Legend SITE TEST REPORT DATE :
CSD AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 1 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

1- GENERAL DATA AND INFORMATION.

Panel No: Designation

Make AREVA Rated current 1/5 A


Serial No: Aux: Voltage 110-250VDC/ 100-240VAC
Model No: MICOM P54631AA6M0570K Rated Voltage 125 VDC
Application DIFF. WITH DIST & DEF PROTN Software version
CT Ratio 1500/1 PT Ratio 115/√3kV/115/√3V

2- MECHANICAL CHECK AND VISUAL INSPECTION:


For Mechanical Check/Visual Inspection Use CL-NG-6460-002-056

3- ELECTRICAL TEST:
For Electrical Test Use CL-NG-6460-002-057

3.1- Function Test: With relay energized condition

ITEM DESCRIPTION CHECKED


1 Watchdog contacts (M11-M12 open, M13-M14 closed)
Set Clock to local time
2 Date & time
Time maintained when Aux. Supply removed
Make Test Mode Enable under commissioning menu to check ALARM LED
3
(Yellow)
Make Test Mode Enable under commissioning menu to check OUT OF SERVICE
4
LED (Yellow)
5 Apply any fault condition to check TRIP LED (Red)
6 Apply Test LEDs under commissioning menu to check all 8 programmable LEDs.
Measured FIELD SUPPLY Between terminals M7 – M9
7
Voltage Between terminals M8 – M10
8 Disturbance report check
9 DC loss test

3.2- INPUT OPTO-ISOLATORS CHECKS:

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 2 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
Go to Commissioning Test, Test mode (test mode), then go to system data column to check the Status of the binary
inputs.

V DC Applied Terminal No.


OPTO Input RESULT
Remarks
No. +Ve Terminal No. -Ve Terminal No. Display 0 to 1

OPTO-1 E2 E1 Spare
OPTO-2 E4 E3 Spare
OPTO-3 E6 E5 Spare
OPTO-4 E8 E7 Spare
OPTO-5 E10 E9 Spare
OPTO-6 E12 E11 Spare
OPTO-7 E14 E13 Spare
OPTO-8 E16 E15 Spare
OPTO-9 C2 C1 Spare
OPTO-10 C4 C3 Spare
OPTO-11 C6 C5 Spare
OPTO-12 C8 C7 Spare
OPTO-13 C10 C9 Spare
OPTO-14 C12 C11 Spare
OPTO-15 C14 C13 Spare
OPTO-16 C16 C15 Spare
OPTO-17 G2 G1 Spare
OPTO-18 G4 G3 Spare
OPTO-19 G6 F5 Spare
OPTO-20 G8 G7 Spare
OPTO-21 G10 G9 Spare
OPTO-22 G12 G11 Spare
OPTO-23 G14 G13 Spare
OPTO-24 G16 G15 Spare

3.3- OUTPUT RELAYS CHECKS (With Relay Energized):


Note: Go to Commissioning Test, Test mode (blocked), Test Pattern mode and select each relay
To be tested and Apply Contact Test, after test; apply remove test to de-energized the relay.

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 3 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

Output
Output Contact No. Output relay status Remarks
Relay No.
RL1 L1 – L2 Spare
RL2 L3 – L4 Spare
RL3 L5 – L6 Spare
RL4 L7 – L8 Spare
RL5 L9 – L10 Spare
RL6 L11 – L12 Spare
RL7 L13 – L14 – L15 Spare
RL8 L16 – L17 – L18 Spare
RL9 K1 – K2 Spare
RL10 K3 – K4 Spare
RL11 K5 –K6 Spare
RL12 K7 – K8 Spare
RL13 K9 – K10 Spare
RL14 K11 – K12 Spare
RL15 K13 – K14 – K15 Spare
RL16 K16 – K17 – K18 Spare
RL17 J1 – J2 Spare
RL18 J3 – J4 Spare
RL19 J5 – J6 Spare
RL20 J7 – J8 Spare
RL21 J9 – J10 Spare
RL22 J11 – J12 Spare
RL23 J13 – J14 – J15 Spare
RL24 J16 – J17 – J18 Spare
RL25 H1 – H2 Spare
RL26 H3 – H4 Spare
RL27 H5 – H6 Spare
RL28 H7 – H8 Spare
RL29 H9 – H10 Spare
RL30 H11 – H12 Spare
RL31 H13 – H14 – H15 Spare
RL32 H16 – H17 – H18 Spare

4- MEASURMENTS CHECK:
4.1- CURRENT INPUTS CHECK: (TS-1)

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 4 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
DISPLAYED SECONDARY DISPLAYED
APPLIED CT RATIO
INPUT CURRENT VALUE PRIMARY VALUE
VALUE (A) APPLIED
(A) (A)
IA 1
IB 1 1200/1
IC 1

4.2- CURRENT INPUTS CHECK: (TS-2)


DISPLAYED SECONDARY DISPLAYED
APPLIED CT RATIO
INPUT CURRENT VALUE PRIMARY VALUE
VALUE (A) APPLIED
(A) (A)
IA NA NA NA
IB NA NA NA NA
IC NA NA NA

4.3 VOLTAGE INPUTS CHECK:


APPLIED DISPLAYED SECONDARY
INPUT VT RATIO DISPLAYED PRIMARY VALUE
VALUE VALUE
VOLTAGE APPLIED (KV)
(V) (V)
VAB 115
VBC 115
VCA 115 115/√3 kV/
VA 66.4 115/√3 V
VB 66.4
VC 66.4

5- SETTING CHECK:
Ensure all the settings are applied for used functions and printout the enclosed setting [ ok ].

6- DISTANCE FUNCTION CHECK:


6.1- IMPEDANCE REACH CHECK:

Item Description Checked


1 Print out from FREJA attached
Impedance tolerance: +/- 10 % for all zones.

6.2- OPERATING TIME TESTING:

Item Description Checked


1 Print out from FREJA attached

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 5 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

6.3 VTS FUNCTION TEST:

Setting:
VTS time delay = 5.0 Sec
VTS I> inhibit = 1.0 A
VTS I2> inhibit = 0.05 A

6.3.1 Loss of one or two phases test: (Under load Condition)


Fixed setting: V2 = 10 volt, I2> inhibit less than setting.
Set Time Measured Time
Phase Pick up Drop Of V2 = 10V
(sec) (Sec)
AN
BN
CN
5.0
AB
BC
CA

 Measured VTS I2> inhibit = mA


6.3.2 Loss of all 3 phase voltages: (Under load condition test)
Fixed Setting: a- for fuse fail pick up; V1=10 volts.
b- for fuse fail reset; V1=30 volts.

Pick up measurement
Reset measurement voltage(v)
voltage(v)

6.3.3 Absence of 3 phase volts on line Energization test :

1. Apply 3 phase current less than VTS I> inhibit with no volts and Check no tripping [ ok ]
2. Apply 3 phase current greater than VTS I> inhibit with no volts and Check zone 1 tripping occurred [ ok ]
3. Measured VTS I> = 0.997 A
4. Check the relay blocking from the external fuse fail [ ok ]

6.4 SOTF TEST:

SETTING:

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 6 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

-SOTF active with

-SOTF delay = sec.


-TOC reset delay = sec
-Close Pulse = msec

Setting: All Zones Enabled


Apply fault condition and same time apply CB close command within the time set in TOC Reset Delay, relay will be
tripped by SOTF. If CB close command after TOC time then relay will be tripped zone trip.

Measured Time
SOTF IN Internal detection External detection
(m sec) (m sec)
Zone 1
Zone 2
Zone 3
Zone p
Zone 4
CNV

 Measured SOTF delay time = Sec.


 Measured TOC reset delay = Sec.
 Measured Close Pulse = mSec

6.5 POWER SWING BLOCKING TEST:


Setting
PSB unblock time delay = Sec.
PSB reset delay = mSec.

a) Check the power swing blocking for Zones 1, 2, 3, P, 4 [ ok ].

Item description Setting time Measured time Remark


Z1 Z2 Z3 Z4
PSB unblock time 5.0

PSB reset time 1.0


6.6 Scheme Communication Logic:

Setting:

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 7 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
 Aid Dist delay = 0 m sec
 Unblocking delay = 100 m sec
 TRev Guard = 100 m sec

6.6.1 Permissive Under Reach Scheme:

Send Logic : CS=ZM1 : _____ok_______


Trip Logic : Trip=ZM2+CR : _____ok_______
Trip without CR : __________ ___ m Sec.
Trip with CR : ______________m Sec.
Time Send : ______________m Sec.
6.6.2 Permissive Under Reach unblocking scheme:

Send logic : CS = ZM1 : _____ok_______


Trip Logic : Trip=ZM2+CR : _____ok_______
Trip without CR : Trip=ZM2 : ___________ _ m Sec.
Trip : Trip = ZM2 + CR+LGS : ______________m Sec.
Trip (delay) :Trip = ZM2 + LGS : ____ _________m Sec.
Time Send : ______________m Sec.
6.6.3 Permissive Over Reach Scheme:

Send Logic : CS=ZM1&ZM2 : _____ok_______


Trip Logic : Trip=ZM2+CR : _____ok_______
Trip without CR : __________ __ m Sec.
Trip with CR : ______________m Sec.
Time Send : ______________m Sec.
6.6.4 Permissive Over Reach unblocking scheme:

Send logic : CS = ZM1&ZM2 : _____ok_______


Trip Logic : Trip=ZM2+CR : _____ok_______
Trip without CR : Trip=ZM2 : ___________ __ m Sec.
Trip : Trip = ZM2 + CR+LGS : _______________m Sec.
Trip (delay) : Trip = ZM2 + LGS : ____ ___________m Sec.
Time Send : _______________m Sec.
6.6.5 Blocking 1 Scheme:
Send logic : CS = ZM4 : _____ok_______
Trip logic : Trip = ZM2 +NO CR : _____ok_______
Trip without CR : ______________m Sec.
Trip with CR : _________ __ m Sec.
Time Send : ______________m Sec

6.6.6 Blocking 2 Scheme:

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 8 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
Send logic : CS = ZM4 : _____ok_______
Trip logic : Trip = ZM2 +NO CR : _____ok_______
Trip without CR : ______________m Sec.
Trip with CR : __________ __ m Sec.
Time Send : ______________m Sec.

6.6.7 Weak End Infeed Echo (Permissive over reach Scheme):

 Apply a short pulse to DIST Channel Receive Input Without any fault Injection and check Channel send is
given: [ ok ]

 Operating time: m sec

6.6.8 Weak End Infeed Trip (Permissive over reach Scheme):

Setting
WI V< V thresh = 45.0 V
WI trip delay = 0.5 Sec.

phase U ph setting U ph measured (V)


Remark
(V)
R
S 45
T

 Measured WI Trip time = 517.0 m sec

6.6.9 Current Reversal Logic Check (Permissive Over Reach Scheme):


 Apply a reverse / forward fault to check: t rev guard:

Fault type t rev guard setting (m sec) t rev guard measured (m sec)
Reverse/ forward 100

7- Over Current Protection:


7.1.1 OVER CURRENT PROTECTION (NON DIRECTIONAL) STAGE 1

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 9 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
PHASE SETTING (A) PICK UP (A) DROP OFF (A)
A
B 0.5
C
7.1.2 OVER CURRENT PROTECTION (NON DIRECTIONAL) STAGE 2

PHASE SETTING (A) PICK UP (A) DROP OFF (A)


A
B 1.0
C
7.1.3 OVER CURRENT PROTECTION (NON DIRECTIONAL) STAGE 3

PHASE SETTING (A) PICK UP (A) DROP OFF (A)


A
B 1.5
C

7.1.4 OVER CURRENT PROTECTION (NON DIRECTIONAL) STAGE 4

PHASE SETTING (A) PICK UP (A) DROP OFF (A)


A
B 2.0
C

7.1.5 OPERATING TIME STAGE (1&2)

TMS=1.0
CAL TIME MEASURED TIME
CURVE LIMIT
@ 3* IS PHASE Stage 1 Stage 2
IEC standard inverse 6.3 A 5.98 – 6.62
IEC very inverse 6.75 B 6.46 – 7.14
IEC ext. inverse 10 C 9.5 – 10.5
UK long time inverse 60 A 57 – 63
IEEE mode inverse 2.43 C 2.28 – 2.52
IEEE very inverse 2.94 A 2.75 – 3.05
IEEE ext .inverse 3.65 B 3.51 – 3.89
US inverse 0.924 C 0.87 – 0.97
US shot time inverse 7.66 A 7.31 – 8.08
Definite time 1.0 B 0.95 – 1.05

7.1.6 OPERATING TIME STAGE (3&4)

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 10 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

Setting (Sec.) Measured (Sec.)


Phase
Stage 3 Stage 4 Stage 3 Stage 4
A
B 0.5 0.1
C

7.2 DIRECTIONAL OVER CURRENT


7.2.1 CURRENT SENSITIVITY TEST

Current measured
Phase RCA setting Voltage applied Current setting
Pickup Drop of
A
B 30⁰ 115 V 0.5 A
C

7.2.2 OPERATION ANGLE BOUNDARY LIMIT (FORWARD DIRECTION)

Phase angle pickup


RCA Voltage Current Current
Phase From To
setting applied setting Applied
Pickup Drop of Pickup Drop of
A
B 30⁰ 115 V 0.5 A 0.6 A
C

7.2.3 OPERATION ANGLE BOUNDARY LIMIT (REVERSE DIRECTION)

Phase angle pickup


RCA Voltage Current Current
Phase lead Lag
setting applied setting Applied
Pickup Drop of Pickup Drop of
A
B 30⁰ 115 V 0.5 A 0.6 A
C

8- EARTH FAULT PROTECTION (NON DIRECTION)

8.1.1 EARTH FAULT STAGE 1

SETTING (A) PICKUP (A) DROPOFF (A)


0.2

8.1.2 EARTH FAULT STAGE 2

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 11 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
SETTING (A) PICKUP (A) DROPOFF (A)
0.4

8.1.3 EARTH FAULT STAGE 3

SETTING (A) PICKUP (A) DROPOFF (A)


1.0

8.1.4 EARTH FAULT STAGE 4

SETTING (A) PICKUP (A) DROPOFF (A)


1.5

8.1.5 OPERATING TIME STAGE (1&2)

TMS=1
CAL TIME MEASURED TIME LIMIT
CURVE
@ 3* IS Stage 1 Stage 2
IEC standard inverse 6.3 5.98 – 6.62
IEC very inverse 6.75 6.46 – 7.14
IEC ext. inverse 10 9.5 – 10.5
UK long time inverse 60 57 – 63
IEEE mode inverse 2.43 2.28 – 2.52
IEEE very inverse 2.94 2.75 – 3.05
IEEE ext .inverse 3.65 3.51 – 3.89
US inverse 0.924 0.87 – 0.97
US shot time inverse 7.66 7.31 – 8.08
Definite time 1.0 0.95 – 1.05

8.1.6 OPERATING TIME STAGE (3&4)

Setting (Sec.) Measured (Sec.)


Stage 3 Stage 4 Stage 3 Stage 4
0.1 0.0

8.2 DIRECTIONL EARTH FAULT PROTECTION

8.2.1 CURRENT SENSITIVITY TEST

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 12 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

Current measured
RCA setting Voltage applied Current setting
Pickup Drop of
60⁰ 115 V 0.2 A

8.2.2 OPERATION ANGLE BOUNDARY LIMIT (FORWARD DIRECTION)

Phase angle
Voltage Current Current
RCA setting From To
applied setting Applied
Pickup Drop of Pickup Drop of
60⁰ 115 V 0.2 A 0.3 A

8.2.3 OPERATION ANGLE BOUNDARY LIMIT (REVERSE DIRECTION)

Phase angle
Voltage Current Current
RCA setting lead Lag
applied setting Applied
Pickup Drop of Pickup Drop of
60⁰ 115 V 0.2 A 0.3 A

8.2.4 POLARIZING VOLTAGE Vn (3V0) PICKUP AND DROP OFF TEST

Vn (3V0) measured
Vn (3V0) setting
Pick up Drop of
5V

Check the directional earth fault blocking from the fuse fail function [ OK ]
9. Fault Locator Function:
Line Length: 100 km Line Impedance: 10 Ω ФL: 85⁰
Fault Type Fault Impedance () Expected display (%) Actual display (kM)
A-N 2.5 25
B-N 5.0 50
C-N 7.5 75
A-B 2.5 25
B-C 5.0 50
C-A 7.5 75
A-B-C 10.0 100

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 13 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
10. Residual over voltage:

Stage 1
Phase Setting Pick up Drop of Time Setting Measured
(V) (V) (V) (Sec) (Sec.)
A
B 5.0 5.0
C

Stage 2
Phase Setting Pick up Drop of Time Setting Measured
(V) (V) (V) (Sec) (Sec.)
A
B 10.0 10.0
C

AIDED DEF TEST (INSTANTANEOUS)

Settings:

Vn> (3Vo) = 1.0 V

IN >FW (3Io) = 500 mA Polarization = Zero sequence

IN >RV (3Io) = 200 mA RCA: -60 degree

DEF Start DEF Reset Boundary Angle Limit


Injection Angle
(mA) (mA) From To
FWD
-60⁰
REV

POLARIZING VOLTAGE (3V0) PICKUP AND DROP OFF TEST:


Note:
 Apply 3phase volts healthy voltage inject only one phase current for this test to the phase under test and
reduce voltage of phase under test.
 Vo=Vn/3= (Va+Vb+Vc)

Vn(3V0) setting Vn (3V0) measured (V)


(V) Pick up Drop of
1.0

11- SCHEME TEST:

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 14 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

11.1.1 DEF Scheme:


 Aid DEF delay = 100 m sec

Scheme: permissive over reach


Send Logic : Forward Fault : _____ok_______
Trip Logic : Forward Fault + CR : _____ok_______
Trip Time Measured with CR : ______________ m Sec
Trip Time Measured without CR : ______________ Sec
Send Time : _______________m Sec

Scheme: blocking 1
Send Logic : Reverse Fault : _____ok_______
Trip Logic : Forward Fault + NO CR : _____ok_______
Trip Time Measured with CR : ______________ Sec
Trip Time Measured without CR : ______________m Sec
Send Time : ______________m Sec

11.1.2 Weak End In feed Echo (Permissive over reach Scheme):

 Apply a pulse to DEF Channel Receive Input Without any fault Injection and check Channel ECHO send is
given: [ ok ]

 Operating time: m sec

11.1.3 Weak End In feed Trip (Permissive over reach Scheme):

Setting
WI V< V thresh = 45.0 V
WI trip delay = 1.0 Sec

V< setting V< measured (V)


Remark
(V)

45

 Measured WI Trip time = Sec

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 15 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

11.1.4Current Reversal Logic Check (Permissive Over Reach Scheme):

 Apply a reverse / forward fault to check: t rev guard:

t rev guard setting t rev guard measured


Fault type Send Time
(m sec) (m sec)
Reverse/ forward 150

12- DIFFERENTIAL TEST

12.1 Current differential bias characteristic (87-1)

Item Description Setting


1 IS1 0.20 A
2 Is2 2.0 A
3 K1 30 %
4 K2 150 %
5 T 0 Sec

12.2 Pick-up test


I min = 1s1/ (1-0.5k1) x 0.5

Actual Trip Time


Fault Expected Pickup Actual Pickup Drop-off Expected Trip Time
in m-sec at 2
Type In Amp In Amp In Amp in m-sec
x I Pickup
A-N 0.118 A <40 ms
B-N 0.118 A <40 ms
C-N 0.118 A <40 ms

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 16 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

12.3Lower slope test (Injected current < Is2)


I Diff I > (k1 * I + Bias + Is1)/2 = 0.25 A
Bias current Differential current Expected Measured value
Actual Trip
Injected in inject differential current of diff. current Expected Trip
Time
Phase (Amps) in phase for tripping (Amp) Time
in m-sec at
(Amp) in m-sec
2 x I Pickup
A B C A B C
1.0 X 0.25 A <40 ms
1.0 X 0.25 A <40 ms
1.0 X 0.25 A <40 ms
12.4Upper slope test (Injected current > Is2)
I Diff I > (K2 * I Bias - (K2-K1) IS2 + IS1
Bias current Differential current Expected Measured
Injected in inject differential current value of Expected Trip Actual Trip Time
Phase (Amps) in phase for tripping diff. current Time in m-sec at
(Amp) (Amp) in m-sec 2 x I Pickup
A B C A B C

3.0 X 1.15 A <40 ms

3.0 X 1.15 A <40 ms

3.0 X 1.15 A <40 ms

12.5 Secondary Injection Local Relay


Single Phase Injection (Local Relay)

Phase Injected Current (A) Remote End Reading

A 1.0 NA

B 1.0 NA

C 1.0 NA

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 17 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

13. CIRCUIT BREAKER FAILURE TEST (50BF)

13.1 CBF Stage-1 CB Trip:


Set Current Current measured
(mAmp) Pickup Drop off

Pick-up +/- 10% or 0.025 In, whichever is greater

13.2 Timing Test:


CB1 I< SETTING(A) SET TIME(mS) TRIP TIME (mSec)

+/- 2 ms or 2%, whichever is greater


* Initiation by EXTERNAL (applied pulse to opto input)

14. Synch Check Test

14.1Synchro-Check Voltage check

Fix U1 at normal voltage and change U2.

MEASURED VOLTAGE U2
SETVALUE APPLIED PICK-UP Fix U2 at
Errors %
DU % (V) VOLTAGE U1 Voltage (V) normal
+DU -DU
+U -U +DU % +DU % voltage
and
6.5 66.4 change
10.0 66.4 U1.

MEASURED VOLTAGE U1
SETVALUE APPLIED PICK-UP
Errors %
DU % (V) VOLTAGE U2 Voltage (V)
+DU -DU
+U -U +DU % +DU %
6.5 66.4
10.0 66.4

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 18 of 19
LINE DIFFERENTIAL RELAY – MICOM P546

14.2 Synchro-Check Frequency Check

Fix U1 at normal frequency and change frequency of U2.

PICK-UP Df
Df (U2) LIMITS
+f -f +Df -Df
50mHz 45 – 50 mHz
Fix U2 at normal
frequency and change frequency of U1.

PICK-UP Df
Df (U1) LIMITS
+f -f +Df -Df
50mHz 45 – 50 mHz

14.3 Synchro-Check Phase Angle Check

Fix U1at zero reference phase angle and change phase angle of U2.

SET ANGLE DIFFERENCE (U2) Errors %


VALUE + Angle - Angle +D Angle -D Angle +D Angle -D Angle
10
20

Fix U2 at zero reference phase angle and change phase angle of U1.

SET ANGLE DIFFERENCE (U1) Errors %


VALUE + Angle - Angle +D Angle -D Angle +D Angle -D Angle
10
20

14.4Voltage Check Function test

Set U1 =66.4V, U2 =66.4V, f1 and f2 = 60Hz.


LB/DL ________________ [ ]
LL/DB ________________ [ ]
LB/LL ________________ [ ]

14.5VOLTAGE CHECK TEST


Function: LL/DB
LL=

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :
SITE TEST REPORT DATE :

AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 19 of 19
LINE DIFFERENTIAL RELAY – MICOM P546
DB=

Function: DL/LB
DL=
LB=

15. Auto Reclose Test

15.1Dead time measurement

Dead time 1 sec Dead time 2 sec Dead time 3 sec


Set time Meas. time Set time Meas. time Set time Meas. time

15.2Reclaim time measurement

Set time sec Measured Time sec

TEST EQUIPMENTS
Type: Freja 300
Type: Digital Multimeter
Type: Timer

DATE:
TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name : Name :