Distribution Transformers

Electrical Apparatus 
Three-Phase Pad-mounted
Compartmental Type Transformer 210-12
GENERAL
At Cooper Power Systems, we are
constantly striving to introduce new
innovations to the transformer industry,
bringing you the highest quality, most
reliable transformers. Cooper Power
Systems Transformer Products are ISO
9001 compliant, emphasizing process
improvement in all phases of design,
manufacture, and testing. In order to
drive this innovation, we have invested
both time and money in the Thomas A.
Edison Technical Center, our premier
research facility in Franksville,
Wisconsin. Headquarters for the
Systems Engineering Group of Cooper
Power Systems, such revolutionary
products as distribution-class
UltraSIL™ Polymer-Housed
Evolution™ surge arresters and
Envirotemp™ FR3™ fluid have been
developed at our Franksville lab.
With transformer sizes ranging from 45
kVA to 12 MVA and high voltages
ranging from 2400 V to 46 kV, Cooper
Power Systems has you covered. From
fabrication of the tanks and cabinets to
winding of the cores and coils, to
production of arresters, switches, tap
changers, expulsion fuses, current limit
fuses, bushings (live and dead) and
molded rubber goods, Cooper Power Figure 1.
Systems does it all. Cooper Power Three-phase pad-mounted transformer.
Systems transformers are available with
our patented Envirotemp FR3 fluid, a
less-flammable and bio-degradable Product Scope
fluid or electrical grade mineral oil.
Electrical codes recognize the Type Three Phase, 50 or 60 Hz, 65 ºC Rise
advantages of using Envirotemp FR3 (55 ºC, 55 ºC/65 ºC)
fluid both indoors and outdoors for fire Fluid Type Envirotemp™ FR3™ or Mineral oil
sensitive applications. Envirotemp FR3
fluid-filled units meet Occupational Size 45 – 12,000 kVA
Safety and Health Administration Primary Voltage 2, 400 – 46,000 V
(OSHA) and Section 450.23 NEC
Requirements. Secondary Voltage 208Y/120 V to 14,400 V
Inverter/Rectifier Bridge
K-Factor (up to K-19)
Vacuum Fault Interrupter (VFI)
UL Listed & Labeled and Classified
Specialty Designs
Factory Mutual (FM) Approved
Solar/Wind Designs
Differential Protection
Seismic Applications (including OSHPD)

1111 • Supersedes 0398 1


Three-Phase Pad-mounted Compartmental Type Transformer

bay-o-net LIQUID LEVEL GAUGE nameplate


drip shield
fusing laser – scribed anodized aluminum

low-Voltage
Bushing
Low-voltage
molded epoxy
bushings with
NEMA spades

Low-
LOADBREAK switch Voltage
Bushing
support

High-Voltage Bushing

SILL
Suitable for skidding, 5-position tap changer REMOVable
rolling, and jacking Cabinet walls

parking stand Ground pad and strap for x0


Figure 2.
Three-phase pad-mounted compartmental type transformer.

2
210-12

TABLE 1
Three-Phase Ratings
Three-Phase 50 or 60Hz
kVA Available1:
45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, 5000, 7500, 10000, 120000
1Transformers are available in the standard ratings and configurations shown or can be customized to meet specific needs.

TABLE 2
Audible Sound Levels
NEMA TR-1 Average
Self-Cooled, Two Winding kVA Rating Decibels (dB)
45-500 56
501-700 57
701-1000 58
1001-1500 60
1501-2000 61
2001-2500 62
2501-3000 63
3001-4000 64
4001-5000 65
5001-6000 66
6001-7500 67
7501-12000 68

TABLE 3
Insulation Test Levels
kV BIL
Induced Test 180 or 400
KV Class Hz 7200 Cycle Distribution Applied Test 60Hz (kV)
1.2 30 10
2.5 45 15
5 60 19
8.7 75 26
15 95 34
TWICE RATED VOLTAGE
25 (grd Y Only) 125 40
25 150 50
34.5 (grd Y Only) 125 40
34.5 150 70
46 200 95

TABLE 4
Temperature Rise Ratings 0-3300 Feet (0-1000 meters)
Standard Optional
Unit Rating (Temperature Rise Winding) 65 ºC 55 °C, 55/65 ºC
Ambient Temperature Max 40 ºC 50 ºC
Ambient Temperature 24 Hour Average 30 ºC 40 ºC
Temperature Rise Hotspot 80 ºC 65 ºC

3
Three-Phase Pad-mounted Compartmental Type Transformer

A*
H
F-3

3.5"

I-3
D E I
F C G

B CABINET/TANK DIMENSIONS PAD DIMENSIONS

Figure 3.
Transformer and Pad dimensions.
* Add 9" for Bay-O-Net fusing.

TABLE 5
Fluid-filled - aluminum windings 55/65°C Rise1
65° Rise DEAD-FRONT -LOOP OR RADIAL FEED -BAY-O-NET FUSING OIL FILLED -ALUMINUM WINDINGS
OUTLINE DIMENSIONS (in.) Gallons of Approx. Total
kVA Rating A* B C D E F G H I Fluid Weight (lbs.)
45 50 68 39 42 26 68 72 43 20 150 2,600
75 50 68 39 42 26 68 72 43 20 160 2,800
112.5 50 68 49 42 26 68 72 53 20 165 2,900
150 50 68 49 42 26 68 72 53 20 170 3,350
225 50 72 51 42 30 72 76 55 20 180 3,800
300 50 72 51 42 30 72 76 55 20 190 4,450
500 50 89 53 42 30 72 93 57 20 240 5,700
750 64 89 57 42 30 72 93 61 20 380 8,200
1000 64 89 59 42 30 72 93 63 20 480 10,100
1500 73 89 86 42 30 72 93 90 24 570 13,950
2000 73 72 87 42 30 72 76 91 24 640 15,000
2500 73 72 99 42 30 72 76 103 24 760 18,850
3000 73 84 99 46 37 84 88 103 24 780 19,000
3750 84 85 108 47 38 85 88 112 24 800 19,500
5000 84 96 108 48 48 96 100 112 24 930 29,400
7500 94 102 122 54 48 102 100 126 24 1,580 41,900
1 Weights, gallons of fluid and dimensions are for reference only, and not for construciton. Please contact Cooper Power Systems for exact dimensions.
* Add 9" for Bay-O-Net fusing.

TABLE 6
Fluid-Filled - Copper Windings 55/65°C Rise1
65° Rise DEAD-FRONT -LOOP OR RADIAL FEED -BAY-O-NET FUSING OIL FILLED -COPPER WINDINGS
OUTLINE DIMENSIONS (in.) Gallons Approx. Total
kVA Rating A* B C D E F G H I of Fluid Weight (lbs.)
45 50 64 39 34 30 64 69 43 20 160 2,900
75 50 64 39 34 30 64 69 43 20 170 3,100
112.5 50 64 49 34 30 64 69 53 20 175 3,200
150 50 64 49 34 30 64 69 53 20 180 3,650
225 50 64 51 34 30 64 73 55 20 190 4,100
300 50 64 51 34 30 64 75 55 20 200 4,750
500 50 81 53 34 30 64 85 57 20 250 6,000
750 64 89 57 42 30 72 93 61 20 390 8,600
1000 64 89 59 42 30 72 93 63 20 500 10,500
1500 73 89 86 42 30 72 93 90 24 590 14,350
2000 73 72 87 42 30 72 76 91 24 660 15,800
2500 73 72 99 42 30 72 76 103 24 790 19,450
3000 73 84 99 46 37 84 88 103 24 800 19,800
3750 84 85 108 47 38 85 88 112 24 840 20,500
5000 84 96 108 48 48 96 100 112 24 970 36,400
7500 94 102 122 54 48 102 100 126 24 1620 46,900
1 Weights, gallons of fluid and dimensions are for reference only, and not for construciton. Please contact Cooper Power Systems for exact dimensions.
* Add 9" for Bay-O-Net fusing.

4
210-12

STANDARD features Tank/Cabinet Features


Connections and  Bolted cover for tank access (45-
Neutral 1750 kVA)
Configurations  Welded cover with hand hole
(2000-12,000 kVA)
 Delta - Wye: Low voltage neutral
 Three-point latching door for
shall be a fully insulated X0 bushing
with removable ground strap. security
  Removable sill for easy installation
Grounded Wye-Wye: High voltage
neutral shall be internally tied to the  Lifting lugs (4)
low voltage neutral and brought out 
as the H0X0 bushing in the Stainless steel cabinet hinges &
secondary compartment with a mounting studs
removable ground strap.  Steel divider between HV and LV
 Delta-Delta: Transformer shall be compartment
provided without a neutral bushing.  20” Deep cabinet (45-1000 kVA)
 Wye-Wye: High voltage neutral  24” Deep cabinet (1500-7500 kVA)
shall be brought out as the H0  30” Deep cabinet (34.5/19.92 kV)
bushing in the primary
compartment and the low voltage  Pentahead Captive Bolt
neutral shall be brought as the X0- 
bushing in the secondary Stainless steel 1-hole ground pads
compartment. (45-500 kVA)
 Stainless steel 2-hole ground pads
 Wye-Delta: High voltage neutral
shall be brought out as the H0 (750-10,000 kVA)
bushing in the primary  Parking Stands
compartment. No ground strap
shall be provided (line to line rated Valves/Plugs
fusing is required).  One-inch upper filling plug
High and Low Voltage  One-inch drain plug (45-500 kVA)
Bushings  One-inch combination drain valve
 200 A bushing wells (15, 25, 35 kV) with sampling device in low voltage
compartment (750-12,000 kVA)
 200 A, 35 kV Large Interface
 Automatic pressure relief valve
 600 A (15, 25, 35 kV) Integral
bushings (dead-front) Nameplate
 Electrical-grade wet-process  Laser-scribed anodized aluminum
porcelain bushings (live-front) Nameplate

Figure 4 Figure 5 Figure 6


Drain valve with sampler. Automatic Pressure relief valve Liquid level gauge

5
Three-Phase Pad-mounted Compartmental Type Transformer

optional FEATURES Switches Metering / Fan / Control


High and Low Voltage  One, two or three On/Off loadbreak  Full metering package
Bushings switches  Current Transformers (CT’s)
 4-position loadbreak V-blade
 200 A (15, 25 kV) bushing inserts  Metering Socket
switch or T-blade switch
 200 A (15, 25 kV) feed thru inserts  NEMA 4 Control Box (Optional
 Delta-wye switch Stainless Steel)
 200 A (15, 25 kV) (HTN) bushing  3-Position V-Blade selector switch  NEMA 7 Control Box (Explosion
wells with removable studs
 100 A, 150 A, 300 A Tap Changers Proof)
 High-voltage 600 A (15, 25, 35 kV)
deadbreak one-piece bushings  Dual voltage switch  Fan Packages
 Low voltage 6-, 8-, holes spade Gauges and Devices Testing
 Low voltage 12-, 16-, 20, holes  Liquid level gauge (Optional  Customer Test Witness
spade (750-2500 kVA) Contacts)  Customer Final Inspection
 Low voltage bushing supports  Pressure vacuum gauge (Optional  Zero Sequence Impedance Test
Contacts and Bleeder)
Tank/Cabinet Features  Heat Run Test
 Dial-type thermometer (Optional
 Stainless steel tank base & cabinet  ANSI Impulse Test
Alarm Contacts)
 Stainless steel tank base, cabinet   Audible Sound Level Test
Cover mounted pressure relief
sides & sill device  RIV (Corona) Test
 100% Stainless Steel Unit  Ground connectors  Dissolved Gas Analysis (DGA) Test
 Service entrance (2 inch) in sill or  Hexhead captive bolt  8 or 24 Hour Leak Test
cabinet side
 Breaker mounting provisions
 Touch-up paint (domestic) Coatings (Paint)
 Copper Ground Bus Bar
Overcurrent Protection  ANSI Bell Green
 Bay-O-Net fusing (Current sensing,
 Kirk-Key Provisions  ANSI #61 Light Gray
dual sensing, dual element, high
 Nitrogen Blanket amp overload)  ANSI #70 Sky Gray
 Bus duct cutout  Bay-O-Net expulsion fuse in series  Special paint available per request

Special Designs with a partial range under-oil ELSP Nameplate


current limiting fuse (below 23 kV)
 Factory Mutual (FM)  Stainless Steel Nameplate
 Cartridge fusing in series with a
 UL Classified partial range under-oil ELSP current
limiting fuse (above 23 kV) Decals and Labels
 Triplex  High voltage warning signs
 MagneX™ Interrupter with ELSP
 High altitude current limiting fuse  Mr. Ouch
 K-Factors  Kyle™ Vacuum Fault Interrupter  Bi-Lingual Warning
 Step-up (VFI)  DOE Compliant
 Critical Application  Visible Break Window  Customer stock code
 Modulation Transformers  Fuse/switch interlock  Customer stenciling
 Seismic Applications (including Valves/Plugs  Shock and Arc Flash Warning Decal
OSHPD)
 Drain/sampling valve in high-volt-  Non-PCB Decal
age compartment
 Globe type upper fill valve

Overvoltage Protection
 Distribution-, Intermediate-, or,
Station-class surge arresters
 Elbow arresters (for dead-front
connections)

6
210-12

CONSTRUCTION Tanks life cycle assessment software utilized


by the US Dept. of Commerce reports
Transformer tanks are designed for
Core that Envirotemp FR3 fluid’s overall
high strength and ease of handling, environmental performance impact
The three-legged, step-lap mitered installation, and maintenance. Tanks score (results from adding the impacts
core construction is manufactured are welded using precision-cut, hot of water intake, smog, ozone
using a high-quality cutting machine. rolled, pickled and oiled steel. They are depletion, indoor air, human health,
For maximum efficiency, cores are sealed to protect the insulating fluid habitat alteration, global warming,
precisely stacked, virtually eliminating and other internal components. fossil fuel depletion, eutrophication,
gaps in the corner joints. Transformer tanks are pressure-tested ecological toxicity, critical air pollutants,
Five-legged wound core or shell-type to withstand 7 psig without permanent and acidification) is 1/4th that reported
triplex designs are used for wye-wye distortion and 15 psig without rupture. for mineral oil (and that’s without
connected transformers, and other consideration for Envirotemp FR3
Tank Finish
special transformer designs. fluid’s transformer insulation life
An advanced multi-stage finishing extending properties). FR3 fluid has
Cores are manufactured with precision process exceeds ANSI/IEEE Std also earned the distinction of having
cut, burr-free, grain-oriented silicon C57.12.28™ standards. The eight- received the first published EPA
steel. Many grades of core steel are stage pre-treatment process assures Environmental Technology Verification
available for optimizing core loss coating adhesion and retards of transformer materials. The green tint
efficiency. corrosion. It converts tank surfaces to reflects its favorable environmental
Coils a nonmetallic, water insoluble iron profile and readily distinguishes it from
phosphate coating. petroleum based oils. Envirotemp FR3
Pad-Mounted transformers feature a fluid is FM global Approved and
rectangular coil configuration with wire- The paint method consists of two Underwriters Laboratories Classified
wound, high-voltage primaries and distinct layers of paint. The first is an “Less-Flammable” per NEC Article
sheet-wound secondaries. The design epoxy primer (E-coat) layer which 450-23, fitting the definition of a Listed
minimizes axial stress developed by provides a barrier against moisture, salt Product per NEC.
short circuits and provides for and corrosives. The two-component
magnetic balancing of tap urethane final coat seals and adds
connections. ultraviolet protection.
Coils are wound using the highest Vacuum Processing
quality winding machines providing Transformers are dried and filled with
exacting tension control and conductor filtered insulating fluid under vacuum,
placement for superior short-circuit while secondary windings are
strength and maximum efficiency. energized. Coils are heated to drive out
Extra mechanical strength is provided moisture, ensuring maximum
by diamond pattern, epoxy coated penetration of fluid into the coil
paper insulation, used throughout the insulation system.
coil, with additional epoxy at heavy Insulating Fluid
stress points. The diamond pattern
distribution of the epoxy and carefully Transformers from Cooper Power
arranged ducts, provide a network of Systems are available with Envirotemp
passages through which cooling fluid FR3 fluid or electrical grade mineral
can freely circulate. insulating oil. The highly refined mineral
oil is tested and degassed to assure a
Coil assemblies are heat-cured under chemically inert product with minimal Figure 7.
calculated hydraulic pressure to ensure acid ions. Special additives minimize VFI transformer with visible break.
performance against short-circuit oxygen absorption and inhibit
forces. oxidation. To ensure high dielectric
Core and Coil Assemblies strength, the mineral oil is re-tested for
dryness and dielectric strength, Pad-Mounted VFI Transformer
Pad-Mounted transformer core and refiltered, heated, dried, and stored
coil assemblies are braced with heavy The VFI transformer combines a
under vacuum before being added to
steel ends to prevent the rectangular conventional distribution transformer
the completed transformer. from Cooper Power Systems with the
coil from distorting under short-circuit
conditions. Plates are clamped in place Envirotemp FR3 fluid is a bio-based, proven Vacuum Fault Interrupter (VFI).
using presses, and welded or bolted to sustainable, natural ester dielectric This combination provides both voltage
form a solid core and coil assembly. coolant for use in Envirotran transformation and transformer over
Core and coil assemblies exceed transformers where its unique fire current protection in one space saving
ANSI/IEEE requirements for short- safety, environmental, electrical, and and money saving package. The Pad-
circuit performance. Due to the rigidity chemical properties are advantageous. Mounted VFI transformer protects the
of the design, impedance shift after It is formulated from seed oils and transformer and provides proper
short-circuit is comparable to that of performance enhancing additives. coordination with upstream protective
circular wound assemblies. Envirotemp FR3 fluid quickly and devices. When a transformer fault or
thoroughly biodegrades in the overload condition occurs, the VFI
environment, and is non-toxic per breaker trips and isolates the
acute aquatic and oral toxicity tests. transformer.
Building for Environmental and The three-phase VFI breaker has
Economic Sustainability (BEES) total

7
Three-Phase Pad-mounted Compartmental Type Transformer

independent single-phase initiation, but SPECIAL APPLICATION with valuable information, leading to
is three-phase mechanically gang- scheduled repair or replacement, and
tripped. A trip signal on any phase will TRANSFORMERS minimizing the duration and expense of
open all three phases. This feature Data Center Transformer an outage. With a dry-type transformer,
eliminates single-phasing of three there is no reliable way to measure the
phase loads. It also enables the VFI With focus rapidly shifting from simply health or likelihood of an impending
breaker to be used as a three-phase maximizing uptime and supporting failure.
load break switch. demand to improving energy utilization,
the data center industry is continually Solar Transformer
Due to the resettable characteristics of looking for methods to increase its As a result of the increasing number of
the VFI breaker, restoring three-phase energy efficiency and reliability. Utilizing states that are adopting aggressive
service is faster and easier. cutting edge technology, Cooper Renewable & Alternative Energy
The sealed visible break window and Power Systems' Hardened Data Portfolio Standards, the solar energy
switch is an option that can be Center (HDC) transformers are the market is growing - nearly doubling
installed to provide visible break solution. Designed with special year over year. Cooper Power
contact. This feature provides attention given to surge protection, Systems, a key innovator and supplier
enhanced safety and allows an HDC liquid-filled transformers provide in this expanding market, is proud to
operator to see if the loadbreak switch superior performance under the offer Envirotran transformers
contacts are in an open or closed harshest electrical environments. specifically designed for Solar
position before performing Contrary to traditional dry-type units, Photovoltaic medium-voltage
maintenance. HDC transformers provide applications. Cooper Power Systems is
unsurpassed reliability, overloadability, working with top solar photovoltaic
Envirotran FM Approved Special operational life, efficiency, thermal developers, integrators and inverter
Protection Transformer loading and installed footprint. These manufacturers to evolve the industry
The Envirotran transformer from Cooper Power Systems units have and change the way we distribute
Cooper Power Systems is FM reliably served more than 750MW of power.
Approved and suitable for indoor critical data center capacity for a total
of more than 4,000,000 hours without In accordance with this progressive
locations. Factory Mutual Research stance, every Cooper Envirotran Solar
Corporation’s (FMRC) approval of the an hour of downtime.
transformer is filled with non-toxic,
Envirotran transformer line makes it The top priority in data center biodegradable Envirotemp FR3
easy to comply with and verify operations is uninterrupted service. dielectric fluid, made from renewable
compliance with Section 450.23, 2008 Envirotran HDC transformers from seed oils. On top of its
NEC, Less-Flammable Liquid-Filled Cooper Power Systems, having biodegradability, FR3 fluid substantially
Transformer Requirements for both substantially higher levels of insulation, extends the life of the transformer
indoor and outdoor locations. are less susceptible to voltage surges. insulation, saving valuable resources.
Envirotran FM Approved transformers Cooper Power Systems has What better way to distribute green
offer the user the benefit of a experienced zero failures due to power than to use a green transformer.
transformer that can be easily specified switching transients. The ANSI/IEEE In fact, delaying conversion to
to comply with NEC, and makes FM standard impulse withstand ratings are Envirotran transformers places the
Safety Data Sheet compliance simpler, higher for liquid-filled transformers, burden of today’s environmental issues
while also providing maximum safety making them less susceptible to onto tomorrow’s generations. Cooper
and flexibility for both indoor and insulation failure. The Envirotran HDC can help you create a customized
outdoor installations. transformer provides ultimate transformer, based on site specific
protection by increasing the BIL rating characteristics including: temperature
Because the “FM Approved” logo is one level higher than standard liquid- profile, site altitude, solar profile and
readily visible on the transformer and filled transformer ratings. The cooling required system life. Some of the
its nameplate, NEC compliance is now system of liquid-filled transformers benefits gained from this custom rating
easily verifiable by the inspector. provides better protection from severe include:
Envirotran FM Approved transformers overloads - overloads that can lead to
are manufactured under strict compli- significant loss of life or failure.  Reduction in core losses
ance with FMRC Standard 3990, and Data center design typically includes  Improved payback on investment
are filled with FM Approved Envirotemp multiple layers of redundancy, ensuring
FR3 fire-resistant dielectric coolant.  Reduction in footprint
maximum uptime for the critical IT
load. When best in class transformer  Improved fire safety
manufacturing lead times are typically  Reduced environmental impact
weeks, not days, an unexpected
transformer failure will adversely affect For the solar photovoltaic industry,
the facility’s reliability and profitability. Cooper Power Systems is offering
Therefore, the ability to determine the standard step up transformers and
electrical and mechanical health of a dual secondary designs.
transformer can reduce the probability
of costly, unplanned downtime.
Routine diagnostic tests, including key
fluid properties and dissolved gas
analysis (DGA), can help determine the
health of a liquid-filled transformer.
Although sampling is not required for
safe operation, it will provide the user

8
210-12

Wind Transformer K-Factor Transformer Modulation Transformer


Cooper Power Systems is offering With a drastic increase in the use of Bundled with an Outboard Modulation
custom designs for renewable energy ferromagnetic devices, arcing devices, Unit (OMU) and a Control and
power generation. Cooper Power and electric power converters, higher Receiving Unit (CRU), a Modulation
Systems manufactures Generator frequency loads have increased Transformer Unit (MTU) is designed to
Step-Up (GSU) transformers for significantly. This harmonic loading has remotely achieve two way
installation at the base of every wind the potential to generate higher heat communication.
turbine. Additionally, grounding levels within a transformer's windings The use of an MTU reduces travel time
transformers are available for wind and leads by as much as 300%. and expense versus traditional meter
power generation. Harmonic loading has the potential to reading performed by high voltage
induce premature failure in standard-
DOE Efficiency electricians. Additionally, with MTU it is
design distribution transformers. possible to manage and evaluate
Effective January 1, 2010, the United In addition to standard UL "K-Factor" energy consumption data, providing
States Department of Energy (DOE) ratings, transformers can be designed reduced metering costs and fewer
has mandated improved efficiency to customer-provided specifications tenant complaints.
values for most liquid type, medium detailing precise loading scenarios.
voltage transformers. As a result, all An MTU utilizes existing utility
Onsite measurements of magnitude
applicable Cooper Power Systems infrastructure, therefore eliminating the
and frequency, alongside harmonic
transformers are designed to meet or need to engineer and construct a
analysis of the connected load can be
exceed the standard efficiency values dedicated communication network.
performed by Cooper Power Systems
per DOE 2010; Final Ruling, 10 CFR engineers or a third party consultant.
Part 431. Contact your local Cooper These field measurements are used to
Power Systems representative to find determine exact customer needs and
out more. outline the transformer specifications.
Underwriters Laboratories® Cooper Power Systems will design
(UL®) Listed & Labeled/ harmonic-resistant transformers that
Classified will be subjected to the unique
The Envirotran transformer from harmonic loads. These units are
Cooper Power Systems can be designed to maintain normal
specified as UL Listed & Labeled, and/ temperature rise under harmonic, full-
or UL Classified. Underwriters load conditions. Standard UL
Laboratories (UL) listing is a verification "K-Factor" designs can result in
of the design and construction of the unnecessary costs when the "next-
transformer to the ANSI/IEEE highest" K-Factor must be selected for
standards. UL listing generally is the a calculated design factor. To save the
most efficient, cost-effective solution customer these unnecessary costs,
for complying with relevant state and Cooper Power Systems can design the
local electrical codes. UL Combination transformer to the specific harmonic
Classification/Listing is another way in spectrum used in the application.
which to comply with Section 450.23, K-factor transformers from Cooper
2008 NEC requirements. This Power Systems are filled with mineral
combines the UL listed transformer oil or Envirotemp FR3 fluid and enjoy
with a UL Classified Less-Flammable the added benefits of dielectric cooling Figure 8.
Liquid and complies with the use such as higher efficiencies than dry- Modular transformer.
restrictions found within the liquid type transformers.
Classification.
Inverter/Rectifier Bridge
Cooper Power Systems complements
its range of applications for
transformers by offering dual winding
designs. These designs are intended
for connection to 12-pulse rectifier
bridges.

9
Three-Phase Pad-mounted Compartmental Type Transformer

PRODUCT ATTRIBUTES TESTING THOMAS A EDISON RESEARCH


AND TEST FACILITY
To set us apart from other transformer Cooper Power Systems performs
manufactures, Cooper Power Systems routing testing on each transformer We are constantly striving to introduce
includes the following guarantees with manufactured including the following new innovations to the transformer
every three-phase pad-mounted tests: industry, bringing you the highest
transformer. quality transformer for the lowest cost.
 Insulation Power Factor: This test Cooper Power Systems Transformer
Engineered to Order (ETO) verifies that vacuum processing has Products are ISO 9001 compliant,
thoroughly dried the insulation emphasizing process improvement in
Providing the customer with a well system to required limits. all phases of design, manufacture, and
developed, cost-effective solution is
the number one priority at Cooper  Ratio, Polarity, and Phase testing. We have invested millions of
Power Systems. Using customer Relation: Assures correct winding dollars in the Thomas A. Edison
specifications, Cooper Power Systems ratios and tap voltages; checks Technical Center, our premier research
will work with the customer from the insulation of HV and LV circuits. facility in Franksville, Wisconsin
beginning to the end to develop a Checks entire insulation system to affirming our dedication to introducing
solution to fit their needs. Whether it is verify all live-to-ground clearances. new innovations and technologies to
application specific, site specific, or a the transformer industry. Headquarters
 Resistance: This test verifies the
uniquely specified unit, Cooper Power for the Systems Engineering group of
integrity of internal high-voltage and Cooper Power Systems, this research
Systems will provide transformers with low-voltage connections; provides
the best in class value and facility is fully available for use by our
data for loss upgrade calculations. customers to utilize our advanced
performance, saving the customer time
and money.  Applied Potential: Applied to both electrical and chemical testing labs.
high-voltage and low-voltage
Made in the U.S.A. windings, this test stresses the
Cooper Power Systems three-phase entire insulation system to verify all
pad-mounted transformers are live-to-ground clearances.
produced right here in the United  Induced Potential: 3.46 times
States of America. Our manufacturing normal plus 1000 volts for reduced
facilities are positioned strategically for neutral designs.
rapid shipment of products.
Furthermore, should the need arise,  Loss Test: These design verification
Cooper Power Systems has a broad tests are conducted to assure that
network of authorized service repair guaranteed loss values are met and
shops throughout the United States. that test values are within design
tolerances. Tests include no-load
Superior Paint Performance loss and excitation current along
Protecting transformers from nature's with impedance voltage and load
elements worldwide, Cooper Power loss.
Systems E-coat system provides  Leak Test: Pressurizing the tank to 7
unrivaled transformer paint life, and psig assures a complete seal, with
exceeds ANSI standards C57.12.28 no weld or gasket leaks, to eliminate
and C57.12.29. In addition to the the possibility of moisture infiltration
outside of the unit, each transformer or fluid oxidation.
receives a gray E-coat covering in the
interior of the tank and cabinet, Design Performance Tests
providing superior rust resistance and Include:
greater visibility during service.  Temperature Rise: Our automated
If the wide range of standard paint heat run facility ensures that any
selections does not suit the customer's design changes meet ANSI/IEEE
needs, Cooper Power Systems will temperature rise criteria.
customize the paint color to meet their  Audible Sound Level: Ensures
requirements. compliance with NEMA
Rectangular Coil Design requirements.
 Lightning Impulse: To assure
Cooper Power Systems utilizes a superior dielectric performance, this
rectangular coil design. This winding test consists of one reduced wave,
technique results in a smaller overall two chopped waves and one full
unit footprint as well as reducing the wave in sequence, precisely
transformer weight. The smaller unit simulating the harshest conditions.
size does not hinder the transformer
performance in the least. Units have
proven short circuit withstand
capabilities up to 12 MVA.

10
210-12

11
Three-Phase Pad-mounted Compartmental Type Transformer

© 2011 Cooper Industries. All Rights Reserved.


Cooper Power Systems, Envirotemp, FR3, Envirotran, MagneX, UltraSIL,
Evolution, and Kyle are valuable trademarks of Cooper Industries in the U.S. and
other countries. You are not permitted to use the Cooper Trademarks without the
prior written consent of Cooper Industries.
IEEE Std C57.12.28™ and Std C57.12.29™ standards are trademarks of the
Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication is
not endorsed or approved by the IEEE.
IEEE® is a registered trademark of the Institute of Electrical and Electronics
Engineers, Inc.
ANSI® is a registered trademark of American National Standards Institute.
National Electrical Code® and NEC® are registered trademarks of the National
Fire Protection Association, Inc., Quincy, MA.
Underwriters Laboratories® and UL® are registered trademarks of Underwriters
Laboratories, Inc.
FM Approved®, FMRC, and Factory Mutual Research Corporation are
trademarks of FM Global.