Вы находитесь на странице: 1из 7

7th International Conference on Optimization of Electrical and Electronic Equipment OPTIM 2000,

Brasov (Romania), 11.-12. May 2000; Proceedings pp 251-258

400 KV SUBSTATION STRANDED CONDUCTOR BUSES


- Tests and Calculations of Short-Circuit Constraints and Behaviour -
Norbert STEIN Amir M. MIRI
FGH, Forschungsgemeinschaft für Elektrische Anlagen Institute of Electric Energy Systems and High-Voltage
und Stromwirtschaft, D-68219 Mannheim, Germany Engineering, University of Karlsruhe, P.O. Box 6980,
D-76128 Karlsruhe, Germany. Phone++49-721-608-3061,
Email miri@ieh.etec.uni-karlsruhe.de

Wolfgang MEYER
Universität Erlangen-Nürnberg,
Lehrstuhl für Elektrische Energieversorgung,
D-91058 Erlangen, Germany

Abstract: FGH and VDE have completed an extensive short-circuit assessment methods of IEC 865-1 and
programme of short-circuit tests on strained bus conductors. VDE 0103 so as to cover the so far not accessible ar-
Planning of the test series was done by DKE WG 121.2.2
'Short-Circuit Tests' and was performed under their rangements of droppers and long spans of stranded
guidance and that of CIGRE 23-03 ESCC TF (Effects of conductors with droppers that FGH and DKE 121.2
Short-Circuit Currents). The tests were performed on conducted the former study [2] and the present one, [1]
arrangements with and without droppers fitted to the bus having been the basis for introducing the calculation
conductors. For the arrangements with droppers the di- procedure for so-called 'Long Spans' into the standard.
fferent possible current paths were studied. Evaluation and
furthergoing study of test results are in progress. Parallel The second aim of the present tests is to further the
FE numerical simulations have been carried out by Prof. studies of the ESCC Task Force of CIGRE 23-03 on
Miri at IEH, Karlsruhe University. Beside the numerous 'Equivalent Static Load' for portal structures and their
variations of the short-circuit data - s.c. current and du- foundations.
ration - the geometrical/mechanical parameters of the test The new test series comprises 100kV and 400kV
arrangements were varied - e.g. conductors, phase distan-
ces, suspension insulator chains, anchoring steel structure arrangements of long spans of stranded conductor bus-
stiffness and eigenfrequency - to a degree to cover a wide bars strained between portals, without and with drop-
scale of practical applications. The latter parameter varia- pers leading down to a lower conductor level. The basic
tions were achieved by studying typical and exemplary geometric parameters of the former [1, 2] have been ap-
100kV and 400kV arrangements. The present paper deals plied, where possible, for compatibility. In particular,
with the recent 400kV part of these investigations (the 100kV
part to be published in ETEP [6]) with respective test conductor sag values were maintained. The available
results, together with parallel numerical studies and, also, material is immense, and the present paper had there-
first possible consequences to be drawn as to the standard- fore to be confined to the 400kV part and its results as
ized rules for assessing short-circuit performance by IEC far as the applicability of the procedures of [3, 4, 5] for
TC73 for Publ. 865. The authors give a survey of the tested 'long spans' holds valid at present: tensile forces on the
arrangements, together with the parameter variations
(structure mechanical and electrical) thus achieved, the suspension points and bus conductor displacement. The
detailed measurements of structure mechanical constraints respective 100kV results will be in [6], and a com-
and displacements and respective test results in exemplary prehensive presentation of the complete data is planned.
form. They report on the numerical studies applying FEM to Chapter 2 gives a survey of the complete tests, the
the test programme, which show a remarkable accuracy in great number of measuring points, exemplary results as
comparison with the actual test results. Finally, first
approaches as to modification requirements for the men- regards time dependency and maximum values of
tioned IEC/EN/VDE calculation procedures for assessing tensile loads on the suspension portals in comparison
short-circuit performance and strength are presented. with results of FEM calculations by the University of
Karlsruhe as explained in Chapter 3. Maximum dis-
Key words: Short circuits, measurement of mechanical
effects, structural analysis, Finite Element Method placement bh and minimum air clearance dmin are given.
Chapter 4 reports on a first approach to the extension of
1. INTRODUCTION the existing IEC/VDE rules to spans with droppers
It was with the intent to further the development of the developed at the University of Erlangen-Nürnberg. Both

251
calculatory efforts show a very remarkable degree of
agreement with the test results.

2. TESTS
The general test arrangement is shown in Fig. 1a and
the structural, geometrical and electrical short-circuit
parameters are assembled in Table 1. The paper itself
relates to arrangements 8 to 12, where the crossarm is at
11.22 m, the phases are at 3.00 m and the span is a
close bundle duplex ACSR conductor. Current path A,
i.e. without droppers, represents the reference case
which is accessible to calculation according to
IEC/VDE for the case B, which is with droppers not
carrying short-circuit current, and also for case C where
the short-circuit current flows over half the span and
then through the droppers to the lower level horizontal
rigid conductors. The essential data and force and strain
measuring points of the N portal are in Fig. 1b. The
calculatory efforts of Chapters 3 and 4, as far as forces

b) Portal N: Measuring points and geometric


parameters 400 kV

are concerned, relate mainly to measuring points KP


and to MAFU of Fig. 1b. The further measurements in
the portal for the determination of ESL, on the bus
conductors and in particular those along the conductor
support structure at the lower end of the droppers will
form the object of future publications. The conductor
Fig. 1 Test arrangement displacements at midspan were evaluated from high-
a) Span speed video recordings.

Table 1 400kV Test Parameters


Variants 1- 7: 100 kV

Va r ia n t 1 2 3 4 5 6
Span 40m 1 x AC S R 5 3 7 / 5 3 a = 2 m c u rre n t p a t h :

D r o p p e rs
w ith o u t 4 4 4 4 4 4 4 4 4 4 A
1 x AC S R 5 3 7 /5 3

3 .2 3 .2 3 .2 3 .2 1 .6 3 .2 1 .6 3 .2 1 .6 1 .6
D r o p p e r le n g th / m 6 .0 4 5 6 .0 4 5 5 .0 4 5 / 6 .0 4 5 5 .0 4 5 5 .0 4 5
C o n d u c to r 1 x AC S R 5 3 7 / 5 3
C u rr e n t p a th A B C B C B
20 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 0 .1 / 0 .3 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 0 .1 / 0 .3 / 0 .5
IK tK B
2 8 ,3 0 .1 /0 .2 /0 .3 /0 .5 /1 . 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 0 .1 / 0 .3 0 .1 / 0 .3 0 .1 / 0 .3 / 0 .5
kA 40
s 0 .1 /0 .2 /0 .3 /0 .5 /1 . 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3

Va r ia n t 7 8 9 10 11 12
Span 40m 2 x AC S R 5 3 7 / 5 3 a = 3 m

D r o p p e rs 4 4
w ith o u t 7 7 7 7 7 7 7 7
1 x AC S R 5 3 7 /5 3
C
1 .6 1 .6
3.2 3.2 3.2 3.2 5.6 5.6 5.6 5.6
D r o p p e r le n g th / m 5 .0 4 5 9 .1 4 5 9 .1 4 5 1 0 .5 4 5 1 0 .5 4 5
C o n d u c to r 2 x AC S R 5 3 7 / 5 3
C u rr e n t p a th C A B C B C
20 0 .1 / 0 .3 / 0 .5 0 .5 0 1 .0 0 .3 / 1 .0
IK tK
2 8 ,3 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 / 0 .5 0 .3 / 0 .5 / 1 .0 0 .3 / 0 .5 / 1 .0
kA 40
s 0 .1 / 0 .3 / 0 .5 0 .1 / 0 .3 / 0 .5 0 .3 / 0 .5 / 1 .0 0 .1 / 0 .3 / 0 .5

252
The portal structures, beside their design drawings and values to be considered for every parameter of each
construction data, are defined as regards their static and, constellation. The variance is, as can be seen exemplari-
in particular, their oscillatory behaviour by essential ly from Figs. 4 to 6, astonishingly small.
structural properties Stiffness and Eigenfrequency, Figs. 2 a) and 3a) show exemplary oscillograms of
measured in separate mechanical tests and listed in the the considered quantities from 100 kA / 40 kA - 0.5 s
following. These mechanical tests show absolutely tests on arrangement No. 9 (current B). The same
linear elastic characteristics for both portals given in arrangement and test parameters are used in Chapter 3
terms of the values of stiffnes SN and SM, the resulting to demonstrate the quality of FEM calculation through
stiffness to be used for the IEC/VDE simplified model the conformity of measured (Fig. 2a and 3a) and
is Sres. The respective values for the 400kV suspension calculated (Fig. 2b and 3b) oscillograms.
points at 11.22 m crossarm height and phase distance a
Short-circuit tensile forces: The only loads to be con-
= 3 m are:
sidered are the swing-out maxima Ft and the conductor-
fall maxima Fr. Conductor pinch forces do not occur, or
SN = 1.086 kN/mm SM = 1.223 kN/mm are negligible with single or close bundle conductors.
Sres = 0.575 kN/mm. Fig. 4 gives for current paths A, B and C (8 - 12) the
measured valus of Ft and Fr over the respective values
The relevant first eigenfrequencies excited at the of short-circuit duration. The mean values are connect-
mounted mid crossarm, i.e. next to the suspension ed by straight lines only for the purpose of better
points, are 9 Hz for the N-portal crossarm and 9.5 Hz readability. Linear interpolation between measuring
for the M-portal crossarm, while the complete portals points could be misleading, as intermediate 0.2 s values,
have basic frequencies of 3 Hz and 4.3 Hz, respectively, for instance, in Fig. 4b show.
the M-portal having the stiffer construction (see above). For current paths A and B a clear tendency for a
reduction of values for very low short-circuit durations
is obvious, which is less significant on C. The values
for case C, where the short-circuit current uses only half
of the span length, are clearly reduced against both
other cases A and B.

Bus conductor displacement: Figures 5 and 6 give the


maxima of the horizontal bus conductor displacements
towards the outside bh and the minimum air clearance
between these conductors dmin in the swing-back phase
after short-circuit for variants 8 - 12. These are acces-
sible by present IEC/VDE rules for the case A. The
extrema occur on the first swing-out (at or near the
instant of Ft for tk ≥ 0.2 s) and the first return of the
span conductor(s) after short-circuit. The oscillations of
these conductors in most of the cases persist over rather
long periods of time after short-circuit with only
moderate damping of the original displacements. Al-
though values are not given in this paper, it should be
mentioned that large and persisting oscillations occur,
in a much more important degree, in the movements of
the droppers in cases B and particu-larly in C. Short-
circuit durations of 0.2 to 0.3 s produce the worst cases
of span-conductor approach, while displacement to-
wards the outward is roughly constant beyond a short-
Fig. 2 Exemplary measured (above) and FEM-calculated circuit duration of 0.2 s. It is obvious that case C values
(below) oscillograms of short-circuit tensile forces for short-circuit displacement bh of the span conductor
KP for 100 kA/40 kA - 0.5 s test on variant No. 9 and minimum clearance between the neighboring spans
(curent path B) dmin, with the short-circuit current using only half of the
span, must be less than both other cases.
For each combination of test parameters as compiled
in Table 1, at least two identical consecutive tests were
performed to show the variance of behaviour and
effects. For reasons of symmetry, this gives at least four

253
c) 40
kN Ft
40 kA
Ff Ff
30

20 kA Ft
20
28,3 kA
F
10

0
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 s 1,0
tk

Fig. 4 Short-circuit tensile force Ft and drop force Ff


a) Cases A, B b) Case C

a) 3,0
m
2,5 28,3 kA 20 kA A
A B
2,0
40 kA
1,5
Fig. 3 Exemplary measured (above) and FEM-calculated d min 1,0
(below) oscillograms of short-circuit constraint
MAFU at the junction tower/foundation for 100 0,5
kA / 40 kA - 0.5 s test on arrangement 9 (current 0,0
path B). Same test as Fig. 2
a) 50 b) 3,0
m 20 kA
kN
Ff 2,5 28,3 kA
40 40 kA 40 kA
F t
2,0

30 Ff Ff 1,5
Ft Ft d min 1,0
28,3 kA 20 kA
F 20 0,5
0,0
10
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 s 1,0
tk
0
5
Fig. 5 Minimum air clearance dmin
a) Cases A, B b) Case C
b) 50
kN a) 1,00
Ff
40 40 kA A
Ft m
Ff 40 kA
0,75 B
30 Ff Ft A
Ft
20 kA 0,50 28,3 kA B
F 20
28,3 kA bh
A
0,25
10 20 kA
B
0 0,00
5 6

254
b) adjusting the model to achieve first the proper stiffness
0,75 and then eigenfrequency values. As usual conductors
m are done in truss elements - with particular dashpot
40 kA elements for duplex conductors. The programme ap-
0,50
plied was ABAQUS. The calculation was so far per-
28,3 kA formed for variants 1 to 10 of Table 1 and a short-cir-
b h 0,25 cuit duration of 0.3 or 0.5 s. The remarkable accordance
20 kA of calculation with measurement expresses itself in
particular in the comparison of the measured and calcu-
0,00 lated exemplary oscillographs and absolute values of
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 s 1,0 Fig. 2 and 3. The achieved results are evidence at once
tk for the validity of the applied method, as well as of its
practical use.
Fig. 6 Maximum horizontal displacements bh 4. CALCULATION ACCORDING TO IEC 60865-1
a) Cases A, B b) Case C
In IEC 60865-1 [3], identical to EN 60865-1 [4] and
DIN EN 60865-1/VDE 0103-[5], a method is standard-
3. CALCULATION WITH ADVANCED METHODS ized for the mechanical effects on substation buses with
The simplified methods of calculation in IEC/VDE are flexible conductors due to short-circuit currents. The
useful and necessary for typical design cases by hand or tensile forces Ft, Ff and Fpi and the maximum horizontal
computer-aided [7] calculation and allow parameter- displacement bh can be determined analy-tically. IEC
sensitive in-vestigations in a very short time by use of 60865-2 [9] gives an example for the calculations. The
personal com-puters. Only general input data are re- physical background, the assumptions made and the
quired, and the results are maximum values of tensile derivation of the method are described in detail in [10,
forces and dis-placements. The procedure is adjusted to 11]. The confrontation with many test results gives a
practical requirements and contains simplifications with good agreement. This standard is so far only applicable
safety margins. to arrangements without droppers, and the aim is to
Advanced methods use finite element or finite dif- show how to take into account droppers at midspan.
ference modelling, and powerful software is available The basis for the investigations are the test results
on workstations and personal computers. They can be described above.
applied to any structural configuration with single and At first, a calculation of the static sag is carried out
bundled conductors and forcing function [8]. The com- using the change-of-state equation. For variant 8 (with-
putation of the dynamic response of the complete out droppers) of Table 1, it corresponds to the tests. For
structure including their nonlinear behaviour is pos- the variants with droppers, an additional mass has to be
sible, and accurate results can be obtained, limited only added in midspan which consists of the mass of the
by the degree of detail in the modelling and the avai- clamp and about half the mass of the dropper due to its
lability of reliable basic structural data. The calculation stiffness and its fixation in the clamps.
of eigenfrequencies, time histories of forces, moments For the design of busbars, the maximum short-circuit
and deformations allows to study the system behaviour, duration Tk is stated by the protection concept. The
to detect and improve weak points, or to ascertain the actual short-circuit duration tk is unknown, can be lower
short-circuit strength even for complex cases. The range and can lead to higher tensile forces than Tk. Therefore
of validity of simplified methods can be investigated. the maximum values are determined by [3], which
During more than 20 years, the users of the ad-
vanced methods have acquired an excellent know-how occur within 0 < tk ≤ Tk [10]. In contrast, the short-
in the modelling and computation of substation struc- circuit duration tk is known when calculating tests and
tures. Test results have always been taken for compari- yields the swing-out angle δk at the end of the current
son and adaptation. flow, see [10, equ. (4.8)]. If tk ≥ Tres, the con-ductor
The possibilities and experience gained with these swings out to its highest position at δm = 2δ1 and then
detailed methods now allow to fill out and extend the back. Tres is the resulting oscillation period of the span
required framework set up by singular test result data by during current flow and δ1 = Arctan r the direction of
inter- and extra-polation varying the original test para- the maximum radial force Ft. r means the ratio of
meters in a degree that could not be done in actual electromagnetic force and gravitational force on the
testing. Only thus can the control basis for the develop- conductor. If tk ≤ Tres, δm = Arccos (1 - r sin δk) holds; Ft
ment of simplified calculation methods for new appli- is maximum at δ1 if δk ≥ δ1, otherwise at δk. Ft acts at
cations be laid. the end of the drop down from δm.
In consequence, the test structure of Fig. 1 is dis- For the variants 2 - 7 and 9 - 12, many investigations
cretized in a full detail FE model, using appropriate have been done. The best agreement with the tests could
beam elements for the framework of the portals and be achieved with the following assumptions:

255
- Disregard of the dropper mass: Fig. 4a, b shows that a)
50
droppers without current have no significant influence 0%
kN
on the tensile forces and the displacements. +25 %
- Disregard of the influence on the main-conductor 40
movement by the droppers: In contrast to the main-
conductor movement without droppers, there is a -25 %
change in the trajectory when the dropper is stretched. 30
Kinetic energy of the main conductor is converted into
elastic energy in the dropper and back during the fall
down. Due to the energy conservation law the tensile 20
forces Ft will not differ very much compared with the Fc
case without droppers; Fig. 4a, b confirms this.
- Influence of the current path on the electromagnetic 10
current path:
force: Cases A and B induce in the main conductors the A B C
electromagnetic force per unit length [10, eq. (*19)]
0
" 2 0 10 20 30 40 kN 50
µ (I ) lc
F'= 0 k2 (1) Fm
2π a l
b)
1,2
With Case C, the current flows only through half the +25 %
m 0%
main conductor and then through the dropper. The
transverse force on the main conductor due to the 1,0
electromagnetic force between the droppers is con-
sidered by substituting Ic in (1): 0,8 -25 %

"
µ0 ( I k 2 )
2
lc / 2 + ld / 2 0,6
F'= (2)
2π a l b hc
0,4
lc is the main-conductor length, ld the dropper length
and l the span length.
0,2 current path:
The comparison with the test results is given in Fig.
7; calculated values on vertical axis (index c) versus A B C
measured values on horizontal axis (index m). Each 0,0
sign marks a compared result different for cases B and 0,0 0,2 0,4 0,6 0,8 1,0 m 1,2
C and additional case A. Fig. 7a shows the greater one b hm
of each pair of tensile forces Ft, Ff, which is relevant for
design purposes. For Ik = 40 kA, Ft is always higher
than Ff; for 28.3 and 20 kA they are similar. Fig. 7b Fig. 7 Comparison between calculation and test
compares the maximum horizontal displacements bh. In a) Maximum of Ft and Ff
addition, the location of the relative error 0 % and the b) Horizontal displacement bh
technical limit ± 25 % are depicted as broken lines;
above the 0-% line the calculated values are on the safe - When comparing the horizontal displacements, it
side. should be kept in mind that they are measured with
an increment of 5 cm.
Fig. 7 points out:
- Most of the calculated values are on the safe side, The outcome of the calculation in comparison with
the error is less than 25 %. the tests permits to extend the method stated in IEC
- When they are not on the safe side, they are 60865-1 [3] to arrangements with droppers in midspan.
sufficiently small and occur only in the case of tk = The procedure should be as follows:
0.1 s. - the static tensile force Fst and the sag are estimated
- Due to the greater static tensile force, the tensile for- with an additional mass in the span equal to the
ces of case B are a little bit higher than those of A. clamp mass plus half the mass of the dropper.
- In tendency, the horizontal displacement is calculat- - Using this value of Fst, the short-circuit tensile forces
ed too high especially for 40 kA caused by physical Ft, Ff, Fpi and the maximum horizontal displacement
effects which cannot be taken into account [10]. bh are calculated according to subclause 2.3 of IEC
60685-1.

256
- If the current is flowing over half the span and the
droppers, eq. (19) of IEC 60685-1 for the electro- 4. EN 60865-1, Short-circuit currents - Calculation of
magnetic force on the main conductor should be effects. Part 1: Definitions and calculation method,
replaced by eq. (2) above. Brussels: CENELEC, 1993
5. DIN EN 60865-1/VDE 0103, Kurzschlussstroeme -
Berechnung der Wirkungen. Teil 1: Begriffe und
Berechnungsverfahren, Berlin: VDE, 1994
ACKNOWLEDGEMENT
The investigations were sponsored by the 6. Stein,, N., Meyer, W., Miri. A.M.: Tests and Calcu-
"Bundesminister für Wirtschaft" of Germany through lations of Short-Circuit Forces and Displacements in
the"Arbeitsgemeinschaft.Industrieller.Forschungsver- High-Voltage Substations with Strained Conductors
einigungen " Otto von Guericke e.V. (AiF) under the and Droppers, ETEP 2000
project number 9784. The authors wish to express their 7. PC Programme IEC 865, University of Erlangen, 1999
thanks to AiF for this substantial support,and also to
RWE Energie AG and Bayernwerk AG for their 8. Miri, A.M., Schwab, A.J., Kopatz, M.: Kurzschluss-
practical help to make the tests possible. stroeme und Leiterbewegungen in Hochspannungs-
schaltanlagen in Seilbauweise, Elektrizitätswirtschaft
REFERENCES 87 (1988), pp. 429-436
1. Herrmann, B., Stein, N., Kiessling, G.: Short-circuit 9. IEC 60865-2, Short-circuit currents - Calculation of
effects in high-voltage substations with stranded effects. Part 2: Examples of calculation, Geneva: IEC,
conductors. Systematic full-scale tests and a simple 1994
calculation method, IEEE Transactions on Power
Delivery 4 (1989), pp. 1021-1028 10. IEC TC 73/CIGR SC 23 WG 11, The mechanical
effects of short-circuit currents in open air substations
2. Hosemann, G., Miri, A.M., Stein, N., Zeitler, E.: The (Rigid and flexible bus-bars), Vol. 105, Geneva; IEC,
behaviour of droppers in high-voltage substations Paris: CIGRE, 1996
under short-circuit, in Proceedings of the 5th
International Symposium on Short-Circuit Currents in 11. Meyer, W., Herold, G., Zeitler, E-: Short-circuit
Power Systems, Warszawa, 1992 currents - Calculation of effects. The second edition of
IEC Publication 865, in Proceedings of the 6th
3. IEC 60865-1, Short-circuit currents - Calculation of International Symposium on Short-Circuit Currents in
effects. Part 1: Definitions and calculation method, Power Systems, Liège (Belgium), 1994.
Geneva; IEC, 1993

257

Вам также может понравиться