Вы находитесь на странице: 1из 10

IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, VOL. PAS-89, NO.

8, NOVEMBER/DECEMBER 1970 1891

General Equations for Fault Currents in


Transmission Line Ground Wires
CONRAD F. DESIENO, SENIOR MEMBER, IEEE, PETER P. MARCHENKO, MEMBER, IEEE, AND
GREGORY S. VASSELL, SENIOR MEMBER, IEEE

Abstract-General equations are presented and derived which and presented equations for its calculation for cases where the
enable the accurate calculation of fault currents in overhead trans- fault current source is at onlv one terminal of the line [1]. These
mission line ground wires at any point along the ground wire to equations were analytically derived, assuming uniformly distrib-
either side of the point of fault, given the fault current contribution uted "leakance" or conductance from ground wire to earth.
from both terminals of the line. The equations are based on uni- In 1963, Sebo and Regeni published test results indicating the
form tower footing resistance, which is treated as uniformly distrib-
uted conductance between ground wire and ground. The results, "end-effect" current distribution in the vicinity of the fault
easily and inexpensively calculated by digital computer, are com- [2], and in 1969 Sebo published an equivalent circuit method of
pared with test measurements previously published and excellent calculating these currents [3].
agreement is indicated. At the American Electric Power Service Corporation the
importance of the accurate analysis of ground wire current
distribution has been recognized for a long time, and an analytical
INTRODUCTION method has been developed which was first outlined in an in-
THE continuous growth in the capacity and capability of ternal report dated May 1966. The method, which is similar in
power systems, including extensive interconnections and general approach. to that of [1 ] but more extensive in coverage, is
large concentrations of generation and transformer capacity, based on the treatment of finite and discrete tower footing
results in ever-increasing values of fault currents in transmission resistance as a uniformly distributed conductance between
lines of all voltage classes. This, together with increased em- ground wire and ground. This approach is the inverse of that
phasis on reliability and design economy, points up the value of used in classical transmission line analysis, where uniformly
an accurate and convenient method for determining ground wire distributed parameters are replaced by discrete parameters in a
fault currents and related voltages, particularly near the point T or II configuration. The resulting general equations are easily
of fault, as a function of significant variables. Such a method and economically solved by the use of a digital computer and
would aid the engineer in determining the optimum design of are in excellent agreement with actual measured quantities.
future lines, including the selection of ground wires to with- The paper presents and discusses these general equations and
stand anticipated fault currents, as well as in evaluating the their derivation, and compares their solution with previously
performance and reliability of existing lines. This paper presents published test results.
a set of general equations for lines with one and two ground wires Derivation and Discussion of Equations
to meet the above requirements.
It is well known that the fault current flow along a ground The appendixes outline the development of generalized
wire diminishes as the distance from the point of fault increases equations for calculating the current in the ground wire of trans-
through diminishing current flows to earth at successive ground- missioin lines at any point along its length, including the end-
ing points, until it reaches an essentially constant value several effect current distribution near the point of fault and near the
miles from the fault point. This constant value is easily calcu- line terminals. Appendix I covers transmission lines with one
lated by using the self-impedance of the ground wire and its ground wire and Appendix II covers lines with two ground wires
mutual impedance with the phase conductors; the higher values both cases with fault current sources at each terminal. The
of current close to the point of fault have been difficult to calcu- discussion is directed primarily to overhead transmission lines,
late and generally have been neglected. In 1937 the Joint Sub- but the analysis and equations are equally applicable to fault
committee on Development and Research of the Edison Electric currents in underground cable sheets with uniformly distributed
Institute and the Bell Telephone System published test results conductance to ground. Furthermore, although this paper deals
indicating the distribution of fault current along the ground wire specifically only with the equations for ground wire current, the
material presented can be used to obtain the voltages along
the ground wire.
Paper 70 TP 101-PWR, recommended and approved by the The basic approach toward the derivation of the general
Transmission and Distribution Committee of the IEEE Power
Group for presentation at the IEEE Winter Power Meeting, New equations in both appendixes is to form differential equations
York, N.Y., January 25-30, 1970. Manuscript submitted September for the currents and voltages along the ground wire by treating
12, 1969; made available for printing December 2, 1969.
The authors are with the Americani Electric Power Service Cor- the finite resistance or conductance to earth at each tower or
poration, New York, N.Y. 10004. ground wire grounding point as a uniformly distributed conduct-
1892 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, NOVEMBER/DECEMBER 1970

ance between the ground wire and ground and by assuming that 138 KV
LINE DATA:
the distance between grounding points is small compared to the 1. GROUND WIRE- I59Ikcmii ACSR GROUND
LINE CONFIGURATION

length of the line. These differential equations are similar to 60 2. EARTH RESISTIVITY-
100 OHM-METERS
--WIRE
FAULTED,, 14.4
those used in the analysis of voltages and currents in transmis- ZZ 3. NUMBER OF TOWERS PER PHASE ~'Fr I
sion line phase conductors where the resistance, inductance, and
WLU
t x 50 MILE-5 A! I_ ~ 224
-
-- 14'
4. AVERAGE TOWER FOOTING
capacitance parameters actually are uniformly distributed. 40
RESISTANCE -20 OHMS
5. FAULT CURRENT CONTR I BUTION- \ 1
,,
The differential equations then are solved by standard methods, cUr 71% FROM LEFT TERMINAL
29% FROM RIGHT TERMINAL /
/ +
and known terminal voltage-current relations are used to evalu- _,
ate the associated constants.
The specific assumptions made in the solutions of these
equations, in addition to that of uniformly distributed con-
ductance to ground, are 1) that the station grounding grids to
which the ground wires are connected solidly at the line terminals
have negligible resistance to earth, and 2) that there is negligible 2 4 6 8 10 11 12 14 16 56
resistance between the two ground wires at each tower or ground- DISTANCE ALONG THE LINE IN MILES
ing point. Fig. 1. Example of calculated ground wire fault current profile
The general equations derived by the above analytical method for 138-kV double-circuit transmission line with one ground wire;
fault current contributions from both terminals.
are indicated as (26) and (27) in Appendix I for one ground wire,
and (72)-(75) in Appendix II for two identical ground wires. 701
Current and voltage equations for nonidentical ground wires 138 KV
Zar l-t e

LINE DATA:
LINE CONFIGURATION
are also available in Appendix II. 1. GROUND WIRES -2 X 159 kcmfl ACSR
60 - 2. EARTH RESISTIVITY- 100 OHM- METERS O.W. V WG
4G.W.
The above equations can be easily programmed for solution z
3. NUMBER OF TOWERS PER MILE- 5
4. AVERAGE TOWER FOOTING FFAULTED-a.+
14.4'
by digital computers. At the American Electric Power Service w as 50 - RESISTANCE- 20 OHMS FPHASE --24
-
14'
5. FAULT CURRENT CONTRIBUTION
Corporation, the General Electric time-share computer service a
o D 71% FROM LEFT TERMINAL + + I,
is used for this purpose, with the equations programmed in U4 29% FROM RIGHT TERMINAL -37'- 4 i.
13'
+ 4 t -
FORTRAN II on the G.E. Mark I System. The total on-line
1
computer time for a typical single-ground-wire case, including a W 30

complete profile of ground wire current distribution, is approx- C 20


imately 10 minutes, including data entry, for a total computer
cost of approximately $2. For two ground wires, a complete set
0
½
of current distribution values costs less than $3.
Fig. 1 illustrates the typical distribution of fault current
0 2 4 6 8 10 12 14 16
along the single ground wire of a 138-kV double-circuit tower DISTANCE ALONG THE LINE IN MILES
line with a single-phase fault at a tower 11 miles from the left Fig. 2. Example of calculated ground wire fault current profile
terminal and with both terminals contributing current to the for 138-kV double-circuit transmission line with two ground wires;
fault. At the faulted tower, approximately 55 percent of the total fault current contributions from both terminals.
fault current flows in the ground wire toward the left terminal,
41 percent flows in the ground wire toward the right terminal COMPARISON OF CALCULATED AND TEST RESULTS
and the remaining 4 percent enters the earth directly through The ground wire fault profiles resulting from the generalized
the tower footing. The ground wire currents diminish rapidly equations of the appendixes compare very favorably with test
toward both terminals as additional but diminishing amounts of measurements published in [1] and [2]. Although a precise and
current enter the earth through successive tower grounding rigorous comparison is not possible because of the lack of com-
points. The current reaches a fairly constant value starting plete data in these references, sufficient data are available to
approximately three miles away from the fault point, with a assure that the analytical method and equations presented here
very slight increase in ground wire current as each terminal is are valid and produce practical and meaningful results.
approached. Fig. 3 compares the current profiles for a single ground wire
Fig. 2 illustrates a similar current profile for each of the two with the fault current source at the left terminal only, as calcu-
ground wires of a double-circuit 138-kV line, with a single- lated by the equations of Appendix I with the test results in-
phase fault 11 miles from the left terminal. The phase conductor dicated in [1, fig. 3]. Since the tower footing resistance was not
closest to ground wire v is faulted, and the higher mutual imped- provided in [1], it was assumed to be 5 ohms; the ground wire
ance between this ground wire and the faulted phase conductor was deduced to be 133 000 cmil copper. The calculated and test
accounts for its higher current. results are in precise agreement for currents to the right of the fault
To aid the engineer in the selection of ground wires when point and in excellent agreement to the left of the fault point,
designing new lines, many current profiles similar to Figs. 1 and 2 particularly at the important fault and terminal points. It was
can be calculated to evaluate the effects of variables such as found, furthermore, that even a substantial variation in the
ground wire characteristics, tower footing resistance, number of assumed tower footing resistance did not significantly affect this
towers per mile, soil resistivity, point of fault along the line, comparison.
ratio of fault current contribution from left and right terminals, Fig. 4 provides a comparison between calculated and test
location of ground wire with respect to phase conductors, etc. results for a two-ground-wire single-phase line. The measure-
Depending on the application, it may be necessary only to ments are reproduced from [2, fig. 12]. The faulted conductor of
determine the current profiles in the immediate vicinity of the the tested line was symmetrically located below the two ground
fault and of the line terminals, thus decreasing the already wires, so that theoretically the fault current distribution is the
nominal computer time and cost. same in each ground wire. The difference between left and right
DESIENO et al.: FAULT CURRENTS IN TRANSMISSION LINE GROUND WIRES 1893

The validity of the method, which is closely related to classical


81 120 KV transmission line theory, is proven by excellent agreement be-
LINE CONFIGURATION
70 _ _ _I---O.S T - tween calculated and measured results.
The method of analysis and the resulting equations, which
are easily programmed for digital computer solution, present a
powerful tool to aid the engineer in designing future transmission
O I___
_
lines and analyzing the capability of existing lines to with-
oz stand the ever-increasing fault current magnitudes. Although the
w L) 50AERG SANBEWENTOER 706T
paper is directed primarily to overhead transmission lines, the
C - - ..
method and equations are equally applicable to underground
cables with uniformly distributed conductance to ground.

880 870 860 850 840


APPENDIX I
830 820
TOWER NUMBER DEVELOPMENT OF GENERALIZED EQUATIONS FOR CURRENT
IN GROUND WIRE AT ANY DISTANCE FROM POINT OF FAULT
Fig. 3. Comparison of calculated and measured ground wire fault
current distribution for 120-kV double-circuit line with one ON TRANSMISSION LINE WITH ONE GROUND WIRE
ground wire; fault on all three phases of one circuit, supplied Fig. 5(a) is a schematic diagram showing a three-phase single-
by single-phase source from left terminal only.
ground-wire transmission line of length I on which a single-phase-
to-ground fault has been imposed at a distance d from the
left terminal to cause the indicated current flow in the faulted
phase conductor, ground wire, and earth return. Fig. 5(b)
shows a segment of the ground wire to the left of the point of
fault. Towers are assumed to be spaced at intervals of Ax with
tower footing resistance of Rt.
In Fig. 5(b) the difference between the ground wire fault
current Iw(x+Ax) at the span midpoint x + Ax and the ground
wire fault current 1W(x)' at the previous span midpoint x is the
current Ie,' which flows through the tower footing resistance
Rt, that is
I Iw(x+Ax) -Iw(x)I = Ie (1)
8)
Also, the current into earth Ie, can be expressed as the voltage
of the ground wire multiplied by the tower footing conductance
Fig. 4. Comparison of calculated and measured ground wire
fault current distribution for 120-kV single-circuit line with
G6% 1=Rt:
two ground wires; fault current source at left terminal only. 1
le/ =
RI VW.
G,VW0 =- (2)
ground wire measured currents was very small in most spans, Combining (1) and (2) and dividing both sides by Ax yields
the maximum being 20 percent of the average in a span approx-
imately 1 mile to the left of the fault point. Presumably this was 'w(x+Ax) - Iw(z) = G
due to differences in ground wire contact resistance and metering Ax Ax
Vw.
(3)
accuracy.
The differences between measured and calculated values in- If x is in miles, the coefficient of Vw' on the right-hand side of
dicated in Fig. 4 are caused mostly by a large difference from (3) is in units of conductance per mile. If there are K towers per
average in measured tower footing resistance at two important mile and Ax is the distance between towers, then Ax = 1/K or
towers. The resistance to ground of the tower immediately to the K = 1/Ax.
left of the fault point was 30 percent of the average, whereas Let G equal tower footing conductance per mile; then
that of the tower immediately to the right was 280 percent of
the average; the remaining towers were much closer to the average. G = GtK =
Ax (4)
This caused the current to the right of the fault point to be less
than the calculated value, which was based on the average Replacing the coefficient of V,' in (3) with the new coefficient
tower footing resistance, uniformly distributed along the line. G, conductance per mile, yields
Nevertheless, there is meaningful agreement between tested
and calculated values, particularly for the important current 'w(x+ax) - 'w(x) = GVw'. (5)
profile to the left of the fault point, further attesting to the Ax x

validity of the equations.


To obtain a differential equation from (5), the normal and
CONCLUSIONS rigorous procedure is to take the limit of the left-hand side as
This paper has presented and derived a set of equations for Ax approaches zero. In this case Ax cannot actually approach
accurately calculating the fault current distribution and related zero because it is the distance between towers. However, a
voltages in overhead transmission line ground wires. These ana- physically plausible argument can be presented namely, that
lytically derived equations are based on the assumption of uni- for long lines Ax is negligibly small compared to the line length
formly distributed conductance between ground wires and earth. and effectively approaches zero.
1894 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, NOVEMBER/DECEMBER 1970

Dividing both sides of (7) by Ax yields


x o
M~~~~~=I
I=-i3I'
d
y-l-d
-
y-o
C; I o
SYSTEM (INCREASING x-P)
x-d SYSTE
(-INCREASING Y) YS V2(X+AX)'AX-V = Iiw'Zww -If'Z (8)
EQUIV. f EQUIV.
W W
GROUND
RT W
RT RT WR Taking the limit of (8) as Ax approaches zero in relation to the
EARTH length of the line, yields a second current-voltage relation:
(a)
x
(INCREASING x--)
x+Ax
dV lw Zww -
IfZaw. (9)
I I1E I'VLI'
RT
I w(x) V t RRT
IRTR
w (x+ ) WIRE W
Using (6) and (9) and referring to Fig. 5(a) the following set of
EARTH
differential equations applies. For 0 < x < d, to left of fault:
-

If -,IWX) If -I w(x +A, x)


(b) =
dx GVW ' (6)
-
PHASE
(INCREASING x-eI CONDUCTOR
x
a
IW x+x
rpntiNn dI'
dx
I
= '
-_'Zww I'
- IfZaw (9)
V'w(K)t RT Vw(x+Ax) RT WIREW"
EARTH and for (I - d) > y > 0, to right of fault:
(c)
dy = GVW/' (10)
Fig. 5. (a) Schematic diagram of three-phase single-ground-wire dy
transmission line of length 1 and average tower footing resistance
Rt, with single phase-to-ground fault at distance d from left -dVw'' ,..
terminal. (b) Segment of ground wire to left of point of fault.
dy
= "Zww Zaw. (11)
(c) Segment of ground wire between two towers to left of fault.
By differentiating (6) with respect to x and (10) with respect
Thus the following differential equation can be written: to y, we obtain
dIw' - Iv_'
(6)
dx dx2
= G-
dx
(12)
Clearly (6) involves an approximation, since a finite discrete d'Iwff G dVw
ft

parameter G-1 is being replaced by a distributed parameter G. = (13)


However, for lines of practical length this approximation yields
dy2 dy
practical and completely acceptable results. Combining (9) with (12) and (11) with (13), respectively:
Further argument toward the practical acceptability of
the above approximation can be presented by pointing to d2Iw
the long-established practice of representing the distributed dx2 -_GZwwIw' -If'GZaw =
(14)
resistance, inductance, and capacitance parameters of a trans-
mission line by "lumped" parameters in a T or II configuration. d___f_GZ-wwI' = -IfcGZaw (15)
The concept proposed here is to represent, for the purpose of dy2
mathematical analysis, the lumped tower footing conductance Equations (14) and (15) may be solved by standard methods
Gt by the distributed tower footing conductance per mile G. to obtain the general solution
Thus the argument here is the inverse of that used in classical
transmisssion line theory.
For a segment of ground wire between two towers, to the left Iw' = Al'1e + A2'-Yx + Zaw I ' (16)
of the fault, as shown in Fig. 5(c) the drop in voltage along the
ZWw
ground wire between x and x + Ax can be expressed as I,,' = Ai"t'e + A2%E-7Y + Zaw
zw I f1f (17)
Vw(x+Ax)' Vw(x)' Iw'ZwwAx If Zaw,&X
- = (7) -

where Vw(x+Ax)', V,(x)', Iw' Ax are all defined in Fig. 5(c) and where 7y2 = GZ,w.
Substituting I,,' and I,," into (6) and (10) yields
If line-to-ground fault zero-sequence current contribution
= 31o 1 1
Z,,O, self-impedance of ground wire w with earth return VW' = - All'yeyx- A21 ye (18)
=Ra + 3e +j Xa + ie, Q/mi [4]
3/ ff
VW = GAlyJ7'
- -Af
Alffye - yc
A2 C fy (19)
A atw mutual impedance between faulted phase conductor
a and ground wire w with earth return Assuming that at x = 0 and y = 0 there are good station
Re + j grounds with negligible impedance between ground wire and
-
_ , U/mi [4]. earth, the voltage between the ground wire and earth is essen-
DESIENO et at.: FAULT CURRENTS IN TRANSMISSION LINE GROUND WIRES 1895

tially zero, so that at x = 0 At x = d the total line-to-ground fault current If (point of


fault) can be determined from (23)-(25) as
Vw' 0 = - Aly--
G G
A217
If = 1,0 + Il" + Ie
A1' = A2' = A' = 2A' cosh yd + 2A" cosh y(t - d)
and at y = 0
+ Zaw q1 ± If) + G' sinh yd.
VW," = 0 = -A11'y
G G
A2"
Using the relation between A' and A" from (22):
A1' = A21' = A".
Substituting A' and A" in (16) and (17) and using If= 2A' [cosh 'yd± ~ sinh yd ± ih7 1 Zafw
[ GRt tanh ay(I - d)] +zw
Ex + E-'
cosh yx =- 2 From this equation and (22)
yields
if 1 _Zaw
Zwto
Iw' = 2A' cosh yx + Zaw If (20) A' =
Zww 2(cosh yd) [1 + (tanh -yd) (C?+ tanh y(l-d))]

I1,"
2A" cosh yy + zaw
= (21)
zww A" =
at x = d, y = 1 - d, Vw = Vw' = V,,'. Then from (18) and (19)
If 1 _Zzww,
aw tanh yd
Vw = G y [Eyd _ E-,yd] = -A [Cy1>(I-d) _ -,y(-d) .

2[sinh 'y(l - d)] Ir


± (tanh yd) LR + d)/
But
sinh x _ 2 x Substituting these values of A' and A" in (20) and (21), the
sinh -yx = 2 final equations for current in the ground wire at any point along
the line are
and
ye( I d) _ Y( I _d) If 1 aw) cosh 'x
sinh 7(I-d)= 2 (ww
2,0
Therefore,
(cosh -yd) [1 + (tanh yd) (Gy + Iahald)
2A' sinh yd = 2A" sinh y(l - d) Zaw (26)
+-I
and
I _ -
wo
A" = A' sinh yd
(22) iwff=~~~~~~~~~~~wf
Zaw) (tanh Gd) cosh (yy
sinh y(l - d) If(1 -

At the faulted tower, the current into earth is


Vw
[sinh y (I - d)] [I + (tanh yd) t+ tanh -y (l d))
-

Ie
R= ++zZawI.f (27)
From (18) for x = d
2 These equations can be applied to a radial line with fault
Vw = Vw' = GAly(e2fd
G
- yd)
C-yA' sinh -yd. contribution from one side only by letting If' = If and If' = 0.
Therefore
APPENDIX II
Ie = 2yA' sinh yd. (23) DEVELOPMENT OF GENERALIZED EQUATIONS FOR CURRENT IN
GRI GROUND WIRES AT ANY DISTANCE FROM POINT OF FAULT
ON TRANSMISSION LINE WITH Two GROUND WIRES
From (20) and (21), letting x = d and y = 1 - d
Fig. 6 is a schematic diagram showing a three-phase double
Iw' = 2A' cosh yd + aw If' (24) ground-wire transmission line of length 1 with a single phase-to-
Zaw ground fault at a distance d from the left, along with the fault
Iw' = 2A" cosh y(l - d) + Z I". (25) current flow in the faulted phase conductor, ground wires, and
ZwW earth return.
1896 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, NOVEMBER/DECEMBER 1970
From (36) we get
< d
x= ° If=3I'a y-lI-d
x-d
Iil=3111
f Y=O
_ I 111=
' -1 d2Iw' - ZwI ,I,
+
Zaw
f- (38)
SYSTEM L NCRENG ) ( INCREASING y) SYSTEM
GZ,,,
GVd Vdx2 ZVW0
v ZvwI
w
EQUI V. I EQUIV.
I* IIt Differentiating (38) twice with respect to IL, yields
? ? ? Ili, -1 GRD.-WIRE'EuW"
d2IN' 1 d41' ZwwG d21,
I,

V< V T- GRO-WIRE "V'


dx2 GZ, dx4 GZ-,w dx2 (39)
RTEI RrT RT
Replacing d2I'//dx2 and Iv' in (37) by their new expressions
Fig. 6. Schematic diagram of three-phase double-ground-wire (38) and (39) we get
transmission line of length 1 and average tower footing resistance 1 d4Iw' Zww, d2lw' GZV , d2IwI
Rt; single phase-to-ground fault at a distance d from left terminal.
GZVW dx4 ZW dX2 GZww dx2 GZwwIw, + GZawfJ
Applying (6) independently for each ground wire to the left of - G(ZvzIw -Zavl fJ)).
the point of fault (0 < x < d)
Rearranging the terms gives
dlw, ' (28)
dx GVWI
dx4° -G(Z,,,4 + ZVV) dx2 + G2(ZVVZWW - Z2 W)I
- = GVD,. (29) - G2(ZvvZa0 - ZwZaWZ)lf'. (40)
dx
Applying (9) independently for each ground wire adding the Equation (40) may be solved by standard methods for linear,
effect of mutual impedance between ground wires w and v, we get constant coefficient differential equations to yield

dV,' = Iw'Zww + Iv'Zvw -If aw (30) I,, = AlE17 + A2CT1X + A36'y2x


dx
+ A4C -2Z + ZvvZaw - Zv Z I II (41)
Z vZWW -Zs2
dVv=
dx
Iv-Zvv + Iw'Zvw - I'Zav. (31)
where
Similar equations are developed for point to the right of the
point of fault (0 < y < 1 - d), as follows:
7,
(G[Zww + ZV, +
V-
V(Zw - Zvv)2 + 4Zv)]t1/2 (42)
2
dl," = CV,," (32)
dy
72 =
xG[Zw + ZV,2,- /(Zw ,- zv,,)2 + 4ZV
2
2)]t1/2 (43)
d-,,"
dy
=
IGV (33)
From (28)
- I "Zw + iv"Zvw -IfZato (34) I
dIY
dy VW, =

dyV" = IV"IZvv + iw"Zvw - If Zav (35) By substituting in this equation the derivative of (41) we get
dy

Differentiating (28), (29), (32), and (33) and substituting the VW= (y,AElZ - ylA2&TlX + Y2A3JE2 - Y2A4c-YI). (44)
derivatives of the voltages from (30), (31), (34), and (35) we
get:
Using the boundary conditions x = 0 and VW,' = 0 we get
d21,' dVw,'
=G--
dx2 G [y,(Al - A2) + 72(A3 -A)] = 0
= GZwwIw' + GZvowl' - GZawIf'
from which
d21= dVv'
dx2 dx A, = A2defined as A,'
GZ vvl v' + GZvwIw'
= - GZa vI/f A3 = A4 defined as A2'.

Rearranging the terms gives Using these new notations in (41) and (44), we get
w
GZwolw' = GZvwlv' - GZawIf' (36) I.'= A,' cosh y,x + A2' cosh 72 + Zvvaw Z
oaj
2 (45)
dx2 ZVVeZWW2 -
ZVW2
d7 ' =GGZvwlw' GZ,,,avlJ/. (37) V I, =
1
Q,y,,Al' sinh -y,x + 7Y2A2' sinh 'y2x). (46),
dx2
DESIENO et al.: FAULT CURRENTS IN TRANSMISSION LINE GROUND WIRES 1897

Similarly, we can obtain the equations for v ground wire as Solving the set of equations resulting from (60) we get the
follows: following expression for the constants:
I,' = A1'Bi cosh y1x + A2'B2 cosh 7Y2X Al' = (1 - A - B) [sinh id {(1 + B1) [coth yld
ZwwZ a v- Z vwZ aw
+ l(7
zvvzww-zVW + coth y1(I - d)] + K1(B2 -_ 131) + 71(1 -
B0(1 + 12)
K(2- 1) 7Y2(B32-1
v'=
I
C
(7yA1'B1 sinh y1x + Y2A2'B2 sinh y2x) (48)
* [coth 72d + coth 72 (1 - d)]} (61)
where
B, 12/V-W (49) A2' = 71(-B')Il-A-1) [72(B2 - 1) sinh 72d
2
* {(1 + B1) [coth 71d + coth y1( - d)]
11 722/-
(50)
71(Bi2 -Bj) ± 71(1- B1) (1 + B2) [cothy1d
212-1
+
For simplification, we make the following additional notations: K(B2 - 1) 9(B2-)
A = ZvzZaw
ZVVZWW
ZvwZav
-Z VW2
(51) + coth 72(1- d)]} (62)

ZwwZav - ZvwZaw Al" I(l- A - B)


B = - (52)
* [sinh y7(l d) {(1- + B1) [coth yid
Using these notations in (45)-(48) we get the final form of the
expressions for currents and voltages in ground wires w and v
as follows: + coth 71(l d)]- 71(B2 -B)
1,'= A1' cosh yix + A2' cosh 72x + AI/' (53)
+ 'Y1(-7(B12 - 1) [coth 72d + coth Y2(1-d)]
VW = - (Al'y7 sinh ylx + A2'2 sinh Y2x) (46)
G (63)
lv' = A/B1 cosh y1x + A2'B2 cosh 72x + B1f' (54) A2" 71(1 - BI)If(l- A - B)
* [72(B2 - 1) sinh 72(1- d) {(1 + B1) [coth -yd
v,' = C- (A1'B13y sinh yix + A21B2Y2 sinh Y2x). (55)

In order to obtain the equations of Iw', Iv", Vw', and VvU, we


start from (32)-(35) and follow step by step exactly the same
+ coth
71(1 -
712(B-2 B)
d)] + 7Y2(132 1

procedure as used for Iw', IV', VU.,' and VU'. Now the currents 712(-Bj) (I + B2) [coth 72d + coth 72(1-d)]j]-
and voltages are functions of y with different coefficients:
Iw" = A1" cosh 7Wy + A2" cosh 72Y + AIf' (56) (64)
If ground wires are identical, Z ,,,,; then
VW' = G
C
(A1'71i sinh 72Y + A2'72 sinh 72y) (57) 71 = [G(ZWW + ZV,) ]112 (65)
IV," = A11'B1 cosh yiy + A2"B2 cosh 72Y + BIf " (58) 72 = [C(ZWW - ZW)]1112 (66)

Uv" = - (Al"Bg17 sinh yly + A2'B272 sinh 721). (59) G_ 'Y12 ZWw
-

B1 zz,,w
At the point of fault where x = d and y = - d, the four
boundary conditions necessary to evaluate the constants A1' [G(Z2w + Z,,w)I/G Zww Z,,w -
(67)
zv,w
= _ = 1

zvw
_____________ _

A21, A1", and A2" are


1
Vwtt VU,'
=
22 -ZWW
VWf= VIt(0 B2=
= Uw,(60)
=[(Zww Zv-)]/C -

ZV,,W
- Zww _ z
z,VW
--1.
if=Izwl + IV, + Ia" + IV"f+ R . (68)
1898 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, NOVEMBER/DECEMBER 1970

Using (51)and (52) for ZM02C = Z,e, we get paper, improvements could be made by treating the tower footing
resistance as a probability function. Undoubtedly the footing resis-
tance distribution in the limited region of interest for a particular
1 - A - B = 1 Zaw + Zav (69) fault would have a narrower dispersion than the distribution rep-
Zww + ZAVW resenting the line as a whole. If sufficient footing resistance on a
Also tower-by-tower basis were available for typical lines in a geographic
area of interest, it would be possible to construct frequency distri-
butions from these that would be appropriate for a fault picked at
ij I _ Zaw + Zav) random for any point on the line. Such an approach would inherently
I _Ztvff + ZVW (70) include the probability that the footing resistance on one side of the
fault were different from that on the other side, resulting in a change
sinh yid {2 [coth -y1d + coth -yi(l- d) ] + in the maximum current level obtained.
If it is further assumed that a uniform ground wire is to be used
over the entire length of the line and that short circuits are equally
Zaw + Zav likely at any point, the probability approach could be extended
Al" 1-Zww±+Zvw) to select a shield wire characteristic that would yield an acceptably
low probability of cumulative annealing over the anticipated life of
=

sinh Ty(l- d) {2[coth y1d + coth 1y(l - d)] + Ki the conductors.


K,
A2' = 0 and A2" = 0. (71)
The equations of the currents in case of identical ground
wires are J. A. Pinnello (Commonwealth Edison Company, Chicago, Ill. 60690):
Itot-A1' cosh yix + AIfl (72) The authors are to be congratulated on developing useful equations
to calculate ground wire currents for phase-to-ground transmission
I' A1' cosh yix + BI/f (73) line faults and for subsequently verifying the assumptions with
measured values. The accurate determination of ground wire
I,'= A1" cosh yly + Alf' (74) currents under fault conditions is important to insure proper trans-
missfon line design.
I'= A1' cosh yly + BIf'. (75) At Commonwealth Edison Company we have also been involved
in determining ground wire currents. Our approach was to set up an
These equations can be applied to a radial line with fault equivalent circuit incorporating the faulted phase conductor, the
contribution from one side only by letting If' equals If and If" system equivalent sources, and the ground wire and earth return
equals 0. circuits. This representation was used in a conventional fault study
computer program to calculate the currents. The authors' approach
of directly calculating the currents and voltages required consider-
ACKNOWLEDGMENT ably less computer data preparation.
The authors wish to thank R. A. McLeod for his contributions In the course of our studies we found currents in excess of ground
during the initial stages of the study, D. Goldstein for his as- wire capacity. We then conisidered opening the transmission line
ground wire to station ground connection at one or both sources.
sistance in solution of the final differential equations, and M. D. This resulted in substantially reducing ground wire currents. The
Adams for his development of the computer program. equations developed in the paper were based on a zero-impedance
connection between the line ground conductors and the station
REFERENCES ground and therefore are not valid if the ground wires are not
[1] Joint Subcommittee Report, "Computation of zero-sequence connected as such. A useful extension of these results would be to
impedances of power lines and cables," Edison Electric In- include the appropriate boundary conditions for this case.
stitute and Bell Telephone System, vol. 4, Rep. 37, pp. 303-
331, January 1937.
[2] I. Sebo and L. Regeni, "Measurement of the zero-sequence Manuscript received February 5, 1970.
current distribution on a transmission line," Per. Potytec.
Elec. Eng., vol. 7, pp. 295-317, 1963.
[3] S. A. Sebo, "Zero-sequence current distribution along trans-
mission lines," IEEE Trans. Power App. Syst., vol. PAS-88,
pp. 910-919, June 1969.
[4] W. A. Lewis, The Transmission of Electric Power, vol. 2,
lithoprinted ed. Chicago: Illinois Institute of Technology, Stephen A. Sebo (Ohio StateUniversity, Columbus, Ohio 43210):I wish
1948, pp. 3.15-3.19. to congratulate the authors on the analysis described in their paper.
They have presented a valuable contribution of the complex problem
of zero-sequence current distribution along transmission lines.
Since the late 1920's, when Carson published his classic papers on
conductors with ground return, numerous attempts to solve this
problem have been described. Measurements have been carried on,
Discussion and different computation methods have been developed. The most
extensive list of references can be found in [5].
The number of published test results is rather limited. There
were only five or six experiments where the actual current distri-
L. 0. Barthold (Power Technologies, Inc., Schenectady, N.Y. 12301): bution between ground wire and ground was studied along a trans-
The paper serves a double purpose in calling attention to a problem mission line. Such experiments were published, e.g., in 1931 [6],
area not studied in sufficient detail heretofore and at the same 1934 [7], 1959 [8], and 1963 [2]. Even in some of these cases, es-
time providing a solution tool superior to others available. sential data have not been provided.
As is usually the case, the completion of any improvement in As for the computational methods, some publications took only
solution methods tends to expose even further possibilities for the resistive components into consideration and obviously this
refinements. It would seem that in the calculation contained in the assumption is incorrect. Different methods were published as-

Manuscript received February 13, 1970. Manuscript received February 16, 1970.
DESIENO et al.: FAULT CURRENTS IN TRANSMISSION LINE GROUND WIRES 1899

suming distributed conductance between ground wire and ground tower footing resistance and fault location. We wonder, however,
and introducing hyperbolic functions, e.g., in 1937 [1], 1958 [9], whether such refinements are justified in light of basic design as-
1959 [8], and 1959 [10]. Another group of publications describes sumptions and uncertainties, such as future fault current mag-
methods where the ground wire-tower-ground loops are examined nitudes and often unpredictable future station locations, which
and the currents in the ith loop can be computed, e.g., [11], [12]. would change the line lengths as well as the fault current con-
The authors are to be commended for their study, which is an tributions.
important step in the series of methods using hyperbolic functions. The equations presented can contribute materially to the engineer's
The agreement between the computed and measured values in- judgment by allowing him to test the sensitivity of the results to
dicates the value of this method of computation. meaningful variations in the parameters. If this judgment can be
It would be interesting to have some additional information about aided further by probabilistic treatment, so much the better. On
the following: the other hand, the engineer's judgment must not be clouded by
1) Can the method be applied for short lines, i.e., lengths of too much attention to minute detail. Thus, any increase, in complexity
five to ten spans between the point of fault and feeding point? of treatment must be justified on its overall merits.
2) Is it possible to compute the end effect at the feeding point? Mr. Pinnello suggests the extension of our approach to cover the
3) Can an attempt be made to use the method if the soil resistivity case of open ground wire connections at the source stations. We have
is not homogeneous along the line? followed this suggestion and have derived the following equations
4) How small is the percentage deviation between the computed for one ground wire, starting with (16)-(19) and applying the
results and the test measurements previously published in [2], with boundary conditions I,' and I.' = 0 at x and y = 0 to determine
reference to Fig. 4? the A constants:

I, =
QI - )+z {ZwIe-'d
ch
1- tanh
d
y(l - d) - GRJ] + 1/Y(ld) [1 + tanh (l - d) 4
sinh yx +
Zaw I,- E) (77)

cosh -yd Ltanh Td + tanh T(l -d) + G e

I
1 _f + If,E-d(1 + tanh -ed) + IfeC-Y(-d) (1- tanh d - ' )]
I
xZti
~ L0
Z= ¾
coshy(l - d) Ftanh yd + tanh y(l - d) + GR 1
GRt?~j sinh yy + iate I/'(l
ZWW
- -
(76)
L J~~~~~R

REFERENCES Applying these equations to a typical 138-kV line yields the


[5] H. R. J. Klewe, Interference Between Power Systems and Tele- following results.
communication Lines. London: E. Arnold, 1958. 1) For a fault 11 miles from the station, as in Fig. I., disconnlecting
[6] J. E. Clem, "Reactance of transmission lines with ground the ground wire at both stations reduces the maximum ground wire
return," AIEE Trans., vol. 50, pp. 901-918, September 1931. current I,,' from 55.3 to 54.7 percent of the total fault current.
[7] W. G. Radley and S. Whitehead, "Recent investigations on 2) For a fault 2 miles from the station, disconnecting the ground
telephone interference," J. Inst. Elec. Eng. (London), vol. 74, wire reduces I,,' from 58.3 to 50.6 percent.
pp. 201-239, March 1934. 3) As the distance from the fault point to the left terminal de-
[8] K. Sailer, "Die Schutzwirkung des Erdseiles im Fehlerfall," creases further, the portion of fault current flowing in the ground
Elektrotech. Maschinenbau, vol. 76, pp. 25-31, February 1959. wire immediately to the left of the fault point decreases rapidly,
[9] K. H. Feist, "Die Erderspannung geerdeter Stromdurch-
flossener Leiter bei Wechselstrom niedriger Frequenz und ihr whereas the ground wire current to the right of the fault point
elektrisches Strdmungfeld im Erdreich," doctoral dissertation, increases rapidly. Also, the total fault current increases rapidly.
Technische Hochschule, Hanover, Germany, 1958. The ground wire current profile for a fault 1 mile from the left
[10] P. Denzel and B. Gersdorff, Untersuchungen fiber die M6glich- terminal is shown in Fig. 7, for both the solidly grounded and
keit der Selektiven Erdschlusserfassung durch Messung des im
Erdseil von Freileitungen fliessenden Nulistroms. Cologne,
Germany: Westdeutscher Verlag, 1959.
[11] S. Butterworth, Electrical Characteristics of Overhead Lines. 70

Leatherhead, England: Engineering Research Associates, 1954. LINE DATA SAME AS FIG.
[12] "Currents in earth wires at the top of pylons and their effect 60 FAULT CURRENT CONTRIBUTION: 82% FROM LEFT
on the potentials of the pylons and stations in the neighbor- z2:
I TERMINAL
hood of a point of short circuit to earth," contrib. 78, Int.
Tel. Tel., Consultive Group Rep., November 1963. D
50 I_ I '
_ TERMINAL

0 a:u
40 GROUND WIRE DISCONNECTED
> AT BOTH TERMINALS
30 1
: 0
O,

a00
J, \ %i GROUND WIRE SOLIDLY GROUNDED
Itz
0_ 20 BOTH TERMINALS
fir-
Conrad F. DeSieno, Peter P. Marchenko, and Gregory S. Vassell: 1
The authors wish to thank the discussers for enlarging the scope FAULT POINT
of the paper through their questions and suggestions, and they
C
appreciate the kind comments. 0 2 3 4 5 6 7 54 56
We agree with Dr. Barthold that further refinements can be made DISTANCE ALONG THE LINE IN MILES
in selecting ground wire characteristics in the design of lines by
using probability functions in the treatment of such variables as Fig. 7. Calculated ground wire fault current profile for 138-kV
double-circuit transmission line with one ground wire; fault point
1 mile from left terminal, showing effect of disconlnecting the
Manuscript received April 9, 1970. ground wire from station ground at both terminals.
1900 IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, VOL. PAS-89, NO. 8, NOVEMBER/DECEMBER 1970

disconnected ground wire conditions. As illustrated, disconnecting resistance assumption and the resulting end-effect error at the feed-
the ground wire reduces I,,' at the fault point from 67.0 to 36.9 ing point are not critical to any evaluation of ground wire capability
percent. However the current I.' in the span immediately to the or to the proper selection of the ground wire in designing new lines.
right of the fault increases from 31.2 to 60.8 percent. Thus, the Using the general approach presented, a more complicated set of
maximum ground wire current is reduced from 67.0 to 60.8 percent, equations probably could be derived by changing the boundary
which is not a substantial reduction for design purposes. conditions to include a finite resistance between ground wire and
Dr. Sebo extends appreciably the list of references and provides an ground at the terminals, but we doubt that the effort is justified
interesting short history of this subject. He raises some interesting for practical applications.
questions, to which we comment as follows. 3) The equations as presented are based on the assumption of
1) We have not checked the results of our method against other homogeneous soil having uniform resistivity. Where resistivity is not
approacl.hs for very short lines with the fault five to ten spans away uniform or is not known, an appropriate range is assumed and the
from the feeding point. Judging from the excellent agreement be- upper and lower current values are calculated. Then the engineer
tween test results and calculations at the point of fault, which is in can best judge the effects of these assumptions or discontinuities.
itself an end effect, we feel that the results for short lines are meaning- 4) Referring to Fig. 4, the computed current was 0.8 percent higher
ful and of sufficient accuracy for design purposes. The profile in- than the test result at the span immediately to the left of the fault
dicated in Fig. 7, where the fault is only 1 mile from the feeding point, point, which is the most important span from a capability and design
certainly appears realistic. viewpoint. The computed current to the right of the fault point was
2) We also feel that the end effect at the feeding point is reasonably 15.2 percent higher than the test current. As indicated in the paper,
accurately indicated. The boundary assumption of zero resistance the resistance of the tower to the left of the fault point was 30
and zero voltage between ground wire and ground at the feeding percent of the average and that of the tower to the right was 280
points does, of course, have some effect on the current magnitude in percent of the average.
the last several spans, depending on the actual resistances. As in- Again, the authors wish to emphasize that the method presented,
dicated in Fig. 7 for the extreme case of infiniite resistance between together with the resulting equations, is a powerful tool to aid the
ground wire and ground, the current profile is changed materially engineer in the analysis and design of transmission lines to assure
and the end effects are dramatized, but the maximum ground wire that the capability of the ground wire is sufficient to withstand
current is not reduced appreciably. Thus we feel that the zero- anticipated fault currents.

Lightning Strokes to Power Transmission Lines


and the Shielding Effect of Ground Wires
A. BRAUNSTEIN

Abstract-A method for predicting the probability of lightning are presented in several papers; see, for example, [1]-[9]. Due
strokes to transmission lines and the shielding effect of ground wires to the complicated nature of the problem, approximations were
is presented. This method, which is based on electromagnetic field used in several papers, which introduce notable errors. The
concepts, also makes it possible to determine which parts of the method presented here is a more accurate study of the phe-
system (ground wires, phase wires, etc.) are more attractive to
various lightning strokes for a given geometrical configuration of the
nomenon and can, therefore, give the designer a better tool for
transmission line. The study presented showsthat the area "covered" predicting the outage rate of the system.
by a transmission system, in which every lightning strikes the The charges, which are lowered from the cloud toward the
transmission line, and the shielding angle are not constant. They are earth by the down-going leader, cause electric field strength
a function of the down-going charges from the cloud and the con- components in space. Field strength components, whose ampli-
figuration of the transmission line and cannot be expressed by simple tudes vary with time, exist at the ground wires and phase wires,
geometrical methods. at the transmission towers, and at the ground surface. If these
field strength components exceed certain critical values, streamers
(and following leaders) are to be expected from various points
INTRODUCTION at the transmission system. These upward-going discharges may
THE prediction of the area "covered" by a transmission not appear simultaneously, and the first one to meet the down-
line and the shielding effect of ground wires is of major going leader determines a probable stroke to the point from
importance when the outage rate of a power system is studied. which it started. In that way both the area covered by the trans-
Many authors have discussed these problems and some methods mission line and the shielding effect of the ground wires can be
studied.
Paper 70 TP 102-PWR, recommended and approved by the
Transmission and Distribution Committee of the IEEE Power PRESTROKE PHENOMENON AND ELECTROMAGNETIC FIELD
Group for presentation at the IEEE Winter Power Meeting, New
York, N. Y., January 25-30, 1970. Manuscript submitted August 1, The prestroke phenomenon has been studied by many authors
1969; made available for printing December 5, 1969. and is described in numerous papers; for example, [10]-[12].
The author is with the Division of Electrical Power Systems
Engineering, Royal Institute of Technology, Stockholm, Sweden. The down-going leader, which starts from the cloud, proceeds

Вам также может понравиться