The settings data of 7SD522 87L protectio n to Relay 1(local relay) and Relay 2 (remote relay)

,
for instance:
For 7SD5/6 series,

ID = IRel 1 + IRel 2,
IS = IRESTRAINT + RTC error + Sinc error ≈ Idiff> + ε1 IRel 1 + ε2 * IRel 2 + 1,4% * In

Idiff> = Setting value of parameter 1210;


ε1 = depending on the Amount of IRel 1 : Parameter 0253 or 0254 of Relay 1
ε2 = depending on the Amount of IRell 2 : Parameter 0253 or 0254 of Relay 2

Interesting settings:

Setting Relay 1 Relay 2


0205 1000A 1000A
0206 1A 1A
0251 1.00 1.00
0253 5.0% 5.0%
0254 15.0% 15.0%
1210 (Idiff>) 0,3A 0,3A

About Slope 1 and Slope 2:

0251 settings (k_alf/k_alf nominal) *In = 1 * 1 A = 1 A

When the current injected to 7SD52 is sm ller than 1A, parameter 0253 is used – Slope 1;
When the current injected to 7SD52 is larg er than 1A, parameter 0254 is used – Slope 2;
Examples:
1. Slope 1 – check Istab calculated X measured:

When current line is 800 A in primary side,in secondary side is:

IRelay1 = 800*1/1000 = 0,8 A,

IRelay2 = 800*1/1000 = 0,8 A,

Istab calculated at relay 1 or 2:

 Differential current: ID = 0 A
Stab current: IStab = 0,3 + 0,05*0,8 + 0,05*0,8 + 1,4% * 1 A = 0,394 A, or
•IStab(%) = 0 ,394A/1A*100 = 39,4%

Test when injected 0,8 A, only in A phase measured value is:


OBS**** : Even with the current B or C = 0A, this value (31,4%) stabilization is appearing.
Why? Because: Istab = 0,3+0*0,05+0*0,0 +0,014*1 = 0,314 A, or 0,314/1*100 =31,4%

2. Slope 2 – check Istab calculated X measured:

When current line is 2.000 A in primary sid e, in secondary side is:

IRelay1 = 2000*1/1000 = 2 A,

IRelay2 = 200*1/1000 = 2 A,

Measuring expected at relay 1 or 2:

 Differential current: ID = 0 A
Stab current: IStab = 0,3 + 0,15*2 + 0,15*2 + 1,4% * 1 A = 0,914 A
• IStab(%) = 0 ,914A/1A*100=91,4%

Test when injected 2 A, only in A phase –measured value:


3. Trip Test: