Академический Документы
Профессиональный Документы
Культура Документы
ANSI/ISA-61241-1 (12.10.03)-2006
ISBN: 978-1-934-394-02-1
Copyright © 2006 by ISA. All rights reserved. Not for resale. Printed in the United States of
America. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted in any form or by any means (electronic mechanical, photocopying, recording, or
otherwise), without the prior written permission of the Publisher.
ISA
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, North Carolina 27709
-3- ANSI/ISA-61241-1 (12.10.03)-2006
Preface
This preface, as well as all footnotes and annexes, is included for information purposes and is
not part of ANSI/ISA-61241-1 (12.10.03)-2006.
This document has been prepared as part of the service of ISA toward a goal of uniformity in the
field of instrumentation. To be of real value, this document should not be static but should be
subject to periodic review. Toward this end, the Society welcomes all comments and criticisms
and asks that they be addressed to the Secretary, Standards and Practices Board; ISA; 67
Alexander Drive; P. O. Box 12277; Research Triangle Park, NC 27709; Telephone (919) 549-
8411; Fax (919) 549-8288; E-mail: standards@isa.org.
The ISA Standards and Practices Department is aware of the growing need for attention to the
metric system of units in general, and the International System of Units (SI) in particular, in the
preparation of instrumentation standards. The Department is further aware of the benefits to
USA users of ISA standards of incorporating suitable references to the SI (and the metric
system) in their business and professional dealings with other countries. Toward this end, this
Department will endeavor to introduce SI-acceptable metric units in all new and revised
standards, recommended practices, and technical reports to the greatest extent possible.
Standard for Use of the International System of Units (SI): The Modern Metric System, published
by the American Society for Testing & Materials as IEEE/ASTM SI 10-97, and future revisions,
will be the reference guide for definitions, symbols, abbreviations, and conversion factors.
It is the policy of ISA to encourage and welcome the participation of all concerned individuals
and interests in the development of ISA standards, recommended practices, and technical
reports. Participation in the ISA standards-making process by an individual in no way constitutes
endorsement by the employer of that individual, of ISA, or of any of the standards, recommended
practices, and technical reports that ISA develops.
EVEN IF ISA IS UNAWARE OF ANY PATENT COVERING THIS DOCUMENT, THE USER IS
CAUTIONED THAT IMPLEMENTATION OF THE DOCUMENT MAY REQUIRE USE OF
TECHNIQUES, PROCESSES, OR MATERIALS COVERED BY PATENT RIGHTS. ISA TAKES
NO POSITION ON THE EXISTENCE OR VALIDITY OF ANY PATENT RIGHTS THAT MAY BE
INVOLVED IN IMPLEMENTING THE DOCUMENT. ISA IS NOT RESPONSIBLE FOR
IDENTIFYING ALL PATENTS THAT MAY REQUIRE A LICENSE BEFORE IMPLEMENTATION
OF THE DOCUMENT OR FOR INVESTIGATING THE VALIDITY OR SCOPE OF ANY PATENTS
BROUGHT TO ITS ATTENTION. THE USER SHOULD CAREFULLY INVESTIGATE RELEVANT
PATENTS BEFORE USING THE DOCUMENT FOR THE USER’S INTENDED APPLICATION.
HOWEVER, ISA ASKS THAT ANYONE REVIEWING THIS DOCUMENT WHO IS AWARE OF
ANY PATENTS THAT MAY IMPACT IMPLEMENTATION OF THE DOCUMENT NOTIFY THE
ISA STANDARDS AND PRACTICES DEPARTMENT OF THE PATENT AND ITS OWNER.
THE USER OF THIS DOCUMENT SHOULD BE AWARE THAT THIS DOCUMENT MAY BE
IMPACTED BY ELECTRONIC SECURITY ISSUES. THE COMMITTEE HAS NOT YET
ADDRESSED THE POTENTIAL ISSUES IN THIS VERSION.
NAME COMPANY
NAME COMPANY
This standard was approved for publication by the ISA Standards and Practices Board on 24 July 2006.
NAME COMPANY
CONTENTS
Foreword.............................................................................................................................. 9
1 Scope .......................................................................................................................... 11
2 Normative references ................................................................................................... 11
3 Terms and definitions ................................................................................................... 12
4 Construction ................................................................................................................ 12
5 Practice A and practice B ............................................................................................. 12
6 Supplementary rRequirements for electrical apparatus protected by enclosures for
practice A for use in zones 20, 21 and 22 ..................................................................... 12
6.1 General............................................................................................................... 12
6.2 Joints .................................................................................................................. 13
7 Supplementary rRequirements for electrical apparatus protected by enclosures for
practice B for use in zone 20 or 21 or 22....................................................................... 14
7.1 General............................................................................................................... 14
7.2 Joints .................................................................................................................. 14
7.3 Operating rods, spindles or shafts ....................................................................... 16
7.4 Clearance of bolts ............................................................................................... 17
8 Verification and tests .................................................................................................... 18
8.1 General............................................................................................................... 18
8.2 Type tests ........................................................................................................... 18
9 Marking........................................................................................................................ 20
Annex A U.S. major deviations............................................................................................ 21
Bibliography ....................................................................................................................... 23
Foreword
st
All text of IEC 61241-1:2004 (1 edition) is included. U.S. National Deviations are shown by
strikeout through text deleted and underline under text added. There is one annex in this
standard. It is informative and is not considered part of this standard.
This page intentionally left blank.
- 11 - ANSI/ISA-61241-1 (12.10.03)-2006
1 Scope
This part of IEC 61241 standard is applicable to electrical apparatus protected by enclosures and
surface temperature limitation for use in areas where combustible dust may be present in
quantities which could lead to a fire or explosion hazard explosive dust atmospheres classified
as zone 21 or zone 22 hazardous locations in accordance with Article 506 of the NEC ® . It
specifies requirements for design, construction and testing of electrical apparatus.
The ignition protection is based on the limitation of the maximum surface temperature of the
enclosure and on other surfaces which could be in contact with dust and on the restriction of dust
ingress into the enclosure by the use of "dust-tight" or "dust-protected" enclosures.
The application of electrical apparatus in atmospheres which may contain explosive gas as well
as combustible dust, whether simultaneously or separately, requires additional protective
measures.
Where the apparatus has to meet other environmental conditions, for example, protection against
ingress of water and resistance to corrosion, additional methods of protection may be necessary.
The method used should not adversely affect the integrity of the enclosure.
This standard does not apply to dusts of explosives which do not require atmospheric oxygen for
combustion, or to pyrophoric substances.
This standard is not applicable to electrical apparatus intended for use in underground parts of
mines as well as those parts of surface installations of such mines endangered by firedamp
and/or combustible dust.
This standard does not take account of any risk due to an emission of flammable or toxic gas
from the dust.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
IEC 60034-5, Rotating electrical machines – Part 5: Degrees of protection provided by the
integral design of rotating electrical machines (IP code) – Classification
ANSI/ISA-61241-1 (12.10.03)-2006 - 12 -
IEC 61241-0 ANSI/ISA-61241-0, Electrical Apparatus for Use in Zone 20, Zone 21, and Zone 22
Hazardous (Classified) Locations – General Requirements Electrical apparatus for use in the
presence of combustible dust – Part 0: General requirements 1
For the purposes of this document, the terms and definitions given in IEC 61241-0 ANSI/ISA-
61241-0, as well as the following definitions, apply.
3.1
dust ignition protection type “tD”
all relevant measures specified in this standard (e.g. dust ingress protection and surface
temperature limitation) applied to electrical apparatus protected by an enclosure to avoid ignition
of a dust layer or cloud
type of protection for explosive dust atmospheres where electrical apparatus is provided with an
enclosure providing dust ingress protection and a means to limit surface temperatures
4 Construction
If the enclosure of the equipment is in accordance with the requirements of this standard, and all
gaskets preventing the ingress of dust are not stressed by moving parts (e.g. shaft, operating
rod), the enclosure is considered as infallible and the fault analysis is only applicable to the
electrical circuit.
Two different types of practice, A and B, are specified in this standard. Both are intended to
provide an equivalent level of protection.
6.1 General
For apparatus marked for use in zone 21, the tests of 8.2.1.2 for IP6X shall be conducted.
For apparatus marked for use in zone 22, the tests of 8.2.1.3 for IP5X shall be conducted.
– zone 20;
– zone 21;
——————
1 To be published.
- 13 - ANSI/ISA-61241-1 (12.10.03)-2006
At present, there are no additional requirements for practice A to those given in IEC 61241-0
and in this standard.
6.2 Joints
6.2.1 General
All joints in the structure of the enclosure between surfaces, whether permanently closed or
designed to be opened from time to time, shall fit closely together within the tolerances specified
in the documentation. They shall be effectively sealed against the ingress of dust and shall
comply with the following particular requirements:
The length of thread for all screw joints employing parallel threads shall be not less than five
threads.
Hinges shall be clear of joints and shall not be used as a means of obtaining a seal unless they
are provided with facilities for positive location and correct operation is assured; and it is not
possible for damage to occur to either the hinge or enclosure during normal operation and use;
and they are not manufactured from materials that are subject to wear that would affect the
correct operation; and correct compression of the gasket is achieved without causing undue
movement, stress or distortion to the gasket.
Where necessary a suitable register shall be provided for covers and the like to ensure correct
replacement.
Gaskets under compression between joint surfaces may be used to ensure the effectiveness of
the enclosure sealing.
All gaskets shall be of one-piece continuous construction, i.e. with an uninterrupted periphery.
Gaskets, whether of the loose or secured variety, shall be of a form that will provide and
maintain in service a dust-excluding seal between the joint surfaces of the enclosure.
NOTE Unless all gaskets are either cemented or moulded into one face of the jointed surface, the design of the
enclosure should be such that the inspection of the assembly to determine whether gaskets have been fitted correctly
can be made without disturbing the enclosure.
Gasketed joints shall not be supplemented by the application of a sealant material except on one
face only of the joint surfaces.
Gaskets shall be of material that is not subject to appreciable ageing or to plastic flow between
the envisaged maintenance periods as determined by the tests in 8.1 through 8.2.3.
ANSI/ISA-61241-1 (12.10.03)-2006 - 14 -
A flexible seal, e.g. a bellows, shall be such that it is not over-stressed at any point and shall be
protected from external mechanical damage and secured at each end by positive mechanical
means.
• They shall not be used on lids or covers which have to be removed to gain access to field
wiring connections or in-service adjusting facilities.
• The width of a cemented joint shall be equal to or greater than 5 mm.
Openings in enclosures for rods or spindles shall have means, other than grease or compound,
that will prevent the ingress of dust, both when the spindles or rods are in motion and when they
are at rest.
Openings in enclosures for power shafts shall have means, other than grease or compound, that
will prevent the ingress of dust, both when the shafts are in motion and when they are at rest.
6.2.6 Windows
A cemented window shall be cemented either directly into the wall of the enclosure so as to form
with the latter an inseparable assembly, or into a metallic frame such that the assembly can be
replaced as a unit.
A gasketed window may be mounted directly in the wall or cover of the enclosure, no separate
detachable frame being necessary. It shall incorporate a suitable seal or gasket.
7.1 General
For apparatus marked for use in zone 21, the tests of 8.2.1.4 shall be conducted.
For apparatus marked for use in zone 22, the tests of 8.2.1.5 shall be conducted.
7.2 Joints
Plain joints (see Figure 1) shall have a minimum contact width from inside to outside of the
enclosure and a maximum allowable clearance between the surfaces as shown in Table 1.
- 15 - ANSI/ISA-61241-1 (12.10.03)-2006
W
IEC 346/04
Spigotted joints (see Figure 2), which have axial, L, and radial, W, paths neither of which is less
than 1,2 mm, may have diametrical clearances as shown in Table 1 for plain joints. The radial
section, W, of the spigotted joint shall have a maximum allowable clearance, G, as shown in
Table 1 shown for plain joints.
L Part 2
Part 1
I.D. O.D
G
IEC 347/04
For gasketed joints (see Figure 3), requirements are given in Table 2.
ANSI/ISA-61241-1 (12.10.03)-2006 - 16 -
IEC 348/04
For maximum opening dimensions between 305 mm and 915 mm, the effective width of the
gasketed joint shall be increased by 0,003 mm for each millimetre increase in the maximum
opening dimension greater than 305 mm.
7.3.1 General
For apparatus intended for use in zone 20 and 21 and 22, dust exclusion shall not depend on
running contact seals. The equipment shall meet the design details of Tables 3 and 4 and the
tests of 8.2.1 without the running contact seal installed.
If running contact seals are used, the equipment shall meet the design details of Tables 3 and 4
and the dust tests of 8.2.1 without the running contact seals installed.
Power shafts for transmitting power at rotational speeds of 100 r/min or more (see Figure 4),
shall meet the requirements for the length of path from the inside to the outside of the enclosure
as given in Table 3.
- 17 - ANSI/ISA-61241-1 (12.10.03)-2006
D1 D2
L
IEC 349/04
For lengths of path for power shafts between 12,5 mm and 38,5 mm, the maximum diametrical
clearance may be increased by 0,012 mm for each millimetre increase in the length of path
greater than 12,5 mm.
NOTE The minimum length of path may include both the inner and outer lips of the bearing housing.
Operating rods, spindles or shafts having rotary motion of less than 100 r/min or axial motion,
shall have either a threaded joint with three full threads engaging, or have a minimum length of
path from the inside to the outside of the enclosure as given in Table 4.
Minimum length of path for operating rods, spindles or shafts (mm), L 12,5 25,5
Maximum allowable diametrical clearance (mm), D2 – D1 0,13 0,21
For lengths of path for operating rods, spindles or shafts between 12,5 mm and 25,5 mm, the
maximum diametrical clearance may be increased by 0,006 mm for each millimetre length of path
greater than 12,5 mm.
Bolts passing through the enclosure wall shall have a maximum diametrical clearance between
the unthreaded shank of the bolt, N, and the clearance hole in the enclosure, DS-DH, of not more
than 0,26 mm and a length of path, L, of not less than 12,5 mm (Figure 5).
ANSI/ISA-61241-1 (12.10.03)-2006 - 18 -
N
DH
DS
IEC 350/04
8.1 General
In addition to the verification and testing requirements of IEC 61241-0, the following applies.
8.2.1.1 General
In making an assessment for the acceptance of the apparatus following the tests, the effect of
the presence of a combustible dust shall be taken into consideration.
The precautions that shall be taken where a combustible dust is used for the tests is left to the
discretion of the testing authority or others concerned.
The apparatus shall be subjected to the thermal endurance to heat, thermal endurance to cold,
and mechanical tests of ANSI/ISA-61241-0.
EnclosuresFinally, the apparatus, including rotating machines, shall satisfy the requirements for
IP6X, as specified in IEC 60529, or IEC 60034-5 as applicable. The apparatus shall be
considered as belonging to “Category 1 enclosure” as specified in IEC 60529.
- 19 - ANSI/ISA-61241-1 (12.10.03)-2006
The apparatus shall be subjected to the thermal endurance to heat, thermal endurance to cold,
and mechanical tests of ANSI/ISA-61241-0.
All enclosuresFinally, the apparatus, including rotating machines, shall satisfy the test and
acceptance requirements of IP5X, as specified in IEC 60529 or IEC 60034-5 as applicable. For
the purposes of acceptance criteria in accordance with IEC 60034-5, all dusts shall be considered to be
conductive and therefore IP5X shall be assessed against the acceptance criteria of IP6X. The apparatus
shall be considered as belonging to “Category 1 enclosure” as specified in IEC 60529.
a) The apparatus shall be mounted in a test chamber of sufficient size to permit free circulation
of the dust-air mixture around the sample during the test.
A mixture of suitable dust and air shall be circulated by auxiliary equipment and introduced
continuously into the test chamber during the entire test period. The particle size of the dust
shall be such that it passes through a No. 100 ASTM sieve (approximately 0,15 mm mesh
width) with approximately 22 % passing through a No. 200 ASTM sieve (approximately
0,075 mm mesh width).
b) For the test specified above, the apparatus shall be operated at rated load until maximum
temperatures are reached and then disconnected from the supply until it has cooled to
approximately room temperature. The number of cycles of heating and cooling shall be at
least six and shall last for a minimum of 30 h.
NOTE 1 The maximum temperature under load may be obtained by other means than running at rated load. For an
enclosure such as a junction box without any appreciable heating effect (e.g. a switch), the effect of changes in
barometric pressure may be simulated to produce the desired “breathing” effect.
NOTE 2 Heating the chamber to 40 °C and maintaining this temperature for approximately 1 h and subsequently
cooling the chamber to 20 °C and maintaining this temperature for 1 h has been found to be a satisfactory method for
simulating changes in barometric pressure.
When the required number of heating and cooling cycles has been completed, the equipment for
producing the dust-air atmosphere shall be shut off and the accumulated dust shall be removed
from the exterior surfaces of the enclosures by gently brushing, wiping or shaking, with care
being taken to avoid the introduction of additional dust into the enclosures.
Under no circumstances shall the dust be removed by an air blast or by vacuum cleaning.
The enclosure shall then be opened and carefully examined for the degree of dust penetration if
any.
No visible dust shall have entered the enclosure. Dust in joints shall not be considered a failure.
ANSI/ISA-61241-1 (12.10.03)-2006 - 20 -
Proceed as described in 8.2.1.4.1 except the number of cycles of heating and cooling shall be at
least two and for a minimum period of 10 h.
No visible dust shall have entered the enclosure. Dust in joints shall not be considered a failure.
This test shall be carried out in accordance with 23.4.5.1 to 23.4.5.3 of IEC 61241-0 ANSI/ISA-
61241-0 with the additional requirement that the apparatus shall be covered with the maximum
amount of dust that it can retain. As an alternative, a 12,5 mm thick layer of dust paste may be
put on top of the apparatus to simulate the build-up conditions.
NOTE The paste should consist of 45 % dust (e.g. wheat flour) and 55 % water by weight. The temperature value
should be measured after the paste has dried.
A positive pressure of 27 kPa shall be applied to the apparatus for at least 1 minute. During this
test, any breathing or draining device shall be removed and the entry plugged. There shall be no
evidence of damage to the enclosure due to the pressure applied.
9 Marking
29.2, item 4:
The symbol for the type of protection used shall be “tD” (protection by enclosure).
29.2, item 5:
The zone in which the apparatus can be used is prefixed by “A” for practice A and “B” for
practice B.
29.2, item 6:
Practice B does not need to include the IP rating.
- 21 - ANSI/ISA-61241-1 (12.10.03)-2006
Annex A
U.S. major deviations
1 Scope
2 Normative references
4 Construction
This section was eliminated since it concerned requirements for zone 20, which was not included
in this standard.
6.1 General
This section was modified to reflect the removing of zone 20 from the scope of the standard, and
to call out the different testing requirements for zone 21 and zone 22 enclosures.
7.1 General
This section was added as a calling clause for the tests required.
This section was modified to show the order of tests, to call out IEC 60034-5 for rotating
equipment, and to call out the new pressure test.
This section was modified to show the order of tests, to call out IEC 60034-5 for rotating
equipment, and to call out the new pressure test.
This test was added to make sure that gaskets would not become dislodged and cause the
enclosure to admit dust under the pressures involved in temperature cycling.
9 Marking
This section was changed to refer all marking to the general requirements document except for
the “tD” marking, and eliminate the need to mark A or B for the practice used.
This page intentionally left blank.
- 23 - ANSI/ISA-61241-1 (12.10.03)-2006
Bibliography
NFPA 499, Recommended Practice for the Classification of Combustible Dusts and of Hazardous
(Classified) Locations for Electrical Installations in Chemical Process Areas
IEC 60079-0:2004, Electrical apparatus for explosive gas atmospheres – Part 0: General
requirements
IEC 60079-7:2001, Electrical apparatus for explosive gas atmospheres – Part 7: Increased safety
”e”
IEC 60079-11:1999, Electrical apparatus for explosive gas atmospheres – Part 11: Intrinsic
safety 'i'
IEC 60093:1980, Methods of test for volume resistivity and surface resistivity of solid electrical
insulating materials
IEC 60216-2:1990, Guide for the determination of thermal endurance properties of electrical
insulating materials – Part 2: Choice of test criteria
IEC 60243-1:1998, Electrical strength of insulating materials – Test methods – Part 1: Tests at
power frequencies
IEC 60947-3:1999, Low-voltage switchgear and control gear – Part 3: Switches, disconnectors,
switch-disconnectors and fuse-combination units
IEC 61241-10, Electrical apparatus for use in the presence of combustible dust – Part 10:
Classification of areas where combustible dusts are or may be present 2
IEC 61241-14, Electrical apparatus for use in the presence of combustible dust – Part 14:
Selection and installation of apparatus 3
IEC 61241-20-1, Electrical apparatus for use in the presence of combustible dust – Part 20-1:
Test methods – Methods for determining the minimum ignition temperatures of dust 4
__________
——————
2 In preparation.
3 To be published.
4 Under consideration.
Developing and promulgating sound consensus standards, recommended practices, and
technical reports is one of ISA’s primary goals. To achieve this goal the Standards and Practices
Department relies on the technical expertise and efforts of volunteer committee members,
chairmen and reviewers.
ISA is an American National Standards Institute (ANSI) accredited organization. ISA administers
United States Technical Advisory Groups (USTAGs) and provides secretariat support for
International Electrotechnical Commission (IEC) and International Organization for
Standardization (ISO) committees that develop process measurement and control standards. To
obtain additional information on the Society’s standards program, please write:
ISA
Attn: Standards Department
67 Alexander Drive
P.O. Box 12277
Research Triangle Park, NC 27709
ISBN: 978-1-934394-02-1