C.
N.C.

N.C.

N.C.

N.C.
N.O.
N.O.

N.O.
TBX2 TBX3

Model P8UI8DO (Also Representative of P8UI, P8DO and P4UI4DO) (For Spade Lug Connection to
Earth Ground)

TBX1 P2
P1
1
GND For Plug-In Connection to Model 7716U8 Expansion TBX3
+V Connector P3 Only GND
2 AO -4
8 Universal Inputs (Same Ratings & Connections 4 Analog Outputs
GND 0-10 volt or 0-20 mA GND
+V as 7716U8 PCU TB1 & TB2 Inputs)
AO -3
3 GND
GND AO -2
+V GND
4 AO -1
GND
+V 0-20 mA or
0-10 volt device
GND
GND

GND

GND
+V
+V
+V
+V
6

8
5

TBX2

Model P8UI4AOC (Also Representative of P8UI4AOV, P4AOC & P4AOV)

OUTPUTS
P8UI4AOC, P4AOC - 0-20 mA outputs
P8UI4AOV, P4AOV - 0-10 volt outputs
Notes:
1. Relay contact outputs (P8UI8DO, TBX2 and
TBX3) are for connection to a power-limited or
Class II supply listed for Fire Protective
Signaling Service.
2. All other I/O connections are power-limited.

Figure 24. 7716U8 PCU Expansion Boards

40 Guidelines for Smoke Control


Reference Guide Appendix C

For Connection to For Connection to


CSI DCU/PCU CSI UNITARY
CONTROLLER CONTROLLER
ON/OFF SWITCH LAN Only LAN Only
HHC PORT P6
S1 RJ11 RJ11
NOT USED
P3 TB1 PORT A TB2 PORT B
AC GND AC 1 2 3 4 5 1 2 3 4 5

COM +
13.5 VAC input For Plug-in Test/Setup
Use CSI #606502-0004 Connection of CSI Model COM –
Plug-in Transformer HC7410 Only Shield
Splice
LAN +
LAN – See Note 2
Shield
Splice
Notes:
See Note 2 1. All I/O connections are power-limited.
2. Connect shield drain to earth ground
at one location per LAN only.

Figure 25. 7760U8 Unitary Controller Interface


POWER INPUT

GND P1
GND P2
24 VAC
Use CSI Trans. 24 VAC P4
#605602-0005 24 VAC "Hot"
A1-1 P5
GND P6 6 24-VAC @ 0.5 amp (Max) P38 GND
+15V P7 TRIAC OUTPUTS P35 OPN 24 VAC Load
A1-2 P8 CLO (0.5 amp Maximum)
P34
GND P9 6 0–20 mA or 0–5 V Analog Inputs P33 FAN
+15V P10 or Discrete Contact Sensing Inputs H1 Typical Output Load Connection
P32
A1-3 P11 P31 H2
GND P12 P30 H3
+15V P13 For Setup/Test Connection of
A1-4 CSI Model HC7410 Only
HHC PORT

P14
GND P15
RJ11
+15V P16
Typical Discrete Contact
Sensing Input A1-5 P17
GND P18 For Connection to Unitary TB1
+15V Controller LAN Only (16–24 AWG)
P19
SHIELD
Analog Sensor A1-6 P20
0-20 mA or 0-5 V GND P21
Output
+15V P22 NOT USED COM –
P28 COM + Splice
1 P23 P24 1
SENSOR 2 P25 P26 P27 SENSOR 1
Typical Analog Input Connection

For Plug-in Connection of CSI Pressure


Transducer #605540-0002 (0-1.3") Only See Note 2

Notes:
1. All I/O connections are power-limited.
2. Connect shield drain to earth ground
at one location per LAN only.

Figure 26. 7261U8 VAV Unitary Controller II

Guidelines for Smoke Control 41


Appendix C Reference Guide

SHIELD TB1 TB7


Analog Sensor AI-1 N.C.
0-20 mA or 0-5 V GND 8
Output +15V N.O.
AI-2 N.C.
GND 7
+15V N.O.
AI-3 N.C.
Typical Analog Input GND 8 FORM-C RELAY CONTACT OUTPUTS 6
Connection RATED 24 VAC/DC @ 0.5 AMP MAX.
+15V N.O.
AI-4 N.C.
GND 5
+15V N.O.
8 ANALOG INPUTS (0-20 mA or 0-5 V)
TB2 OR DISCRETE CONTACT SENSING INPUTS TB6
AI-5 N.C. 24 VAC/DC Load
GND 4 (0.5 Amp Maximum)
+15V N.O.
Typical Discrete AI-6 N.C.
Contact Sensing Input GND 3 Typical (Normally Open)
+15V N.O. Output Connection
AI-7 N.C.
GND 2
+15V N.O.
AI-8 N.C.
GND 1
+15V N.O.
For Setup/Test Connection of CSI
Model HC7410 Only

TB5 Connection to Unitary


Controller Lan Only

TB3 TB4 TB5


NO CONNECTION
24 VAC Notes:
Use CSI Trans. COM + 1. Relay contact outputs (TB6 & TB7)
#605602-0005 COM – are for connection to power-limited or
Shield
Class II supply listed for Fire
Splice Protective Signaling Service.
See Note 3
2. All other I/O connections are power-
limited.
3. Connect shield drain to earth ground
at one location per LAN only.

Figure 27. 7270U8 Universal Unitary Controller

CSI 9-Conductor
Cable #800480-03
TB1 P1 T
1
2 B C NO
3 NC NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
COMM 4 B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DO -7 5
DO -6 6
8 DUAL CONTACT FORM-C RELAY OUTPUTS
DO -5 7
DO -4 8
DO -3 9 T 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DO -2 10 NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
DO -1 11 B
DO -0 12
A

Connections Pin 1 to 1
through Pin 9 to 9 277 VAC (Max)

Typical (Normally Closed)


Connection Shown

LOAD

Figure 28. Model IRB8 Interface Relay Board

42 Guidelines for Smoke Control


Reference Guide Appendix C

XL8 SERIES ANNUNCIATOR


(U.L. LISTED) used as FSCS
7716U8 PCU
See Note 2 manufactured by Space Age Electronics
TB1
DI-1 1 1B
DI-2 4 1C
DI-3 7 2B
DI-4 10 2C

TB1
7716U8 DISCRETE INPUTS GND 2 1A
XL8 RELAYS
(FSCS OVERRIDE SWITCHES)
TB2
DI-5 1 3B
DI-6 4 3C
DI-7 7 4B
DI-8 10 4C
TB2
GND 2 2A

TB6
N.O. 1 1I
N.O. 4 1F
N.O. 7 2I
N.O. 10 2F
TB7
N.O. 1 3I
N.O. 4 3F
N.O. 7 4I
7716U8 DISCRETE OUTPUT N.O. 10 4F
RELAY CONTACTS XL8 LAMPS
(FSCS LAMPS)
TB6
COM. 2 1E
COM. 5 1H
COM.
Firefighter's Smoke Control
8 2E
COM. 11 Station To 7716U8 PCU Connections 2H
TB7
COM. 2 3E
COM. 5 3H
COM. 8 Connections shown are typical for FSCS Switches/Leds 1-4. 4E
COM. 11 Use additional 7716U8(s) to provide additional zones/controls. 4H

TB-H5
+
+
+ 24 VDC SUPPLY
_ (U.L. Listed)
_ _
See Note 1

See TCON096, 7716 PCU Installation Guide and XL8 Installation


Instructions for additional information. FSCS Terminal Block Designations:
xy - x is XL8 Switch/LED Group
- y is XL8 Terminal Block Designation

Notes
1. Power Supply to be power-limited or Class II Listed for Fire
Protective Signaling Service.
2. Connections between 7716U8 PCUs and XL8 annunciator
must be run in conduit and located adjacent to controller.

Figure 29. Firefighter’s Smoke Control Station To 7716U8 DCU Connections

Guidelines for Smoke Control 43


Appendix C Reference Guide

TB1

7716U8 PCU
Fire Control Panel To Smoke System Connections
Listed Fire Alarm Control Panel
(with Dry Contact Relay Outputs)

TB2

Zone Connections Between Adjacent


Units Run In Conduit

Zoned Smoke Alarm


Dry Contact Relay Outputs
TBX1
N.O.
1
COMM. ZONE 1
GND Inputs Configured as DISCRETE
+V
N.O. INPUTS (DISCRETE ALARM)
2
COMM. ZONE 2
GND
+V
3
Representative zoned smoke alarm connections from GND 8UI/8DO Expansion Board
+V
fire alarm control panel to corresponding zone input 4
of controller for two zone system configuration shown. GND
+V

Figure 30. Fire Control Panel To Smoke System Connections

44 Guidelines for Smoke Control


52
Index
See Modes of operation
pressurize operation mode 6
Numerics purge operation mode 6
trouble operation mode 6
7700 DCU
access restriction 2 Air flow velocity
mounting 2 See Pressure difference
types 33 Air handler units
7716 PCU controlling of 3
mounting 2 Alarm circuit
types 33 See Zone

A B
Actuators Building
See Also Outputs examining 4
types 33
Addressing
controllers 4
AHU C
alarms 6
locking 6 Controllers
configurations 8 local area network types 2
Firefighter’s Smoke Control Stations 23 station addressing 4
graphic pages 23 wiring 5
modules
description 16
Type 1 8
diagram 10
points 28 D
Type 2 10
Dampers
Type 3 12
HVAC control system 5
diagram 12
See Also HVAC control system
points 27
types 33
Type 4 13
diagram 14 Dedicated systems
points 26 testing interval 2
Type 5 14 Design
diagram 15 hardware 4
points 27 software 5
exhaust operation mode 6 programming 5
isolate operation mode 6
Design parameters
multiple units 1
See Smoke control system
operation modes

Guidelines for Smoke Control 45


I/NET Docutrend Reference Guide

operation
definition 4
E parameters 4
smoke detector 5
Equipment
See Smoke control system
Exhaust fans
controlling of 3
L
Local Area Network
application software design 3
F configuration 3
controller types 2
Fire alarm control panels location of 3, 4
dry contact outputs 2, 5 programming 3
testing 5
Fire detector
See Smoke detector
Firefighter’s Smoke Control Station 2 M
AHU 23
implementating 2 Modes of operation
See Also HVAC control system AHU Type 1
exhaust 8
normal 8
pressurize 8
trouble 8
H AHU Type 2
exhaust 11
Hardware normal 10
design 4 pressurize 10
hardware points trouble 11
HVAC control system 4 AHU Type 3
HVAC control system exhaust 12
controlling normal 12
field devices 5 pressurize 12
dampers 5 trouble 13
Firefighter’s Smoke Control Station 5 AHU Type 4
hardware points 4 exhaust 13
addresses 4 normal 13
controlling 4 pressurize 13
grouping 4 trouble 13
labeling 4 AHU Type 5
monitoring 4 normal 14
point types 4 trouble 15
sorting 4 definitions
modes 4 exhaust 6
modification of 2 isolate 6
monitoring pressurize 6
field devices 5 purge 6
trouble 6

46 Guidelines for Smoke Control


Monitoring design parameters 4
See Zone emergency personnel conditions 4
See Also HVAC control system equipment 2
Firefighter’s Smoke Control Station 2
monitoring 2
override 2
evacuation environment 4
N life safety system interfacing 2
nondedicated 2
Nondedicated system
operation 8, 23
UUKL Listed CSI products 2
purpose 1
Nondedicated systems search/rescue operation conditions 4
control strategies 2 stairwell 2
cost effectiveness 2 system examples 25
malfunctioning 2 taps
modification of 2 types 33
testing 24
Smoke detector
HVAC control system 5
O Software
control sequence 25
Output design 5
electric actuators 2 editors 6
transducers 2 password protection 6
variable frequency motor drives 2 programming 5
discrete input points 5
internal points 5
resident I/O points 5
P station addressing 5
station parameters 5
Password protection operation sequence 25
See Software design
Pressure difference
door opening 1
stack effect 1 T
Taps
types 33

S Transducers
types 2
Smoke control system
actuators
types 33
configuration 2
dampers
Z
types 33 Zone
dedicated 2 AHU
definition of 1 See AHU
design 2, 4 control strategies 3

Guidelines for Smoke Control 47


I/NET Docutrend Reference Guide

design critera
number of doors 1
migration of smoke 4
monitoring of 2
multiple alarms 2
multi-story buildings 1
size of 1

48 Guidelines for Smoke Control


P.O. Box 59469, Dallas, Tx 75229
Phone: (972) 323-1111
FAX Phone: (972) 242-0026

CSI Europe
Unit B3, Armstrong Mall
Southwood, Farnborough
Hampshire GU14 ONR, United Kingdom
Phone: 44 1252 370900
FAX Phone: 44 1252 372470

CSI Pacific
36 Hasler Rd.
Osborne Park, Western Australia 6017
Phone: 61-9-244 2799
FAX Phone: 61-9-244 4335

You may obtain copies of this document by ordering


document number TCON120.

TCON120.–.10/96

Вам также может понравиться