11KV/415V Overhead Line Specification(REC)

JUNE 8, 2011  129 COMMENTS (HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/06/08/11KV415V‑OVERHEAD‑
LINE‑SPECIFICATION‑REC/#COMMENTS)

11KV/415V over Head Line’s Specification and Installation (REC):

 11KV LIGHTNING ARRESTER (IS: 3070 (Pt­II)).

Voltage Rating for LA:

The rated voltage of lightning arresters shall be 9 KV (rms).
This will be applicable to the effectively earthed 11 KV systems co‑efficient of earth not exceeding 80 percent as per IS: 4004 with
all the transformer neutrals directly earthed.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 1/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Normal Discharge Current Rating for LA:

The nominal discharge current rating of the lightning arresters shall be 5 KA.

Tests for LA:

The following routine and type tests as laid down in IS : 3070 (Part‑I) shall be carried out.
Routine Test: Dry Power frequency spark over test.
Type Tests (Confirmation) :

1. Voltage withstand tests of arrester insulation.
2. Power frequency spark over test
3. Hundred percent 1.2/550 microsecond impulse spark over test
4. Front‑of‑wave impulse spark over test.
5. Residual voltage test.
6. Impulse current withstand test.
7. Operating duty test.
8. Temperature cycle test on porcelain housing.
9. Porosity test on porcelain components.
10. Galvanizing test on metal parts.

11 KV DROP­OUT FUSE CUTOUTS: (IS: 9385 (part­I to III).)
 
The distribution fuse cutouts shall be outdoor, open, drop‑out expulsion type fuse cutouts suitable for installation in 50 Hz, 11
KV distribution system.
The rated voltage shall be 12 KV.
The rated current shall be 100 A.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 2/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The rated current shall be 100 A.

Rated Lighting Impulse withstands Voltage for Fuse:

To earth and between poles 75 KV (Peak)
Across the isolating distance of fuse base 86 KV (Peak)

Rated One Minute Power Frequency Withstand Voltage (Wet & Dry) for Fuse:

To earth and between poles 28 KV (rms)
Across the isolating distance 32 KV (rms)

Temperature Rise Limit for Fuse:

Copper contacts silver faced 650C
Terminals 500C
Metal parts acting as spring The temperature shall not reach such a value that Elasticity of the metal is changed

Rated Breaking Capacity for Fuse:

The rated breaking capacity shall be 8 KA (Asymmetrical).

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 3/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Construction Details for Fuse:

The cutouts shall be of single vent type (downward) having a front connected fuse carrier suitable for angle mounting.
All ferrous parts shall be hot dip galvanized in accordance with the latest version of IS : 2632. Nuts and bolts shall conform to IS :
1364. Spring washers shall be electro‑galvanized.

Fuse Base Top Assembly:

The top current carrying parts shall be made of a highly conductive copper alloy and the contact portion shall be silver plated for
corrosion resistance and efficient current flow.
The contact shall have a socket cavity for latching and holding firmly the fuse carrier until the fault interruption is completed
within the fuse.
The top assembly shall have an aluminum alloy terminal connector. The top assembly shall be robust enough to absorb bulk of
the forces during the fuse carrier closing and opening operations and shall not over‑stress the spring contact. It shall also prohibit
accidental opening of the fuse carrier due to vibrations or impact.

Fuse Base Bottom Assembly:

The conducting parts shall be made of high strength highly conductive copper alloy and the contact portion shall be silver plated
for corrosion resistance and shall provide a low resistance current path from the bo�om fuse carrier contacts to the bo�om
terminal connector.

Fuse Carrier Top Assembly:

The fuse carrier top contact shall have a solid replaceable cap made from highly conductive, anticorrosive copper alloy and the
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 4/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The fuse carrier top contact shall have a solid replaceable cap made from highly conductive, anticorrosive copper alloy and the
contact portion shall be silver plated to provide a low resistance current path from the Fuse Base Top Contact to the Fuse Link.
It shall make a firm contact with the bu�on head of the fuse link and shall provide a protective enclosure to the fuse link to check
spreading of arc during fault interruptions.
The fuse carrier shall be provided with a cast bronze opening eye (pull ring) suitable for operation with a hook stick from the
ground level to pull‑out or close‑in the fuse carrier by manual operation.

Fuse Carrier Bottom Assembly:

The fuse carrier bo�om assembly shall be made of bronze castings with silver plating at the contact points to efficiently transfer
current to fuse base.
It shall make smooth contact with the fuse base bo�om assembly during closing operation. The bo�om assembly shall have a
lifting eye for the hook stick for removing or replacing the fuse carrier.

Fuse Base (Porcelain):

The fuse base shall be a bird‑proof, single unit porcelain insulator with a creepage distance (to earth) not less than 320 mm. The
top and bo�om assemblies as also the middle clamping hardware shall be either embedded in the porcelain insulator with
sulphur cement or suitably clamped in position.
For embedded components, the pull out strength should be such as to result in breaking of the porcelain before pull out occurs in
a test. For porcelain insulators, the beam strength shall not be less than 1000 kg.

Fuse Tube:

The fuse tube shall be made of fiber glass coated with ultraviolet inhibitor on the outer surface and having arc quenching bone
fire liner inside.
The tube shall have high bursting strength to sustain high pressure of the gases during fault interruption.
The inside diameter of the fuse tube shall be 17.5 mm. The solid cap of the fuse carrier shall clamp the bu�on head of the fuse
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 5/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The inside diameter of the fuse tube shall be 17.5 mm. The solid cap of the fuse carrier shall clamp the bu�on head of the fuse
link, closing the top end of the fuse and allowing only the downward venting during fault interruption.

Type Tests (IS: 9385 Part I & II) for Fuse:

Dielectric tests
Temperature rise test

Mounting Arrangement for Fuse:

The cutouts shall be provided with a suitable arrangement for mounting these on 74 X 40 mm or 100 X 50 mm channel cross arm
in such a way that the center line of the base is at an angle of 15 to 20 deg from the vertical and shall provide the necessary
clearances from the support.
Mounting arrangement shall be made of high strength galvanized steel flat and shall be robust enough to sustain the various
stresses encountered during all operating conditions of the cutout.

11 KV PORCELAIN INSULATORS: (IS: 731 and IS: 3188):
 
The porcelain shall be sound, free form defects, through verified and smoothly glazed. Unless otherwise specified, the glaze shall
be brown color.
The glaze shall cover all the porcelain parts of insulators except those areas which serve as support during firing are left unglazed
for the purpose of assembly.
The design of insulators shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to
deterioration.
The porcelain shall not engage directly with hard metal. Cement used in construction of insulators shall not cause fracture by
expansion or loosening by contraction and proper care shall be taken to locate the individual parts correctly during cementing.
The cement shall not give rise to chemical reaction with metal fi�ings and its thickness shall be as uniform as possible.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 6/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The cement shall not give rise to chemical reaction with metal fi�ings and its thickness shall be as uniform as possible.
The insulators should preferably be manufactured in automatic temperature controlled kilns to obtain uniform baking for be�er
electrical and mechanical properties.
Both pin and strain insulators shall conform to Type B of IS : 731. The strain insulators shall be of Tongue and Clevis type.

 Test Voltage for Insulator:

Highest System Voltage : 12 KV (rms)
Visible Discharge Test: 9 KV (rms)
Wet Power Frequency Withstand Test 35 KV (rms)
Power Frequency Puncture Withstand Test (Pin Insulator) : 105 KV (rms)
Power Frequency Puncture Withstand Test (Strain Insulator):1.3 times the actual dry flashover voltage of the insulator.
Impulse Voltage Withstand Test : 75 KV (rms)

Failing Load for Insulator:

Mechanical Failing Load (For Pin Insulators only) : The insulators shall be suitable for a minimum failing load of 10 KN applied
in transverse director.
Electro‑Mechanical Failing Load (For Strain Insulators) : The insulators shall be suitable for a minimum failing load of 70 KN
applied axially.

Creepage Distance for Insulator:

Highest System Voltage: 12KV
Heavily Polluted Atmosphere Pin Insulator: 320mm
Heavily Polluted Atmosphere Strain Insulator: 400mm

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 7/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Tests: (As per IS: 731 ) for Insulator.

1. Visual examination
2. Verification of dimensions
3. Visible discharge test
4. Impulse Voltage withstand Test
5. Wet Power Frequency Voltage withstand Test
6. Temperature Cycle Test
7. Mechanical Failing Load Test
8. 24 hour Mechanical Strength Test for Strain Insulators
9. Puncture Test
10. Porosity Test
11. Galvanizing Test
12. Electro‑Mechanical Failing Load Test

Routine Tests for Insulator
 
1. Virtual examination
2. Mechanical routine test
3. Electrical routine test

Acceptance Test for Insulator
 
1. Verification of Dimensions
2. Temperature Cycle Test
3. Electro‑Mechanical Failing Load Test
4. Puncture Test
5. Porosity Test
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 8/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

5. Porosity Test
6. Galvanizing Test

Marking for Insulator:

Name or trademark of manufacturer
Month and year of manufacture
Minimum failing load in KN
ISI certificate mark, if any
Markings on porcelain shall be printed and shall be supplied before firing.

 Pin Insulators:

The pins shall of single piece obtained preferably by the process of forging.
They shall not be made by joining, welding, shrink fi�ing or any other process using more than one piece material. The pins shall
be of good finish, free from flaws and other defects.
The finish of the collar shall be such that sharp angle between the collar and the shank is avoided. Aluminum ferrous pins, nuts
and washers, except those made of stainless steel, shall be galvanized. The threads of nuts and taped hole when cut after
galvanizing shall be well oiled or greased.

Dimensions  for Pin Insulators:

Pins shall be of small steel head type S 165 P as per IS : 2486 (Part‑II) having stalk length of 165 mm and shank length of 150 mm
with minimum failing load of 10 KN.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 9/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Tests: (IS: 2486 (Part­I)) for Pin Insulators
 
Checking of threads on heads
Galvanizing test
Visual examination test
Mechanical test
Galvanizing test
Mechanical test
Visual examination test

Helically Formed Pin Insulator Ties:

Helically formed ties used for holding the conductor on the pin insulator shall be made of aluminum alloy or aluminized steel or
aluminum clad steel wires and shall conform to the requirements of IS : 12048. The ties shall be suitable for pin insulator
dimensions of Pt.‑ I and conductor sizes specified.
Elastomer pad for insulator shall be used with the ties to avoid abrasion of the conductor coming into direct contact with the
insulator.

Cross arm strap conforming to IS: 2486 (Pt. – II).

Aluminum alloy die cast thimble‑clevis for a�aching to the tongue of strain, insulator on one end and for accommodating the
loop of the helically formed dead‑end fi�ing at the other end in its smooth internal contour.
 The thimble shall be suitable for all sizes of ACSR conductors as specified. The thimble clevis shall be a�ached to the insulator by
a steel cu�ing pin used with a non‑ferrous split pin of brass or stainless steel.
The thimble shall have clevis dimensions as per IS: 2486 (Pt – II).
Helically formed dead end grip having a prefabricated loop to fit into the grooved contour of the thimble on one end and for
application over the conductor at the other end.
The formed fi�ing shall conform to the requirement of IS : 12048.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 10/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The formed fi�ing shall conform to the requirement of IS : 12048.

Fittings for strain Insulators of Ball & Socket Type:

Cross arm strap conforming to IS: 2486 (Pt‑II).
Forged steel ball eye for a�aching the socket end of the strain insulator to the cross arm strap.
Forgings shall be made of steel as per IS: 2004. Aluminum alloy thimble‑socket made out of permanent mould cast, high strength
aluminum alloy for a�aching to the strain insulator on one end and for accommodating the loop of the helically formed dead‑end
fi�ings at the other end in its smooth internal contour.
The thimble socket shall be a�ached to the strain insulator with the help of locking pin as per the dimensions given in IS : 2486
(Pt‑II).

Tests
 
The helically formed fi�ings for strain insulators shall be subjected to tests as per IS : 12048.
The other hardware fi�ings shall be tested as per IS: 2486 (Part‑I).

Fittings for strain Insulators with Helically Formed Conductors Dead­
End Grips:

Fittings for Strain Insulators of Tongue & Clevis Type

The fi�ings shall consist of the following components:

1. Cross arm strap conforming to IS:2486 (Pt.II)‑1989.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 11/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

1. Cross arm strap conforming to IS:2486 (Pt.II)‑1989.
2. Aluminum alloy die cast thimble‑clevis for a�aching to the tongue of strain insulator on one end and for accommodating the
loop of the helically formed dead‑end fi�ing at the other end in its smooth internal contour. The thimble shall be suitable for all
sizes of conductors ranging from 7/2.11mm to 7/3.35mm ACSR. The thimble clevis shall be a�ached tothe insulator by a steel
cu�er pin used with a non‑ferrous split pin of brass or stainless steel. The thimble shall have clevis dimensions as per IS:2486
(Pt.II)‑1989.
3.    Helically formed dead‑end grip having a pre‑fabricated loop to fit into the grooved contour of the thimble on one end and for
application over the conductor at the other end. The formed fi�ing shall conform to the requirement ofIS:12048‑1987.

Note: As the helically formed fi�ings are made to suit specific sizes of conductors, the purchase should clearly specify the
number of fi�ings required for each size of conductor

Fittings for strain Insulators with  Conventional Dead end Clamps Alternative to
Fitting Covered:

Fi�ings for strain insulators with conventional dead‑end clamps for use with tongue & clevis or ball & socket type insulators
shall consist of the following components :

1. Cross arms strap conforming to IS:2486 (Pt.II)‑1989
2.  Dead‑end clamp made of aluminum alloy to suit ACSR conductors from 7/2.11mm to 7/3.35mm. The ultimate strength of the
clamp shall not be less than 3000 Kg. The shape and major dimensions of clamps suitable for B&S and T&C insulators are shown
in figures 7 & 8 respectively.

GUY STRAIN INSULATORS: (IS: 5300)
 
The porcelain insulator shall be sound, free from defects, thoroughly verified and smoothly glazed.
 The design of the insulator shall be such that the stresses to expansion and contraction in any part of the insulator shall not lead
to its deterioration.
The glaze, unless otherwise specified, shall be brown in color.
The glaze shall cover the entire porcelain surface parts except those areas that serve as supports during firing.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 12/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The glaze shall cover the entire porcelain surface parts except those areas that serve as supports during firing.

Type for Guy Insulators:

The standard guy strain insulators shall be designations ‘A’ and ‘C’ as per IS: 5300.
The recommended type of guy strain insulators for use on guy wires of overhead lines of different voltage levels are as follows:
Power Line Voltage :11KV
Designation of Insulators: C
Dry one minute Power Frequency withstand Voltage: 27 KV (rms)
Wet one minute Power Frequency withstand Voltage: 13 KV (rms)
Minimum Failing Load: 88(KN)

 Tests: (IS: 5300) for Guy Insulators.

1. Visual examination
2. Verification of dimensions
3. Temperature cycle test
4. Dry one‑minute power frequency voltage withstand test
5. Wet one‑minute power frequency voltage withstand test
6. Mechanical strength test
7. Porosity test
8. Acceptance Tests : (to be conducted in the following order)
9. Verification of dimensions
10. Temperature cycle test
11. Mechanical strength test
12. Porosity test

Marking for Guy Insulators:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 13/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Name or trademark of the manufacturer.
Year of manufacture.
ISI certificate mark, if any
Marking on porcelain shall be applied before firing.

Type of Insulators for Guy Insulators:

The standard guy strain insulators shall be of designations ‘A‘ and ‘C‘ as per IS:5300.
The recommended type of guy strain insulators for use on guy wires of overhead lines of different voltage levels are as follows :

Line Voltage Designation of Insulator
415/240Volt A Type
11KV C Type
33KV C Type (2 No’s of Strings in
Series).

Basic Insulator Level for Guy Insulators:
 
Designation of Dry one min power Wet one min power
Insulator frequency withstand frequency
withstand
A Type 18 KV (rms) 8 KV (rms)
C Type 27 KV (rms) 13 KV (rms)

 Mechanical Strength for Guy Insulators:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 14/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The insulators shall be suitable for the minimum failing loads specified as under:

Designation of Insulator Minimum Failing Load
A Type 44 KN
C Type 88 KN

Routine Test as per Tests (IS: 5300) for Guy Insulators:
 
1. Visual examination
2. Verification of dimensions
3. Temperature cycle test
4. Dry one‑minute power‑frequency voltage withstand test
5. Wet one‑minute power frequency voltage withstand test
6. Mechanical strength test
7. Porosity test

Acceptance Tests (to be conducted in the following order):

1. Verification of dimensions
2. Temperature cycle test
3. Mechanical strength test
4. Porosity test

DANGER NOTICE PLATES:
 

As per provisions of IE Rules 1956, Danger Notice Plates in Hindi or English and, in addition, in the local language with the sign
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 15/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

As per provisions of IE Rules 1956, Danger Notice Plates in Hindi or English and, in addition, in the local language with the sign
of skull and bones are required to be provided on power line supports and other installations.
It is further stipulated in the I.E. Rules that such Notice Plates are not required to be provided on supports like PCC, tubular,
wood, steel rails, etc. which cannot be climbed easily without the aid of ladder or special appliances.
To adopt a uniform pa�ern and for helping easy procurement, a specification on Danger Notice Plates has been drawn up.

Standards of Danger Plate
 
The Danger Notice Plates shall comply with IS:2551‑1982.

Dimensions of Danger Plate
 
Two sizes of Danger Notice Plates as follows are recommended:

1. For display at 415 V installations – 200x150mm
2. For display at 11 KV (or higher voltages) installations – 250x200mm

The corners of the plate shall be rounded off.
The location of fixing holes as shown in Figs. 1 to 4 is provisional and can be modified to suit the requirements of the purchaser.

Lettering of Danger Plate
 
All le�erings shall be centrally spaced. The dimensions of the le�ers, figures and their respective position shall be as shown in
figs.
The size of le�ers in the words in each language and spacing between them shall be so chosen that these are uniformly wri�en in
the space earmarked for them.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 16/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Languages of Danger Plate
 
Under Rule No. 35 of Indian Electricity Rules, 1956, the owner of every medium, high and extra high voltage installation is
required to affix permanently in a conspicuous position a danger notice in Hindi or English and, in addition, in the local
language, with the sign of skull and bones.
The type and size of le�ering to be done in Hindi is indicated in the specimen danger notice plates shown in Fig. 2 and 4 and
those in English are shown in Figs.
Adequate space has been provided in the specimen danger notice plates for having the le�erings in local language for the
equivalent of’ Danger’,’ 415′ ‘11000’ and ‘Volts’.

Material & Finishing of Danger Plate:
 
The plate shall be made from mild steel sheet of at least 1.6mm thick and vitreous enameled white, with le�ers, figures and the
conventional skull and cross‑bones in signal red color (refer IS:5‑1978) on the front side. The rear side of the plate shall also be
enameled.

Tests of Danger Plate:

The following tests shall be carried out :

1. Visual examination as per IS:2551‑1982
2. Dimensional check as per IS:2551‑1982
3. Test for weather proofness as per IS:8709‑1977 (or its latest version)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 17/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

ACSR and AAC over head conductors:
 
A Conference on Standardization of Specifications and Construction Practices in Rural Electrification was held on 4th and 5th
January, 1971 in New Delhi. Besides the Rural Electrification Corporation, representatives of various State Electricity Boards, the
Indian Standards Institution (BIS), Central Water & Power Commission (CEA),Central Board of Irrigation and Power and many
other organizations participated in the discussions.
Based on the consensus arrived at the Conference, REC Specification No. 1/1971 covering 7/2.21 mm (25 mm2 aluminum area)
and 7/3.10mm (50mm2 aluminum area) AAC for use on LT lines and 7/2.59 mm (30mm2 aluminum area) and 7/3.35mm (50mm2
aluminum area) ACSR for use on 11 KV and LT lines was issued.
Subsequently, the Specification was revised to incorporate an additional size of ACSR viz 7/2.11mm (20mm2 aluminum area) for
use on 11 KV and LT lines and then again to incorporate three more sizes of ACSR viz. 7/3.35mm (50mm2 aluminum area),
7/4.09mm (80mm2 aluminum area) and 6/4.72mm + 7/1.57 mm (100mm2 aluminum area) for use on 33 KV lines.
The sizes of conductors standardized for lines of different voltages are indicated below :

ACSR Conductor for 33KV Lines :
 
1. ACSR 7/3.35mm (50mm2 aluminum area)
2. ACSR 7/4.09 mm (80mm2 aluminum area)
3. ACSR 6/4.72 mm + 7/1.57 mm (100mm2 aluminum area)

ACSR Conductor for11 KV Lines

1. ACSR 7/2.11 mm (20mm2 aluminum area)
2. ACSR 7/2.59 mm (30mm2 aluminum area)
3.  ACSR 7/3.35 mm (50mm2 aluminum area)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 18/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

ACSR Conductor for LT Lines

1. ACSR 7/2.11 mm (20mm2 aluminum area)
2.  ACSR 7/2.59 mm (30mm2 aluminum area)
3. ACSR 7/3.35 mm (50mm2 aluminum area)
4.  AAC 7/2.21 mm (25mm2 aluminum area)
5. AAC 7/3.10 mm (50mm2 aluminums area)

Standards for ACSR Conductor :

IS: 398 (Pt.I)‑1976 and IS: 398 (Pt.II)‑1976.

Joint in Wires & Conductors:

All aluminums conductors: No joints shall be permi�ed in any wire.
Aluminum Conductor Steel Reinforced :

Aluminum Wires for ACSR Conductor:

No two joints shall occur in the aluminums wires closer together than 15 meters.

Steel Wires for ACSR Conductor :
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 19/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

No joints shall be permi�ed in steel wires used for ACSR of Sizes 20mm2 aluminums area (7/2.11mm), 30mm2 aluminums area
(7/2.59mm), 50mm2 aluminums area (7/3.35mm) and 80mm2 aluminums area (7/4.09 mm).
In the case of ACSR of 100mm2 aluminums area (6/4.72mm + 7/1.57 mm) having seven galvanized steel wires, joints, in
individual wires shall be permi�ed but no two such joints shall be less than 15 meters apart in the complete steel core.

Tests for ACSR Conductor:

The samples of individual wires for the tests shall normally be taken before stranding. The manufacturer shall carry out test on
samples taken out at least from 10% of aluminums wire spools and 10% of steel wire coils. However, when desired by the
purchaser, the test sample may be taken from the stranded wires.
The wires used for all aluminums conductors shall comply with the following tests as per IS:398(Pt.I)‑1976.

1.  Breaking load test
2.  Wrapping test
3.  Resistance test

The wires used for aluminums conductors, steel reinforced shall comply with the following tests as per IS:398

1. Breaking load test
2. Ductility test
3. Wrapping test
4. Resistance test
5. Galvanizing test

Packing & Marking :(IS: 1778­1980)

The gross mass for various conductors shall not exceed by more than 10% of the values given in the following

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 20/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Conductor Size Gross Mass for ACSR Conductor
 

(1) AAC

25mm2 Al. area (7/2.21 mm) 500 Kg.
50mm2 Al. area (7/3.10 mm) 500 Kg.

(2)ACSR

20mm2 Al. area (7/2.11 mm) 1000 Kg.
30mm2 Al. area (7/2.59 mm) 1000 Kg.
50mm2 Al. area (7/3.35 mm) 1500 Kg.
80mm2 Al. area (7/4.09 mm) 1500 Kg.
100mm2 Al. area (6/4.72mm + 7/1.57mm) 2000 Kg.

Conductor Size Normal conductor length for ACSR Conductor

1.  AAC

25mm2 Al. area (7/2.21mm) 1.0 Km.
50mm2 Al. area (7/3.10mm) 1.0 Km.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 21/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

50mm2 Al. area (7/3.10mm) 1.0 Km.

1. ACSR

20mm2 Al. area (7/2.11 mm) 2.0 Km.
30mm2 Al. area (7/2.59 mm) 2.0 Km.
50mm2 Al. area (7/3.35 mm) 2.0 Km.
80mm2 Al. area (7/4.09 mm) 1.5 Km.
100mm2 Al. area (6/4.72mm + 7/1.57mm) 2.0 Km.
Longer lengths shall be acceptable.
Short lengths, not less than 50% of the standard lengths, shall be acceptable to the maximum extent of 10% of the quantity
ordered.

Marking for ACSR Conductor:

The following information shall be marked on each package:

1. Manufacturers’ name
2. Trade mark, if any
3. Drum or identification number
4. Size of conductor
5. Number and lengths of conductor
6. Gross mass of the package
7. Net mass of conductor
8. I.S.I certification mark, if any

Pre stressed Cement Concrete Poles(FOS 2.5) For 11KV & LT Lines:
 
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 22/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

 A research project for evolving economical designs of cement concrete poles for use on 11 KV and LT Lines was entrusted to the
Cement Research Institute (CRI) of India.
The basic design parameters for these poles as given in Clause 6 of this Specification were approved by the Fifth Conference on
standardization of Specifications and Construction Practices in Rural Electrification held in May, 1974.
Some of these design parameters which were based on certain foreign codes/practices and certain other provisions of this
Specification, although at variance with the stipulations of IS:1678 – 1960, had been adopted to achieve economy in the designs.
However, these modifications have since been incorporated in the revised IS:1678 – 1978.
This Specification covers PCC poles with an overall length of 7.5 M, 8.0 M and 9.0 M suitable for use in overhead 11 KV and L.T.
power lines and double pole structures for 11/0.4 KV substations.

Application Standard for PCC Pole:

IS: 1678‑1978, Specification for pre stressed concrete poles for overhead power, traction and telecommunication lines.
IS: 2905‑1966. Methods of test for concrete poles for over‑head power and telecommunication lines.
IS: 7321‑1974. Code of practice for selection, handling and erection of concrete poles for over‑head power and telecommunication
lines.

Average Permanent Load for PCC Pole:
 
That fraction of the working load which may be considered of long duration over a period of one year.

Load Factor for PCC Pole:
 
The ratio of ultimate transverse load to the transverse load at first crack.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 23/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Transverse for PCC Pole:
 
The direction of the line bisecting the angle contained by the conductor at the pole. In the case of a straight run, this will be
normal to the run of the line.

Transverse Load at First Crack for PCC Pole:
 
For design, the transverse load at first crack shall be taken as not less than the value of the working load.

Working load for PCC Pole:
 
The maximum load in the transverse direction, that is ever likely to occur, including the wind pressure on the pole.
This load is assumed to act at a point 600 mm below the top with the bu� end of the pole planted to the required depth as
intended in the design.

Ultimate Failure for PCC Pole:
 
The conditions existing when the pole ceases to sustain a load increment owing to either crushing of concrete, or snapping of the
pre stressing tend on or permanent stretching of the steel in any part of the pole.

Ultimate Transverse Load for PCC Pole:
 
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 24/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The load at which failure occurs, when it is applied at a point 600 mm below the top and perpendicular to the axis of the pole
along the transverse direction with the bu� end of the pole planted to the required depth as intended in the design.

Application for PCC Pole:
 
 7.5 M and 8.0 M Poles

These poles shall be used at tangent locations for 11KV and L.T. lines in wind pressure zones of 50 kg/M2, 75 Kg/M2 and 100
Kg/M2 in accordance with REC Construction Standards referred to in the following:

Pole length: 7.5M

11KV lines without earth wire L.T. lines, horizontal formation.
Reference to REC Construction Standards: A‑4, B‑5

Pole length: 8M

11KV lines with earth wire L.T. lines, vertical formation.
Reference to REC Construction Standards: A‑5, B‑6

9.0 M Poles

These poles shall be used for double pole structures of distribution transformer centers as per REC Construction Standards F‑1 to
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 25/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

These poles shall be used for double pole structures of distribution transformer centers as per REC Construction Standards F‑1 to
F‑4 and for special locations in 11 KV and L.T. Lines, such as road crossings etc.

Materials for PCC Pole::

(1) Cement

The cement used in the manufacture of pre stressed concrete poles shall be ordinary or rapid hardening port land cement
conforming to IS: 269 – 1976 (Specification for ordinary and low heat port land cement) or IS: 8041 E‑1978 (Specification for rapid
hardening port land cement).

(2) Aggregates

Aggregates used for the manufacture of pre‑stressed concrete poles shall conform to IS : 383 – 1970 (Specification for coarse and
fine aggregates from natural sources for concrete). The nominal maximum size of aggregates shall in no case exceed 12mm.

(3) Water

Water should be free from chlorides, sulphates, other salts and organic ma�er. Potable water will be generally suitable.

(4) Admixtures

Admixtures should not contain Calcium Chloride or other chlorides and salts which are likely to promote corrosion of pre‑
stressing steel.

(5) Pre‑stressing Steel

The pre‑stressing steel wires, including those used as un tensioned wires  should conform to IS : 1785 (Part‑I) – 1966
(Specification for plain hard drawn steel wire for pre stressed concrete. Part‑I cold drawn stress relieved wire), IS: 1785 (Part‑II) –
1967 (Specification for plain hard‑drawn steel wire)., or IS : 6003 – 1970 (Specification for indented wire for pre‑stressed concrete).
The type designs given in Annexure‑I are for plain wires of 4 mm diameter with a guaranteed ultimate strength of 175 Kg/mm2.

(6) The concrete mix:

Itshall be designed to the requirements laid down for controlled concrete (also called design mix concrete) in IS : 1343 – 1980
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 26/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Itshall be designed to the requirements laid down for controlled concrete (also called design mix concrete) in IS : 1343 – 1980
(Code of practice for pre stressed concrete) and IS : 456 – 1978 (Code of practice for plain and reinforced concrete), subject to the
following special conditions;

1.  Minimum works cube strength at 28 days should be at least 420 Kg/cm2.
2. The concrete strength at transfer should be at least 210Kg/cm2.
3. The mix should contain at least 380 Kg. of cement per cubic meter of concrete.
4. The mix should contain as low a water content as is consistent with adequate workability. If it becomes necessary to add water to
increase the workability, the cement content also should be raised in such a way that the original value of water cement ratio is
maintained.

Design Requirements for PCC Pole::

The poles shall be planted directly in the ground with a planting depth of 1.5 meters.
The working load on the poles should correspond to those that are likely to come on the pole during their service life. Designs
given in Annexure‑I are for 140 Kg. and 200 Kg. Applied at 0.6 M from top.
The factor of safety for all these poles shall not be less than 2.5.
The average permanent load should be 40% of the working load.
The F.O.S. against first crack load shall be 1.0.
At average permanent load, permissible tensile stress in concrete shall be 30 Kg/cm2.
At the design value of first crack load, the modulus of rupture shall not exceed 55.2 kg/cm2 for M‑420 concrete.
The ultimate moment capacity in the longitudinal direction should be at least one fourth of that in the transverse direction.
The maximum compressive stress in concrete at the time of transfer of pre stress should not exceed 0.8 times the cube strength.
The concrete strength at transfer shall not be less than half the 28 days strength ensured in the design, i.e. 420 x 0.5= 210 Kg/cm2.
For model check calculations on the design of poles, referred to in Annexure‑I, a reference may be made to the REC “Manual on
Manufacturing of solid PCC

Dimensions and Reinforcements for PCC Pole:

The cross‑sectional dimensions and the details of pre stressing wire should conform to the particulars given in Annexure‑I.
The provisions of holes for fixing cross‑arms and other fixtures should conform to the REC standards referred to in clause 4 of
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 27/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The provisions of holes for fixing cross‑arms and other fixtures should conform to the REC standards referred to in clause 4 of
this specification and in accordance with the construction practices adopted by the State Electricity Boards.

Manufacture for PCC Pole::

All pre stressing wires and reinforcements shall be accurately fixed as shown in the drawings and maintained in position during
manufacture. The un tensioned reinforcement, as indicated in the drawings, should be held in position by the use of stirrups
which should go round all the wires.
All wires shall be accurately stretched with uniform pre stress in each wire.
Each wire or group of wires shall be anchored positively during casting. Care shall be taken to see that the anchorages do not
yield before the concrete a�ains the necessary strength.

Cover for PCC Pole:
 
The cover of concrete measured from the outside of the pre stressing tendon shall be normally 20 mm.

Welding & Lapping of Steel for PCC Pole:

The high tensile steel wire shall be continuous over the entire length of the tendon.
Welding shall not be allowed in any case. However, jointing or coupling may be permi�ed provided the strength of the joint or
coupling is not less than the strength of each individual wire.

Compacting for PCC Pole:

Concrete shall be compacted by spinning, vibrating, shocking or other suitable mechanical means. Hand compaction shall not be
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 28/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Concrete shall be compacted by spinning, vibrating, shocking or other suitable mechanical means. Hand compaction shall not be
permi�ed.

Curing for PCC Pole:
 
The concrete shall be covered with a layer of sacking, canvas, hessian or similar absorbent material and kept constantly wet up to
the time when the strength of concrete is at least equal to the minimum strength of concrete at transfer of pre stress. Thereafter,
the pole may be removed from the mould and watered at intervals to prevent surface cracking of the unit, the interval should
depend on the atmospheric humidity and temperature.

The pre stressing wires for PCC Pole:
 
Itshall be de tensioned only after the concrete has a�ained the specified strength at transfer (i.e. 210 Kg/cm2). The cubes cast for
the purpose of determining the strength at transfer should be cured, as far as possible, under conditions similar to those under
which the poles are cured.
The transfer stage shall be determined based on the daily tests carried out on concrete cubes till the specified strength indicated
above is reached. Thereafter the test on concrete shall be carried out as detailed in IS: 1343 – 1960 (Code of practice for pre
stressed concrete).
The manufacturer shall supply when required by the purchaser or his representative, result of compressive test conducted in
accordance with IS : 456 ‑1964 (Code of practice for plain and reinforced concrete) on concrete cubes made from the concrete
used for the poles.
 If the purchaser so desires, the manufacturer shall supply cubes for test purposes and such cubes shall be tested in accordance
with IS: 456 – 1964 (Code of practice for plain and reinforced concrete).
The de tensioning shall be done by slowly releasing the wires, without imparting shock or sudden load to the poles. The rate of
de tensioning may be controlled by any suitable means either mechanical (screw type) or hydraulic.
The poles shall not be de tensioned or released by cu�ing the pre stressing wires using flames or bar croppers while the wires are
still under tension.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 29/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Separate eye­hooks or holes for PCC Pole:

It shall be provided for handling and transport, one each at a distance of 0.15 times the overall length, from either end of the pole.
Eye‑hooks, if provided, should be properly anchored and should be on the face that has the shorter dimension of the cross‑
section. Holes, if provided for lifting purposes, should be perpendicular to the broad face of the pole.
Stacking should be done in such a manner that the broad side of the pole is vertical. Each tier in the stack should be supported on
timber sleepers located at 0.15 times the overall length, measured from the end. The timber supports in the stack should be
aligned in a vertical line.
Poles should be transported with their broad faces placed vertically and in such a manner that shocks are avoided. Supports
should be so arranged that they are located approx. at a distance equal to 0.15 times the overall length from the ends.
The erection of the pole should be carried out in such a way that the erection loads are applied so as to cause moment with
respect to the major axis. i.e. the rope used for hoisting the pole should be parallel to the broader face of the pole.

Testing of PCC Pole:

Transverse Strength Test

Poles made from ordinary Portland cement shall be tested only on the completion of 28 days and poles made from rapid‑
hardening cement only on the completion of 14 days, after the day of manufacture.
The pole may be tested in either horizontal or vertical position. If tested in horizontal position, provisions shall be made to
compensate for the overhanging weight of the pole, for this purpose the over‑hanging portion of the pole may be supported on a
movable trolley or similar device.
The pole shall be rigidly supported at the bu� end for a distance equal to the agreed depth of planting i.e. 1.5 M.
Load shall be applied at a point 600 mm from the top of the pole and shall be steadily and gradually increased to design value of
the transverse load at first crack. The deflection at this load shall be measured.
A pre stressed concrete pole shall be deemed not to have passed the test if visible cracks appear at a stage prior to the application
of the design transverse load for the first crack.

The load shall then be reduced to zero and increased gradually to a load equal to the first crack load plus 10% of the minimum
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 30/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

The load shall then be reduced to zero and increased gradually to a load equal to the first crack load plus 10% of the minimum
ultimate transverse load, and held up for 2 minutes.
This procedure shall be repeated until the load reaches the value of 80 per cent of the minimum ultimate transverse load and
thereafter increased by 5 per cent of the minimum ultimate transverse load until failure occurs. Each time the load is applied, it
shall be held for 2 minutes.
 The load applied to pre stressed concrete pole at the point of failure shall be measured to the nearest five Kilograms.
The pole shall be deemed not to have passed the test if the observed ultimate transverse load is less than the design ultimate
transverse load.

Measurement of Pole Cover for PCC Pole:
 
After completion of the transverse strength test, the sample pole shall be taken and checked for cover.
The cover of the pole shall be measured at 3 points, one within 1.8 meters from the bu� end of the pole, the second within 0.6
meter from the top and the third at an intermediate point and the mean value compared with the specified value.
The mean value of the measured cover should not differ by more than(±)1 mm from the specified cover. The individual values
should not differ by more than (±) 3 mm from specified value.
If these requirements are not met, the workmanship with reference to aligning of the end plates and pre stressing wires and
assembly of moulds should be improved and inspection at pre‑production stage tightened suitably.

Marking for PCC Pole:
 
The pole shall be clearly and indelibly marked with the following particulars either during or after manufacture but before
testing at a position so as to be easily read after erection in position.

1. Month and year of manufacture
2. Transverse strength of pole in Kg.
3. Maker’s serial No. and mark

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 31/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Main Points should be look after for Overhead Line Installation:

Overhead lines:

The general precautions during storage and handling of shall be taken in accordance with relevant IS code.
While laying the conductor shall betaken from top of the drum and the repeated in the direction of arrow on it.. Care shall be
taken to avoid contact with steel works, fence, etc by giving soft wood protection, using wooden rollers.
 Proper tools shall be used during stringing work. During stringing operation standard sag table or chart shall be followed and
care shall be taken to ensure that there are no kinks in the conductor. Joints in conductors shall be staggered. Mid span joints in
conductors shall be avoided.
After stringing the conductor, it shall be clamped permanently with shackle or strain clamps. An angle or section shall be
selected while pulling up conductors.

Jumpers:

While stringing, sufficient length shall of conductors be kept at shackle terminations for making jumpers. Jumpers shall be neat
and as far as possible symmetrical to run of conductors. These shall be made to prevent occurrence of faults due to wind or birds.
PG clamps may be preferred to binding of conductors at jumper location or service taps.

Cross Arms :

The cross arms shall be made of MS Structural steel. The length of cross arms shall be suitable for accommodating the number of
insulators on them with spacing of conductor. A gap of minimum 50 mm shall be left from the center of pin hole to end of cross
arm on either side. The cross arm shall be complete with pole clamp made of MS flat of size not less than 50 x 6 mm with

necessary nuts, bolts, washers, etc. The length of cross arm for carrying guard wires shall always run not less than 300 mm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 32/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

necessary nuts, bolts, washers, etc. The length of cross arm for carrying guard wires shall always run not less than 300 mm
beyond outer most bare conductor of configuration.
Cross arms shall be properly clamped to the support taking into consideration the orientation of lines.

Porcelain insulators and fittings:

The porcelain insulators shall be confirming to IS 731 – 1971 for overhead lines. This shall be glazed, crack / burr free.
The insulator shall have adequate mechanical strength, high degree of resistance to electrical puncture and resistance to climatic
and atmospheric a�ack.
All iron parts shall be hot dip galvanized & all joints shall be airtight. Pin insulators / shackle  insulators / disc insulators shall be
erected on cross arms and ‘D’ iron clamp shall be used or as specified by Engineer‑in‑charge. Shackle insulators shall be used in
conjunction with ‘D’ iron clamps when configuration of conductor is vertical.
These shall also be erected on cross arm at intermediate support in case of long lines, deviation from straight lines. Care shall be
taken that insulators are not damaged during erection.

Binding material:

Binding of conductor with the insulator shall be done with soft aluminum wire / conductor. The binding of conductor to
insulator shall be sufficiently firm and tight to ensure that no intermi�ent contact develops. The end of binding wire shall be
tightly twisted in close spaced spiral around the conductor to ensure good electrical contact and strengthen the conductor.

Supports and spacing of poles:

Support of overhead line shall be of adequate strength confirming in all respects to rules 76 of Indian electricity rules.
Pole spacing and clearance between lowest conductor above the ground level across / along the street shall be in accordance with
rule 85 of Indian electricity rules. Suitable foundation shall be provided for erection of poles.
The foundation shall include excavation in all types of soil and rocks and back filling, RCC, reinforcement, formwork.
Excavation for foundations for poles / stay / strut : After the location of supports / stay are pegged accurately, the excavation
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 33/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Excavation for foundations for poles / stay / strut : After the location of supports / stay are pegged accurately, the excavation
work shall be taken up and care should be taken while excavating that pits are not oversized.
The pit should be excavated in the direction of the line. The depth and size of pit shall be such that normally 1/6th of the length of
pole is buried in the ground and suitable for foundation of support.
For stay the position of pit shall normally be such stay makes as large an angle as possible with the support and it shall be in the
range of 40 to 60 degrees.
The length of stay rod shall project 450 mm above the ground level. The pit for strut shall be located at a distance not less than
1.8M from the pole.
The depth of pit shall be such that at least 1.2M of the strut is buried in the ground.

Stay / strut:

Stay set shall consist of stay rod, anchor plate, bow tightened / turn buckle, thimbles, stay wire and stain insulators.
 The stay rod shall be with stay grip in case of turn buckle is used instead of bow tightened. The entire stay set assembly shall be
galvanized. The stay wire shall be either 7/4.0 mm diameter or 7/3.15 mm diameter GI having tensile strength of not less than 70
kgf/sq mm and confirming to IS 2141. T
The anchor plate shall be of MS galvanized and not less than 300 mm x 300 mm x 6.4 mm thick. The stay rod / buckle rods shall
be minimum 16/19 mm diameter galvanized steel rod having tensile strength not less than 42 kgf/sq mm. Minimum length of
stay rod and buckle shall be 1800 mm and 450 mm respectively.

Erection stay sets:

The anchor plate shall be galvanized MS plate. The stay rod with anchor plate shall be embedded in cement concrete 1:3:6. A stay
shall be provided at all angle and terminal poles. Double stay shall be provided at all dead ends and in such case, these shall be
as far as possible to be set parallel to each other.

Cage guard:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 34/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

All metal supports of overhead lines and metallic fi�ing a�ached shall be permanently and effectively earthed. Cage guard /
cradle guard shall be made of 6 SWG GI wire confirming to IS 2633 including ne�ing, stretching and jointing of cage and lacing
by 10/12 SWG GI wire, binding by 14/16 SWG GI wire.

Danger boards:

All supports carrying HV lines shall be fi�ed with danger plates confirming to IS 2551 at height of 3 M from ground indicating
the voltage of line. The script shall be both in ‘English/Hindi’.

Anti climbing devices:

Necessary arrangement for preventing unauthorized persons from ascending any of the supports and structure carrying HV
lines without the aid of ladder or special appliance shall be made.
 Unless otherwise specified barbed wire confirming to IS 278 having four points barbed spaced 75 +/‑ 12 mm apart shall be
wrapped helically with a pitch of 75 mm around the limb of support and firmly commencing from the height of 3.5 M and up to 5
or 6 M as directed by the engineer.

Lightning arrestor:

Lightning arrestor suitable for HT lines shall be installed one unit per phase at terminations, transformer stations, etc.
The devices shall be connected ahead of fuse provided if any. Independent earth electrode shall be provided for LA.
The earth lead from earth electrode to LA shall be continuous. The LA shall confirm to IS 3070 and shall be non linear
distribution class.
The LA shall be non‑linear type, distribution class, outdoor type suitable for effectively earthed system. The LA shall consist of
line terminal stud, earth terminal stud, number of spark gaps in series with non‑linear resistor, the whole assembly housed inside
a hermetically sealed porcelain bushing.

Neoprene rubber gasket shall be provided between metal caps and porcelain bushing. Non‑linear resistor shall be silicon carbide
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 35/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Neoprene rubber gasket shall be provided between metal caps and porcelain bushing. Non‑linear resistor shall be silicon carbide
blocks metalized at both ends to ensure good electrical contact between terminals, non‑linear resistor & spark gaps.
Mounting bracket shall be hot dip galvanized suitable for mounting LA on structure.

Cable Laying Direct in Ground:

 The method shall be adopted where the cable route is through open country, along road / lanes, etc and where no frequent
excavations are encountered and re excavation is possible without affecting other work.

Width of trenches:

The width of trench for laying single cable shall be 35 cm Where more than one cable are to be laid in the same trench in
horizontal formation, width of trench shall be increased such that the inter‑axial spacing between the cables for 415 volts shall be
20 cm and for 11 shall be 35 cm.

Depth of trenches:

Where cables are laid in single formation, the total depth of trench shall not be less than 75 cm for cable up to 1.1 KV grade and
shall not be less than 120 cm for cable above 1.1 KV grade. Wherever more than one tier formation is unavoidable and vertical
formation is adopted, the depth of trench shall be increased by 30 cm for each additional tier to be formed.

Protective covering:

Cable laid in trenches shall have covering of clean dry sand not less than 170 mm above the base cushion of sand before the
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 36/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Cable laid in trenches shall have covering of clean dry sand not less than 170 mm above the base cushion of sand before the
protective cover is laid.
The cables shall be protected by B class/second class brick of not less than 20 cm x 10 cm x 10 cm or protective cover placed on top
of the sand and both sides of cable for full length of the cable to the satisfaction of Engineer‑in‑charge.

Back filling:

The trenches shall be back filled wit excavated earth free from stones or other scrap edged debris and shall be rammed and
watered, if necessary, in successive layers not exceeding 300 mm unless otherwise specified.

Route marker:

Route marker shall be provided along straight runs of cables and at points of change in direction as approved by Engineer‑in‑
charge and in general at intervals not exceeding 100 meters in straight run. Route marker shall be made out of 100 mm x 100 mm
x 5 mm GI/Al plate bolted or welded on 35 mm x 35 mm x 6 mm MS angle iron of 600 mm long.
Such route markers shall be mounted and grouted parallel to and 0.5 meter away from the side of trench. The work “cable” with
voltage grading and size of cable shall be inscribed on the marker.

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 37/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 38/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/cross‑arm.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 39/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/1.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 40/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/1.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 41/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/2.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 42/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/2.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 43/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/3.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 44/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/3.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 45/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/guy‑strain.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 46/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/guy‑strain.png)

(h�ps://electricalnotes.files.wordpress.com/2011/06/guy‑set.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 47/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 48/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/crimped‑tension.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 49/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 50/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/strain‑insulator.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 51/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 52/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/pipe‑earthing.png)

(h�ps://electricalnotes.files.wordpress.com/2011/06/pin‑ins.png)

https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 53/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/insulator‑pin.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 54/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/insulator‑pin.png)

(h�ps://electricalnotes.files.wordpress.com/2011/06/danger‑board.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 55/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/danger‑board.png)

(h�ps://electricalnotes.files.wordpress.com/2011/06/danger‑board‑11kv.png)
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 56/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(h�ps://electricalnotes.files.wordpress.com/2011/06/danger‑board‑11kv.png)

Advertisements

Tap on video to unmute

Tap on video to unmute

FILED UNDER UNCATEGORIZED

About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical) from Gujarat University. He has more than 14 years
experience in Power Transmission‑Power Distribution‑Electrical energy theft detection‑Electrical Maintenance‑Electrical
Projects(Planning‑Designing‑coordination‑Execution). He is Presently associate with one of the leading business group as a Deputy
Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical

Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for ʺElectrical Mirrorʺ and ʺElectrical Indiaʺ Magazines. He is
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 57/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for ʺElectrical Mirrorʺ and ʺElectrical Indiaʺ Magazines. He is
Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and
help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.

129 Responses to 11KV/415V Overhead Line Specification(REC)

Shona Balaji says:
June 14, 2011 at 6:17 am
excellent

Reply
Eng. Asad says:
March 25, 2013 at 8:36 am
Distance between tow poles of 20KV overhead line.

Reply
karthik says:
September 2, 2011 at 11:52 am
awesome sir.its highly useful for every electrical engineer

Reply
kenny james siame says:
September 19, 2011 at 9:41 pm
Hi, please send me the qoute for the DROP OUT FUSE LINK ASSEMBLY COMPLETE, 11KV.
Give me prices both FOB and CIF Zambia for 300 pieces.
I wait to hear from you.
i thank you in anticipation.
Regards
Kenny.
JSK Co LTD

Reply
Vinay Ghade says:
August 6, 2014 at 8:08 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 58/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

August 6, 2014 at 8:08 pm
Dear Sir ,

i m Vinay Ghade BE electrical engineer having around 7 years experience in designing field. i want to go much deeper in this
field. Any design course you offer or any books that is to be refer.

Reply
dillip kumar garnayak says:
September 14, 2014 at 6:49 pm
good

Reply
vikas says:
October 3, 2011 at 4:09 pm
What should be the minimum spacing between LT overhead conductors ? Is there any IS or IE rule for this.

Reply
Jignesh.Parmar says:
October 6, 2011 at 10:39 am
Yes In both Horizontal congu. and for Vertical confug. 200mm for vertical confu.and 300mm for horizontal confu for P‑P
this is indicate in CPWD noms. Please read my Abstract notes. You will find it.

Reply
vikas says:
October 4, 2011 at 2:31 pm
Is there any IS or IE rule specifying the spacing between two conductors of 415 V overhead line.

Reply
Jignesh.Parmar says:
October 6, 2011 at 10:38 am
Yes In both Horizontal congu. and for Vertical confug. 200mm for vertical confu.and 300mm for horizontal confu for P‑P
this is indicate in CPWD noms. Please read my Abstract notes. You will find it.

Reply
Anuj Bhatnagar says:
October 20, 2011 at 8:45 am
Hi Jignesh,
Can you please send me the drawing and specification of Dead End Clamp and Suspension Clamp.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 59/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Can you please send me the drawing and specification of Dead End Clamp and Suspension Clamp.

Thanks,

Anuj

email:

Reply
M.VENKATA RAO says:
November 20, 2011 at 9:52 am
Dear sir
what is the minium distance from pole to pole in 11kv overhead transmission line?

Reply
Jignesh.Parmar says:
November 27, 2011 at 3:53 pm
Minimum Distance ??? Start from Zero…Normally 25 Meter to 60 Meter according to geographic condition,Type of
Conductor,Type of Pole..

Reply
VASIM SHAIKH says:
November 22, 2011 at 5:09 am
can u plz give me complete details of erection. Right from pole pit dimension to stringing. Looking for a positive reply. thanks

Reply
satheesh says:
December 1, 2011 at 6:02 am
Hello Sir
how to calculate the Drop out Fuse rating for 100 KVA transformer.and formulas..pls tell me

Reply
paulson says:
December 6, 2011 at 10:51 am
how can we terminate a 630KVA transformer y secondary side to LT overhead line.4x400sq.mm cable is required. is there DP
structure required or any other solution?

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 60/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
deepesh sahu says:
January 12, 2012 at 5:43 pm
it is compulsory to use “trinangular configuration in 11kv pole”?

can we use rectangular configuration?
sir plese reply

Reply
M.SATYANARAYANA REDDY says:
January 14, 2012 at 2:19 am
it is compulsary to maintain the 90deg(Straight) angle when 33 kv line crossing the road,any alternatives to road crossing with
above 90 deg(cross)

Reply
vijay says:
February 1, 2012 at 11:18 pm
my station switch yard that is 11/415v lighting arrestor which is ahead of hg fuse set is always busting. and my switch yard is
under 33KV line . please help me out why this was happening

Reply
Pradip says:
February 4, 2012 at 9:39 am
i want to calculation of illumenation of street light scheme 3 kilo meter road length ,wide 15 mtr. pole to pole distance 30 mtr.
total no.of poles. 100 nos pole require.divder (so assume double fi�img .,pole height 9 mtr. ) & how to calulate voltage drop
,cable selections.

Reply
A. ALMOHAMADED says:
February 12, 2012 at 5:41 pm
can i know the max. load of 11kv feeder. and the long

Reply
Jignesh.Parmar says:
February 13, 2012 at 2:24 pm

Depends on:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 61/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Depends on:
(1) Conductor Size (Amp)
(2) Length of line
(3) Permissible Voltage Drop
(4) Type of Load

Reply
k.karthick says:
February 28, 2012 at 11:42 am
wonderful sir,

Reply
Parag says:
April 6, 2012 at 8:06 am
Please provide us total details & drawings for v cross arms, straight cross arms & others.

Thanks,

Reply
Muhammad Farooq Khan says:
June 7, 2012 at 4:50 pm
Hi,
I want to calculate the conductor size of 38 km 11kv OHL. my total load is given in A(KVA) which is 21000KVA.
Please help me out. suggest me a formula and size of conductor.

Reply
Jignesh.Parmar says:
June 8, 2012 at 5:03 pm
Calculate % Regulation from excel sheet given in Excel tools

Reply
Muhammad Farooq Khan says:
June 9, 2012 at 5:15 am
there is no such tool to calculate the Conductor size for OVERHEAD LINE CONDUCTOR.
did ACSR 7/3.40 mm can bear the above given load? for case of 11kv

Reply
Rolly Mondelo says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 62/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Rolly Mondelo says:
June 18, 2012 at 12:17 pm
Dear sir
what is the minimum horizontal and vertical distance from street light pole in a 32 KV overhead transmission line ?

Reply
Rolly Mondelo says:
June 18, 2012 at 1:08 pm
sir, also send me the standard horizontal and vertical clearance in any high voltage transmission line…. thank you and more
power!…

Reply
M.Viswanathan says:
June 22, 2012 at 12:03 pm
Dear Sir,

I required the structural foundation details for the following;
1) DP structure for 11kV line with 250kVA transformer mounted single incomer cum outgoing.
2) and 11kV EB post (RCC)

Reply
sanu says:
August 21, 2012 at 8:22 am
respected sir,
can u please tell me from where i can get rec construction manual.and which publisher is publishing that book.i graetly need that
book.thanks

Reply
Ehsan Ullah says:
September 1, 2012 at 4:30 am
Dear sir,
please tell me the depth of 11 kva pole.

Reply
Jignesh.Parmar says:
September 2, 2012 at 3:31 am
11KVA !!
Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 63/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
Sharad Taide says:
September 21, 2012 at 4:18 pm
Can u please tell me the safest horizontal and vertical distance from the steel shed. height of steel shed is 6m & 8 M

Reply
faucet says:
November 1, 2012 at 7:38 pm
It’s in reality a great and useful piece of info. I am satisfied that you shared this helpful information with us. Please keep us
informed like this. Thanks for sharing.

Reply
M.VENKATA RAO says:
November 2, 2012 at 7:07 am
Sir if phase sequence changes in HT side of transformer then L.T side phase sequence changes or not?

Reply
daniel says:
November 7, 2012 at 11:38 pm
can i hv the diagram or picture of cradle guard?

Reply
wamidhtaha says:
November 10, 2012 at 11:37 am
Dear Sir i need please ( Electrical pole, span, sag, calculation in excel sheet )
if you can send it to my mail
thank you foreward

Reply
srinivas says:
January 9, 2013 at 1:01 pm
Dear sir,
please information Electrical pole, span, sag, calculation in excel sheet ) electrical installation estimating & costing.
Thank you,
Regards,
srinivasulu.R

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 64/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
wamidhtaha says:
January 12, 2013 at 10:47 am
Dear Sirs;
are you can this exel sheet for( Electrical pole, span, sag, calculation)
i necessary need it
i wait your replay in my mail
thank you forward for your a�ention
eng. wamidh / iraq

Reply
Jignesh.Parmar says:
January 12, 2013 at 2:24 pm
Dear wamidhtaha,
I have not such type of Excel Sheet..

Marathi Lekh! arathi Kavita,!arathi vinod says:
January 31, 2013 at 1:06 pm
Magnificent items from you, man. I’ve be aware your stuff prior to and you are simply extremely fantastic. I actually like what
you have bought here, certainly like what you are stating and the way by which you assert it. You’re making it enjoyable and you
continue to care for to stay it smart. I cant wait to learn much more from you. That is actually a wonderful website.

Reply
Chetan Bhavsar says:
March 23, 2013 at 7:43 am
really great great info helped in my project thanks alot……..!!!!!!!!!!!

Reply
Yogesh says:
April 8, 2013 at 10:12 am
Dear All,

In our project, sending end voltage is around 400Volts and receiving end voltage is 360V for 150Meters OH line. Here we are
ge�ing 40 V drop for a very small distance . Let me know the reason for this voltage drop.

Reply
Jignesh.Parmar says:
April 9, 2013 at 6:07 am
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 65/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

April 9, 2013 at 6:07 am
Your question has insufficient information.
1.what is load.(1w..100w…….)
2.which size of over head conductor have you used.

Reply
mahesh says:
April 24, 2013 at 11:58 am
hi,
dis is mahesh
my question:‑ if i want to underground a cable which is already over headed from the street pole to the transformer of rating
250kva, which sqmm cable i have to use?

Reply
Jignesh.Parmar says:
April 25, 2013 at 4:16 pm
Not ge�ing your Point ???

Reply
Er G Singh says:
May 5, 2013 at 3:26 am
Hello Jignesh,
Really useful stuff, can we start a threa about earthing of UG cables?

Reply
Jignesh.Parmar says:
May 5, 2013 at 4:25 am
Already give in the Blog…search in old posts

Reply
AF says:
May 19, 2013 at 9:15 am
Indeed very informative.
A question:
I have seen that the the horizontal distance between the 3 phases (conductors) of 11kV OH line is not same; 2 phases are relatively
closer, as compared to the 3rd one. Does anybody know the reason?

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 66/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
Jignesh.Parmar says:
May 19, 2013 at 10:37 am
Where ?? Horizontal distance should be same in three phase distribution..

Reply
NIKUNJ CHAUHAN says:
May 25, 2013 at 4:42 am
RESPECTED SIR,
IF YOU HAVE NOTES OR EXCEL TOOL ABOUT CALCULATION OF LOAD FLOW ANALYSIS THEN PLEASE UPLOAD IT.
THANK YOU.

Reply
H R Arun says:
June 11, 2013 at 9:45 am
Please provide the sctional drawings of RCC 8.0 Mtr pole, RCC 9.0 Mtr pole, PSC 9.0 Mtr pole

Reply
Rafiq says:
June 22, 2013 at 11:35 am
HI,
How many transformers can be installed in 11/0.4 KV package SUBSTATION/?
Thank You

Reply
dillip kumar garnayak says:
September 14, 2014 at 7:02 pm
HI,
How many transformers can be installed in 11/0.4 KV package SUBSTATION and all transformer calculation

Reply
Ramesh says:
June 27, 2013 at 6:40 am
sir, please send me maintenance schedule double pole isolation unit

Reply
Raja says:
July 20, 2013 at 7:25 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 67/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

July 20, 2013 at 7:25 pm
Really , great use to me

Reply
Prabakaran Balaraman says:
July 25, 2013 at 5:59 pm
sir, plz say about the clearance distance between the pole to pole and also distance between ground surface to conductor

Reply
BHAGWAN SURYAWANSHI says:
August 8, 2013 at 10:03 pm
Tanks for giving that much information I am very happy to read this can i get much more information from you

Reply
Saroja Ranjan Pa anayak says:
August 14, 2013 at 10:13 pm
Dear Sir,

A 11 KV substation is installed on the road at a distance of 5 ft from my residential house and 3 feet from my boundary wall.
Request you to mention the minimum distance that is to be maintained during HV substation installations

Reply
jolly bhatia says:
August 16, 2013 at 7:06 am
Hi
Can u tell me what should be the maximum current which we can get on l t side on 11 kv line and what should be the ra�ing of
the transformer..

Reply
s.ali says:
September 21, 2013 at 6:58 am
time to time i collect information related to my job which stands very helpful for me, thanks, this time i want information
regarding calculation of sag in 11kv transmission line i am diploma engineer in electrical engineering by qualification with
experience.

Reply
vinod says:
October 22, 2013 at 8:56 am
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 68/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

October 22, 2013 at 8:56 am
Whether i can get complete Bill of Material for 11KV switchyard and 11KV overhead transmission line

Reply
M.Y. DESAI says:
October 29, 2013 at 9:33 am
Hi,
Sir.
wheather 415 v multistranded with insulation aluminum conductors for overhead lind available in market, if yes pl.send details.
Thanks.

Reply
utkal mishra says:
November 23, 2013 at 7:25 pm
respected sir
sir please tell me what type of problem will occur if we ll binding a conductor with insulator by AAC in lt line?
regards
er.UTKAL MISHRA

Reply
Badshah Mohideen says:
December 5, 2013 at 5:08 am
Hi Mr. Jignesh,

Congratulate for the website and your excellent effort. I have a doubt, Whether the jumpers can be used as a Isolation point
during outages of 11KV & 33 KV OHL lines i.e. to isolate section of OHL, the jumpers can removed and used as isolation points.

Reply
ankush says:
December 28, 2013 at 6:08 pm
thanks

Reply
Ashok Kr. Thakur says:
December 30, 2013 at 3:01 pm
Hello Mr. Jignesh, Cud u kindly let me know the weight of 6 swg GI wire that is rqd for cage guard of 11kv OHL?

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 69/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
STEWART MAWANA says:
March 27, 2014 at 10:19 am
Hy Mr Jignesh, cld you pliz kindly assist on hw can I calculate cable size when wiring a 600VA
TX which draws 75A at a supply of 0‑240‑230‑180 and 100 and its output is 24Vac

Reply
REHAAN HASSAN says:
April 12, 2014 at 7:30 pm
In rural area and population density is high and locality full with bamboos and large trees in magrahat of south 24 parganas of
west bengal. At these type of places what is the distance between two poles for wring of 440 said lines and also for 220 said lines
as suggested and directed by government. And what measures should be taken.

Reply
angelito cortez says:
June 20, 2014 at 8:39 pm
Good day sir,please can send me the distance of transmission tower 33 kV with wire size 366.2 mm square and what is the
required height of tower use in open area in well site (oil and gas company)

Reply
Mario Enriquez says:
June 23, 2014 at 4:00 pm
Mr. Jignesh,

Currently, 12KV aluminum wires run over a waterway 290 feet, pole‑to‑pole. How much wire sag is there between the poles,
assuming wires have been installed to standard specifications for 12KV distribution? What reduction in wire sag can be expected
if the span is reduced to 220 feet? (Thanks for your impressive site.)

Reply
sunil mane says:
August 24, 2014 at 5:15 pm
I want to know
11 kv conductors types and their current capacity. pl.

Reply
dillip kumar garnayak says:
September 14, 2014 at 6:51 pm
11kva cabule meserment
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 70/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

11kva cabule meserment

Reply
Venu says:
August 25, 2014 at 6:11 am
Hi JIGNESH i need all component list(small components also like fuse) of distribution system from 11kv to 240v please give me a
list

Reply
angelito cortez says:
August 29, 2014 at 8:40 am
Im so glad to thank you its a great great information can i get more information from you.God bless you always.may i know
the drop voltage of different size of cable in every meter.and what is the required size of cable i use for every Kva

Reply
shrikrishna dubey says:
August 31, 2014 at 9:23 am
sir why we are using 9 kv LA in 11 kv system ?

Reply
Hidayat says:
September 4, 2014 at 7:03 pm
what is C&DF test. what is dissipation factor

Reply
D B Dandapat says:
September 9, 2014 at 11:44 am
(i) I have 11 KV O/H distribution line about 1.7 KM (only) and each individual poles are earthed with Earth spikes ( Earth
resistance of each loaction is less than 5 Ohm). But Inspector is insisting us to provide continious earthing for the said O/H line as
per IE rules. I could not traced the same from IE rule book. Expecting your reply and possible help.

(ii) Where dumpers are being operated, what will be the ground clearance (min) for 11 KV O/H line

Reply
imprasad79 says:
September 12, 2014 at 6:32 am

(1) Continuous earth wire of proper size which is solidly earthed at substation is to run all along the route of overhead line. For
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 71/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

(1) Continuous earth wire of proper size which is solidly earthed at substation is to run all along the route of overhead line. For
reason of safety after every fifth span , the pole is to be provided with the earth from the ground. This wire is solidly connected to
the earth provided at the substation and later on every sixth pole is earthed. Galvanized iron wire of 8 SWG or bigger size is used
as earthing conductor. The maximum continuity resistance of earth should not be more than 5 Ohms.

(11) Minimum clearance of conductor above ground while crossing the road or a public through fare for 11 KV is 6.1 Meter and
Vertical Clearance above building if 11 KV line is passing over it is 3.66 Meter .Considering a dumper of Cat 777 OB Dump Truck
(Empty) 100t‑TRK 9780x6105x5147 , its height will be approx 5.2 Meter .

Using all the above mentioned data , Pole of 9 Meter will give enough clearance which suffice your purpose.

Reply
saman says:
October 14, 2014 at 7:57 am
why we are using 3 insulator bracet for 11kVA

Reply
Kaiser Ahmad says:
November 20, 2014 at 6:20 pm
Dear Sir
What should be the working load for a PCC Pole, 9.0 Mtr long with FOS:2.5.
The pole has to be used for 11kV line in a wind pressure zone of 75kg/sqmm.

Reply
ntejeswar says:
November 24, 2014 at 2:38 am
dear sir
this is very useful for me and i want 11kv/0.440kv single line diagram of outdoor sub station

Reply
vinod naik says:
November 24, 2014 at 1:21 pm
sir i want RCC pole standard drawing for all 7.5m , 9m ,11m..

Reply
Dileep Kumar Sahu says:
December 9, 2014 at 11:39 am
What is the meaning of conductor names (ACSR Dog,Rabbit & Weasel)? Do they belong to specific voltage line rating?
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 72/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

What is the meaning of conductor names (ACSR Dog,Rabbit & Weasel)? Do they belong to specific voltage line rating?

Reply
prabir dua says:
December 15, 2014 at 9:56 am
I Politely request you Can you send to me all type of electrical is coad list .

Reply
Vinod Rana says:
January 8, 2015 at 11:12 am
Mr Parmar

This is Rana from Delhi
How much voltage difference is allowed in each phase voltage of 11 KV line.
My incoming voltage is showing R Phase 11000 Volts Y Phase 110100 and B phase is 11500 volts. Is it permissible. the same
corresponding difference i am ge�ing in LT also 415 ,410.400 in each phase.

How to resolve it.

Rgs

Reply
Vinod Rana says:
January 8, 2015 at 11:14 am
PL read 110100 as 11100 volts

Reply
AMAN says:
January 13, 2015 at 2:26 am
THANK YOU.IT IS VERY HELPFUL.

Reply
sakthivel says:
January 21, 2015 at 3:30 am
please tel me the insulator name which used in dp yard

Reply

tkmishra says:
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 73/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

tkmishra says:
January 29, 2015 at 11:13 am
R/s we are engaged in distribution system dealing with 33kv 11 kv and 440 v, working in mpeb (now mppkvvcl we required to
purchase items locally but we don’t have suitable specification book . Can u suggest me some such books

Reply
Samson Paul says:
March 13, 2015 at 10:08 am
Hello,

I really like this article sine this article is so informative for me as I am currently doing my final year project on designing a 11kV
distribution grid exteñsion with the utility company in my country.

Am a final year electrical engineering student at the Papua New Guinea University of Technology.

Am asking if you could help me with my project with necessary information.

Thank you very much.

Reply
rasel says:
March 20, 2015 at 4:04 pm
Would you please inform me what should be the standard height of a 11/. 44kv sub station building as per electrical rules.

Thanks

Reply
Anand Kumar K.S., Sr.Technical officer, Electrical Division, CSIR‑National Aerospace Laboratories, Bangalore says:
March 27, 2015 at 1:41 pm
Dear sir information is very useful to professional engineers

Reply
N.NYNARKUMAR says:
March 31, 2015 at 7:36 am
Dear sir

I would like to thankful to say to that , I am nynarkumar i am working on rggvy project and i have complete in one year, today i
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 74/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

I would like to thankful to say to that , I am nynarkumar i am working on rggvy project and i have complete in one year, today i
am studied in your Rec specifications. it is very valuable information for all site engineers. but i have a small dough for
transformer earthing And LA installation. please give me the valuable answer.

Reply
D.B.V.R.K.S.Sarma says:
May 26, 2015 at 12:11 am
Respected sir
Good morning the information you have provided is useful for every personal who is a�ached with electrical distribution
system, thanks for providing the information, now coming to my doubt i.e I want to know the reason behind maintaining a
distance of 1200 mm in between line support and earthing electrode in distribution system.

Reply
jhulan says:
June 3, 2015 at 8:14 am
How many 9m stp Pole requere 1km 11 kv line

Reply
Kashmira Lal says:
July 3, 2015 at 7:01 am
Dear Jignesh,

Pl.advise for any machine or a�achment used to erect electric poles.

Thanks,
Kashmira

Reply
Dharmendra says:
July 5, 2015 at 4:11 am
Good

Reply
MUKESH KUMAR says:
July 7, 2015 at 1:56 pm

Dear Jignesh,
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 75/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Dear Jignesh,
I saw a pair of shield or ground wire strung/ running below phase conductors in 11 KV overhead power line. Is this required in a
3 phase 11 KV/ 415 volts overhead distribution lines/ street lighting utility poles also; specially on street crossing? I don’t see one
in my locality. Please clarify.

Reply
D.Sarma says:
July 12, 2015 at 3:54 pm
ThoseTho may be guard wires, provided to protect the beneath area when the line conductor cuts because of over loading or
any kind of damage.

Reply
Amit Gupta says:
July 10, 2015 at 7:11 am
How to locate a fault in 11 KV OH line easily. The Line is running through farmers’ land and some of tree touches the OH line
cause earth fault or/and over current fault result in triping the system.

Reply
N.Vignesh says:
July 17, 2015 at 4:07 am
Sir,
I need sag calculation format, kindly reply as soon as possible

Reply
Samson Paul says:
July 18, 2015 at 4:13 am
Hello sir,

Can you please tell me the maximum demand a 11kV can be able to supply?

Reply
sanjoo rawat says:
August 2, 2015 at 12:05 pm
sir,
In LT distribution we are using bamboo seperators. but why in the rainy season LT line got short circuit. can you explain and
help me.

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 76/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
nomi says:
August 27, 2015 at 9:01 pm
In transmission we use insulators of brown colour …. what is the purpose of making the insulator in brown colour?… ans?

Reply
nomi says:
August 27, 2015 at 9:03 pm
can we use white colour insulators in transmission line?

Reply
Himanshu Bansal says:
September 19, 2015 at 8:36 pm
Sir, is there any standard for power transmission and distribution capacity for overhead lines at various voltage levels?

Reply
Ramesh says:
October 18, 2015 at 8:10 am
Dear sir
May i know the transmission line pole/tower heights for different voltage levels i.e starts from 11kVto 400kV

Reply
Reetesh agarwal says:
December 30, 2015 at 3:12 pm
Kind a�n: The Project Purchase Manager

Dear Sir,

AXIS an ISO9001 co is engaged in manufacturing and exports of wide range of

Electrical components and fi�ings

The products manufactured and supplied by AXIS are

Cable lugs‑Copper/Aluminium/Bimetallic –
Brass Cable Glands‑
Ground rods – Copper Bonded /Pure Cu/SS/Galv Steel

Ground Clamps,accessories,Earthing tapes and Conductors
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 77/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Ground Clamps,accessories,Earthing tapes and Conductors
Lightning protection fi�ings –
Exothermic weld Materials
SS cable ties and tags
OH line Clamps and Connectors
Pole line Hardware‑11KV,33KV & 1.1KV
All the above products are manufactured to international standards.

Currently our products are exported to @ 57 countries

A�ached pls find our product profile

We wish to supply range of electrical products to your company’s Various Electrical Projects.

If you have any requirements on above listed products,please do contact us with your enquiry

——————————————————————————–

Thanks and regards

Reetesh Agarwal‑Manager

Axis Electricals Components (I) P. LTD.
Axis House
Plot 104C, Kandivali Co‑op Industrial Estate Ltd.
Kandivali (w),Mumbai‑400 067, India
Tel: +91 22 28696636
Fax: +91 22 28678491
Web : h�p://www.axis‑india.com

Reply
Upnesh sood says:
January 26, 2016 at 8:45 am
diploma in elec. engg.

Reply
Baka says:

March 2, 2016 at 11:00 pm
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 78/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

March 2, 2016 at 11:00 pm
What’s the effect of an 11kv overhead line touching a 415v overhead line

Reply
Olovie Charles Emem says:
March 30, 2016 at 7:44 am
very good work

Reply
arun sharma says:
April 15, 2016 at 11:42 am
Generally which type of conductor will use in LT overhead line form distribution transformer and its current caring capacity.
Above details are required for 100 KVA DTs and 400 KVA DTs

Reply
Ahmed says:
April 19, 2016 at 11:19 pm
Mr. Jagnesh

Can you please tell me what is the safe distance or clearance level from the EMF produce by 11KV transmission lines, with
respect of condensate tanks crossing under the lines.

Regards

Ahmed

Reply
MOHAMMAD IQBAL WANI says:
April 29, 2016 at 11:31 am
SIR, I HAVE SEARCHED ABOUT LT EARTHING ROD AS PER f5 AND f10 DRAWING OF REC BUT I DID NOT FIND IT
KINDLY HEELP ME

Reply
VipinPeter says:
April 30, 2016 at 6:03 am
What will be the common steel section used for the cross arms of a 11kv monopole line……?

Reply
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 79/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

Reply
Gautam Parmar says:
May 16, 2016 at 9:55 am
Hello sir I m Gautam Parmar want to meet u in ahmedabad so pl.give me ur office adress.Txs

Reply
swarup bandurao sarode says:
June 26, 2016 at 3:58 am
It is very usefull

Reply
Debasis Bha acharya says:
July 19, 2016 at 5:05 am
Dear Mr. Jignesh
Can you provide me any Format / process for recording T & D loss in Feeder Separation scheme. Will be obliged to have a li�le
guidance on this. Regards.

Reply
Virupanna Kumbar Viru says:
August 31, 2016 at 2:28 pm
HI,, WHAT IS THE MAXIMUM SPAN LENGTH BETWEEN TWO POLES OF 11KV SYSTEM?

Reply
Zafar Iqbal says:
September 2, 2016 at 4:58 pm
What a lovely nd learn able link
I love it

Reply
Sanjeev Sharma says:
September 3, 2016 at 2:55 pm
Dear Sir, i am encountring a problem of reoccouring of extraordinary CT meter panel blast every 4‑5 months.No local expert in
electrical could diagnose the fault reoccurance. Can you help me some way ………Sanjeev 09876363863 ( Chandigarh).

Reply
Ambuja garnaik says:
September 7, 2016 at 7:32 am
very good,but it not mention the direction of v‑cross arm towards dtr/where the line goes from tapping point.
https://electricalnotes.wordpress.com/2011/06/08/11kv415v­overhead­line­specification­rec/ 80/82
5/20/2017 11KV/415V Overhead Line Specification(REC) | Electrical Notes & Articles

very good,but it not mention the direction of v‑cross arm towards dtr/where the line goes from tapping point.

Reply
dinesh saini says:
September 9, 2016 at 3:28 am
Awesome notes for electrical engineers

Reply
nagendra mathur says:
December 1, 2016 at 9:02 am
Great article. Thanks .
Is there any limit to the size of the conductor/ power that can be transmi�ed over 11 KV overhead line or any guideline regarding
this aspect from REC or any statutory body

Reply
Atanu Pa anayak says:
January 20, 2017 at 12:41 pm
hi sir,
can u provide me a full required items detials with diagram with marking of the items of 9 mtr psc poles with 2phase 2w line

Reply
soundarrajan.a says:
January 29, 2017 at 1:02 pm
Exlant use

Reply
Md Irfan Khan says:
February 25, 2017 at 5:40 am
Dear Sir,

Its very useful article for practical work at site.

As mentioned about the Anti‑climbing device about the barbed wire does it needs any clip or clamping arrangement or it can be
tied to itself.

If possible please send and image.