Electrical Apparatus
Three-Phase Pad-mounted
Compartmental Type Transformer 210-12
GENERAL
At Cooper Power Systems, we are
constantly striving to introduce new
innovations to the transformer industry,
bringing you the highest quality, most
reliable transformers. Cooper Power
Systems Transformer Products are ISO
9001 compliant, emphasizing process
improvement in all phases of design,
manufacture, and testing. In order to
drive this innovation, we have invested
both time and money in the Thomas A.
Edison Technical Center, our premier
research facility in Franksville,
Wisconsin. Headquarters for the
Systems Engineering Group of Cooper
Power Systems, such revolutionary
products as distribution-class
UltraSIL™ Polymer-Housed
Evolution™ surge arresters and
Envirotemp™ FR3™ fluid have been
developed at our Franksville lab.
With transformer sizes ranging from 45
kVA to 12 MVA and high voltages
ranging from 2400 V to 46 kV, Cooper
Power Systems has you covered. From
fabrication of the tanks and cabinets to
winding of the cores and coils, to
production of arresters, switches, tap
changers, expulsion fuses, current limit
fuses, bushings (live and dead) and
molded rubber goods, Cooper Power Figure 1.
Systems does it all. Cooper Power Three-phase pad-mounted transformer.
Systems transformers are available with
our patented Envirotemp FR3 fluid, a
less-flammable and bio-degradable Product Scope
fluid or electrical grade mineral oil.
Electrical codes recognize the Type Three Phase, 50 or 60 Hz, 65 ºC Rise
advantages of using Envirotemp FR3 (55 ºC, 55 ºC/65 ºC)
fluid both indoors and outdoors for fire Fluid Type Envirotemp™ FR3™ or Mineral oil
sensitive applications. Envirotemp FR3
fluid-filled units meet Occupational Size 45 – 12,000 kVA
Safety and Health Administration Primary Voltage 2, 400 – 46,000 V
(OSHA) and Section 450.23 NEC
Requirements. Secondary Voltage 208Y/120 V to 14,400 V
Inverter/Rectifier Bridge
K-Factor (up to K-19)
Vacuum Fault Interrupter (VFI)
UL Listed & Labeled and Classified
Specialty Designs
Factory Mutual (FM) Approved
Solar/Wind Designs
Differential Protection
Seismic Applications (including OSHPD)
low-Voltage
Bushing
Low-voltage
molded epoxy
bushings with
NEMA spades
Low-
LOADBREAK switch Voltage
Bushing
support
High-Voltage Bushing
SILL
Suitable for skidding, 5-position tap changer REMOVable
rolling, and jacking Cabinet walls
2
210-12
TABLE 1
Three-Phase Ratings
Three-Phase 50 or 60Hz
kVA Available1:
45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, 5000, 7500, 10000, 120000
1Transformers are available in the standard ratings and configurations shown or can be customized to meet specific needs.
TABLE 2
Audible Sound Levels
NEMA TR-1 Average
Self-Cooled, Two Winding kVA Rating Decibels (dB)
45-500 56
501-700 57
701-1000 58
1001-1500 60
1501-2000 61
2001-2500 62
2501-3000 63
3001-4000 64
4001-5000 65
5001-6000 66
6001-7500 67
7501-12000 68
TABLE 3
Insulation Test Levels
kV BIL
Induced Test 180 or 400
KV Class Hz 7200 Cycle Distribution Applied Test 60Hz (kV)
1.2 30 10
2.5 45 15
5 60 19
8.7 75 26
15 95 34
TWICE RATED VOLTAGE
25 (grd Y Only) 125 40
25 150 50
34.5 (grd Y Only) 125 40
34.5 150 70
46 200 95
TABLE 4
Temperature Rise Ratings 0-3300 Feet (0-1000 meters)
Standard Optional
Unit Rating (Temperature Rise Winding) 65 ºC 55 °C, 55/65 ºC
Ambient Temperature Max 40 ºC 50 ºC
Ambient Temperature 24 Hour Average 30 ºC 40 ºC
Temperature Rise Hotspot 80 ºC 65 ºC
3
Three-Phase Pad-mounted Compartmental Type Transformer
A*
H
F-3
3.5"
I-3
D E I
F C G
Figure 3.
Transformer and Pad dimensions.
* Add 9" for Bay-O-Net fusing.
TABLE 5
Fluid-filled - aluminum windings 55/65°C Rise1
65° Rise DEAD-FRONT -LOOP OR RADIAL FEED -BAY-O-NET FUSING OIL FILLED -ALUMINUM WINDINGS
OUTLINE DIMENSIONS (in.) Gallons of Approx. Total
kVA Rating A* B C D E F G H I Fluid Weight (lbs.)
45 50 68 39 42 26 68 72 43 20 150 2,600
75 50 68 39 42 26 68 72 43 20 160 2,800
112.5 50 68 49 42 26 68 72 53 20 165 2,900
150 50 68 49 42 26 68 72 53 20 170 3,350
225 50 72 51 42 30 72 76 55 20 180 3,800
300 50 72 51 42 30 72 76 55 20 190 4,450
500 50 89 53 42 30 72 93 57 20 240 5,700
750 64 89 57 42 30 72 93 61 20 380 8,200
1000 64 89 59 42 30 72 93 63 20 480 10,100
1500 73 89 86 42 30 72 93 90 24 570 13,950
2000 73 72 87 42 30 72 76 91 24 640 15,000
2500 73 72 99 42 30 72 76 103 24 760 18,850
3000 73 84 99 46 37 84 88 103 24 780 19,000
3750 84 85 108 47 38 85 88 112 24 800 19,500
5000 84 96 108 48 48 96 100 112 24 930 29,400
7500 94 102 122 54 48 102 100 126 24 1,580 41,900
1 Weights, gallons of fluid and dimensions are for reference only, and not for construciton. Please contact Cooper Power Systems for exact dimensions.
* Add 9" for Bay-O-Net fusing.
TABLE 6
Fluid-Filled - Copper Windings 55/65°C Rise1
65° Rise DEAD-FRONT -LOOP OR RADIAL FEED -BAY-O-NET FUSING OIL FILLED -COPPER WINDINGS
OUTLINE DIMENSIONS (in.) Gallons Approx. Total
kVA Rating A* B C D E F G H I of Fluid Weight (lbs.)
45 50 64 39 34 30 64 69 43 20 160 2,900
75 50 64 39 34 30 64 69 43 20 170 3,100
112.5 50 64 49 34 30 64 69 53 20 175 3,200
150 50 64 49 34 30 64 69 53 20 180 3,650
225 50 64 51 34 30 64 73 55 20 190 4,100
300 50 64 51 34 30 64 75 55 20 200 4,750
500 50 81 53 34 30 64 85 57 20 250 6,000
750 64 89 57 42 30 72 93 61 20 390 8,600
1000 64 89 59 42 30 72 93 63 20 500 10,500
1500 73 89 86 42 30 72 93 90 24 590 14,350
2000 73 72 87 42 30 72 76 91 24 660 15,800
2500 73 72 99 42 30 72 76 103 24 790 19,450
3000 73 84 99 46 37 84 88 103 24 800 19,800
3750 84 85 108 47 38 85 88 112 24 840 20,500
5000 84 96 108 48 48 96 100 112 24 970 36,400
7500 94 102 122 54 48 102 100 126 24 1620 46,900
1 Weights, gallons of fluid and dimensions are for reference only, and not for construciton. Please contact Cooper Power Systems for exact dimensions.
* Add 9" for Bay-O-Net fusing.
4
210-12
5
Three-Phase Pad-mounted Compartmental Type Transformer
Overvoltage Protection
Distribution-, Intermediate-, or,
Station-class surge arresters
Elbow arresters (for dead-front
connections)
6
210-12
7
Three-Phase Pad-mounted Compartmental Type Transformer
independent single-phase initiation, but SPECIAL APPLICATION with valuable information, leading to
is three-phase mechanically gang- scheduled repair or replacement, and
tripped. A trip signal on any phase will TRANSFORMERS minimizing the duration and expense of
open all three phases. This feature Data Center Transformer an outage. With a dry-type transformer,
eliminates single-phasing of three there is no reliable way to measure the
phase loads. It also enables the VFI With focus rapidly shifting from simply health or likelihood of an impending
breaker to be used as a three-phase maximizing uptime and supporting failure.
load break switch. demand to improving energy utilization,
the data center industry is continually Solar Transformer
Due to the resettable characteristics of looking for methods to increase its As a result of the increasing number of
the VFI breaker, restoring three-phase energy efficiency and reliability. Utilizing states that are adopting aggressive
service is faster and easier. cutting edge technology, Cooper Renewable & Alternative Energy
The sealed visible break window and Power Systems' Hardened Data Portfolio Standards, the solar energy
switch is an option that can be Center (HDC) transformers are the market is growing - nearly doubling
installed to provide visible break solution. Designed with special year over year. Cooper Power
contact. This feature provides attention given to surge protection, Systems, a key innovator and supplier
enhanced safety and allows an HDC liquid-filled transformers provide in this expanding market, is proud to
operator to see if the loadbreak switch superior performance under the offer Envirotran transformers
contacts are in an open or closed harshest electrical environments. specifically designed for Solar
position before performing Contrary to traditional dry-type units, Photovoltaic medium-voltage
maintenance. HDC transformers provide applications. Cooper Power Systems is
unsurpassed reliability, overloadability, working with top solar photovoltaic
Envirotran FM Approved Special operational life, efficiency, thermal developers, integrators and inverter
Protection Transformer loading and installed footprint. These manufacturers to evolve the industry
The Envirotran transformer from Cooper Power Systems units have and change the way we distribute
Cooper Power Systems is FM reliably served more than 750MW of power.
Approved and suitable for indoor critical data center capacity for a total
of more than 4,000,000 hours without In accordance with this progressive
locations. Factory Mutual Research stance, every Cooper Envirotran Solar
Corporation’s (FMRC) approval of the an hour of downtime.
transformer is filled with non-toxic,
Envirotran transformer line makes it The top priority in data center biodegradable Envirotemp FR3
easy to comply with and verify operations is uninterrupted service. dielectric fluid, made from renewable
compliance with Section 450.23, 2008 Envirotran HDC transformers from seed oils. On top of its
NEC, Less-Flammable Liquid-Filled Cooper Power Systems, having biodegradability, FR3 fluid substantially
Transformer Requirements for both substantially higher levels of insulation, extends the life of the transformer
indoor and outdoor locations. are less susceptible to voltage surges. insulation, saving valuable resources.
Envirotran FM Approved transformers Cooper Power Systems has What better way to distribute green
offer the user the benefit of a experienced zero failures due to power than to use a green transformer.
transformer that can be easily specified switching transients. The ANSI/IEEE In fact, delaying conversion to
to comply with NEC, and makes FM standard impulse withstand ratings are Envirotran transformers places the
Safety Data Sheet compliance simpler, higher for liquid-filled transformers, burden of today’s environmental issues
while also providing maximum safety making them less susceptible to onto tomorrow’s generations. Cooper
and flexibility for both indoor and insulation failure. The Envirotran HDC can help you create a customized
outdoor installations. transformer provides ultimate transformer, based on site specific
protection by increasing the BIL rating characteristics including: temperature
Because the “FM Approved” logo is one level higher than standard liquid- profile, site altitude, solar profile and
readily visible on the transformer and filled transformer ratings. The cooling required system life. Some of the
its nameplate, NEC compliance is now system of liquid-filled transformers benefits gained from this custom rating
easily verifiable by the inspector. provides better protection from severe include:
Envirotran FM Approved transformers overloads - overloads that can lead to
are manufactured under strict compli- significant loss of life or failure. Reduction in core losses
ance with FMRC Standard 3990, and Data center design typically includes Improved payback on investment
are filled with FM Approved Envirotemp multiple layers of redundancy, ensuring
FR3 fire-resistant dielectric coolant. Reduction in footprint
maximum uptime for the critical IT
load. When best in class transformer Improved fire safety
manufacturing lead times are typically Reduced environmental impact
weeks, not days, an unexpected
transformer failure will adversely affect For the solar photovoltaic industry,
the facility’s reliability and profitability. Cooper Power Systems is offering
Therefore, the ability to determine the standard step up transformers and
electrical and mechanical health of a dual secondary designs.
transformer can reduce the probability
of costly, unplanned downtime.
Routine diagnostic tests, including key
fluid properties and dissolved gas
analysis (DGA), can help determine the
health of a liquid-filled transformer.
Although sampling is not required for
safe operation, it will provide the user
8
210-12
9
Three-Phase Pad-mounted Compartmental Type Transformer
10
210-12
11
Three-Phase Pad-mounted Compartmental Type Transformer
12