Section bar on edge in Still air. Area (A) = 125 x 6 =750 sq.mm. Perimeter (P) = 2 x (125 + 6) = 262 mm. By Emperical Formula : Current I dc = 7.73.A 0.5 x P 0.39 Where I dc -Current in amperes. A - Area in Sq. mm. P - Perimeter in mm. Therefore I dc = 7.73 x (750)0.5 x (262) 0.39 = 1857 Amps.
For AC. Rating of Copper Busbar :
The Skin effect ratio for Flat bar of 125 x 6 for 50 hz. Ac. = 1.221 Divide DC Rating by appropriate value of = √1.12 = 1.10 Therefore AC. Rating I ac I dc √ (R"/R) = 1857/1.10 = 1688 Amps.
For AC. Laminated bars in still air :
The multiplying factor for 4 bars is = 3.2 Hence I ac = 3.2 x 1688 = 5401 Amps.
Multiplying factor for Magnetic Enclosure = 0.85
Current after derating for Magnetic Enclosure= 5401 x 0.85 = 4591 Calculations were so far made for temperature rise of 50o C. Multiplying Factor for Temperature rise of 40oC. = 0.887 Therefore, I ac for Laminated busbar, inside the magnatic enclosure, for Temperature rise of 40°C. Is = 0.887 x4591 = 4072 AMPS.