Mat.No. Rev.
00U0HU0-K081 3A
This page left blank
US - 2
Table of Contents
1. Safety Instructions.................................................................................................................4
1.1 General instructions.......................................................................................................4
1.2 Intended use..................................................................................................................4
1.3 Electrical connection......................................................................................................4
1.4 Personal protection........................................................................................................5
2. Unit Description......................................................................................................................6
2.1 Part number information................................................................................................6
2.2 Technical data and Environmental Conditions...............................................................6
2.3 Rated values for 208/230V 60Hz series THDI = 8%......................................................7
2.4 Rated values for 480V 60Hz series THDI = 8%.............................................................8
2.5 Dimensions
2.5.1 Core Dimensions..................................................................................................9
2.5.2 Capacitor Assembly Dimensions........................................................................12
2.5 Description...................................................................................................................14
2.5.1 International Standards......................................................................................14
2.5.2 Advantages........................................................................................................14
2.5.3 Applications.......................................................................................................15
2.5.4 Reactive-Power Compensation and Resonance Danger Mitigation..................15
2.5.4 Changing Capacitors.........................................................................................15
3. Installation Open Type / IP20 Units.....................................................................................16
3.1 Inductive Core Installation Instructions........................................................................16
3.2 Harmonic Filter Capacitor Assembly Installation Instructions......................................18
3.3.1 Harmonic Filter Standard (-1000 series)............................................................20
3.3.2 Harmonic Filter for KEB COMBIVERT R6-S Line Regen Unit (-1002 series)....20
3.4 Temperature Sensors...................................................................................................20
4. Example waveforms.............................................................................................................21
4.1 Voltage and current at the main line............................................................................21
4.2 Voltage and current with line choke impedance = 3% 480V/60Hz (4% 400V/50Hz)...21
4.3 Voltage and current with the harmonic filter THDI < 8%..............................................22
5. Annex....................................................................................................................................23
5.1 Fourier Analysis / Spectrum.........................................................................................23
5.2 Formula and Abbreviations..........................................................................................23
US - 3
Safety Instructions
1. Safety Instructions
The directions in this chapter must be absolutely observed for the following reasons:
• Safety for people and machines
• Function and susceptibility to faults
• Technical inspector acceptance and certification
• Guarantee and warranties
1.1 General instructions
All work from the transport, to installation and start-up as well as maintenance may
only be done by qualified personnel (IEC 364 and/or CENELEC HD 384 and IEC-
Only
Report 664 and note national safety regulations). According to this manual qualified
Qualified
personnel means those who are able to recognise and judge the possible dangers
Electrical
based on their technical training and experience and those with knowledge of the
Technician
relevant standards and who are familiar with the field of power transmission (VDE
0100, EN 50178, EN 60204 as well as the appropriate regulations for your area).
1.2 Intended use
Frequency inverters / servo drives are drive components which are intended for installation into electrical systems
or machines. They serve exclusively for step less speed regulation / control of three-phase asynchronous / per-
manent magnet motors. Use for other purpose is not recommended and may lead to equipment damage.
The KEB harmonic filter is to be used for reduction of harmonic current distortion
on the main supply network. The filter is a pass through filter connected in the sup-
ply line comparable to a standard AC choke with a laminated iron core. An almost
sinusoidal current is drawn from the line side of the filter and optimum conditions are
Verify created for the inverter or other electrical equipment using a B6 front end rectifier.
Electric
Power Operation of the harmonic filter is exclusively permissible when connected to electri-
System cal distribution systems in compliance with ANSI C84.1-1995 and IEEE-519-1992!
Electrical systems not in compliance can lead to reduction of the filter's effectiveness
and also to destruction of the filter module.
External reactive power compensation must be limited such that the total electrical
network does not become over compensated.
The harmonic filter must not be energized until it is determined that the installation
Verify and connection complies with NFPA-70 or CSA 22.1.
Connection Alterations to the harmonic filter are not allowed. The warranty is void if the product
is altered or disassembled or operated in contradiction to these instructions.
US - 4
Safety Instructions
Before any installation and connection work, the system must be switched off and
Note
secured.
Capacitor
The capacitors in the KEB Harmonic filter and connected motor control device may
Discharge
store a charge. Always wait 5 minutes after switch off before working on any electri-
Time
cal connections.
Cyclic With applications requiring the frequency inverter / servo drive to be switched on and
Turn ON and off cyclically, maintain an off-time of at least 5 min. If you require shorter cycle times
Turn OFF please contact KEB.
US - 5
Unit Description
2. Unit Description
2.1 Part Number Information
17.Z1.C05-1000
Options 1000 = Open Type, Basic Version
1001 = Auxiliary Contact on MMS Unit
1002 = Regen Sync Module
1003 = Regen Sync Module and Aux.
Contact on MMS Unit
1010 = Standard Unit w/ Capacitor Contactor
1011 = Cap Contactor & Auxiliary Contact on
MMS Unit
1012 = Cap Contactor, Regen Sync Module
1013 = Cap Contactor & Auxiliary Contact on MMS
Unit, w/ Regen Sync Module
Unit Type Z1
Unit Size 13 ... 30
US - 6
Unit Description
13.Z1.C03-1000
14.Z1.C03-1000
15.Z1.C03-1000
16.Z1.C03-1000
17.Z1.C03-1000
18.Z1.C03-1000
19.Z1.C03-1000
Part number
US - 7
Unit Description
17.Z1.C05-1000
18.Z1.C05-1000
19.Z1.C05-1000
20.Z1.C05-1000
21.Z1.C05-1000
22.Z1.C05-1000
23.Z1.C05-1000
24.Z1.C05-1000
25.Z1.C05-1000
27.Z1.C05-1000
28.Z1.C05-1000
29.Z1.C05-1000
30.Z1.C05-1000
Part number
Power Rated [hp] 20 25 30 40 50 60 75 100 125 150 200 250 300 400
Current Rated [A] 23 28 34 43 55 62 90 115 150 190 230 290 360 400
Voltage Rated [V] 480V (432...528 +/- 0V)
Frequency Rated 60Hz
Power Loss [W] 260 317 385 487 623 702 1020 1130 1375 1480 1780 1850 2440 2950
Recommended 350 500 600
10 10 8 8 6 6 2 2 2/0 3/0 4/0
wire gauge [AWG] MCM MCM MCM
Recommended
6.0 6.0 10 10 16 16 35 35 70 95 120 185 240 300
wire gauge [mm2]
Stud Size for Ring
- - - - - - M8 M8 M10 M10 M12 M12 M16 M16
Connector1) [mm]
Terminal Torque
3 3 3 3 4 4 12 12 20 20 31 31 60 60
[Nm]
Ground Stud Size
M8 M8 M8 M8 M8 M8 M8 M8 M12 M12 M12 M12 M12 M12
[mm]
Max. Circuit 35 40 50 70 80 90 130 170 220 280 340 430 540 600
Protection 2) [A]
SCCR [kA] 10 10 10 10 10 10 10 10 10 10 10 10 10 10
Manual Motor 10 10 20 20 24 24 50 50 63 75 75 63 63 75
Starter Current 10 50 63 75
Setting 3) [A]
1) Ring connectors must be UL listed (ZMVV) devices and must be crimped on with the manufacturers listed crimp tool and die.
2) These values are recommended. A circuit breaker is recommended since it clears all phases simultaneously. However, the actual required branch
circuit protection for the connected motor control takes precedence.
3) Protects capacitors. Factory and recommended setting. When two values are given there are two MMS units and refer to the setting of each.
US - 8
Unit Description
2.5 Dimensions
2.5.1 Core Dimensions
480V Harmonic Filter Core Dimensions [mm] Open Type IP20 (Sizes 20 - 150 hp)
Part number Figure B C H1 H2 H3 T1 L1 L2 L3 D1 D2
16Z1C05-1000 1 290 280 140 145 161 318 272 185 108 10 18
17Z1C05-1000 1 316 280 152 160 173 334 292 200 112 10 16
18Z1C05-1000 1 352 320 144 150 157 364 328 224 104 10 16
19Z1C05-1000 1 352 320 170 170 185 364 328 224 130 10 16
20Z1C05-1000 1 352 330 184 190 205 364 328 224 144 10 16
21Z1C05-1000 1 352 330 195 210 223 365 328 224 155 10 16
22Z1C05-1000 2 492 525 189 300 280 526 468 344 149 10 16
23Z1C05-1000 2 492 525 202 310 301 530 468 344 162 10 16
24Z1C05-1000 3 662 630 248 310 326 615 626 466 188 15 24
25Z1C05-1000 3 662 650 248 330 324 625 626 466 188 15 24
480V Harmonic Filter Core Dimensions [mm] Open Type IP20 (Sizes 200 - 400 hp)
Part number Figure B C H1 H2 H3 T1 L1 L2 L3 D1 D2
27Z1C05-1000 4 662 660 278 330 358 620 626 466 218 14.5 24
28Z1C05-1000 4 662 660 298 380 378 617 626 466 238 14.5 24
29Z1C05-1000 4 662 740 318 470 470 617 626 466 258 14.5 24
30Z1C05-1000 4 662 740 318 470 470 623 626 466 258 14.5 24
230V Harmonic Filter Core Dimensions [mm] Open Type IP20 (Sizes 7.5 - 40 hp)
Part number Figure B C H H1 H2 T1 L1 L2 L3 D1 D2
13Z1C03-1000 1 352 320 144 150 157 364 328 224 104 10 16
14Z1C03-1000 1 352 320 170 170 185 364 328 224 130 10 16
15Z1C03-1000 1 352 330 184 190 205 364 328 224 144 10 16
16Z1C03-1000 1 352 330 195 210 223 365 328 224 155 10 16
17Z1C03-1000 2 492 525 189 300 280 465 468 344 149 10 16
18Z1C03-1000 2 492 525 202 310 301 465 468 344 162 10 16
19Z1C03-1000 3 662 630 248 310 326 595 626 466 188 15 24
US - 9
Unit Description
Figure 1
Figure 2
US - 10
Unit Description
Figure 3
Figure 4
US - 11
Unit Description
1) Sizes 27-30 require two capacitor assemblies. Note figures 4 & 5 for sizes 27 & 28 and two times figure 5 for 29 & 30.
US - 12
Unit Description
Figure 4
Figure 5
US - 13
Unit Description
2.5 Description
2.5.2 Advantages
The following advantages are given by means of the special design of the KEB COMBILINE harmonic filter:
• Separate filter and capacitor mounting plate; This enables installation into small
spaces as the capacitor mounting can be up to 2 meters away from the filter
• Overall structure is compact; small space requirements for installation
• Installation solution ready-to-connect
• Significant reduction of the capacitive current during no-load operation
• No tendency for AC or DC voltage oscillation during rapid load change
• Significantly smaller voltage drop in comparison to line choke
• Increase inverter lifetime by means of the trapezoidal output voltage and resulting
square-wave current
• Reduction of THDI to <=8%, Given ISC/IL >=20
• Optional THDI <5% (special design)
• Large power range because parallel connection of filter modules is possible. I.e.
two units could be used to feed the double input of the KEB W housing inverter.
• Very high efficiency, due to the use of high grade steel and high frequency coil
winding system
• Easier mounting compared to a trap filter
• Damping against oscillation on main line
• 3 phase current protection device for capacitors prevents voltage imbalance in
case of activation
• 3 phase UL listed high harmonic capacitors for increased life and reliability
US - 14
Unit Description
2.5.3 Applications
The KEB COMBILINE Harmonic Filter can be used to reduce the value of THDI to a level <= 8%. The conditions
required for this assume the ratio of short circuit current to load current (ISC/IL) is 20 or greater, the maximum pre-
distortion of the voltage is not greater than 2%, and the filter is operating at its rated current value.
Under all other conditions the THDI value is still greatly reduced and will none the less provide great benefit to the
building power system.
Applications:
• To achieve compliance with power quality standards
• Used in place of a line choke to provide smaller voltage drop - results in increases motor torque.
• Reduction of effective input current to the motor control. Reactive power (kVAR) is greatly reduced, elimi-
nating the need to oversize upstream devices, transformers, power generators, etc.
• Protection of motor control against voltage spikes or irregularities on the main line
• Reduction of load on "weak" electrical systems
• Effectively triples DC bus capacitor lifetime
• Can be equipped with a synchronization module for use with the R6-S Line Regenerative unit
Therefore it is important to select a harmonic filter such as the KEB COMBILINE filter. Due to the unique KEB filter
design, the amount of capacitance and the relative level of capacitive current at no load is much lower than with
competitive filters. The result is that the use of the KEB filter reduces the risk of resonance danger.
US - 15
Installation
US - 16
Installation
Table 3.1
Recommended Means of Cooling
480V Units
Sizes Required Air Speed Example cooling fan
Across the at a distance of 26.6 cm [10.5 in] or less.
Inductive Core
16,17,18,19,20,21 Nothing Required None
The following images show example fan placement for optimum cooling. The dimensions are approximate and
provide a general location. The units are mm[in].
US - 17
Installation
Table 3.2
Recommended Capacitor Field Wiring Gauge Size
480V Units
Sizes Manual Motor Wire Size Capacitor Connection [Tighten torque]
Starter Rating
16,17 MMS 10A one set of 3 wires 12 AWG or 4 mm2 Fast-on [crimped] 1)
18,19 MMS 20A one set of 3 wires 12 AWG or 4 mm2 Terminal block [2 Nm]
20,21 MMS 25A one set of 3 wires 10 AWG or 6 mm 2
Terminal block [2 Nm]
22,23 MMS 50A one set of 3 wires 8 AWG or 10 mm 2
Terminal block [4 Nm]
24 MMS 63A one set of 3 wires 6 AWG or 16 mm2 Terminal block [4 Nm]
25 MMS 75A one set of 3 wires 4 AWG or 25 mm 2
Terminal block [4 Nm]
27 MMS1 75A one set of 3 wires 4 AWG or 25 mm 2
Terminal block [4 Nm] for (4 AWG)
MMS2 10A one set of 3 wires 12 AWG or 25mm2 Fast-on [crimped] 1) for (12 AWG)
28 MMS1 63A one set of 3 wires 4 AWG or 25 mm2 Terminal block [4 Nm] for (4AWG)
MMS2 50A one set of 3 wires 8 AWG or 10 mm2 Terminal block [2 Nm] for (8AWG)
29 MMS1 63A one set of 3 wires 4 AWG or 25 mm2 Terminal block [4 Nm]
MMS2 63A one set of 3 wires 4 AWG or 25 mm2 Terminal block [4 Nm]
30 MMS1 75A one set of 3 wires 4 AWG or 25 mm2 Terminal block [4 Nm]
MMS2 75A one set of 3 wires 4 AWG or 25 mm2 Terminal block [4 Nm]
208/230V Units
13,14 MMS 10A one set of 3 wires 12 AWG or 4 mm2 Terminal block [2 Nm]
15,16 MMS 20A one set of 3 wires 12 AWG or 4 mm 2
Terminal block [2 Nm]
17 MMS 50A one set of 3 wires 10 AWG or 6 mm 2
Terminal block [4 Nm]
18 MMS 50A one set of 3 wires 8 AWG or 10 mm 2
Terminal block [4 Nm]
19 MMS 50A one set of 3 wires 8 AWG or 10 mm2 Terminal block [4 Nm]
1) Fast-on connectors are Panduit Number DNF14-250FIB and must be crimped on using the Panduit CT-1525
crimp tool.
The manual motor starter(s) is/are used to provide branch circuit protection to the capacitor assembly(s). Under
normal conditions this unit should not activate. However if it is desired to monitor the status of this device, snap
on auxiliary contacts can be purchased separately or as a pre-installed option. See the following part number
scheme.
Sizes 16 to 22: 0090213-S137
Sizes 23 to 24: 0090213-S144
US - 18
Installation
US - 19
Installation
T5
T4
T6
T2
T3
T1
2T1 4T2 6T3 2T1 4T2 6T3
Max. Dist.
2m
3.3.2 Harmonic Filter for KEB COMBIVERT R6-S Line Regen Unit (-1002 series)
Max. Dist.
KEB COMBILINE KEB COMBILINE 1m KEB R6-S
Fuse or EMI FILTER Harmonic Filter Line Regen
MCCB X2B X2B ++
L1 L1 L1.1 U
L1.2 L12
++ ++/+PA
L2 L2 L2.1 V
L2.2 L22
L3 L3 L3.1 -- --/- W
L3.2 L32
PE GND -- PE PE
GND GND T1 T2
NC NO
Max. Dist.
2m
GND
Capacitor Assembly
• The -1002 series filters have a synchronization device installed which connects to the COMBIVERT R6S
regen unit. This solution is only available for filter sizes 16 to 21. (20hp to 60hp)
• In general the -1000 series filters can be used together with the COMBIVERT R6N regenerative unit. In
this case the additional synchronization connection is not required. The diagram is the same but without
the X2B connection. This solution is available for the complete power range size 16 to 30 (20hp to 400hp).
Always refer to the instruction manual of the regenerative unit for complete connection requirements.
US - 20
Waveforms
4. Example waveforms
4.1 Voltage and current at the main line
Without a line choke high current peaks (5 to 10 times the rms value) occur resulting in a high ripple current in the
DC bus of the motor control. This also means higher ripple voltage on the DC bus which can lead to torque ripple
or reduced torque output from the motor.
Voltage
Current
4.2 Voltage and current with line choke impedance = 3% 480V/60Hz (4% 400V/50Hz)
With inductance (line choke) the peak amplitude of the current is reduced to a range of 3 to 5 times the rms value.
This means lower ripple current in the DC bus of the motor control. This reduces heating in the capacitors and
effectively extends the lifetime by a factor of two.
Voltage
Current
US - 21
Waveforms
4.3 Voltage and current with the harmonic filter THDI < 8%
With the harmonic filter, the line-side current is sinusoidal. The peak amplitude of the current is 1.4 times the rms
value. The output of the filter provides a nearly ideal rectangular voltage and current waveform into the motor
control resulting in diode conduction of almost 180 degrees. The voltage on the DC bus is practically flat and the
DC bus capacitors see minimum ripple current. This results in a further extension of life to 3+ times the nominal.
Furthermore the average voltage value of the DC bus does not sag much in comparison to the first two cases. The
result is more motor torque at higher speeds.
Input
Voltage
Current
Output Voltage
Current
US - 22
Annex
5. Annex
5.1 Fourier Analysis / Spectrum
100
80
Current I in % of IH01
60
40
20
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
√
40
THD (Total Harmonic Distortion) THD = ∑
n=2
( )² IN
—
I1
THDV (Total Harmonic Distortion Voltage)
THDI (Total Harmonic Distortion Current)
√
40
PWHD (Partial Weighted Harmonic Distortion) PWHD =
n=14
∑ n
( )²
IN
—
I1
US - 23
Karl E. Brinkmann GmbH
Försterweg 36-38 • D-32683 Barntrup
fon: +49 5263 401-0 • fax: +49 5263 401-116
net: www.keb.de • mail: info@keb.de
KEB worldwide…
© KEB
Mat.No. 00U0HU0-K081
Rev. 3A
Date 01/2015