Вы находитесь на странице: 1из 10

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

Current Transformer Saturation Prevention using a


Controlled Voltage Source Compensator
Ehsan Hajipour, Student Member, IEEE, Mehdi Vakilian, Senior Member, IEEE, and
Majid Sanaye-Pasand, Senior Member, IEEE

Abstract—Current transformer (CT) saturation causes severe In recent years, the new generation of digital relays is
distortion in the measured current waveform which may lead sometimes equipped with a software-based CT saturation
to mal-operation of the protective devices. This paper proposes detection/compensation unit [2]. This unit detects the inception
a low-cost, power electronic device to prevent the CT from
saturation. The proposed compensator is inserted in series with of a CT saturation incident and tries to prevent the relay
the relay in the CT secondary circuit and acts as a controlled volt- inappropriate operation by blocking its trigger command [7]
age source (CVS). The proposed CVS generates a time varying or by reproduction of the distorted samples of the CT output
voltage to cancel the voltage developed across the CT burden; current [8]. Various valuable algorithms have been presented in
therefore, the CT magnetic flux remains almost constant and the literature which focus on the detection of CT saturation [1],
undistorted during the power system transients. It will be shown
that this device can precisely compensate fault current, inrush [9], [10], and to digitally compensate the CT distorted output
current, and other probable transient currents despite of its [4], [8], [11], [12]. These algorithms can be implemented only
simplicity. The proposed device can be employed to compensate into the modern digital relays [13]. In addition, they might not
the already in-service CTs connected to non-digital and digital be able to accurately reproduce the input current in all different
relays. Comprehensive computer simulations are carried out scenarios.
to validate the effectiveness of the proposed compensator. The
performance of a sample compensator of this type is validated A major part of the already in-service relays are elec-
through special high current laboratory experiments (carried out tromechanical, static and initial digital type relays that do not
over several hundred Amperes up to 1.6 kA) and the obtained support digital inputs and modern communication protocols.
results illustrate the capability of the proposed compensator to For example, a power system asset analysis implemented by
prevent CT saturation. National Grid USA in New York State depicts that over 85%
Index Terms—Current transformer (CT), CT compensation, of the relay population in their system are non-digital relays
CT saturation, hardware-based compensator. [14]. These types of relays cannot be equipped with the afore-
mentioned software-based saturation compensation/detection
I. I NTRODUCTION algorithms. In this case, hardware-based compensation of the
CT is a low-cost and effective solution that can be employed.
T HE accurate and proper performance of protection de-
vices is directly related to the correct replication of power
system high current waveform in the current transformer (CT)
A hardware-based CT compensator is an analog circuit
inserted into the CT secondary circuit and prevents the CT
from saturation. This type of compensators does not break
secondary terminal [1]. Consequently, current waveform dis-
the analog connection between the CT and the relay and
tortion due to CT saturation significantly threatens the reliable
can be employed to compensate a CT which is connected
operation of the relays [2], [3]. CT saturation compensation is
to either non-digital or digital relays. In [15]–[17], different
a safe and effective way to prevent the relays mal-operation.
hardware-based algorithms have been proposed to estimate
This paper mainly focuses on the saturation compensation of
and compensate the CT magnetizing current. These algorithms
the already in-service CTs which may become undersized over
are only applicable to measurement CTs. In [18], the dc
the years due to: i) the unanticipated changes in the power
offset component of a CT’s secondary transient current is
system topology (i.e. transmission line construction) and thus,
eliminated by injection of a similar compensating current into
increase in the power system short circuit capacity [4], ii)
the CT secondary winding terminals. A major drawback of
implementation of auto-reclosing schemes in an existing power
this method is the dependence of its performance on accurate
network [5]. In these cases, replacement of the undersized CT
estimation of the fault inception instant. Additionally, its
is an expensive and undesired solution, where the number of
performance will be affected by presence of noise [13]. In
changes during a substation refurbishment needs to be kept
[5], the CT has been compensated during the dead time of an
minimum [6].
auto-reclosing scheme. Through the dead time interval, the CT
E. Hajipour and M. Vakilian are with the Center of Excellence in primary winding is open-circuit and therefore, the proposed
Power System Management and Control, Department of Electrical Engi- hardware compensator of [5] could eliminate the CT residual
neering, Sharif University of Technology, Tehran 11365-11155, Iran (e-mail:
e hajipour@ee.sharif.edu; vakilian@sharif.edu). flux employing a bi-directional controlled switching. However,
M. Sanaye-Pasand is with the Electrical and Computer Engineering School, when the fault current is flowing in the power system, the CT
College of Engineering, University of Tehran, Tehran 14395-515, Iran. He primary current is not zero and consequently, the proposed
is also with the Control and Intelligent Processing Center of Excellence,
Electrical and Computer Engineering School, University of Tehran, Tehran compensator in [5] is not applicable. In [13] and [19], a resistor
14395-515, Iran (e-mail: msanaye@ut.ac.ir). is dynamically inserted into the CT secondary circuit by a

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

Rb Lb The Proposed Compensator Rt Rt


i1 i2 λ(t)−λ(t0 ) = vCT (τ )dτ = [vB (τ ) + vCV S (τ )] dτ →
VCVS t0 t0
+

CVS Unit
vB Rt Rt

-
+
+

Magnetizing

µ-Processor
λ(t)−λ(t0 ) = vB (τ )dτ + vCV S (τ )dτ = 0 → λ(t) = λ(t0 ).

Analogue
Interface
vCVS
Branch
t0 t0

vCT
(3)
-
- where λ(t0 ) represents the CT magnetic flux at t0 .
i2 Process Unit Theoretically, (3) shows that in an ideal operation of the
proposed compensator, the CT magnetic flux remains constant
over time, independent of the magnitude and waveform of the
Fig. 1. Schematic diagram of the proposed compensator. CT primary current and therefore, the CT will not saturate.
This observation is valid for any current waveform such
as symmetrical sinusoidal current, fault current including a
power electronic switch, generating a flux to oppose the time- decaying dc component, inrush current and combination of
varying flux associated with the decaying dc component of the them.
fault current. In this method, heat dissipation is a factor that To implement the aforementioned compensation algorithm,
might hinder its application [1]. firstly, the CT secondary current i2 (t) is sampled by a high
It should also be noted that: while, all of the aforementioned precision current sensor. Then, as shown in Fig. 1, vB (t) can
hardware-based methods only focus on the CT compensation be calculated as follows:
under presence of a fault current, this paper opens a new di2 (t)
door to reproduce other saturated current waveforms, such as: vB (t) = Rb i2 (t) + Lb (4)
dt
inrush current, harmonically polluted current [11], and evolv- where Rb and Lb are the resistance and inductance of the CT
ing faults. This paper employs a low-voltage dc source, four secondary circuit. These parameters can be measured using
power-electronic switches, and a low-cost microprocessor to the CVS unit as demonstrated in [20].
prevent CT saturation. Using a simple switching strategy, the The proposed compensator estimates its required output
proposed compensator applies a voltage (equal and opposite to voltage vCV S (t) based on the estimated vB (t) and through
that of the CT burden) to the CT secondary circuit terminals. (2). Afterwards, the proper command is sent to the controlled
Therefore, the voltage across the CT core is kept virtually voltage source (CVS) unit and it applies vCV S (t) to the CT
zero and thus, the CT magnetic flux remains almost constant secondary circuit terminals.
and undistorted. Theoretically, the proposed compensator can The following sections describe the proposed hardware of
inhibit CT saturation independent of the CT primary current the CVS unit and its switching strategy to realize the relation
waveform. In addition, this paper introduces a simple formu- in (2).
lation to determine the appropriate parameters of the proposed
compensator. The results of a wide range of simulations which
are carried out on an accurate CT model has revealed the B. Hardware Implementation
efficiency and reliability of the proposed method. Furthermore, Fig. 2 depicts hardware implementation of the pro-
the performance of the proposed method is verified against a posed compensator. This hardware consists of a dc voltage
sample protective CT, through experimental results. source, four power electronic switches (including freewheeling
diodes), an instant-on switching solid-state relay (IO-SSR),
II. T HE P ROPOSED C OMPENSATION A LGORITHM and a microprocessor which manages the switching sequence.
To minimize the adverse effect of the power plant noise on
A. Theoretical Background of the Proposed Compensator
the proper performance of the proposed compensator, it is
The schematic diagram of the proposed compensator struc- recommended to install this device adjacent to the relay in
ture is illustrated in Fig. 1. The proposed compensator is the substation relay room.
connected in series with the CT burden, which consists of Under normal operating condition of the power system,
the CT internal resistance and reactance, the lead equivalent the proposed compensator is bypassed by the IO-SSR. This
impedance, and the relay burden. Therefore, the voltage across normally closed (NC) contactor will prevent occurrence of any
the CT magnetic core vCT can be obtained as follows: undesired open-circuit in the CT secondary circuit. After the
vCT (t) = vB (t) + vCV S (t) (1) detection of a transient inception, the microprocessor issues
a control command to open the IO-SSR. Simultaneously, the
where vB and vCV S represent the voltage developed across the
compensator which has been already bypassed by the IO-SSR,
CT burden and the compensator output voltage, respectively.
is inserted into the CT secondary circuit. The typical response
In this paper, the compensator output voltage vCV S is
time of an IO-SSR is less than 1 ms [21], while a CT would
controlled such that it satisfies the following integral equation:
not become saturated at least for about 1/6 of cycle (3.3 ms
Zt Zt
for a 50 Hz power system) after the fault inception [22].
vCV S (τ )dτ = − vB (τ )dτ (2)
In this paper, the instantaneous current algorithm [23] has
t0 t0 been employed for fast fault detection. In this method, a
Therefore, the CT magnetic flux λ(t) can be computed using transient inception is detected when 16 consecutive samples
(1) and (2) through the following relation: of the CT secondary current i2 (t) exceed the CT nominal

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

Controlled Voltage Source (CVS) Unit 50


40
1

vB(V)
30

IO-SSR
VDC 

vCVS
20 ΔTTd d
10 t2 t4
t1 t3
0
0 0.5 1 1.5 2 2.5
Gates

0
Control

vCVS (V)
Signal i2
μProcessor 2
Conditioning -V
-VDDC
1 2 5
Signal Processing Unit  on  on  on
0 0.5 1 1.5 2 2.5
Fig. 2. Hardware implementation of the proposed compensator. Time (ms)

Fig. 3. The basic concept of the switching control strategy.


secondary current (1 A or 5 A). Since this algorithm only
uses three processor operations (two COMPARE instructions, Fault Detector NOT
and one ADD instruction), it can be implemented by using FD AND
Switch on
a fast sampling rate (200 kHz employed in this paper). At 0 CVS unit
this sampling frequency, this detection algorithm leads to a vref

Compare
delay of 80 µs. It should be noted that during the operation of vCVS AND
Close
the compensator, the freewheeling diodes across the electronic IO-SSR
meas.
switches prevent the CT secondary current from being chopped vCVS
abruptly [24]. Unhealthy Status
In the proposed compensator, the microprocessor controls
Fig. 4. The proposed logic used to detect the compensator unhealthy status.
the CVS output voltage by turning the switches ON or OFF.
By proper control of these switches, the microprocessor is
able to generate arbitrary voltage pulses with desired width
paper, the current sensor sampling rate is 200 kHz, while the
and magnitude of [−VDC , 0, +VDC ].
compensator output pulses are generated with delay frequency
of fd = 1/∆Td = 25 kHz, as shown in Fig. 3.
C. Switching Control Algorithm As it can be seen in Fig. 3, there is a time delay of
Fig. 3 depicts the basic concept of the proposed switching ∆Td between vCV S (t) and vB (t). In this paper, ∆Td is set
control algorithm. This figure demonstrates a typical voltage to 40 µs. The effect of this time delay on the performance
developed across the CT burden vB and its corresponding of the proposed compensation method will be thoroughly
compensator output voltage vCV S . As shown in Fig. 3, in investigated in section III-B.
the proposed switching strategy, time is discretized through If the magnitude of VDC is not chosen properly, it is
i i
application of a set of constant steps of ∆Td . At the beginning possible to obtain δon > 1, through (5). In this case, δon
i
of each time step ti , a control command δon i
is sent from should be set to +1, or −1; depending on the sign of δon .
the microprocessor to the CVS. This command contains: 1) A formula is introduced in section III, in order to select the
polarity of the desired voltage sgn(δon i
)=[−1,0,+1] and 2) VDC parameter appropriately and to prevent obtaining a value
i
i
width of the required pulse |δon | in percentage of ∆Td . of δon > 1.
In the proposed switching control, the pulse width is de-
termined such that the integral of vCV S (t) over each step of D. Self-Checking Routine
∆Td equals to the integral of vB (t) over the past recent time
step. For example, in Fig. 3, the δon 5
is selected in a way that Since the proposed compensator is installed in series with
A1 equals A2 (A1 = A2 ). To achieve this, one may estimate the CT secondary circuit, it should be ensured that any
i+1
δon as follows: probable failure of its components would not affect the ap-
Rti Rti propriate performance of the protection system. Therefore,
i+1
VDC δon ∆Td = −Rb i2 (t)dτ − Lb di2 (τ ) it is recommended to equip the device with a self-check
" ti−1 ti−1 # scheme. The proposed logic to check the health status of the
i+1 −Rb
Rti Lb device is depicted in Fig. 4. F aultDetector unit, which was
→ δon = VDC ∆Td i2 (t)dτ + Rb (i2 (ti ) − i2 (ti−1 ))
ti−1 described earlier, determines the power system condition. If
(5) power system operates under normal condition, F D would be
The CT secondary current i2 (t) is sampled at a frequency zero, otherwise F D = 1.
of fs , 200 kHz in this paper. Therefore, the above integral Under normal operation of the power system (F D = 0),
would be substituted by a simple trapezoidal rule of integration the IO-SSR switch is closed and all of the CVS switches are
determination and summation. It should be noted that in this kept in OF F state. Therefore, the output voltage across the

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

meas. meas. 1
CVS unit (vCV S ) would be zero (vCV S = vref = 0). If VXnew  5VXold
occurrence of any failure causes IO-SSR to open, then, an
open-circuit voltage would appear across the IO-SSR switch.
0.8
  0.65 VXnew  2VXold
The compensator monitors the CVS output voltage (vCV meas.
S ),
0.6   0.36


and if any non-zero voltage is observed, it switches the
0.4
CVS unit ON in order to short the CT secondary circuit.
Simultaneously, an alarm signal (Equipment Failure EF as 0.2
stated in IEC 60044-8 [25]) will be sent to the substation
control room. 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Under power system fault circumstance (F D = 1), the VXold VXnew
IO-SSR switch is opened and the CVS unit compensates
the voltage developed across the CT burden. If any failure Fig. 5. Appropriate value of α based on (8).
threatens the proper operation of the CVS unit (such as burning
of the switches), the measured output voltage of the CVS unit
meas.
(vCV S ) would not be equal to the reference voltage (vref = the primary system reactance and resistance up to the point of
vCV S ) selected by the processor. The processor monitors the desired power system fault.
CVS output voltage, and if a difference is found between this Assume that for an already in-service CT or for a newly
meas.
voltage and its reference (vCV S 6= vref = vCV S ), then the installed CT, it is required to increase the CT saturation voltage
processor issues a close command to the IO-SSR and the CVS from VXold to VXnew by using the proposed compensator.
unit is bypassed. Simultaneously, an alarm signal (Equipment Parameter α is defined as follows:
Failure) will be sent to the substation control room. VDC
α = √ new (7)
As it can be seen, the IO-SSR and the CVS unit backup 2VX
each other and therefore, considerably reduce the compensator It is shown in the appendix that the new saturation voltage
probability of threatening the proper operation of the protec- of the CT would be equal or greater than VXnew , if α satisfies
tion system under an unhealthy status. the following"constraint:
√ #
1 − α2 π −1 V old
III. S ELECTION OF T HE C OMPENSATOR PARAMETERS α − − sin α ≤ X (8)
α 2 VXnew
It is trivial that if the magnitude of dc voltage source Fig. 5 depicts the minimum value of α which satisfies the
VDC is selected equal or larger than the maximum magnitude equality condition of relation (8), while the ratio of VXold to
of vB (t), then, the proposed compensator can completely VXnew (the right hand side term in this relation) is varied. If
cancel the burden voltage at each time step and therefore, α is set to 1, then, the compensator completely cancels the
CT saturation will be certainly prevented. In this case, the effect of the voltage developed across the CT burden and
CT magnetic flux remains constant over time. However, it consequently, the CT magnetic flux remains constant over
is quite reasonable and practical to design the compensator time. While, If α < 1, then the magnetic flux λ(t) can vary
in such a way that the CT magnetic flux varies between over time, however it would not exceed the CT saturation
its two saturation limits (positive and negative), and not to flux and consequently, the CT will not saturate. In this case,
exceed these limits. In response, the magnitude of dc voltage the compensator supports the CT to feed its burden up to
source VDC could be decreased to reduce the compensator its nameplate rating without losing its accuracy. Refer to the
requirement. To do so, the standard procedure of CT sizing appendix for more detailed description.
based on the CT saturation voltage VX is employed in this The steps which should be followed for proper determina-
section [26]. tion of VDC are summarized as follows:
1) The real saturation voltage of the CT is obtained using
A. Appropriate Magnitude of DC Voltage Source its nameplate information or through some proper tests
For a CT, the saturation voltage VX is defined as that of and is represented by VXold ;
symmetrical voltage across the secondary winding of the CT 2) Based on the power system parameters, and the CT
for which the peak induction just exceeds the saturation flux burden, the required saturation voltage of the CT VXnew
density [26]. The CT saturation voltage is a key parameter (to avoid its saturation) is calculated through (6);
for the proper CT sizing. For example, (without using any 3) By solving the equality condition in relation (8), the
compensator) to avoid saturation of a CT due to a fault current minimum acceptable value of α is determined.
including a dc offset component and under a pure resistive 4) The appropriate value of VDC is calculated as follows:

burden, the CT saturation voltage should be higher than the VDC ≥ α (1 + ε) 2VXnew (9)
right hand side term of (6), as it is determined
 in [26]: where ε represents the error which is introduced into
X this computation process by inherent time delay of
VX > Is × Zs 1 + (6)
R the compensator, as will be discussed in the following
where Is is the primary current divided by the CT turns ratio, section.
and Zs is the total secondary burden of the CT. X and R are 5) According to IEC 60044-8 [25], the rated auxiliary dc

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

Voltage (V) Current (A)


30 50
 f d  25 kHz 0
 = 5.03%
 (%)

20
%

   5.03% -50 (a)


10 500

0 0
5 10 15 20 25 30 35 40 45
ffdd (kHz)
(kHz) -500 (b)
2.0
Bsat

B (T)
Fig. 6. The compensation error ε contributed by the compensator time delay 0
(VXnew /V old = 4).
X
-2.0 (c)
40 45 50 55 60 65 70 75 80
Time (ms)
power supply voltage of an electronic current trans-
former (ECT) can be selected from the standard values Fig. 7. a) The CT secondary current without (solid line) and with (dash
of {24 V, 48 V, 60 V, 110 V, 220 V}. Therefore, the line) compensation, b) vB (dash line) and vCV S (solid line), c) the CT
magnetic flux density without (solid line) and with (dash line) the proposed
nearest larger value of these standard levels should be compensator.
chosen as VDC .

A. Steady State Analysis


B. Proper Value of ∆Td
In this section, performance of the proposed compensator is
As it can be seen in Fig. 3, a time delay equal to ∆Td exists investigated during steady state symmetrical ac current injec-
between the compensator output voltage vCV S and the voltage tion. The total CT secondary circuit impedance |RCT + Zb |
across the CT burden vB . It is shown in the appendix that this is 9.76 Ω. Therefore, an ac current with the magnitude of
delay will result in an error of ε as follows: i2 = 42.0 A generates VXnew = 410 V across the CT sec-
V new ondary terminal. Fig. 7 depicts the performance of the CT
ε = 2 Xold sin (πf ∆Td ) (10)
VX with and without the proposed compensator. Fig. 7(a) shows
where f is the power system nominal frequency. that without the compensation application, the CT becomes
Fig. 6 depicts ε versus the delay frequency fd = 1/∆Td deeply saturated, while the proposed compensator prevents CT
where VXnew /VXold = 4. As it can be seen, through this saturation. Fig. 7(b) depicts the voltage across the CT burden
equation a delay frequency of 4 kHz results in an error of vB and the compensator output voltage vCV S . As it can be
about 31.4%. However, if the frequency is increased, its error seen, vCV S is in phase with vB and in opposite polarity. Fig.
reduces rapidly to a value of about 5.03% in fd = 25 kHz. In 7(c) illustrates the corresponding magnetic flux density B. As
this paper, the delay frequency is set to 25 kHz (in a 50 Hz it can be seen, in the compensated CT, the maximum value of
power system) and therefore, ∆Td would be 40 µs. The error B is about Bsat , which verifies the formulas presented in the
introduced by this time delay is canceled through choosing a paper appendix, where the value of VDC is chosen in such a
proper value for VDC as in(9). way to limit the maximum of B to Bsat .
Fig. 8 depicts the CT input/output ratio curve between the
RMS of its primary current I10 and the RMS of its secondary
IV. S IMULATION R ESULTS current I2 under different values of VDC . In an ideal operation
of the CT, this curve should follow a straight line of I2 =
In this section, several simulations are presented to show I10 . As it can be seen in this figure, by variation of VDC ,
the effectiveness of the proposed compensator. An appropriate CT accuracy limit primary current Ial [25] can be arbitrary
CT model, including accurate representation of the magnetic tuned to avoid the core saturation. Without compensation, the
core hysteresis characteristic is developed using the Jiles- CT accuracy limit primary current is Ial old
= 25.5 A (indicates
Atherton theory [27]. The simulated CT is 300:1-8 VA and a 5P20 CT based on IEC 60044-8 [25]). However, while the
its parameters have been provided in [4]. The CT saturation VDC parameter is set to 220 V, the CT accuracy limit primary
voltage is VXold = 205 V. Assume that, in order to avoid CT current is increased to Ial new
≈ 2Ialold
= 48.8 A (represents a
saturation it is required to increase the CT saturation voltage 5P40 CT based on IEC 60044-8 [25]). Therefore, one may
to VXnew = 2VXold = 410 V. Realizing that the delay frequency conclude that VXnew = 2VXold ; as it was requested in the first
fd is set to 25 kHz, the error of ε would be 2.5%. In addition, stage.
α is equal to 0.36 according to Fig. 5. Therefore, using (9), the
required voltage magnitude of the dc voltage source is 214.0
V, while it is assumed to be 220 V (a standard dc voltage B. Transient Currents Analysis
level for auxiliary dc power supply in the substations [25]). This section investigates the performance of the proposed
The CT burden Zb is the CT nominal burden of 8 Ω (with compensator during power system transient currents. A perma-
power factor of 0.8). The current sensor sampling frequency nent fault of 2.5 kA (rms) has a fully offset decaying dc com-
fs is assumed to be 200 kHz. ponent, and a time constant of τ = 100 ms has been injected

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

100
30 ideal

Current (A)
20 Uncomp.
80 67.1 A
10 Comp.

}
440 V
60 48.8 A 0
I2 (A)

VDC
35.2 A 220 V -10 (a)
40 25.5 A 110 V (b)
200

Voltage (V)
Uncomp.
20 0

0 -200
0 20 40 60 80 100
2 (c)
I1' (A)

B (T)
Fig. 8. CT input/output ratio curves when the VDC parameter varies. 1
Compensated
Uncompensated
0
20 ideal 50 100 150 200
Current (A)

Uncomp. Time (ms)


10 Comp.
Fig. 10. a) The CT secondary current in the presence of a 3.5 kA fault, b)
0 vB (t) (dash line) and vCV S (t) (solid line), c) the CT magnetic flux density.
(a)
200 (b)
Voltage (V)

phase displacement are less than 0.21%, and 3.6 minutes,


0
respectively.
Fig. 11(a) depicts a complex fictitious scenario to verify
-200
2 (c)
the independence of the proposed compensator from the CT
primary current waveform. In this imaginary case, an inrush
B (T)

1
current waveform is appeared in the first two cycles of the CT
Uncompensated
primary current. Then, a permanent fault is happened. The du-
Compensated
ration of this initial fault assumed to be 2 cycles, followed by
0
50 100 150 200 an auto-reclosing dead time of 2 cycles. Afterward, the circuit
Time (ms) breakers are closed again and the second fault is experienced.
As it can be seen in Fig. 11(b), the proposed compensator
Fig. 9. a) The CT secondary current in the presence of a 2.5 kA fault, b) output voltage vCV S precisely follows the variation of vB .
vB (t) (dash line) and vCV S (t) (solid line), c) the CT magnetic flux density.
Fig. 11(c) illustrates how the compensator properly prevents
the CT core from saturation, while without using the proposed
compensator, the CT experiences a deep saturation. In this
to the CT primary terminals, as shown in Fig. 9(a). Without case, the CT maximum ratio error and its phase displacement
using the compensation scheme, the CT experiences a deep are less than 0.06%, and 5.2 minutes, respectively. This figure
saturation, while the compensator prevents this phenomenon. depicts that the proposed compensation methodology works
Fig. 9(b) depicts the compensator output voltage vCV S and the properly while it is independent of the current waveshape
voltage across the CT burden vB . As it can be seen, in this (inrush, fault, and combination of them). This promising
case, the maximum of vB is less than VDC = 220 V (similar to feature distinguishes the proposed compensator from others
a case of α = 1), therefore, as shown in Fig. 9(c), the proposed available in the literature [13], [15]–[19].
compensator can properly maintain the magnetic flux density
B virtually zero. This observation verifies the effectiveness of
the proposed switching strategy. A typical full-cycle discrete V. E XPERIMENTAL R ESULTS
Fourier filter (DFT) has been employed to extract the CT In order to show the reliability and effectiveness of the pro-
ratio error and the CT phase displacement. For the scenario posed compensator, experimental test are also carried out. The
considered here, the maximum CT ratio error and phase error developed compensator consists of: i) a low-cost dsPIC33F
are less than 0.04%, and 1.4 minutes, respectively. Microchip as the microprocessor, ii) a LA 25-NP LEM Hall
Fig. 10(a) illustrates a similar fault with a magnitude of 3.5 effect current sensor with high immunity to external infer-
kA. As it can be seen in Fig. 10(b), once α is selected less ences, iii) four IRFP3710 IOR fast power MOSFET switches
than 1 (0.36 in this study), the compensator lets the CT to and, iv) a Siemens V2306 miniature power PCB relay as the
supply its burden, without saturation, up to its nominal rating. normally closed (NC) IO-SSR contactor. In addition, an AC-
Therefore, the CT magnetic flux density deviates from zero; DC converter (220 Vac to 24 Vdc) has been employed as the
however, it is shown in the appendix that the CT magnetic compensator dc voltage source.
flux would stay certainly below the CT saturation flux λsat . A 300:1 10P5-1VA protective current transformer is chosen
Thus, the CT will not enter its saturation region. In this to be compensated. The CT saturation voltage VXold is 4.82 V
scenario, the CT maximum ratio error, and the CT maximum and it is desired to increase this saturation voltage to VXnew =

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

50:1 I1
Ideal Regulating R Standard CT
20 Transformer
Current (A)
Transformer
Uncomp. Ammeter
10 Comp. Diode A
High Current

220 V
(transient test)
0 Loop I2 Burden

-10 (a)
Clamp Test CT
200 (b)
Voltage (V)

Current Sensor IO-SSR


0

dsPIC33FJ256
Analogue
Interface
-200
2 (c)
Switches Gates
B (T)

1 Comp. USB
Uncomp.
Process Unit CVS Unit
0
0 20 40 60 80 100 120 140 160 180
Time (ms) Fig. 12. Schematic diagram of the experimental test setup.

Fig. 11. a) The CT secondary current in an autoreclosing scheme, b) vB (t) TABLE I


(dash line) and vCV S (t) (solid line), c) the CT magnetic flux density. L ABORATORY- MEASURED RATIO ERRORS AND PHASE DISPLACEMENTS

Compensated (VDC = 20 V) Uncompensated


I1 (A) εr (%) 4ϕ (minutes) εr (%) 4ϕ (minutes)
4VXold = 19.28 V. The delay frequency is 25 kHz and based on 381 0.81 56.8 3.18 263.8
(10), ε is 5.03%. Through (8), for VXold /VXnew =0.25, α would 558 1.12 79.2 21.3 1283.4
be equal to 0.593. Therefore, VDC should be selected greater 771 0.60 63.4 36.8 1875.6
than 17.00 V as presented in (9); which is set to 20 V in the 912 0.57 32.6 49.7 2340.8
experiments. 1098 7.71 131.8 58.1 2628.2
Fig. 12 demonstrates schematic diagram of the implemented 1353 20.4 337.2 60.2 2806.6
test setup. A regulating transformer and a variable resistor 1398 22.9 354.0 63.1 2927.6
are employed to control the magnitude of the circuit current. 1569 29.7 476.8 74.1 3010.2
The illustrated diode would be inserted only in the transient
tests. A large 50:1 short-circuited power transformer is used
to generate high magnitude currents. A clamp-on ammeter the corresponding results for the uncompensated CT. Table I
and a typical commercial ammeter are used to monitor the reports the CT ratio error (εr ), and its phase displacement
RMS of CT primary and secondary currents during the steady- (4ϕ) ) when the CT is compensated (employing a VDC = 20
state experiments. In addition, a standard CT is inserted to the V) versus the uncompensated CT related parameters.
high current loop to record the primary current wave shape As it can be seen in Fig. 13, since the CT burden is 6 Ω and
during the transient analysis. A digital oscilloscope saves all the CT saturation voltage VXold is 4.82 V, the CT will begin to
the measured data to the in-site laptop. Based on IEC 60044-8 saturate in I2 of about 0.8 A (I1 = 240 A) without the proposed
[25], for a CT with 1 A secondary rated current and 1 VA rated compensator. It is worth mentioning that while the CT burden
power, the rated burden is 1 Ω. However, in this paper, in order is chosen significantly larger than its rated value (6 Ω instead
to investigate the performance of the proposed compensator of 1 Ω), the CT saturates even under its primary rated current
under high degree of the CT saturation, the under-test CT (I1 =300 A). However, with the proposed compensator, the ac
burden is selected to be 6 Ω (purely resistive). By increasing saturation of CT occurred at I1 equal to 1024 A and 1179 A
the CT burden, the required primary current to saturate the for VDC equal to 20 V and 28 V, respectively. For VDC = 40
CT has been proportionally decreased. The implemented test V, CT saturation would happen for a current more than the
circuit is capable of generating steady state sinusoidal currents maximum permissible current of the test setup (I1 = 1.6 kA).
up to 1.6 kA. The new obtained saturation voltages VXnew for VDC = [20 V,
24 V, 40 V] are equal to [4.267 VXold , 4.91 VXold , >6.25 VXold ].
The CT saturation voltage is successfully increased to 4VXold
A. Steady State Experiments by VDC equal to 20 V, as predicted through (9).
In these experiments, the injected primary current is sinu- The recorded CT secondary currents with and without the
soidal. The RMS value of CT primary and secondary currents proposed compensator are depicted in Fig. 14, when I1 is
are read using a clamp-on ammeter, and a regular ammeter, equal to 885 A. As it can be seen in Fig. 14(a), without
respectively, as shown in Fig. 12. The obtained input/output the compensator, CT becomes deeply saturated, while the
ratio curves are depicted in Fig. 13, when the dc voltage compensator prevents the CT core from saturation. Fig. 14(b)
source VDC is set to 20 V, 28 V and 40 V, respectively. represents the voltage across the CT burden vB and the
Please note that these voltage levels are not in compliance with compensator output voltage vCV S . As it can be seen, vCV S
IEC 60044-8 [25] and just have been selected to investigate is in phase with vB but with opposite polarity.
the compensator performance. In addition, Fig. 13 illustrates A 20 VDC voltage source can prevent the CT from satura-

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

6 20 V 28 V 40 V Uncompensated

5 1179 A
}
40 V 5

Current (A)
1024 A 28 V VDC
4 20 V 0
I2 (A)

3
-5
2 240 A
Uncomp. 10 20 30 40 50 60 70 80
1 Time (ms)
0
0 200 400 600 800 1000 1200 1400 1600 Fig. 15. Performance of the proposed compensator when VDC is selected
I1 (A) less than its proper value.

Fig. 13. Experimentally measured input/output ratio curves without and with 1) Regulating transformer
the proposed compensator when the CT burden is 6 Ω. 2) 50:1 single-phase power transformer
3) Under test and Standard CTs
4 (a) Ideal 4) The proposed compensator
Current (A)

2 Uncomp. 5) Digital oscilloscope


0 Comp. 6) A typical measured transient current
-2
-4
(b)
Voltage (V)

20

-20
0 20 40 60 80 100
0
Time (ms) Clamp
Under-Test CT
Fig. 14. a) The measured CT secondary current without (dash line) and with
(solid line) the proposed compensator, b) the recorded voltage across the CT
burden vB (t) (dash line) and the compensator output voltage vCV S (t) (solid
line).

old
tion up to 4Ial =1024 A. In Fig. 15, a 1360 A symmetrical ac
current is applied to the CT when the compensator dc voltage Standard CT
source is set to 20, 28, and 40 V, respectively. As it can be
seen, 20 V and 28 V dc voltage sources cannot prevent CT Fig. 16. Transient test setup and a typical recorded signal.
saturation. However, if it is compared with the uncompensated
CT, the depth of CT saturation is noticeably decreased. This
figure shows how the compensator prevents CT saturation up compensator prevents the CT deep saturation. However, the
to its boundaries, even with improper sizing of VDC . effect of a very slight saturation can be seen on the CT
secondary current waveform which is due to overlooking the
B. Transient Experiments inductance of the CT burden. Fig. 17(c) depicts the voltage
In order to verify the performance of the proposed method measured across the CT burden vB and the compensator
during a transient current injection, a diode is inserted into the output voltage vCV S . Note that none of the known hardware-
presented circuit in Fig. 12. Therefore, the CT primary current based compensators can perform well in the presence of the
would be a half-wave rectified waveform which is similar to presented transient current. For example, since this current
a typical inrush current. The regulating transformer is tuned does not have negative half-cycles, dynamically insertion of a
to obtain a primary current with maximum of 650 A. Fig. resistor [13], [19] could not help to suppress the CT saturation.
16 depicts the test setup and a typical recorded signal. As
it can be seen, to achieve a higher current level, the high-
current capacity primary conductor has been wound in multi- VI. C ONCLUSIONS
turns (four turns) around the CT under test.
Fig. 17(a) illustrates the measured currents at the secondary A hardware-based compensator using a controlled voltage
terminals of both the standard and under-test CTs, without source has been introduced to prevent CT saturation. This
the proposed compensation. As it can be seen, the under-test compensator cancels the voltage developed across the CT
CT experiences a very deep saturation. Fig. 17(b) depicts the burden and therefore, prevents the CT magnetic flux from
results of a same test when the under-test CT is compensated entering its saturation region. Some promising features of the
with the proposed compensator. As it can be seen, the proposed proposed compensation method are summarized as follows:

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

Current (A) 2 100 vB (t )

Voltage (V)
VDC
50
1
00
0 -50 vCT (t )  vB (t )  VDC
(a) VDC
-100
2
Current (A)

00  5 
10 
315 
220
1
2

 t (rad/s)
ωt rad
s  2

0
(b) Fig. A.1. The voltage across the CT terminal vCT (t) under ideal compen-
sation and steady-state ac current injection.
10
Voltage (V)

0 !
V
-10 θ = sin −1
√ DC (A.3)
(c) 2VXnew
-20
40 60 80 100 120 140 160 180 The CT magnetic flux associated with vCT can be eval-
Time (ms) uated by integration of (A.2). Here, the CT operates under
Fig. 17. a) The CT primary (solid line) and secondary (dash line) currents steady-state condition and due to voltage waveform symmetry
without the proposed compensator, b) CT primary (solid line) and secondary λ(2π) = λ(0). Therefore, the maximum CT magnetic flux
(dash line) currents with compensation, c) recorded vB (dash line) and vCV S λmax can be written as:
(solid line). VDC h π i
λmax = cot θ − + θ (A.4)
2πf 2
The ability to compensate current signal for both non-
• It is required to limit this magnetic flux to the CT saturation
digital and digital relays; flux λsat that can be calculated based on the real CT saturation
• The ability to compensate both in-service and newly voltage VXold through the following relation [26]:
installed CTs; V old
λsat = √ X (A.5)
• Eliminating the requirement for replacing the in-service 2πf
CTs with larger ones; Considering (A.4) with (A.5), one may conclude (A.6) in
• Preventing false operation of the protective relays due to order to avoid CT saturation:
π i √
CT saturation;
h
VDC cot θ − + θ ≤ 2VXold (A.6)
• Providing a simple theoretical control strategy with the 2
√ new
ability to compensate different possible current wave- Defining α = VDC /( 2VX ), (A.6) can be rewritten as
forms (fault current, inrush current, evolving fault, etc); follows: "√
• Low-cost hardware preserving a simple hardware struc-
#
1 − α2 π V old
ture, while having a set of appropriate design parameters. α − − sin−1 α ≤ X (A.7)
α 2 VXnew
The reliability and effectiveness of the proposed compen-
sator has been verified through a wide range of simulation 2) Selection of ∆Td : Assume that the compensator output
studies. The carried out experimental tests depicts the promis- voltage vCSV has a time delay equal to ∆Td corresponding
ing performance of the proposed device. to vB . In addition, vB has its maximum foreseen magnitude
as presented in
√(A.1). Here, the voltage across the CT is:
A PPENDIX vCT (t) = 2VXnew √ [sin (2πf t) − sin (2πf (t + ∆Td ))]
D ERIVATION OF T HE F ORMULAS FOR T HE PARAMETERS → vCT (t) = 2VXnew cos (2πf t) [2 sin (πf ∆Td )]
(A.8)
1) Magnitude of VDC : Assume that it is determined to Therefore, the CT magnetic flux can be calculated as:
increase the CT saturation voltage to VXnew . Therefore, the √ new
2VX sin (πf ∆Td )
maximum anticipated steady state voltage across the CT λεmax = (A.9)
πf
burden would be:
√ Considering λsat from (A.5), the error contributed by the
vB (t) = 2VXnew sin(2πf t) (A.1)
time delay ε can be calculated as follows:
Fig. A.1 depicts this voltage across the CT burden. Assume λε V new
ε = max = 2 Xold sin (πf ∆Td ) (A.10)
that the compensator dc voltage source is equal VDC . Ideally, λsat VX
the compensator output voltage vCSV can cancel vB while it is
less than VDC . Therefore, the voltage across the CT magnetic R EFERENCES
core vCT wouldbe:
[1] B. Schettino, C. Duque, P. Silveria, P. Ribeiro, and A. Cerqueira, “A
0 |vB (t)| ≤ VDC new method of current-transformer saturation detection in the presence
vCT (t) = (A.2)
vB (t) ∓ VDC |vB (t)| > VDC of noise,” IEEE Trans. Power Del., vol. 29, pp. 1760–1767, Aug. 2014.
[2] M. Stanbuty and Z. Djekic, “The impact of current transformer saturation
Fig. A.1 illustrates a typical waveform of vCT . In this figure, on transformer differential protection,” IEEE Trans. Power Del., vol. 30,
θ demonstrates the intersection point of VDC and vB . no. 3, pp. 1278–1287, June 2015.

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2016.2580585, IEEE
Transactions on Power Delivery

10

[3] T. Smith and R. Hunt, “Current transformer saturation effects on Ehsan Hajipour (S’12) received the B.Sc. and
coordinating time interval,” IEEE Trans. Ind. Appl., vol. 49, no. 2, pp. M.Sc. degrees in electrical engineering from Sharif
825–831, Mar. 2013. University of Technology, Tehran, Iran, in 2008 and
[4] F. Badrkhani, M. Sanaye-Pasand, M. Davarpanah, A. Rezaei-Zare, and 2010, respectively, where he is currently pursuing
R. Iravani, “Compensation of the current-transformer saturation effects the Ph.D. degree.
for digital relays,” IEEE Trans. Power Del., vol. 26, pp. 2531–2540, His research interests include power system pro-
Oct. 2011. tection, power system optimization, and digital sig-
[5] E. Hajipour, M. Salehizadeh, M. Vakilian, and M. Sanaye-Pasand, nal processing.
“Residual flux mitigation of protective current transformers used in an
auto-reclosing scheme,” IEEE Trans. Power Del., 2015, Early Access.
[6] D. Dolezilek, “Case study: replace substation wiring with rugged fiber
communications,” in IEEE Power Syst. Comf. and Expostion (PSCE),
Phoenix, AZ, 2011, pp. 1–8.
[7] W. Rebizant, J. Szafran, and A. Wiszniewski, Digital Signal Processing
in Power System Protection and Control. Springer-Verlag, 2011.
[8] N. Chothani and B. Bhalja, “New algorithm for current transformer
saturation detection and compensation based on derivatives of secondary
currents and Newton’s backward difference formulae,” IET Gener.
Transm. Distrib., vol. 8, no. 5, pp. 841–850, 2014.
[9] E. dos Santos, G. Cardoso, P. Farias, and A. de Morais, “CT saturation
detection based on the distance between consecutive points in the plans
formed by the secondary current samples and their difference-functions,”
IEEE Trans. Power Del., vol. 28, no. 1, pp. 29–37, Jan. 2013.
Mehdi Vakilian (M’95-SM’15) received the B.Sc.
[10] Q. Wu, Z. Lu, and T. Ji, Protective Relaying of Power System Using
degree in electrical engineering and the M.Sc. degree
Mathematical Morphology. Berlin, Germany: Springer-Verlag, 2009.
in electric power engineering from Sharif University
[11] A. Wiszniewski, W. Rebizant, and L. Schiel, “Correction of current
of Technology, Tehran, Iran, in 1978 and 1986,
transformer transient performance,” IEEE Trans. Power Del., vol. 23,
respectively, and the Ph.D. degree in electric power
pp. 624–632, Apr. 2008.
engineering from Rensselaer Polytechnic Institute,
[12] E. Hajipour, M. Vakilian, and M. Sanaye-Pasand, “Current transformer
Troy, NY, USA, in 1993.
saturation compensation for transformer differential relays,” IEEE Trans.
He was with the Iran Generation and Transmission
Power Del., vol. 30, no. 5, pp. 2293–2302, Oct. 2015.
Company, Tavanir, Iran, from 1981 to 1983, and
[13] M. Davarpanah, M. Sanaye-Pasand, and R. Iravani, “Saturation supres-
then with Iranian Ministry of Energy from 1984 to
sion approach for the current transformer-Part I: Fundamental concepts
1985. Since 1986, he has been with the faculty of
and design,” IEEE Trans. Power Del., vol. 28, no. 3, pp. 1928–1935,
Department of Electrical Engineering of Sharif University of Technology,
July 2013.
Tehran. During 2001 to 2003 and since 2014, he has been Chairman of the
[14] “Report on the condition of physical elements of transmission and
department. From 2003 to 2004 and for part of 2007, he was on leave of
distribution systems,” Niagara Mohawk Power Corp., NY, Tech. Rep.
study at the School of Electrical Engineering and Telecommunications of the
CASE 06-M-0878, 30 Sept. 2011.
University of New South Wales, Sydney, Australia. He has been the Director
[15] Q. Xu, A. Refsum, and R. Watson, “Application of external compen-
of the Power System Educational Group in the department for about six years.
sation to current transformers,” IEE Pro. Sci. Meas. and Technol., vol.
He is also the Director of a committee in charge of restructuring the Electrical
143, no. 2, pp. 147–150, Mar. 1996.
Engineering Undergraduate Education at Sharif University of Technology,
[16] D. Slomovitz and H. de Souza, “Shielded electronic current transformer,”
Tehran, from 2007 to now. His research interests are transient modeling of
IEEE Trans. Instrum. Meas., vol. 54, no. 2, pp. 500–502, Apr. 2005.
power system equipment, especially power transformers; optimum design of
[17] A. Baccigalupi and A. Liccardo, “Low-cost prototype for the electroni-
high-voltage equipment insulation; monitoring of power system equipment
cally compensation of current transformers,” IEEE Sens. J., vol. 9, no. 6,
and their insulation; power system transients; and distribution system studies.
pp. 641–647, June 2009.
[18] D. Bradley, C. Gray, and D. O’Kelly, “Transient compensation of current
transformers,” IEEE Trans. Power App. Syst., vol. PAS-97, no. 4, pp.
1264–1271, July 1978.
[19] M. Davarpanah, M. Sanaye-Pasand, and R. Iravani, “Saturation su-
pression approach for the current transformer-Part II: Performance
evaluation,” IEEE Trans. Power Del., vol. 28, no. 3, pp. 1936–1943,
July 2013.
[20] E. Hajipour and M. Vakilian, “Accurate protection current transformer
parameters determination method under high noise immunity,” in 23rd
Iranian Conf. Elect. Eng. (ICEE), Tehran, Iran, 2015, pp. 1545–1550.
[21] Solid state relays general information, Carlo Gavazzi Company.
[Online]. Available: www.carlogavazzisales.com
[22] J. Pan, K. Vu, and Y. Hu, “An efficient compensation algorithm for Majid Sanaye-Pasand (M’98-SM’05) received the
current transformer saturation effects,” IEEE Trans. Power Del., vol. 19, B.Sc. degree in electrical engineering from The
pp. 1623–1628, Oct. 2004. University of Tehran, Tehran, Iran, in 1988 and
[23] M. Ohrstrom, “Fast fault detection for power distribution systems,” the M.Sc. and Ph.D. degrees in electrical engineer-
Master’s thesis, Royal Institute of Technology (KTH), Stockholm, 2003. ing from The University of Calgary, Calgary, AB,
[24] F. de Leon, A. Farazmand, S. Jazebi, D. Deswal, and R. Revi, “Elimina- Canada, in 1994 and 1998, respectively.
tion of residual flux in transformers by the application of an alternating Currently, he is a Professor with the School of
polarity dc voltage source,” IEEE Trans. Power Del., vol. 30, no. 4, pp. Electrical and Computer Engineering, University of
1727–1734, Aug. 2015. Tehran. His research interests include power system
[25] Instrument Transformers- Part 8: Electronic Current Transformers, IEC protection, control, and transients.
Std. 60 044-8, 2002.
[26] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Std. C37.110, 1996.
[27] U. D. Annakkage, P. G. McLaren, E. Dirks, R. P. Jayasinghe, and A. D.
Parker, “A current transformer model based on the Jiles-Atherton theory
of ferromagnetic hysteresis,” IEEE Trans. Power Del., vol. 15, pp. 57–
61, Jan. 2000.

0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

Вам также может понравиться