ISO 9001 ISO 14001 ISO 9001 ISO 14001 ISO 9001 ISO 14001
Certified number : 01 100 89394 Certified number : 01 104 9245101 Certified number : 01 100 79269 Certified number : 310102-UK Certified number : 00608Q11061R2M Certified number : 00609E20454R2M
Fujitsu General (Thailand) Co., Ltd. Fujitsu General (Shanghai) Co., Ltd. Fujitsu General Central Air-conditioner (Wuxi) Co., Ltd.
“ ” is a worldwide trademark of FUJITSU GENERAL LIMITED and is a registered trademark in Japan and other countries or areas.
*Echelon ®, LONWORKS ®, and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries.
*BACnet ® is a registered trademark of the American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE).
The colors may be different from the actual colors because this catalog is printed matter.
Product specifications are subject to change without notice.
Distributed by :
OU
UTDOOR UNITS
Small Office
Various Line-up
for each buildings
4HP AJ*A40LALH
5HP AJ*A45LALH Large Homes
6HP AJ*A54LALH
Service and
Building owners Installers End users
Management companies
Compact Cassette Cassette Low Static Pressure Duct Slim Duct Medium
(Drain Pump internal) Static Pressure Duct
High Floor / Ceiling Ceiling Wall Mounted Wall Mounted Central Group Touch Panel System Controller Wireless Simple Wired Wired
Static Pressure Duct (EEV internal / EEV external) Remote Controller Remote Controller Controller (Software) Remote Controller Remote Controller Remote Controller Remote Controller
(Touch Panel)
02 03
FEATURES
100
80
60 High performance and low noise Efficiency is improved by
realized by large propeller and mounting of new active filter
40
optimization of angle. module.
20
0
0 3 6 9 12 15 18 21 24
Time (h)
DC fan motor
Miniaturized, low noise, high
efficiency, multi-stage DC fan motor
is mounted.
Subcool heat exchanger
Cooling performance is
improved by mounting of dual
tube heat exchanger.
effect
Pressure
High EER / COP
66 % 50% 46 % 50%
UP UP
5.73 5.75
DC twin rotary compressor
High efficiency compressor motor
Efficiency in all load regions is good.
Especially good performance from low to
100% Optimized refrigerant flow design medium at normal operation.
4 HP 5 HP 6 HP 100% 3.95
High
3.45 Highly accurate parts
: EER : COP
Compressor
efficiency
DC Twin Rotary compressor
High
EER COP Compressor capacity
Cooling part load Heating part load
Heating
(kW)
capacity
Heating capacity is improved at low outdoor
temperature by our advanced technology.
The minimum and maximum temperature range can be set. The temperature setting is offset automatically over a J-II series (6HP)
certain period of time.
16.6
Set Temp.
(°C) Heating Cooling
Heating Set Temperature Down
33%
30 Down
MAX. - 4°C Down Current model (6HP class)
Down
28
Economy operation
26 Control Temperature
Economy operation UP !
24
Set Temp.
22
Economy operation Economy operation
20 Control Temperature
18 Up
MAX. +2°C -20 -10 0
Up 7
16 Cooling Set Temperature Outdoor temperature (°C)
14
12
10
Original Set point
Set Temp. limitation setting
Capacity save operation
The power consumption at peak can be limited.
Low Noise Design
Low noise design of outdoor unit Low noise mode
Capacity
Setting Capacity save Significantly reduced noise by optimized Outdoor unit can be switched to silent mode,
range
airflow structure design of outdoor unit. Current model depending on the installation environment.
56dB
100% Setting
level J-II series (4~ 6HP)
80%
53dB Noise
level
Rated noise value
60%
40% -5dB ~ -6dB
0%
Low noise mode
Central Remote Controller Time
6HP class (Cooling) Time
Temperature(°C)
35
ON
18:00 20:00 22:00 Set Temp. J-II series
30
Operation stopped at oil recovery Time 25
Heating operation Current ON 20
model OFF
15
Function setting is required. Time
1 indoor unit (Master) can apply this function.
06 07
FEATURES
More Convenience
Central Control of Small Office, Shop, etc. Individual and Central Control of Large Homes
Building Management Convertor for A/C Wireless Remote Controller Wired Remote Controller
central controller Central Remote Controller UTY-LNH* UTY-RNK*
System BMS Control UTY-DCG*
Network Convertor
for LONWORKS ®
UTY-VLGX
Network
Convertor Group
BACnet ® Gateway
(Software) UTY-VGGXZ1 Remote Controller
UTY-ABGX UTY-CGG*
Max. controllable
Lighting facilities 18 indoor units
Ventilation system
• Automatic display of number
Central of connected indoor unit
Security system Remote Controller
UTY-DCG* • Max. controllable
Max. controllable
100 indoor units
100 units
or
System
Controller (Software)
• Max. controllable
UTY-APGX R*: RY (FUJITSU), RG (GENERAL)
Max. controllable 18 indoor units UTY-RSK* UTY-RHK* K*: KY (FUJITSU), KG (GENERAL)
1,600 indoor units With operation mode Without operation mode H*: HY (FUJITSU), HG (GENERAL)
G*: GY (FUJITSU), GG (GENERAL) G*: GY (FUJITSU), GG (GENERAL)
Central
Remote Controller
or Central
Network Convertor
for LONWORKS ® Remote Controller
or
System Controller Network
(Software) Touch Panel Convertor Wired Wired Simple IR Receiver Unit Wireless Wired
Controller Group Remote Controller Remote Controller Remote Controller + Remote Controller Remote Controller
Remote Controller + Wireless +
BACnet ® Gateway Group Simple
(Software) Remote Controller Wireless
Remote Controller Remote Controller Remote Controller
08 09
FEATURES
Power supply
Piping length from Height difference between indoor (Outdoor )
first separation tube to and indoor units
the farthest indoor unit
15 m max.
40 m max. Easy wiring connection
• Decreasing wiring mistakes by using non-polar 2 wires.(Remote controller cable is 3 wires) Flexible installation by
Total piping length
• Improvement of wiring installation by common with V-II power supply method. 4 way pipe direction
180 m max.
(°C)
Wide operating range 50
Cooling
46°C
40
Installation in extreme temperature
conditions is possible due to an
30 Heating
21°C
Easy to connect J-II system V-II system
20
increase in operational range.
10
with V-II communication system Connects without a converter
Cooling : -5°C~46°C -20°C area
Heating : -20°C~21°C 0 Operation possible
-10 -5°C in heating.
10 11
FEATURES OUTDOOR UNITS
Specifications
Easy Maintenance Model name
Capacity range HP
AJ*A40LALH
4
AJ*A45LALH
5
AJ*A54LALH
6
Max.connectable indoor unit*1 7 8 9
Power source 1Ø, ~ 230 V, 50 Hz
Cooling 12.1 14.0 15.5
Capacity kW
Heating 13.6 16.0 18.0
Cooling 3.25 3.89 4.49
EER
Heating
Cooling
kW
3.17
3.72
3.81
3.60
4.56
3.45
W/W
COP Heating 4.29 4.20 3.95
Easy to read 7-segment LED Error status can be checked easily via Air flow rate m 3/h 6,200 6,400 6,900
Confirm detail operational and trouble status without using specific equipment the indoor unit wired controller Sound pressure level
Cooling
dB(A)
50 51 53
Heating 52 53 55
An error code is displayed on a liquid crystal
screen. Heat exchanger fin Blue fin
Dimensions (H×W×D) mm 1,334 x 970 x 370
Wired Remote Controller
Weight kg 117
Faulty unit number (Remote controller address)
Refrigerant charge kg 4.8 5.3
Error code
Liquid 9.52
Connection pipe diameter mm
Gas 15.88 19.05
Cooling -5 to 46
7-segment LED Operation temperature range °CDB
SU MO TU WE TH FR SA
Heating -20 to 21
Note : Specifications are based on the following conditions. AJ* : AJY (FUJITSU), AJH (GENERAL)
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
The protective function might work when using it outside the operation range.
43(Liquid)
the PCB
51(Gas)
(410)
370
40
Emergency Stop Function
32
36
970 32 370 12
1334
Central Remote Controller or Touch Panel Controller : all units
connected within VRF network system with Central Remote
Emergency Emergency
Controller or Touch Panel Controller will be stopped. Touch
T hPPanell
1000
stop function stop function
907
Controller 3-Way valve (Liquid)
111
70
le port)
((Liquid valve))
(Gas valve)
ab
Ø28 (C
297
Trouble diagnosis by Service Tool
279
120
Transmission cable
21
25
95
155
142
131
87
(Non-polar 2 wires)
50
50
50
le port)
Ø28 (Cable port) Ø28 (Cable port)
89 Pipe port 21 55 Ø28 (Cable port) 21 65 Ø28 (Cable port)
• Detail operation status and recent
Ø28 (Cab
Pipe port Pipe port
error history can be checked and
analyzed by using Service Tool. Service Tool A
UTY-ASGX Software Detail A
• Last 5 min. operation memory can 65 15
227
USB adaptor
305
be also recorded.
14
341
(Field supplied)
Equipment Detail (Diagram)
50
50
438 Pipe & cable port
622
12 AJ* : AJY (FUJITSU), AJH (GENERAL) 13
INDOOR UNITS
Indoor Unit Lineup Comprehensive range of indoor units of variety design and capacity ranges
available which can be selected to suit any air conditioning needs.
Compact Cassette
AUXB07GALH AUXB09GALH AUXB12GALH AUXB14GALH AUXB18GALH AUXB24GALH
Cassette
Cassette
AUXD18GALH AUXD24GALH AUXA30GALH AUXA36GALH AUXA45GALH AUXA54GALH
Slim Duct
(Drain pump internal)
ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH ARXD24GALH
Duct
Floor
(*Same as Ceiling models)
AB*A12GATH AB*A14GATH AB*A18GATH AB*A24GATH
Ceiling Ceiling
AB*A12GATH AB*A14GATH AB*A18GATH AB*A24GATH AB*A30GATH AB*A36GATH AB*A45GATH AB*A54GATH
Wall Mounted
AS*A07GACH AS*A09GACH AS*A12GACH AS*A14GACH AS*A18GACH AS*A24GACH AS*A30GACH
Wall Mounted
With this model,
Wall Mounted connection of
(EEV external) EV kit is necessary.
AS*E07GACH AS*E09GACH AS*E12GACH AS*E14GACH
14 15
INDOOR UNITS
Compact Cassette
Models Improvement of the airflow distribution High lift drain pump
AUXB07GALH
AUXB09GALH
Ceiling panel
Max.
AUXB12GALH 1 700mm
AUXB14GALH A
B
AUXB18GALH C
AUXB24GALH D 3
Model name AUXB07GALH AUXB09GALH AUXB12GALH AUXB14GALH AUXB18GALH AUXB24GALH Models: AUXB07 / AUXB09 / AUXB12 / AUXB14 / AUXB18 / AUXB24
Power source 230V ~, 50Hz 530
700 Hanging bolt position
Capacity Cooling 2.2 2.8 3.6 4.5 5.6 7.1
kW
Heating 2.8 3.2 4.1 5.0 6.3 8.0
Ceiling openings
Airflow rate High 540 550 600 680 710 1,030
□ 580 to 660
700
Med m3/h 450 450 530 590 580 830
540
Low 350 350 390 390 400 450
370
Sound pressure level High 34 35 37 38 41 50
Med dB(A) 30 30 34 34 35 44
530
Low 25 25 27 27 27 30 IR receiver
Drain hose
Dimensions (H x W x D) mm 245 x 570 x 570
Weight kg 15 17
Connection Liquid (Flare) ø6.35 ø9.52 146
pipe diameter
Gas (Flare) mm ø12.70 ø15.88 285 285 183 40
Drain ø25 (I.D) ; ø32 (O.D.)
Cassette Model name UTG-UF*C-W
215
Grille
Dimensions (H x W x D) mm 50 x 700 x 700
Weight kg 2.6
19
114
114
262
123
30
30
F* : FY (FUJITSU) ; FG(GENERAL) Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB. Ceiling Gas pipe
Note : Specifications are based on the following conditions. Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB. Control Box
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. Voltage : 230 [V]. Liquid pipe
16 17
INDOOR UNITS
Cassette
Models Improvement of the airflow distribution High lift drain pump
AUXD18GALH The louvre design distributes air
AUXD24GALH leaving a space between the Ceiling panel
Max.
chassis and the ceiling allowing far
AUXA30GALH and wide air flow distribution. 850mm
AUXA36GALH Front part Ceiling Bottom view
AUXA45GALH
AUXA54GALH
Rear part High ceiling mode
Powerful, wide airflow and quiet operation Much less temperature irregularity
Round louvre happens by spreading airflow widely This cassette can be installed up to a height of 4.2m (36/45/54).
450mm
3-dimensional blade Previous blade
Optional parts
One way aperture installation IR Receiver Unit : UTY-LRH*B1
Heat exchanger Heat exchanger Air Outlet Shutter Plate : UTR-YDZC
< Motor side > < Motor side > Separation
phenomenon of
Panel Spacer : UTG-BGYA-W
Wind velocity
Fast Quiet airflow Insulation Kit for High Humidity : UTZ-KXGA / UTZ-KXGB
causes noise Parallel
No airflow separation apertures Wide Panel : UTG-AGYA-W
Fresh Air Intake Kit : UTZ-VXGA
Slow
Uneven airflow
H*: HY(FUJITSU), HG(GENERAL)
: Spin direction : Airflow direction : Turbulent flow noise
Model name AUXD18GALH AUXD24GALH AUXA30GALH AUXA36GALH AUXA45GALH AUXA54GALH Models: AUXD18 / AUXD24 (Slim type)
Power source 230V ~, 50Hz
AUXA30 / AUXA36 / AUXA45 / AUXA54
Capacity Cooling 5.6 7.1 9.0 11.2 12.5 14.0
kW
Heating 6.3 8.0 10.0 12.5 14.0 16.0 IR receiver 796
(Option) 950
Hanging bolt position
Input power W 39 46 59 80 99 119
Airflow rate High 1,150 1,280 1,600 1,800 1,900 2,000
Ceiling opening
Low 870 870 1,100 1,100 1,100 1,100
□ 860 to 910
36 38 40 44 46 47
950
Sound pressure level High
699
Med dB(A) 30 33 38 38 39 39
420
Low 29 29 33 33 33 33
607
Dimensions (H x W x D) mm 246 x 840 x 840 288 x 840 x 840
Weight kg 22 27
Drain hose
Connection Liquid (Flare) ø9.52 358
pipe diameter (Control) Box
Gas (Flare) mm ø15.88 ø19.05
Drain ø25 (I.D.) ; ø32 (O.D.) 358 278 60
Cassette Model name UTG-UG*A-W 40
Grille
298(256)
Dimensions (H x W x D) mm 50 x 950 x 950
200
Weight kg 5.5
142
142
10
G* : GY(FUJITSU) ; GG(GENERAL) Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
140
44
Ceiling Liquid pipe Gas pipe
Note : Specifications are based on the following conditions. Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. Voltage : 230 [V]. Wire hole
18 19
INDOOR UNITS
Filter (Accessory)
ARXB07 / ARXB09 ARXB12 / ARXB14 / Filter
Duct indoor unit
Filter ARXB18 (3pcs.)
Low noise level Two-direction drain piping (2pcs.)
Low static pressure
Normal mode
A low noise level has been achieved for each capacity mode
Airflow drop
Air-intake
Airflow
prevention
Air intake direction can be selected to match the installation site.
Model 7 9 12 14 18 Low noise
realized
Static pressure Optional parts
Pa 0 to 50
range Remote Sensor Unit : UTY-XSZX
Noise level dB(A) 24 27 25 30 30 IR Receiver Unit : UTB-YWC
(Low speed) Bottom side Back side Drain Pump Unit : UTZ-PX1BBA
Static pressure (Pa)
Model name ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH Models: ARXB07 / ARXB09 / ARXB12 / ARXB14 / ARXB18 886 (596)
170
kW
Heating 2.8 3.2 4.0 5.0 6.3
Input power W 46 55 63 90 96 886 (596) 217
Control box
Airflow rate High 440 590 800 890 (Bolt pitch) 194
370
Med m3 / h 310 370 500 750 810
1
Low 280 340 450 700 730 Brackets
(Bolt pitch)
3
390
Static pressure range 0 to 50 0 to 50 0 to 50 0 to 50 0 to 50 Brackets
Pa 2
587
595
Standard static pressure 25 25 25 25 25
364
Sound pressure level High 29 31 30 33 36
dB(A)
65 75
Med 26 29 28 32 34
166
Low 24 27 25 30 30
24 47
Dimensions (H x W x D) mm 217 x 663 x 595 217 x 953 x 595
20
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
217
Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB. 2 Refrigerant piping flare connection (Liquid)
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. 3 Drain piping connection
20 21
INDOOR UNITS
Flexible installation
Ceiling concealed
Model name ARXD07GALH ARXD09GALH ARXD12GALH ARXD14GALH ARXD18GALH ARXD24GALH Models: ARXD07 / ARXD09 / ARXD12 / ARXD14 / ARXD18 / ARXD24
*Service accessibility must be allowed for when installing the product.
Power source 230V ~, 50Hz
Please consult the installation manual for the necessary service access size.
Capacity Cooling 2.2 2.8 3.6 4.5 5.6 7.1
kW
Heating 2.8 3.2 4.0 5.0 6.3 8.0 51 G
174
152
71
30
Input power W 44 50 54 92 83 122
Airflow rate High 550 600 600 800 940 1,330
Med m3/ h 490 550 510 710 840 1,240
(Bolt pitch)
377
Low 440 480 450 610 750 1,100
82
Static pressure range 0 to 90 0 to 90 0 to 90 0 to 90 0 to 90 0 to 50
Pa
Standard static pressure 25 25 25 25 25 25 48
High 30 35 30
Sound pressure level 28 29 34 34
Med F E
dB(A) 25 26 27 32 32 32
(All surroundings) D
Low 22 24 24 28 28 29
C
Dimensions (H x W x D) mm 198 x 700 x 620 198 x 900 x 620 198 x 1,100 x 620 (Bolt pitch)
10 ARXD07-14 ARXD18 ARXD24
163
119
Weight kg 17 18 22 26 43
198
168
89
78
55
47
78
22 23
INDOOR UNITS
Low energy consumption by DC fan motor. Can be installed for various location 4.Motor
The maintenance of the motor and fan can be easily carried out by removing
the rear panel and the lower part of the casing while leaving the main
chassis installed.
Installation styles
Easy setting by using remote controller
Slim & Compact design Low energy consumption by Embedded in Ceiling Hanging from Ceiling
In the case of bottom return air connection, not only does the indoor high efficiency DC fan motor The change of static
pressure range is possible
unit design allow for installation in a narrow ceiling space of up to
Improved motor efficiency from previous model. by remote controller
270mm, Further space savings have been achieved by mounting
the electrical control box internally inside the chassis.
NEW NEW
1,200 1,135mm
Two-direction drain
Control box is now included as
part of the main chassis
piping
270mm Optional parts
One touch operating and easy Remote Sensor Unit : UTY-XSZX Flange (Round) : UTD-RF204
to install long life filter Long Life Filter : UTD-LF25NA IR Receiver Unit : UTB-YWC
Duct indoor unit Flange (Square) : UTD-SF045T Drain Pump Unit : UTZ-PX1NBA
(Optional Parts) 24 model 30 / 36 / 45 model Two-direction drain piping
Model name ARXA24GBLH ARXA30GBLH ARXA36GBLH ARXA45GBLH Models: ARXA24 / ARXA30 / ARXA36 / ARXA45
Power source 230V ~, 50Hz *Service accessibility must be allowed for when installing the product.
Capacity Cooling 7.1 9.0 11.2 12.5 Please consult the installation manual for the necessary service access size.
kW
Heating 8.0 10.0 12.5 14.0
Input power W 94 108 194 240
1177(Bolt pitch) 114
270 66
168
Airflow rate High 1,280 1,410 1,840 1,970 Outlet
32 32
Med m 3/h 990 1,280 1,600 1,860 ø200
(knock 1
240
Low
240
840 1,150 1,470 1,640 out hole)
281
138 264 264 264
3
447(Bolt pitch)
Static pressure range 0 to 150 0 to 150 0 to 150 0 to 150 82
Pa
138
700
Standard static pressure 40 50 50 60
3
Sound pressure level High 31 34 37 41 2
Med dB(A) 27 32 35 38
161
173
ø205 hole 75
Low 23 29 33 36
Dimensions (H x W x D) mm 270 x 1,135 x 700 Front view
P.C.D. ø225
Weight kg 36 40 1015 240
107
121 1135 270
Connection Liquid (Flare) ø9.52
Top view
pipe diameter
Gas (Flare) mm ø15.88 ø19.05 Side view (L) Side view (R)
24 25
INDOOR UNITS
ARXC36GATH
ARXC45GATH
Previous model New model
(ARXC36GATH)
500mm
Easy installation (Compact size & Lightweight) Plastic fan Heat exchanger
ø225mm
Models : ARXC36 1,050 500
A compact size and lightweight indoor unit has been
Volume Weight
400mm
developed by reducing the basic chassis and the overall
material weight. 47.5% 42% 400 Optional parts
down down
Long-Life Filter : UTD-LF60KA
IR Receiver Unit : UTB-YWC
ARXC36GATH : 43kg (unit: mm) Casing (Plastic) Remote Sensor Unit : UTY-XSZX
123
139
862
41
Airflow rate High 2,600 3,500 88
Med m3/ h 1,950 3,000
500(Bolt pitch)
1
Low 1,450 2,460
585
2
Static pressure range 100 to 200 100 to 250
Pa
Standard static pressure 100 100 3
Sound pressure level 45 49 Rear view 71
High
4
Med dB(A) 38 45 Side view (R)
295 851
Low 32 42
1,050 85
Side view (L)
Dimensions (H x W x D) mm 400 x 1,050 x 500 Top view
Weight kg 43 46
Connection Liquid ø9.52 (Flare)
pipe diameter
Gas mm ø19.05 (Flare)
Drain ø25 (I.D.) ; ø32 (O.D.)
Front view
1 Refrigerant piping flare connection (Liquid)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
2 Refrigerant piping flare connection (Gas)
Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. 3 Drain piping connection
26 27
INDOOR UNITS
Floor / Ceiling
Models Double auto swing Super vane
AB*A12GATH A combination of up/down and right/left directional swing Double Louvre Super vane with newly developed special
AB*A14GATH allows three-dimensional air direction control. configuration boosts airflow sending cool air quickly to every
corner of the room.
AB*A18GATH RIGHT and LEFT SWING UP and DOWN SWING
AB*A24GATH
3
The slim and lightweight design allow the unit to be suspended 1
from the ceiling or installed on the floor. 1
2 4
Auto-closing louvre
5 2
This type suits many room designs When operation is stopped, the louvres will automatically close.
Floor standing 3 (This function is available on all non-ducted models.)
4
5 steps selectable
4 steps selectable
Compact design
Symmetrical, slim and compact design.
Model name AB*A12GATH AB*A14GATH AB*A18GATH AB*A24GATH Models: AB*A12 / AB*A14 / AB*A18 / AB*A24
Power source 230V ~, 50Hz
Capacity Cooling 3.6 4.5 5.6 7.1
kW
Heating 4.0 5.0 6.3 8.0
Input power W 30 42 74 99
Airflow rate High 660 780 1,000 1,000
Med m3/ h 570 640 720 820
Low 490 550 580 680
Sound pressure level High 36 40 46 47
Med dB(A) 32 36 39 42
Low 28 34 35 37
Dimensions (H x W x D) mm 199 x 990 x 655
Weight kg 25 26 26 27
Connection Liquid (Flare) ø6.35 ø9.52 2 1
pipe diameter
Gas (Flare) mm ø12.70 ø15.88
Drain ø25 (I.D.) ; ø32 (O.D.)
2
1
AB*: ABY(FUJITSU), ABH(GENERAL)
Note : Specifications are based on the following conditions. 1 Refrigerant piping flare connection (Liquid)
Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
2 Refrigerant piping flare connection (Gas)
Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. 3 Drain piping connection
Voltage : 230 [V].
3 3
28 29
INDOOR UNITS
Ceiling
Models Double auto swing and wide airflow High lift drain pump
AB*A30GATH Auto airflow direction and auto swing Optional drain
Max.
AB*A36GATH Right and left
pump unit allows
flexible installation 500mm
AB*A45GATH design.
AB*A54GATH
Easily concealed in any installation
Fresh air intake
5 steps selectable
Up and down
Fresh
air
1
Indoor Outdoor
2
3
4
Model name AB*A30GATH AB*A36GATH AB*A45GATH AB*A54GATH Models: AB*A30 / AB*A36 / AB*A45 / AB*A54
Power source 230V ~, 50Hz
Capacity Cooling 9.0 11.2 12.5 14.0
kW
Heating 10.0 12.5 14.0 16.0
Input power W 66 85 131 180
Airflow rate High 1,630 1,690 2,010 2,270
Med m3/ h 1,370 1,400 1,600 1,780
Low 1,140 1,170 1,230 1,280
Sound pressure level High 42 45 48 51
Med dB(A) 38 38 42 45
Low 33 34 35 36
Dimensions (H x W x D) mm 240 x 1,660 x 700
Weight kg 46 48
Connection Liquid (Flare) ø9.52 ø9.52
pipe diameter
Gas (Flare) mm ø15.88 ø19.05
Drain ø25 (I.D.) ; ø32 (O.D.)
30 31
INDOOR UNITS
Wall Mounted
Models (EEV internal model) Models (EEV external model) Compact size Width Auto swing louvre
AS*A07GACH AS*E07GACH Powerful output even compact design 790mm The Auto Swing Louvre function
AS*A09GACH AS*E09GACH Though the indoor unit is compact, it features a large, high
ensures that the air direction
corresponds to the mode selected.
AS*A12GACH AS*E12GACH pressure cross fan (90mm diameter) in a centre mounted
configuration and a Lambda type heat exchanger to provide plenty
AS*A14GACH AS*E14GACH of power.
1
Sw
3
ing
4
Step
Swing
790mm
Filter features
High quality air conditioning by incorporation of high performance filter. Deodorizing effect (Odor reduction rate)
Ammonia Trimethylamine
Long-life* Ion (ppm) (ppm) New style high power DC fan motor Easy maintenance
Deodorization Filter 160 160
Easy maintenance
With no filter
With no filter • High power
120 120 has been realized as
• Wide rotation range
The filter deodorizes by powerfully decomposing absorbed 80 80 New filter • High efficiency the front panel can
odors using the oxidizing and reducing effects of ions generated New filter
40 40 • Compact size removed for easy access.
by the ultra-fine-particle ceramic.
0 0 Open panel
(*The filter can be used for approx. 3 years if it is washed under water to restore 0 30 60 120 (min) 0 30 60 120 (min)
its surface action when it is dirty.)
Hydrogen sulfate
(ppm)
Apple-catechin Filter 160
With no filter
120
Fine dust, invisible mold spores, and harmful microorganisms 80 New filter Testing organization :
are absorbed onto the filter by static electricity, and further 40 Environmental Sanitary Inspection Center Symmetrical design
growth is inhibited and deactivated by the polyphenol 0 Test method :
extracted from apples. 0 30 60 120 (min) Deodorization Test
Symmetrical, clean design that suits all interiors.
Model name AS*A07GACH AS*A09GACH AS*A12GACH AS*A14GACH AS*E07GACH AS*E09GACH AS*E12GACH AS*E14GACH Models: AS*A07 / AS*A09 / AS*A12 / AS*A14
Power source
AS*E07 / AS*E09 / AS*E12 / AS*E14
230V ~, 50Hz 230V ~, 50Hz
Capacity Cooling 2.2 2.8 3.6 4.5 2.2 2.8 3.6 4.5
kW 790
Heating 2.8 3.2 4.1 5.0 2.8 3.2 4.1 5.0 215
Input power W 17 18 22 34 15 16 21 34
Airflow rate High 490 500 560 670 490 500 560 680
Med m 3/h 450 450 480 490 450 450 480 490
Low 370/420*1 370/420*1 420 420 370/420*1 370/420*1 420 420
275
Sound pressure High 35 36 39 44 34 35 38 43
level
Med dB(A) 33 33 35 37 32 32 34 35
Low 27/31*1 27/31*1 31 32 26/30*1 26/30*1 30 30
Dimensions (H x W x D) mm 275 x 790 x 215 275 x 790 x 215
470
Weight kg 9 9 3
530
Connection Liquid (Flare) ø6.35 ø6.35
pipe diameter 660
Gas (Flare) mm ø12.70 ø12.70 EV kit (UTR-EV09XB/ UTR-EV14XB ) Optional parts:
1 2
65
Drain ø13.8(I.D.) ; ø15.8-ø16.7(O.D.) ø13.8(I.D.) ; ø15.8-ø16.7(O.D.)
EV Kit (option) - UTR-EV09XB UTR-EV14XB 416 19
222 32
UPWARD
Vertical installation
Install the unit as confirmed direction.
AS*: ASY(FUJITSU), ASH(GENERAL) Cooling : Indoor temperature of 27˚CDB / 19˚CWB, and outdoor temperature of 35˚CDB / 24˚CWB.
wire
UPWARD wire
121
Note : Specifications are based on the following conditions. 2 Refrigerant pipe flare connection (Gas)
by more than 5°
Heating : Indoor temperature of 20˚CDB / (15˚CWB), and outdoor temperature of 7˚CDB / 6˚CWB.
Install the unit as confiremed direction .
97
Install the unit where it will not be tilted
by more than 5°
Horizontal installation
65
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m. 3 Drain piping connection OUTDOOR UNIT
SIDE
INDOOR UNIT
SIDE
32 33
INDOOR UNITS
Wall Mounted
Models “Vertical airflow” Air conditioner filter features
AS*A18GACH provides powerful floor level heating
AS*A24GACH 5
(24/30)
“Horizontal airflow” does not blow cool air Antibacterial deodorizing pre-filter with special ceramic powder
Apple-catechin Filter
Easy maintenance Fine dust, invisible mold spores, and harmful microorganisms
are absorbed onto the filter by static electricity, and further
998mm DC fan motor 1120mm
Simplification of drain pan cleaning improves
maintenance-ability.
growth is inhibited and deactivated by the polyphenol
extracted from apples.
34 35
CONTROLLER
Control System
Every user's needs are supported by offering a variety of controls, such as individual
control, central control and building management control options.
Outdoor unit
System Controller Software Wired Remote Controller
UTY-APGX
USB Adaptor *2
(Touch panel)
UTY-PEGX(Option) UTY-RNR*
Internet or Public Indoor unit
(Field supplied)
Telephone Line
R*:RY(FUJITSU), RG(GENERAL)
Outdoor unit
Wired Remote Controller
Remote / Monitoring side UTY-RNK*
Indoor unit
UTY-DTG*
Simple Remote Controller
UTY-RSK*
G*:GY(FUJITSU), GG(GENERAL)
UTY-DCG*
Simple Remote Controller Signal Amplifier
UTY-RHK* UTY-VSGXZ1
General-purpose Without
G*:GY(FUJITSU), GG(GENERAL)
Building Control Computer operation mode
Network Convertor
(Field supplied)
UTY-VGGXZ1
3 6 9 12 15 18 21
7
SU MO TU WE TH FR SA
3 6 9 12 15 18 21
36 37
CONTROLLER
Display
Cooling/heating priority - - - - -
LONWORKS® 2 Remote Controllers External Switch Controller
Network Indoor unit can be controlled Indoor units can be controlled by combining Address display - - - - -
from both remote controllers. with Card-key switch such as hotel room.
Room temp - - - - - - - - -
Transmission line
line is non-polar 2-conductor. Multi language - - - - - -
Signal Amplifier Network Convertor Network Convertor Summer time - - - - -
UTY-VSGX UTY-VGGXZ1 UTY-VGGXZ1
USB Name registration - - - - - -
Web Monitoring Tool Web Monitoring Tool
Adaptor
Backlight - - - -
Trouble free operation at all times UTY-AMGX
by remote monitoring system. Period Week Week - - - Week Week Year Year
Schedule timer On/Off, Temp,
Service Tool 8 4 - - - 4 20 20 144
UTY-ASGX mode, times per day
Big Multi system Single system
(VRF network system side) On/off timer - - - - - - - -
Timer
Service Tool Sleep timer - - - - - - - - -
Internet
or Extensive monitoring and analysis - - - - - -
Program timer - - -
Public Telephone Line functions for installation and maintenance.
(Monitoring side) Auto off timer - - - - - - - -
USB Adaptor Day off - - - - -
Transmission line
Min. unit of timer setting (Minutes) 10 30
●
30 - - 5 10 10 10 10
Outdoor Touch Panel Wired External Switch Module link
unit Controller Remote Controller Controller Status monitoring system - - - - - -
Remote Controller line
(2 wires) Electricity charge calculation - - - - - - - -
(Monitoring side) (Monitoring side) Indoor unit Central Remote Simple IR Receiver Remote Controller line Error history -
(Cassette) Controller Remote Controller unit (3 wires)
Control
*2 *2
Emergency stop - - - - - - -
USB cable
Control via internet - - - - - - - -
Indoor unit Group Simple LONWORKS® Network
(Duct) Remote Controller Remote Controller E-mail notification for malfunction - - - - - - - -
Ethernet
38 39
CONTROLLER
Individual Thermo Weekly Auto off Ex) At interval time hour Set interval time hour (17:00 to 24:00)
control sensor timer timer (17:00 to 24:00)to ON Auto OFF
prevent forgetting to
turn off Set off time Summer Time display Name Registration
(30 to 240 minutes) • This function can be set easily from • Indoor unit names can be registered in
17:00 24:00
OFF Menu screen the remote controller screen.
This makes it easy to identify the
Accurate and comfortable control 2 schedules Weekly Timer indoor unit you want to control in the
• 2 schedules such as for the summer and winter can be set. room.
• Indoor temperature can be detected accurately by the inclusion of
• 8 setting changeable per day of week (Setting items: On/Off,
a thermo sensor in the body of the wired controller.
Temperature, Mode, Time)
Ex)
Simplified installation
Uses non-polar 2-wire type Auto Address Setting/Setting Position Notification
• The faulty wiring can be I.U. Y1Y2 Y3 I.U. Y1Y2 Y3 • Reduce errors and install time compared with the current specifica-
Schedule 1 (Summer schedule) Schedule 2 (Winter schedule)
Setting temp. Setting temp.
prevented by using tion Rotary SW
ON OFF OFF
26°C ON OFF OFF non-polar 2-wire. • When will be set remote controller groups, can also be set
25°C non-polar
24°C 2-wire automatically new Wired remote controller address
23°C
• After auto address setting of new wired remote controller groups,
OK OK
what number can also confirm addresses
Time Time
8:40 11:40 17:30 20:40 8:40 10:00 15:30 17:30 20:40
Address → 04 03 02 01
Y1 Y2 Y1 Y2
Set Temperature Auto Return
• The setting temperature automatically returns to the previous
setting temperature. The appropriate indoor unit
performs the air blow and
• The time range in which the set temperature can be changed is LED lamps blink.
10 to 120 minutes.
05
Cooling operation Heating operation
Setting temp. Set temperature change Auto return Setting temp. Set temperature change Auto return
24°C 25°C Easy Maintenance
22°C
23°C Error History Display
Settable time range
Settable time range
Room temperature sensor Room temperature 10 to 120 minutes
10 to 120 minutes
• The errors that occur in the indoor unit or
display 11:40 13:40
Time
11:40 13:40
Time remote controller are saved as a history.
• A maximum of 32 error incidents can be saved.
Set Temperature Upper and Lower Limit Setting
Backlight • The set temperature range can be set for each operation mode.
(Cooling / Heating / Auto)
• Backlight enable easy operation in a
During Cooling During Heating Specifications
darkened room.
30°C 30°C
• For the lighting time of Backlight, 30 Model name UTY-RNR*
25°C
or 60 seconds can be set. 25°C
• Backlight activates while the buttons Power Supply DC 12V
are operated and goes off 30 or 60 Dimensions (H x W x D) (mm) 120 x 120 x 20.4
18°C 10°C
seconds after the operation stops. Original temp. Lower limit Original temp. Upper limit Weight (g) 220
setting range setting setting range setting
DC12V is supplied by the indoor unit. R* : RY(FUJITSU), RG(GENERAL)
40 41
CONTROLLER
16
Simple Remote Controller Max. controllable
16
indoor units indoor units
UTY-RNK* UTY-RSK*
UTY-RHK* (Without Operation mode)
The room temperature can be controlled by detecting Compact remote controller provides access to
the temperature accurately from the built-in sensor basic functions
• Simple operation with Built-in Weekly / Daily Timer. • Up to 16 indoor units can be controlled with one remote controller.
• Control up to 16 indoor units. • Suitable for hotels or offices as it is easily operated with no complex
• Up to 2 wired remote controllers can be connected to a single indoor unit. functions.
UTY-RSK* UTY-RHK*
Without Operation mode
Functions Functions
Powerful features and compact size Built-in timers Easy-to-understand time bar display User-friendly operation Backlight
This Wired Remote Controller incorporates four primary functions Weekly timer : Possible to set ON/OFF time to • Provides access to basic operations, such as Start / Stop, Fan • Backlight enables easy operation in a
into a single unit. operate twice each day of the week. control, Operation mode switching, and Room temperature darkened room.
setting. • Backlight activates during all button
Setup screen example Screen after setup • A large On / Off button is provided in the centre of the remote operations, and lasts 10 seconds in
Individual Thermo Weekly Setback Set to Wednesday: 8:00 to 20:00. controller for easy operation. Operation mode and 5 seconds in stop
control sensor timer timer 24°C • Can be used jointly with other individual control unit. mode after a button is pressed.
0 3 6 9 12 15 18 21 Time • Following an error display, diagnostics can be carried out on the
controller.
Setback timer : Possible to set temperature for two times spans
and for each day of the week.
Accurate and comfortable Setup screen example
83.5mm
location, suitable for all Fan control
requirements. Operation mode *1
Example of changing sensor Diagnosis check function European switch box JIS built-in box Room temp. setting
Day Night
Specifications Specifications
Model name UTY-RNK* Model name UTY-RSK* UTY-RHK*
DC12V is supplied by the indoor unit. K* : KY(FUJITSU), KG(GENERAL) DC12V is supplied by the indoor unit. K* : KY(FUJITSU), KG(GENERAL)
42 43
CONTROLLER
16
IR Receiver Unit
indoor units
UTY-LNH* UTB-YWC
Selectable
60min.
2˚C
Address setting
1˚C
During installation work, address setting can be performed using
Heating operation
the Wireless Remote Controller, thus eliminating manual switch
setting. IR Receiver Unit
When the sleep timer is set, the set temperature automatically drops
1˚C every 30 minutes. The set temperature can drop to a max. of 4˚C. Transmission line UTY-LRH*B1
60min.
90min.
Timer setting
Wireless
Remote Controller
Specifications Specifications
Model name UTY-LNH* Model name UTY-LRH*B1
44 45
CONTROLLER
8
remote controller
UTY-CGG* groups
Useful functions
Max. connectable
Group control of indoor units with
simple operation
64
group R.C. in
1 Timer setting at all the Indoor Unit Operation Indicators
connected indoor units is Timer setting at all the connected indoor units
a VRF network possible by centralized timer is possible by centralized timer on
• Up to 8 remote controller groups can be controlled by one Group Remote Controller. system
on the front panel.
With cover closed the front panel.
• Up to 64 Group Remote Controllers can be connected in one VRF network system. : On : Off
• Network Convertor (UTY-VGGXZ1) is required to connect Group Remote Controllers : Timer operation : Selection
* 1 : "AUTO " is not available for a heat pump model unless it is set up for the master indoor unit.
* 2 : "FAN " is not available for a heat pump model
Built-in weekly timers * 3 : "HEAT " is not available for a cooling only model
The weekly timer is provided as a standard function.
1. The timer can be set up for up to 4 times per day. (On / Off, operating mode, set temperature)
2. Allows separate settings for each day of the week.
ON / OFF switching Cooling / Heating switching Temperature switching Temperature switching Stop setting
(Peak power cut) (Anti-freeze)
Specifications
Ope.
Ope.
Ope.
Ope.
Ope.
46 47
CONTROLLER
100
Indoor units
UTY-DCG*
Functions
Central control of small- and medium-sized buildings and Max. controllable
Operation guidance
Easy Installation
• The control panel and power supply unit can be installed • Automatic or manual indoor unit registration
separately.
• For flexibility in installation, the Control panel can be built into the Indoor unit registration
wall or fix on the wall.
Setting pattern 1 Setting pattern 2
Indoor unit registration
System overview
Ceiling
start
Power supply unit
Group : 2F
Specifications
Group : Tenant A Group : Tenant B Group : Tenant C Model name UTY-DCG*
G* : GY(FUJITSU), GG(GENERAL)
48 49
CONTROLLER
400
Indoor units
UTY-DTG*
Up to 400 indoor units can be controlled
High visibility and easy operation via high resolution Group A Group B
7.5 inch TFT-LCD touch panel screen
• Large-sized 7.5-inch TFT color
• LCD Easy finger touch operation
• Stylish shape and design to suit all application
It allows multiple indoor unit grouping
• No additional component is required for installation
• Up to 400 indoor units can be controlled
• Selectable 2 display types (Icon / List) in monitoring mode Emergency stop control
Air conditioner can be turned
• Corresponds to 7 different languages, English, Chinese, French, German, Spanish, Russian, Polish.
off through the external input control
Emergency stop function
Functions
Function Versatility
• Up to 400 indoor units can be controlled CSV format data edited by PC can be imported to
• It allows multiple indoor units grouping Touch Panel Controller.
• Schedule timer function is standard (20 patterns per day)
• Emergency stop function(through the external input control)
• Temperature upper and lower limit setting
• The clock of each indoor unit correct setting Data transfer available
by USB
G* : GY(FUJITSU), GG(GENERAL)
50 51
CONTROLLER
4
VRF network
UTY-APGX systems
Energy saving management With UTY-PEGX Option
Max. controllable
System Controller realizes the advanced integrated monitoring & control of 400
Outdoor units Peak cut operation Option Outdoor unit capacity save Option
VRF network system from small scale buildings to large scale buildings.
A power meter is connected to detect the total power consumption Outdoor unit capacity save switches the outdoor unit capability
• Up to a maximum of 4 VRF network systems, 1600 indoor units, and 400 outdoor units Max. controllable while shifting the indoor unit set temperature, set the indoor unit upper limit to suppress power consumption during hot summers
can be controlled.
• Supports VRF S series, V series and V-ll series. 1,600
Indoor units
forced thermostat off, and taking other measures to carefully
control the power
and cold winters by averaging the power saving effect of each
refrigerant system. You can select from 50% or more of the
• In addition to air conditioning precision control function, central remote control, consumed while Outdoor unit Forced thermostat Target power
capacity upper limit.
stop range off range consumption
electricity charge calculation, schedule management, and energy saving functions are maintaining comfort and
strengthened and building manager and owner needs are met. conducting control to
Outdoor unit
maintain the target
Power consumption
capacity
power consumption set upper limit
Functions for each time.
The indoor units to be
controlled can be freely
User friendly view and operation grouped and the control
Shows change in power Ideal control line (Use of
• Click & Operate : The property is shown visually from the • Freely define groups for batched control : Indoor units can be level can be set. consumption by time average power consumption) Outdoor unit capacity control screen Time
perspective most suitable for operation and operated accordingly freely grouped for simple batched control from a tree menu.
(Click & Operate). You can select from among the 4 displays of Grouping by hierarchal structure, such as by section, division or
site, building, floor, or list. department is possible.
Indoor unit rotation operation Option Batched stop
The operation of indoor units can be automatically rotated within a Batched stop at a freely set time for a property, building, or freely
Click & Operate the whole building ! Properties can be shown using one of the four Click & Operate any specified unit(s)! group in accordance with the set annual schedule to reduce power set block unit can be done to prevent any air conditioning unit from
displays of site, building, floor, or list. consumption while maintaining comfort. The indoor unit operation being forgotten to be turned off at the end of office hours, etc. In
stoppage rate can be selected. addition, any air conditioning unit whose operation is left on can be
immediately identified by the icon color for a building or indoor unit
in the monitoring screen and batched stop conducted in response.
Batched stop
Forget to turn off Entire building stopped
Indoor unit rotation screen
Site view List view
Floor view
Click & Operate the unit !
52 53
CONTROLLER
Remote centralized control Schedule control Error display & E-mail notification
System Controller may be used on site or remotely over various • Annual schedules can be set for each remote controller group / Error is notified with popup
networks for remote central control. System Controller requires Remote central control user defined group. message, audible sound
2 softwares working together. VRF Controller runs on site and 1 VRF Explorer can control or monitor up to 10 sites. • Start / stop, operating mode, remote controller prohibition, and and E-mail real time when
communicate with VRF system. VRF Explorer runs remotely and temperature settings can be set up to 144 times per day at 10 error occurs. Error for the
provides user interface and communicate with the VRF Controller. VRF Explorer minute intervals for up to 101 configurations for each remote past 1 year are logged and
VRF Controller and VRF Explorer program may run in a single PC Building management company,
controller group. can be reviewed later.
VRF Controller
or in different PCs separated by network. By using VRF Explorer management center, etc. • Settings can be made for periods straddling midnight.
A maximum of
software, one PC can perform central control of 10 VRF system 10 locations, such as • Allows programming of special settings for holidays, including
sites with max. 20 buildings per site. offices or factories public holidays, for a complete year.
• Low noise operation of outdoor unit can be scheduled.
VRF Controller
On site central control Internet
or
Max. 4 VRF network systems per site Telephone Line
or
LAN Operating & control record
Displays the history of
operation status and control.
Internet
or
Telephone Line
or
LAN
1 VRF Controller can be monitored from any number
VRF Explorer of VRF Explorers (Up to 5 connections simultaneously).
Central Monitoring Screen
for all Properties VRF Explorer Building Management Company A
(In charge of the day shift)
VRF Explorer
VRF Explorer Diverse control of indoor units
Prohibition Setting
• Indoor unit operation state, operation
mode, etc. are displayed This prohibits changes to the operation mode, temperature, start / stop, etc.
Building
Management Company B
Internet
• Indoor unit start / stop and operation mode
(In charge of the night shift) or
Office Management Center
Telephone Line switching
VRF Explorer
or
LAN
VRF Controller • Temperature setting, Remote Controller Multiple language display
prohibition.
Corresponds to 7 different languages (English, Chinese,
VRF Explorer French, German, Spanish, Russian, Polish)
Security Company
<OPTION AVAILABLE>
Security Support Energy Saving Software UTY-PEGX(*1) Additional support for energy saving function and Electricity Charge Apportionment using electricity meter.
Employs SSL Encryption Technology Detailed User Management
Encryption technology is used for communications to User identification : Authorization using <PACKING LIST>
remote sites to prevent information from being stolen. user IDs and passwords is employed to Name and shape Quantity Application
prevent unauthorized access.
Encryption DVD-ROM 1 Includes the software and manuals for System Controller. Both VRF Controller and VRF Explorer software are included.
Access authority : The functions that can
Wibu Key 1 Software protection key to be inserted in a USB slot running System Controller. System Controller may only run on a PC with Wibu Key.
be used are restricted for individual login (Software protection key) However, Wibu key is not required for remote VRF Explorer software.
users to prevent unauthorized use.
Personal computer must be field supplied. U10 USB Network Interface must be field supplied. Contact Echelon® Corporation or its local sales representative for detail.
Product Name : U10 USB Network Interface - TP/FT-10 Channel Model Number : 75010R
*1: Energy Saving Software (UTY-PEGX) is available for the indoor units and the outdoor units after revision code B or later.
54 Microsoft® Windows® 8 will be supported.(Future release) 55
CONVERTOR & ADAPTOR
16
Network Convertor for LONWORKS ® Max. controllable
4
single indoor units Units to BMS
UTY-VGGXZ1 UTY-VLGX
Max. connectable Max. controllable
4
Group Remote
100
Outdoor units
Controllers
• This Network Convertor is to be used for connecting single split system or Group • For connection between VRF network system and a LONWORKS® open network for Max. controllable
Remote Controller (UTY-CGGY / UTY-CGGG) with the VRF network system.
• Please select the function by switching the dip switch during the installation.
management of small to medium-sized BMS and VRF network system.
• The UTY-VLGX permits central monitoring and control of a VRF network system 128
Indoor units
from a BMS through a LONWORKS® interface.
• Up to 128 Indoor units can be connected to one Network Convertor for LONWORKS®
Please consult your distributor for connectable split type air conditioner. Ventilation system
Up to 100 Network Convertors may be connected in single VRF network system.
One Network Convertor is considered as a single refrigerant system,
irrespective of the number of connected single models.
LONWORKS®
Network VRF network system 2
Power Supply 208-240V 50/60Hz, Single phase Power Supply 208-240V 50/60Hz, Single phase
None
Terminal resistor
(It attaches at the terminal of a network.)
56 57
CONVERTOR & ADAPTOR
4
VRF network
Signal Amplifier
UTY-ABGX systems UTY-VSGXZ1
Max. controllable
• It is possible to connect medium to large sized BMS to VRF network system via BACnet®, a global standard for
open networks. 400
Outdoor units
• Transmission Line length can be extended up to 3,600m with multiple
Signal Amplifiers.
• A maximum of 1600 indoor units with 4 VRF network systems (a maximum of 400 indoor units & 100 outdoor • Up to 40 signal amplifiers can be installed in a VRF network system.
units for one network system) can be connected to one BACnet® Gateway. • A signal amplifier is required,
Max. controllable
• It is possible to control or monitor VRF network system from BMS via BACnet® Gateway.
1,600
(1) When the total wiring length of the transmission line exceeds 500m.
• Compatible with BACnet® (ANSI / ASHRAE-135-2004) application specific controller (B-ASC). (2) When the total number of units on the transmission line exceeds 64.
• Compatible with BACnet®/IP over Ethernet. Indoor units
• Scheduling function, Alarm & Event functions as well as Electricity Change Apportionment function are provided
in BACnet® Gateway.
• Connection between VRF network system to personal computer is possible via small U10 USB interface. Installation example
However, both U10 USB interface & personal computer are field supplied items. Dimensions (Unit : mm)
• Corresponds to 7 different languages, English, Chinese, French, German, Spanish, Russian, Polish.
B
Installation example A C
D
VRF network system 1
BACnet ® BACnet ® Operator
Workstation (B-OWS)
Signal Amplifier
USB adaptor *1
(Field supplied)
Outdoor unit
Indoor unit Specifications
Model name UTY-VSGXZ1
Lighting facilities
Power Supply 208-240V 50/60Hz, Single phase
VRF network system 2
Security system Power Consumption (W) 4.5
USB adaptor Dimensions (H x W x D) (mm) 67 x 288 x 211
(Field supplied) BACnet ® Gateway Automatic fire alarm interface
(UTY-ABGX) Weight (g) 1,500
Outdoor unit
Indoor unit USB adaptor
(Field supplied) Ventilation system
DVD-ROM Software
(Software) Protection Key
= BACnet® Gateway for each system.
USB adaptor
3 6 9 12 15 18 21
100
UTY-ASGX Outdoor units 5) Error History 6) Remote File Download
Displays the error information for each Operation and error history data can be
Max. Monitor and unit. The error information can downloaded. Only the required data may
Extensive monitoring and analysis functions for installation and maintenance. control sequentially be displayed up to 50 items be downloaded specifying the refrigerant
• Operation status can be checked and analyzed to detect even the small abnormalities. 400
Indoor units
as they occur starting with the latest
error.
system, unit and time range.
• Data collected and stored on site can be checked later, off-line, off-site for more detail analysis.
• One VRF network system with maximum number of up to 400 units can be monitored and controlled.
• Operation status and various sensor information can be monitored and checked real time in the form of list, refrigerant circuit
diagram, graphs as well. 7) Commissioning Tool 8) Network Topology Analyzer *
• Simple operation control functions are useful during maintenance.
Test run commands can be executed with this tool. A list of units connected to the VRF system network is
• The recent error history can be retrieved from units on demand to perform analysis on the cause of the error, after connecting During test running, the outdoor unit / indoor unit sensor data can be saved displayed in network segments in tree form.
Service Tool to the VRF network system. (commissioning log data).
• Commissioning tool supports test runs, data storage for each unit and saving of data as CSV files, which may be formatted to After the end of test running, this data can be exported in CSV file format.
create commissioning report.
• Connectable to any point of transmission line with USB adaptor*1 (field supplied)
• Connection between VRF network system to personal computer is possible via small U10 USB interface. However, both U10
USB interface & personal computer are field supplied items.
• 14 advanced functions are available for the VR-II series for through servicing and through shooting. 9) Remote Setting * 10) System Time Setting *
・The operating state (Solenoid valve) of RB unit can be checked. Function (Field) Setting for indoor unit is An arbitrary time is set for all the remote controllers within the system.
* 1: Service Tool (UTY-ASGX) will only support USB type network adaptor and will not support transmission adaptor of the traditional type(UTR-YTMA) realized remotely
Wiring connection
USB adaptor
(Field supplied) (Field supplied)
Transmission line 13) Error Memory Reader * 14) Time Guard Information *
Easy to
carry out with When an error occurs at an outdoor unit, the operation data records before Reference data for judging the maintenance period of indoor and outdoor
Indoor unit USB adaptor the error are acquired over a network and saved to a CSV file. units (compressor,FAN, etc. integrated time) is output to a CSV file.
*USB Adaptor is U10 USB Network interface of Echelon ® Corporation. Note: To perform "Error Memory Reading", Service Tool and the correspond-
ing outdoor unit must be connected directly with each other. Refer to
the Operation Manual of the Service Tool for detail. *: Supported by Ver. 1.1 or later
3) Equipment Detail (List) 4) Operation History Interface USB port for U10 USB Network Interface and Software protection key
Displays the detail information for sensor The indoor units or outdoor unit Software required Internet Explorer 7.0 or 8.0 or 9.0 / Adobe® Reader® 9.0 or later
values, electrical components etc. of operation history can be recorded. Hardware required DVD-ROM Drive
units in a specified refrigerant system in The displayed operation history can be
list form. The information here can be printed out and saved to a CSV file. <PACKING LIST>
used along with the detail information in
Name and shape Quantity Application
diagram form, to check the operation
status of units and make detail analysis DVD-ROM 1 Includes the software and manuals for Service Tool.
on the cause, in case an error occurs.
Wibu Key 1 Software protection key to be inserted in a USB slot running Service Tool.
(Software protection key) Service Tool may only run on a PC with Wibu Key.
Personal computer must be field supplied. U10 USB Network Interface must be field supplied. Contact Echelon® Corporation or its local sales representative for detail.
Product Name : U10 USB Network Interface - TP/FT-10 Channel Model Number : 75010R
Microsoft® Windows® 8 will be supported.(Future release)
60 61
SERVICE & MONITORING
USB adapter
(Field supplied)
<PACKING LIST>
Name and shape Quantity Application
VRF Network VRF Network VRF Network VRF Network DVD-ROM 1 Includes the software and manuals for Web Monitoring Tool.
System 1 System 2 System 3 System 4
Wibu Key 1 Software protection key to be inserted in a USB slot running Web Monitoring Tool.
VRF Network System Max. 400 Max. 400 Max. 400 Max. 400
Indoor unit Indoor unit Indoor unit Indoor unit (Software protection key) Web Monitoring Tool may only run on a PC with Wibu Key.
Personal computer must be field supplied. U10 USB Network Interface must be field supplied. Contact Echelon® Corporation or its local sales representative for detail.
Product Name : U10 USB Network Interface - TP/FT-10 Channel Model Number : 75010R
Microsoft® Windows® 8 will be supported.(Future release)
62 63
DESIGN SUPPORT
In addition, at night during the hot season, when the outside air temperature An external static pressure is improved by adopting a powerful fan
drops the outside air is drawn inside without heat exchange, alleviating the motor. Exhaust air Outside air Exhaust air
load on the air conditioning equipment. Supply air This allows for application in a wide variety building.
Room air
Rated flow rate 250 m3/h 350 m3/h 500 m3/h 800 m3/h 1000 m3/h
Models: UTZ-BD025B / UTZ-BD035B / UTZ-BD050B / UTZ-BD080B / UTZ-BD100B
External static pressure Extra high / High / Low Pa 105 / 95 / 45 140 / 60 / 45 120 / 60 / 35 140 / 110 / 55 105 / 80 / 75
Temperature Exchange
VENTILATION
64 65
DESIGN SUPPORT
Duct type
Unit: mm
Model Name W1 W2 H1 H2 D1 D2
Installation limitation
UTD-GXSA-W 683 645 The equipment installation limitation range is shown. The distance range
UTD-GXSB-W 883 845 180 148 9 84 from the wall, etc., is automatically displayed to make it easy to provide highly
reliable layout designs.
UTD-GXSC-W 1,083 1,045
Wired Remote Wireles Remote
Controller Controller
Net Dimension
(H x W x D)
mm
(inch)
180x683x(84+9)
[7-3/32x26-7/8x(3-5/16+11/32)]
180x883x(84+9)
[7-3/32x34-3/4x(3-5/16+11/32)]
180x1083x(84+9)
[7-3/32x42-5/8x(3-5/16+11/32)]
Product specifications & Link information
Contains the basic information required for air conditioner design, including unit Product parameter
Net kg 2.0 (4.4) 2.5 (5.6) 3.0 (6.7) Link
Weight
(lb.) size, capacity, input power, noise, and airflow rate.
Gross 3.0 (6.7) 3.5 (7.8) 4.0 (8.9)
*:URL: http://airstage.fujitsugeneral.com Power source
Color White Input power
Capacity
Louver Motor Stepping Motor Airflow rate
Accessories Fitting Flame, etc.
Sound pressure level
Dimensions
+ FUJITSU GENERAL
Website*
66 67
DESIGN SUPPORT
Design Simulator
Select Your Preferences
Enter your requirements, select your controls and options, Select your language, region, default unit names and your
design your layout and let the program do the rest. preferred units of measurement. The program will then perform
the required calculations and return the results in the format you
Put the charts and pens away and design your projects on your computer with ease using the Design Simulator. Everything from selecting want to see. Once this is done once, the program will remember
indoor and outdoor units, allocating controls and optional parts to designing the piping and wiring systems is made easier using the program's your choices for future use.
built-in features. Once your project is designed take advantage of the Export functions to easily get materials lists, product specifications,
refrigerant calculations and more - it'll even export to Word or Excel formats, and group the relevant CAD data for your project.
68 69
OPTION REFERENCE
Multi-Tenant Dwellings
Liquid Pipe Liquid Pipe
VRF improves the quality of multi-tenant buildings
while reducing tenant complaints. High quality VRF
systems let owners save on energy costs and
reduced maintenance costs. With VRF, each tenant
Header Header has individual control over the temperature setting for
UTR-H0906L UTR-H0908L the comfort of their home.
Gas Pipe Gas Pipe
QUALITY
By delivering quiet, efficient heating and cooling,
VRF improves the quality of multitenant buildings and
reduces tenant complaints.
INDIVIDUAL BILLING
Using the Energy Charge Apportionment feature,
landlords can easily bill each tenant for the
percentage of total energy the individual tenant
consumes.
INDIVIDUAL COMFORT
With VRF, each tenant can have their own controller
to set their room temperature for their maximum
comfort.
Specifications
Separation Tube
Model name UTR-BP090X or UTP-AX090A
CONVENIENT CENTRAL CONTROL
Total cooling capacity of indoor unit (kW) 28.0 or less Landlord can monitor and control all indoor units from
a central location. Landlord can even troubleshoot or
solve tenant complaints remotely.
Header
3-6 Branches UTR-H0906L
Model name
3-8 Branches UTR-H0908L QUIET
Total cooling capacity of indoor unit (kW) 28.0 or less Indoor units ensures a quiet, comfortable living
environment for all tenants.
EV Kit
Model name UTR-EV09XB UTR-EV14XB
AS*E07GACH AS*E12GACH
Application Model
AS*E09GACH AS*E14GACH
70 71