Академический Документы
Профессиональный Документы
Культура Документы
Protective Relays
David Angell
Idaho Power
Daqing Hou
Schweitzer Engineering Laboratories, Inc.
Presented at the
61st Annual Georgia Tech Protective Relaying Conference
Atlanta, Georgia
May 2–4, 2007
Abstract—Capacitive Coupled Voltage Transformers circuit and equivalent circuit are shown in Fig. 1 and Fig. 2,
(CCVTs) and Bushing Potential Devices (BPDs) have supplied respectively. The equivalent circuit includes stray capacitance
high voltage relay potential circuits for many years. The and winding resistance of the compensating reactor and also
transient performance of a CCVT has been analyzed, and
solutions for their transient performance have been incorporated
stray capacitance, winding resistance, and leakage inductance
in relaying systems since the 1970s. Little analysis has been of the step-down transformer.
performed on BPD transient performance. A BPD has been
Line Voltage
tested and characterized to determine the parameters that affect
the output voltage during system fault conditions.
Current Transformers (CTs) that saturate during system C1
faults produce a nonsinusoid output that, when filtered, presents GAP RR
a reduced magnitude and phase shifted current to protective
relays. The response of distance relays for various levels of CT
saturation are analyzed and presented. L TR
GAP CF LF
B
Finally, utility experience with relays sourced by CCVTs and C2
U
R
BPDs with the intent of validating the models and relay setting D
adjustments for input source errors are presented. CA RA RF E
N
100
TRANSIENT RESPONSE: SOLID-Ratio Voltage, DASH-CCVT Output The subsidence voltage causes a measured voltage
magnitude reduction and phase angle shift as shown in the
80
polar plot, Fig. 6 and Fig. 7, for peak and zero voltage fault
60 initiation. The numbers marked in the plots are the sequence
40 that the fault voltage goes through after the fault initiation.
20
120 60
volt
-20
150 30
-40
-60
-80
4 2
3
-100
-2 -1 0 1 2 3 4 5 5
180 0
cycle
60
40
240 300
20
270
volt
0
Fig. 6 CCVT voltage peak subsidence transient fundamental voltage
-20
120 60
-40
-60
-80
150 5 30
4
-100
-2 -1 0 1 2 3 4 5
cycle
a few cycles as shown in Fig. 4. A simplified equivalent Fig. 7 CCVT voltage zero subsidence transient fundamental voltage
circuit is shown in Fig. 5. Notice how the voltage magnitude is severely reduced and
significantly out of phase with the actual fault voltage, points
Ls Ce Lc 5 and 6, respectively in Fig. 6 and Fig. 7.
Rb
Vs I Vo
Lb
6
IMPEDANCE TRAJECTORY: SOLID-Ratio Voltage, DASH-CCVT Transient E. Utility CCVT Performance
IMPEDANCE TRAJECTORY: SOLID-Ratio Voltage, DASH-CCVT Transient
90
5 70
X-ohm
50
4
failed circuit switcher contact on a line reactor that is selected
40
30
3 10
2
creating a B-C fault. A remote Zone 1 relay, set to protect a
1
41-mile line with a SIR of 1.45, trips for this event. The
CCVT sourcing the protective relay has an active
0 ferroresonance suppression circuit. The resulting transient
impedance lies within the Zone 1 reach due to the subsidence
-1
transient as shown in Fig. 11 and Fig. 12.
-2
-2 -1.5 -1 -0.5 0 0.5 1 BC-Phase Voltage and Current
R-ohm 150
100
Fig. 8 CCVT output impedance trajectory of voltage-peak fault
50
volt
IMPEDANCE TRAJECTORY: SOLID-Ratio Voltage, DASH-CCVT Transient 0
10 IMPEDANCE TRAJECTORY: SOLID-Ratio Voltage, DASH-CCVT Transient
50
-50
40
9 30 -100
20
8 10 -150
0 2 4 6 8 10 12
X-ohm
7 -10
-20
-30 15
6
-40
-50
0 20 40 60 80 100 120 140 160 180 200 10
5 R-ohm
X-ohm
5
amp
4
0
3
-5
2
-10
0 2 4 6 8 10 12
1 cycle
0
Fig. 10 B-C phase voltage and current for B-C fault
-1
-1 -0.5 0 0.5 1 1.5 2 2.5 3 3.5 4
BC-Phase Apparent Impedance
R-ohm 6
TABLE I
PARAMETERS THAT AFFECT CCVT TRANSIENT PERFORMANCE -1
-3 -2 -1 0 1 2 3 4 5
Re-ohm
Parameter Small Large
Transient Transient Fig. 11 Zone 1 overreach for B-C fault
CCVT Capacitance High Low The second case occurred when a breaker was closed into a
three-phase fault. A remote Zone 1 relay, set to protect a
Ferroresonance Suppression Passive Active
Circuit 13-mile line with a SIR of 29, trips for this event. The
resulting transient impedance lies within the Zone 1 reach due
Transformer Ratio High Low
to the subsidence transient as shown in Fig. 12 and Fig. 13.
Burden Resistive Inductive
Bus Voltage Dip* Small Large
* The transient error is proportional to the
change in bus voltage due to a fault.
4
100
Three-Phase Voltages and Currents: SOLID-A,DASH-B,DOT-C The secondary of the BPD contains a coupling coil, phase
angle adjustment capacitors, and power factor adjustment
50
capacitors. The coupling coil and phase angle adjustment
capacitors provide for aligning the secondary potential with
volt
-5
BPDs are designed to withstand overvoltage up to rated
-10
line-to-line voltage that result when neutral voltage shift
-15
occurs. Therefore, a ferroresonance suppression circuit is not
0 2 4 6
cycle
8 10 12
required. A typical BPD and equivalent circuit are shown in
Fig. 12 Voltages and currents for three-phase fault Fig. 14 and Fig. 15, respectively. Refer to the Appendix for
Three-Phase Apparent Impedance: SOLID-A,DASH-B,DOT-C
the model parameters.
0.8
0.7
C1 SW
0.6
Secondary
0.5 Cpa Cpf 115
Coupling
Primary
C2 C3 66.4
Coil
0.4
Im-ohm
SW
0.3
0.2
Fig. 14 GE KA-105 BPD circuit
0.1
L3 R3
0
L2 R2 m I2 + I3
-0.1
-0.5 -0.4 -0.3 -0.2 -0.1 0 0.1 0.2 0.3 0.4 0.5 Lb
Re-ohm
Cpa
Fig. 13 Zone 1 overreach for three-phase fault Ce L1 R1 V3 Cpf Vb
1-m
In the first case, the Zone 1 reach was reduced to eliminate I1 Rb
the transient overreach. In the second case, a 1.75-cycle time Vp V1 V2
I2 I3
delay was added to eliminate the overreach. N1 N2 N3
F. Recommended CCVT Specification Primary Coupling Secondary Burden
In order to minimize the CCVT subsidence transient, use Fig. 15 GE KA-105 BPD equivalent circuit
the following criteria: B. BPD Voltage Transient
• High capacitance, e.g. 10 nano-fared
A BPD produces a similar response to a change in voltage
• Large transformer ratio, e.g. 15 kV / 115 / 66 V to that of a CCVT. However, because the BPD employs a low
• Passive ferroresonance circuit step-down transformer ratio, the BPD response is more
• Resistive CCVT burden dependent on the secondary burden as shown in Fig. 16
through Fig. 19. A high inductive burden (low power factor)
III. BUSHING POTENTIAL DEVICE significantly increases the amount and duration of the transient
A. BPD Construction error as shown in Fig. 18 and Fig. 19.
BPDs are manufactured to match a particular bushing type,
e.g. GE “U” or “F” type. The BPD may be applied on a
bushing type ranging from 69 to 230 kV. The construction of
a BPD is based on tapping a point within the degrading
insulation of a bushing. This makes use of the capacitive
effect of a breaker bushing to produce a capacitive voltage
divider. The BPD reduces the primary voltage to a medium
voltage level, e.g. 4 kV, which is applied to a transformer to
produce the secondary potentials of 115 and 66 volts.
5
Voltage Peak: SOLID-ratio voltage, DASH-secondary Voltage Peak: SOLID-ratio voltage, DASH-secondary
1 1
0.5 0.5
volt
volt
0 0
-0.5
-0.5
-1
-1 -0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
0.5
0.5
volt
0
volt
-0.5
-0.5
-1
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
-1
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06 seconds
seconds
Fig. 16 BPD response for burden of VA=5 and pf=1.0 with exact pf Fig. 19 BPD response for burden of VA=30 and pf=0.7 with exact pf
compensation compensation
1
Voltage Peak: SOLID-ratio voltage, DASH-secondary C. Parameters That Affect BPD Transient Performance
• Burden: Inductive burdens result in worst transient
0.5
performance.
• Transformer Ratio: A low step-down transformer ratio
volt
Voltage Zero, VA=30.0; pf=1.0 lagging power factor burden with capacitor Cpf will
improve the transient performance.
1
-1
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
boundary faults.
seconds
D. Utility BPD Performance
Fig. 17 BPD response for burden of VA=30 and pf=1.0 with exact pf
compensation Two examples are provided demonstrating BPD
performance. The first case involves a relaying system
Voltage Peak: SOLID-ratio voltage, DASH-secondary
1 consisting of both numerical and electromechanical relays
0.5
resulting in a high burden, 10 ohms at 65% power factor. The
protected line is 40 miles long with an SIR of 5.8. A ground
volt
0
fault occurs 64% from a station. The large and slow decaying
-0.5 BPD transient results in an underreach for this fault as shown
-1
in Fig. 20 and Fig. 21.
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
0.5
volt
-0.5
-1
-0.02 -0.01 0 0.01 0.02 0.03 0.04 0.05 0.06
seconds
Fig. 18 BPD response for burden of VA=5 and pf=0.7 with exact pf
compensation
6
50
2
volt
-50 1.5
Im-ohm
-100
0 2 4 6 8 10 12
1
10
0.5
5
amp
0 0
-10
0 2 4 6 8 10 12 Fig. 23 C-A phase apparent impedance
cycle
E. Mitigation of CCVT and BPD Subsidence Transient
Fig. 20 Voltage and current for a C-phase fault at 64% of line length
The characteristic of the CCVT and BPD subsidence
18
C-Phase Apparent Impedance
transient is a reduction in fundamental voltage for a few
cycles. This will result in a Zone 1 distance relay overreach
16
for remote terminal faults. The preferred mitigation to apply
14
depends on the fault clearing requirements of the transmission
12 system. If the system can tolerate a few cycles for fault
10
detection, then time delay the Zone 1 output by up to two
cycles. However, for the system with stringent fault clearing
Im-ohm
8
times, the Zone 1 relay reach should be reduced based on the
6 chart shown in Fig. 24. Fig. 24 is obtained using typical
4
passive and active CCVTs with a resistive burden of 5 kΩ,
representative of the load of several modern microprocessor
2
relays and meters.
0 1
-4 -3 -2 -1 0 1 2 3 4 5 6
0.9
Re-ohm
0.8
Fig. 21 Apparent impedance of a C-phase fault at 64% of line length
max. zone 1 reach setting (pu)
0.7
The second case involves all numerical relays presenting a
Passive CCVT
3-mile line with a SIR of 1.87, trips when a clamp fails, 0.5
structure one station beyond the remote end bus. The resulting 0.3 Active CCVT
transient impedance lies within the Zone 1 reach due to the 0.2
50
Fig. 24 Distance element performance as function of source impedance ratio
-50
developed to deal with the transient overreach concerns from
-100
-150
CCVT transients. The system impedance ratio (SIR) is
0 2 4 6 8 10 12
estimated from the fault voltage and current, when this value
100
is high and causes a concern of overreach, a time delay is
added to the instantaneous tripping distance elements. The
50
fault impedance is then closely monitored to detect any CCVT
transient signatures. Therefore, on the detection of a high SIR,
amp
-50
the relay applies the Zone 1 delay and monitors the voltage
transient. If the transient signature is small and does not
-100
0 2 4 6
cycle
8 10 12 indicate overreach, the time delay is quickly removed to allow
a quicker operation of the elements. The logic adapts to the
Fig. 22 C-A phase voltage and current quality of the CCVT used and only adds time delay when
necessary.
7
A. CT Saturation 10
amp
magnitude and a leading phase shift. This error will cause -10
pu
-10
4
-20
2
-30
-3 -2 -1 0 1 2 3 4 5 6 7 0
-3 -2 -1 0 1 2 3 4 5 6 7
cycle
Distance Calculations: SOLID-Using CT Output, DASH-Using Ratio Current
10
Fig. 28 CT output and distance measurement with 6.3 ms to saturation
8
Currents: SOLID-CT Output, DASH-Ratio
6 20
pu
4 10
2 0
amp
0 -10
-3 -2 -1 0 1 2 3 4 5 6 7
cycle
-20
10
8
0
amp
6
pu
-10
4
-20
2
-30
-3 -2 -1 0 1 2 3 4 5 6 7 0
-3 -2 -1 0 1 2 3 4 5 6 7
cycle
Distance Calculations: SOLID-Using CT Output, DASH-Using Ratio Current
10
Fig. 29 CT output and distance measurement with 4.5 ms to saturation
8
Currents: SOLID-CT Output, DASH-Ratio
6 20
pu
4 10
2 0
amp
0 -10
-3 -2 -1 0 1 2 3 4 5 6 7
cycle
-20
6
pu
-10
4
-20
2
-30
-3 -2 -1 0 1 2 3 4 5 6 7 0
-3 -2 -1 0 1 2 3 4 5 6 7
cycle
Distance Calculations: SOLID-Using CT Output, DASH-Using Ratio Current
10
Fig. 30 CT output and distance measurement with 3.3 ms to saturation
8
6
pu
0
-3 -2 -1 0 1 2 3 4 5 6 7
cycle