Вы находитесь на странице: 1из 43

The Pulse Mixed Use Project at Residential Particular Specification Part B

City Dubai South-Parcel 1&4 Section S60

Contents
S60 FIRE PROTECTION ......................................................................................................................................... 4

PART 1 SYSTEM OBJECTIVES .................................................................................................................................... 4


100.005 SCOPE OF SERVICES .................................................................................................................................... 4
100.010 PERFORMANCE OBJECTIVES ....................................................................................................................... 4
100.020 DESIGN PARAMETERS .................................................................................................................................. 5
100.050 SYSTEM SCHEMATICS................................................................................................................................... 7
100.060 SYSTEM DRAWINGS ...................................................................................................................................... 7

PART 2 SELECTION SCHEDULES FOR REFERENCE SPECIFICATIONS.................................................................. 8


210.000 PIPELINES ....................................................................................................................................................... 8
210.010 GENERAL: ....................................................................................................................................................... 8
210.020 STEEL PIPES AND FITTINGS: ........................................................................................................................ 8
210.020A STEEL PIPES AND FITTINGS: ........................................................................................................................ 8
210.020B STEEL PIPES AND FITTINGS: ........................................................................................................................ 8
210.020C STEEL PIPES AND FITTINGS: ........................................................................................................................ 8
210.070 PIPEWORK ACCESSORIES: ........................................................................................................................... 9
210.080 GENERAL WORKMANSHIP ............................................................................................................................ 9
210.090 WORKMANSHIP, STEEL PIPEWORK: ............................................................................................................ 9
210.130 WORKMANSHIP: ........................................................................................................................................... 10
211.000 PIPELINE ANCILLARIES................................................................................................................................ 10
211.010 GENERAL: ..................................................................................................................................................... 10
225.000 CLEANING AND CHEMICAL TREATMENT ................................................................................................... 10
225.010 GENERAL: ..................................................................................................................................................... 10
251.000 TESTING AND COMMISSIONING OF MECHANICAL SERVICES ................................................................. 11
251.010 GENERAL: ..................................................................................................................................................... 11
252.000 VIBRATION ISOLATION MOUNTINGS .......................................................................................................... 11
252.010 GENERAL: ..................................................................................................................................................... 11
254.000 IDENTIFICATION - MECHANICAL ................................................................................................................. 11
254.010 GENERAL: ..................................................................................................................................................... 11
290.000 FIXING TO BUILDING FABRIC ...................................................................................................................... 11
290.010 GENERAL: ..................................................................................................................................................... 11
291.000 OFF-SITE PAINTING AND ANTI-CORROSION TREATMENT ....................................................................... 11
291.010 GENERAL ...................................................................................................................................................... 11
291.020 PAINT MATERIALS: ....................................................................................................................................... 11
291.030 WORKMANSHIP ............................................................................................................................................ 12

PART 3 SPECIFICATION CLAUSES SPECIFIC TO S60............................................................................................. 13


300.000 GENERAL ...................................................................................................................................................... 13
300.010 STANDARDS: ................................................................................................................................................ 13
300.021 FIRE AUTHORITY REQUIREMENTS:............................................................................................................ 13
300.040 BONDING ....................................................................................................................................................... 13
310.000 PRODUCTS/MATERIALS............................................................................................................................... 13
310.001 LANDING VALVES ......................................................................................................................................... 13
310.002 SPRINKLER INSTALLATION ......................................................................................................................... 13
310.003 BREECHING INLETS ..................................................................................................................................... 14
310.004 PORTABLE FIRE EXTINGUISHER ................................................................................................................ 15
310.005 AUTOMATIC DRY POWDER EXTINGUISHERS............................................................................................ 15
310.006 CLEAN AGENT EXTINGUISHER SYSTEM.................................................................................................... 15
310.007 FIRE BLANKETS ............................................................................................................................................ 15
310.008 SPARES AND TOOLS.................................................................................................................................... 16
310.010 FIRE HOSE REELS:....................................................................................................................................... 16
310.010A FIRE HOSE REELS:....................................................................................................................................... 16
310.010B FIRE HOSE REELS:....................................................................................................................................... 16
310.010C FIRE HOSE REELS:....................................................................................................................................... 17
310.021 FIRE PUMP SET: ........................................................................................................................................... 17
310.021A FIRE PUMP SET: ........................................................................................................................................... 18
310.021B FIRE PUMP SET: ........................................................................................................................................... 19
310.021C FIRE PUMP SET: ........................................................................................................................................... 21
310.021D FIRE PUMP SET: ........................................................................................................................................... 22
310.022 FACTORY PERFORMANCE TEST: ............................................................................................................... 22
310.022 SYSTEM PERFORMANCE TEST: ................................................................................................................. 22
310.040 FLOW SWITCH: ............................................................................................................................................. 22
310.055 CLEAN AGENT FIRE SUPPRESSION SYSTEM:........................................................................................... 22
310.065 WET CHEMICAL FIRE SUPPRESSION SYSTEM:......................................................................................... 39
310.075 DELUGE WATER SPRAY SYSTEM ............................................................................................................... 40
310.076 PREACTION AUTOMATIC SPRINKLER SYSTEM ......................................................................................... 40
310.095 FOAM DELUGE SYSTEM ............................................................................................................................. 40
320.000 WORKMANSHIP ............................................................................................................................................ 43
320.005 GENRAL REQUIREMENTS ........................................................................................................................... 43
320.006 OPERATION AND ATTENDANCE OF THE FIRE PROTECTION SYSTEM ................................................... 44

5148212/D3028/Rev 0 S60/2 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

320.007 RECORDS AND DOCUMENTATION ............................................................................................................. 44


320.008 TRAINING AND INSTRUCTION TO THE OPERATOR................................................................................... 44
320.010 INSTALLATION: ............................................................................................................................................. 44
320.020 FIXING: .......................................................................................................................................................... 44
320.030 ISOLATION: ................................................................................................................................................... 44

5148212/D3028/Rev 0 S60/3 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

S60 FIRE PROTECTION


PART 1 SYSTEM OBJECTIVES

100.005 SCOPE OF SERVICES

shall be included by the Contractor as part of this project are as follows:

Fire Protection System for Parcel 1 buildings and podium levels.


Fire Protection System for Parcel 4 building and podium levels.

schedules for clarity of the actual systems and services required, refer to and comply with

technical information in relation to; the systems listed above, part 1 of this specification and
the drawings/ schematics/ schedules.

Also comply with any and all clauses relating to; workmanship, installation, work on site,
fixing, access, marking, identification, labelling, accessories, inspection & testing, testing &
commissioning, operation & maintenance, training, system demonstration, notifications,
spare parts & tools, quality control, safety, delivery, storage, protection, certification,
programming, documentation, submittals, installation records, surveys, guarantee and
warranty etc., as detailed in part 3

100.010 PERFORMANCE OBJECTIVES

To develop, supply, install, test and commission a Fire Protection system in accordance
with; specification, and in accordance with all relevant; Regulations,
British/European Standards (BS, BS-EN, ISO, EN), and local approval/ Dubai Municipality
Green Building Regulations/ Dubai Civil Defence/ statutory authority requirements for Fire
Protection and other relevant good practice guides & codes of practice.

To provide a safe and efficient Fire Protection system left in a safe and reliable working
manner.

Coordinate with all other services to provide a neat and efficient system.

The Contractor shall include for the complete design, installation, testing and commissioning
of the fire protection equipment detailed on the drawings and in this specification. The
Contractor shall include for all labour, materials, tools and tackle, complete with all supports
and fixings back to approved building structural members and all items necessary for a
complete, functional system operating in line with the design intent irrespective of these
items being explicitly mentioned or not.

The Contractor shall be responsible for verifying all dimensions and location of other
services, the correct setting out of the installation and fire protection equipment and
coordination with the local authority having jurisdiction (AHJ) (including obtaining approval of
materials, fittings, shop drawings and the installation). Refer to the General A Clauses for
details of the local authority having jurisdiction.

The Contractor shall ensure the entire fire protection and detection system design and
installation is in accordance with the latest published regulations and requirements of the
local AHJ. All materials and components shall be UL listed, wherever possible as the first
proposal with LPCB approval only being proposed as an alternative where UL listing is
unavailable and such approval is in accordance with the local AHJ.

5148212/D3028/Rev 0 S60/4 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Firefighting systems for the development shall comprise of the following fire protection
equipment as applicable in accordance with the requirements of the Local Authority having
Jurisdiction and as shown on the drawings:

Sprinklers;
Landing valves and fire hoses;
Hose reels;
Portable fire extinguishers;
Automatic dry powder extinguishers;
Clean agent extinguishing systems;
Deluge Spray systems for LGP tanks
Automatic Pre action system for lift machine rooms
Foam protection system in high hazard areas;
Trolley mounted extinguishers for transformer rooms;

Fire cabinets shall be provided by the specialist Contractor and fixed by the Main Contractor.
The fire extinguishing equipment shall be installed in the cabinets by the Contractor as
shown on the drawings.

100.020 DESIGN PARAMETERS

Supply, install, test and commission a Fire Protection system in accordance with S60 of
this specification

The Building Services Contractor shall, at his cost, appoint a specialist Contractor for the
design, supply, installation, testing and commissioning of the Fire Protection System and
equipment in accordance with this specification and the local authority having jurisdiction.
The specialist Contractor shall be one of those listed elsewhere in the specification and be
approved by the local authority having jurisdiction
The Specialist Contractor shall coordinate and work in close liaison with the Infrastructure
Contractor to ensure that all firefighting systems for the development are fully integrated and
interfaced with fire protection and alarm system to ensure that a fully operational and reliable
system is put into operation.

The design shall be based on following standards:

Sprinklers & Pre action systems NFPA 13


Wet risers, Hose Reels, Hoses NFPA 14
Fire pumps NFPA 20
Clean Agent Extinguishing Systems NFPA 2001
LPG Code of Practice NFPA 54 and 58
Foam Deluge System NFPA 11 and 16
Portable Extinguishers NFPA 10/UL 711 or BS5423, Kite marked and
LPCB approved (AHJ approval required)
Hazard Classifications Refer to Drawings

In addition, the fire protection system and all equipment shall have approval from the local
authority having jurisdiction.

The Contractor shall hand over prior to the completion of the Works the record drawings and
manuals in accordance with NFPA and BS 5306.

5148212/D3028/Rev 0 S60/5 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

100.030 SYSTEM DESCRIPTION

The principal water fire protection system for this building is a pumped system with a UL
Listed/FM Approved pump set located at lowest basement level. The system shall be in full
compliance with NFPA 13, 14, 20 and other relevant NFPA sections to provide a combined
multi-zone wet riser Class III system.
All first aid firefighting stations for hose reels, landing valves, extinguishers etc. shall be
located as shown on the drawings and to the requirements and regulations of the local
Authority Having Jurisdiction. The fire hose reels, landing valves along with hose and
extinguishers in public areas and landscaped areas shall be installed in MS epoxy coated
cabinets. All equipment within the fire cabinets shall be neatly placed with all loose hoses
hung from proprietary wall brackets, the fire hose reels level and all extinguishers
conveniently arranged for easy withdrawal. Contractor shall coordinate with Interior
Designer/Architect for all requirements of unobstructed access to the firefighting systems

All retail/F&B areas shall be subject to Tenant fit-out works, supervised valve connection
shall be provided to enable the Tenant to make modifications to the system as required to
suit the fit out. Under this Contract, however, the specialist Contractor shall install all fire
protection systems in accordance with the details given on the drawings issued with this
contract. Any Tenant fit-out works shall be subject to future fit-out contracts.

Within the generator room , a foam firefighting system shall be installed. The system shall
be in full compliance with NFPA 16 and the requirements and regulations of the local
authority having jurisdiction.

The main LV room and telecom rooms shall be protected by a clean agent fire suppression
system that shall be in full compliance with NFPA 2001 and the requirements and
regulations of the local authority having jurisdiction.

Electrical rooms, Etisalat room and Telecom rooms shall be protected by a wall mounted
automatic dry powder extinguishers which shall be in full compliance with NFPA and the
requirements and regulations of the local authority having jurisdiction.

The Contractor shall also supply trolley mounted extinguishers to fight fire within the
transformer rooms which shall be in full compliance with the requirements and regulations of
the local authority having jurisdiction and DEWA (E) & UAE Fire and life safety code of
practice.

The Contractor shall include additional sprinklers where ceiling void above false ceiling is
more than 800 mm. The contractor shall be responsible for verifying these areas and provide
additional sprinkler heads as required.

The Contractor shall also provide first aid extinguishers, fire blankets and other ancillary fire
protection equipment as defined within this specification and to obtain approval from the
local authority having jurisdiction.

The Specialist Contractor shall install all fire protection systems in accordance with the
details given on the drawings issued with this contract, and shall be reviewed in conjunction
.

The entire fire protection system, including, sprinklers, wet riser, hose reels and other fire
protection systems shall be installed as a complete installation that is tested, commissioned
and set to work upon handover of the building.

100.040 CONTROL REQUIREMENTS

The local authority having jurisdiction require all landing valves shall have a residual
pressure of 6.9 bar (g). The specialist Contractor shall confirm all relevant design details,

5148212/D3028/Rev 0 S60/6 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

including this one, with the local authority having jurisdiction and issue all response to the
Engineer for approval.

Refer the relevant infrastructure documentation for technical specification for fire pumps, fire
water reserve, pump control, indicators and associated information that form part of the
Central Utility building as part of the infrastructure scope of works.

All valves and zone flow switches (sprinkler) shall be monitored on the fire alarm panel in the
respective buildings and shall also be interfaced to the building fire alarm panel and systems.

100.050 SYSTEM SCHEMATICS

Refer to the accompanied drawing registers.

100.060 SYSTEM DRAWINGS

Refer to the accompanied drawing registers.

5148212/D3028/Rev 0 S60/7 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

PART 2 SELECTION SCHEDULES FOR REFERENCE SPECIFICATIONS

210.000 PIPELINES

210.010 GENERAL:

Comply with work section general clauses reference Y10.1000 and those detailed below.
Supply pipes and fittings as specified in work section S60
All fittings used shall have UL listing/FM approvals and be approved for installation on
fire water services.

210.020 STEEL PIPES AND FITTINGS:

Type: General requirements.


Application: Applicable to all steel pipes and fittings used for fire fighting installation.
Fluid conveyed: fire fighting water.
Working pressure: to suit system operating characteristics as designed by the
specialist.
Working temperature: ambient, i.e. maximum 50°C.

210.020A STEEL PIPES AND FITTINGS:

Type A:
Application: Fire fighting system pipework for wet risers, sprinkler pipework etc. up
to 50mm diameter.
Material: Carbon steel (Carbon <0.25%), ERW.
Standard: API 5L Grade 'B' Schedule 40, black finishes.
Malleable cast iron fittings, screwed
Black - reference Y10.2070A
Jointing materials
Screwed joints to BS 21
Paste and hemp and PTFE tape - reference Y10.3030A
Where chemical cleaning is required - reference Y10.3030C

210.020B STEEL PIPES AND FITTINGS:

Type B
Application Fire fighting system pipework for wet risers, sprinkler pipework etc.
65mm diameter and above.
Material: Carbon steel (Carbon <0.25%), ERW.
Standard: API 5L Grade 'B' Schedule 40, black finishes.
Fittings, grooved for mechanical joints
Black steel - reference Y10.2080B
Jointing materials
Circular flanges
Flanges to BS EN 1092-1 PN 25
Welding flanges - reference Y10.3010A
Jointing rings for circular flanges
Non-metallic flat for flanges to BS EN 1092-1 - reference Y10.3020A
Mechanical joints, grooved steel pipes - reference Y10.3140A

210.020C STEEL PIPES AND FITTINGS:

Type C
Application Suction line pipework from the RCC storage tanks to the pump sets
(refer to specification section S10 for details).

5148212/D3028/Rev 0 S60/8 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

210.070 PIPEWORK ACCESSORIES:

Application: Fire fighting systems.


Wall, floor and ceiling masking plates
Chromium plated - reference Y10.3190A.
Pipe rings and clips
Steel pipework - reference Y10.3200A

210.080 GENERAL WORKMANSHIP

Application Fire fighting systems.


Appearance - reference Y10.4010
Spacing - reference Y10.4020
Gradients - reference Y10.4030
Air venting requirements
Automatic air vents - reference Y10.4040B
Drain requirements - reference Y10.4050
Expansion and contraction - reference Y10.4060
Pipe fittings
Bends/swept tees - reference Y10.4070A
Pipes through walls and floors - reference Y10.4110
Pipe sleeves - reference Y10.4120A
Pipe sleeves through fire barriers - reference Y10.4125
Connections to equipment - reference Y10.4130
Distribution headers - reference Y10.4140
Temporary plugs, caps and flanges - reference Y10.4150A.
Flanged joints general - reference Y10.4160
Dissimilar metals - reference Y10.4170
Pipe rings and clips - reference Y10.4180
Anchors - reference Y10.4190
Location
As required by the specialist Contractor.
Pipe supports - reference Y10.4210
Support spacing - reference Y10.4220
Isolation and regulation - reference Y10.4230A
Maintenance and renewal - reference Y10.4240
Cleaning - reference Y10.4250
Non-ferrous components - reference Y10.4260

210.090 WORKMANSHIP, STEEL PIPEWORK:

Application: Fire fighting system pipework.


Welding, general
Class 1 - reference Y10.5010A
Welded joints - reference Y10.5020
Painting welded joints - reference Y10.5030
Flanged joints - reference Y10.5040
Screwed joints - reference Y10.5050
Mechanical joints - reference Y10.5060
Anchors
U-bolts - reference Y10.5070A
Flanges - reference Y10.5070B
Pipework painting - reference Y10.5090

All pipework shall be painted with two coats of red oxide primer throughout the entire
pipework installation. In addition the pipework shall be painted with a red enamel paint finish

5148212/D3028/Rev 0 S60/9 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

in all areas of the building where the pipework is exposed to view, including plantrooms, car
parks, etc. and to the approval of the local authority having jurisdiction. Where the pipework
is not enamel painted the pipework shall be suitably marked in accordance with this
specification and to the approval of the local authority having jurisdiction.

210.130 WORKMANSHIP:

Application: Fire fighting systems.


Protection of underground pipework - reference Y10.9030
Location
All buried pipework.
Protection of buried pipes - reference Y10.9040B
Location
All buried pipework.
Protection of pipes in screed
Wrap with two protective tapes before laying.
Corrosion protective tape - reference Y10.9100
Steelwork painting - reference Y10.9120A

211.000 PIPELINE ANCILLARIES

211.010 GENERAL:

Comply with work section general clauses reference Y11.1000 and those detailed below:

Supply valves as specified in work section T61.


Isolation valves, strainers, check valves, test, drain valves and other ancillaries used
on fire fighting water services shall have UL listing/FM approval. All isolating valves
shall be lockshield type.
All the supervised isolation valves (as per NFPA/Local Authority requirements) shall
be OS and Y gate valves.
All supports/hangers used on firewater pipework shall be suitable for the duty and
have UL listing/FM approval.

225.000 CLEANING AND CHEMICAL TREATMENT

225.010 GENERAL:

Comply with work section general clauses reference Y25.1000 and those detailed below:

Supply cleaning and chemical treatment as specified in section T61.


Tubes and all items of equipment shall be delivered, stored and maintained in storage
with their open ends effectively plugged, capped or sealed. All fittings, valves and
sundry items shall be stored in clean bins or bagged and stowed in suitable racks. All
such stored items shall be maintained under weatherproofed cover to be supplied by
the Contractor until they are ready for incorporation in the works. Particular care shall
be taken to ensure that electrical equipment and components are kept clean and dry.
Before installations are handed over or subjected to the inspection and tests the entire
installation shall be thoroughly cleaned, both internally and externally.
All fire protection installations shall be flushed out with clean water. During the
flushing out provision shall be made to exclude any items of plant that could be
damaged by the cleaning operation. The entire operation shall be carried out to the
satisfaction of the Engineer.
Where the water circuit of the wet riser, hose reel and the sprinkler systems and the
fire water storage tank are completely independent of the domestic system, the water
in fire systems shall be chemically treated to prevent corrosion and inhibit the growth
of bacteria. The chemicals used shall be suitable for fire fighting systems and to the
Engineer's approval.

5148212/D3028/Rev 0 S60/10 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

251.000 TESTING AND COMMISSIONING OF MECHANICAL SERVICES

251.010 GENERAL:

Comply with work section general clauses reference Y51.1000 and those detailed below.

All testing and commissioning shall be completed in accordance with requirements,


regulations and to the approval of the local authority having jurisdiction and the site
Engineer.

The fire protection systems shall be tested in accordance with NFPA and the relevant
clauses in Specification section T61. The hydraulic test pressure for pipework shall be 1.5
times the pumps closed valve pressure or 16 bar whichever is higher.

Carry out testing and commissioning as specified in section T61.

252.000 VIBRATION ISOLATION MOUNTINGS

252.010 GENERAL:

Comply with work section general clauses reference Y52.1000 and those detailed below.
Install approved vibration isolation mountings under the fire pumps.

254.000 IDENTIFICATION - MECHANICAL

254.010 GENERAL:

Comply with work section general clauses reference Y54.1000 and those detailed below.
Provide identification - mechanical as specified in work section T61.

Provide complete identification, labelling etc. in line with NFPA and the requirements and
regulations of the local authority having jurisdiction.

290.000 FIXING TO BUILDING FABRIC

290.010 GENERAL:

Comply with work section general clauses reference Y90.1000 and those detailed below.
Fixings for all fire fighting and life safety equipment shall be in accordance with NFPA/UL/FM
requirements and to the approval of the local authority having jurisdiction and the site
Engineer.

Carry out fixing to building fabric as specified in work section T61.

291.000 OFF-SITE PAINTING AND ANTI-CORROSION TREATMENT

291.010 GENERAL

Comply with work section general clauses reference Y91.1000 and those detailed below.
Carry-out off-site painting and anti-corrosion treatment as work section T61.

291.020 PAINT MATERIALS:

Application All fire fighting system equipment and ancillaries


Paint materials
All fire fighting pipework (whether exposed or concealed) shall be given two coats of
approved primer and two coats of approved enamel paint.
Reference Y91.2010A
Paint quality - reference Y91.2020

5148212/D3028/Rev 0 S60/11 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

291.030 WORKMANSHIP

General - reference Y91.3010


Weather and other conditions - reference Y91.3020
Cleaning and preparing for painting
Steel surfaces - reference Y91.3030A
Application off-site - reference Y91.3040
Application - reference Y91.3050
Cold galvanizing - reference Y91.3060
Protection of bright machine parts - reference Y91.

5148212/D3028/Rev 0 S60/12 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

PART 3 SPECIFICATION CLAUSES SPECIFIC TO S60

300.000 GENERAL

The following sections within part 3 of this specification shall be read for general and
additional information relating to S60 type systems. Information within part 1 of this
specification (i.e. sections 100.010, 100.020, 100.030 & 100.040: performance data, design
data, system descriptions, and control requirements) shall take precedence over any
possible conflicting information in part 3. Part 3 shall be read for additional information to part
1. Any information in part 3 (and only that piece of information) conflicting with part 1 shall
be disregarded.

300.010 STANDARDS:

Comply with NFPA, BS 5306-1 and the requirements and regulations of the local authority
having jurisdiction.

300.021 FIRE AUTHORITY REQUIREMENTS:

Ensure all system components are approved by the local authority having jurisdiction.

300.040 BONDING

Incorporate provision for earth bonding.

310.000 PRODUCTS/MATERIALS

310.001 LANDING VALVES

A wet hydrant riser shall be provided where shown on the drawings and as required in
accordance with the local authority having jurisdiction and the approved drawings prepared
by the specialist Contractor.

The landing valves shall be UL listed oblique pattern globe type with non-rising bronze
spindle, fitted with a leather strap and padlock with two keys. The hand wheel shall be
marked to show direction of rotation and the valve shall be complete with blank plug and
chain. Inlet size shall be 65mm flanged and the outlet 65mm female to suit instantaneous
coupling in accordance with the requirements and regulations of the local authority having
jurisdiction. The landing valve shall include an adjustable pressure-reducing device to
ensure an outlet pressure of 6.9 bar, in accordance with NFPA requirements (or as
acceptable to the local authority having jurisdiction).

All landing valves shall be housed in landing valve boxes, cupboards or fire cabinets labelled
"Wet Riser Outlet". The fire cabinets shall be in compliance with the requirements and
regulations of the local authority having jurisdiction and to the requirements of the Architect.

All landing valves shall be provided with 30m length of 65 dia Angus Duraline or equal and
approved fire hose and aluminium alloy nozzle to the requirement and regulations of the
local authority having jurisdiction. All hoses shall be supported from the wall on suitable
supports/hose rack.

310.002 SPRINKLER INSTALLATION

The Specialist Contractor shall design, supply, install, test and commission an automatic wet
sprinkler system protecting the building.

The sprinkler installation shall be designed in accordance with NFPA-13 and current local
requirements and regulations of the local authority having jurisdiction.

5148212/D3028/Rev 0 S60/13 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

The Contractor's attention is drawn to the extensive air conditioning ductwork and pipework
installation in the building. It is the Contractor's responsibility to coordinate the sprinkler
pipework and sprinkler head locations with all other services. In order to ensure that
locations of all services are coordinated, the Contractor shall produce reflected false ceiling
drawings showing the coordinated locations of all services and submit them for approval.
The final location of sprinkler heads shall be in accordance with these approved drawings.

The Contractor shall install sprinklers within the Tenant and Freehold areas of the building in
accordance with the drawings. The Contractor shall allow sufficient tolerance on the
installation to facilitate relocation of the sprinkler heads. The Contractor shall also
hydraulically size the distribution network within leased/freehold premises to allow additional
heads to be installed, 10% per floor, to allow additional compartmentation of the larger
areas. The details shall be agreed with the Engineer and the local authority having
jurisdiction.

In all areas where the ceiling void is more than 800mm, the space above the false ceiling
shall also be protected in line with requirements of NFPA.

The type of sprinkler heads to be used in the building shall be:

a) Car park - Bronze construction, pendant or upright type.


b) Plantrooms/pump rooms/AHU - Bronze construction, pendant or upright type.
rooms/stores etc. without false
ceiling and ceiling void.
c) Services areas with false - Bronze construction, powder coated white
ceilings (e.g. service corridors, finish, partly recessed with powder coated
stores etc.). white finish escutcheon plate.
d) Staircases - Bronze construction, powder coated white
finish side-wall mounted with powder coated
white finish escutcheon plate.
e) Public areas (e.g. apartments - Bronze construction, powder coated paint
areas, lobbies, corridors, finish, semi recessed with powder coated
toilets, etc.) and offices paint finish escutcheon. Colour subject to
Architects approval.
f) Sidewall application - Bronze construction, extended coverage,
semi recessed, powder coated paint finish
with escutcheon plate (for car park paint finish
and escutcheon plate are not required).
Colour subject to Architects approval.

All sprinkler heads shall, subject to approval of the local authority having jurisdiction, operate
at 68°C, be quick response type and shall be UL listed/FM approved. Higher actuation
temperatures may be recommended in certain locations. The specialist Contractor shall
check NFPA and the requirements and regulations of the local authority having jurisdiction
and allow for such sprinklers.

310.003 BREECHING INLETS

Install breeching inlets adjacent to the road, as shown on the drawings and as required by
the local authority having jurisdiction.

Three separate breeching inlets are shown on the drawings and shall be labelled: -

WET RISER
SPRINKLER INLET
TANK FILL

All necessary approvals of the local authority having jurisdiction shall be obtained by the
Contractor and forwarded to the Engineer for his approval.

5148212/D3028/Rev 0 S60/14 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

The inlet breeching valves shall be UL listed and of vertical or horizontal pattern (as
indicated on the drawings) having a 100mm flanged outlet and two 65mm instantaneous
male inlets complete with blank caps and chains. The breeching inlet shall be equipped with
a 25mm drain valve to drain the riser. The entire breeching inlet shall be enclosed in an
approved mounted box, typically stainless steel but subject to the Architects approval, with a
labelled wired glass door. The stainless steel shall be to AS 304 or 321. The breeching
valve shall be complete with check valve.

310.004 PORTABLE FIRE EXTINGUISHER

The Contractor shall supply and install water portable fire extinguishers in the positions
shown on the drawings. The stored pressure extinguishers shall be 4.5 kg ABC Dry powder
or 5 kg carbon dioxide type (light hazard area), or 9 kg carbon dioxide type (ordinary hazard
area) or dry chemical powder 2 kg as shown on the drawings. The extinguisher shall include
a gauge for indication of pressure.

The Contractor shall ensure the portable extinguishers are installed at a suitable height in
the specified cabinets. Where fire extinguishers are installed on the wall, they shall be
complete with wall mounting brackets. Where fire extinguishers are located within fire
cupboards/cabinets they shall be placed on the floor of the cupboard/cabinet. The fire
extinguishers shall be designed and constructed either in accordance with the latest NFPA
10, shall be UL listed or with the latest BS5423, shall be kite marked and LPC approved;
subject to the approval of the Local AHJ.

The number of extinguishers required shall be as per the specialist Contractors design,
subject to the Engineers approval and approval of the local authority having jurisdiction (the
number shown on the drawings are indicative only).

310.005 AUTOMATIC DRY POWDER EXTINGUISHERS

Ceiling suspended, 6 kg capacity each, automatic ABC dry powder extinguishers (having
sprinklers/nozzles with heat operated bulbs) shall be installed in all Electrical rooms,
Telecom rooms, Etisalat rooms and as generally identified on the drawings.

The number of extinguishers required shall be as per the specialist Contractors design,
subject to the Engineers approval and approval of the local authority having jurisdiction (the
number shown on the drawings are indicative only).

310.006 CLEAN AGENT EXTINGUISHER SYSTEM

Clean Agent Extinguishing systems shall be installed in the rooms indicated.

In all areas where clean agent extinguishing systems are specified, the system shall be
designed and installed to protect the ceiling and floor voids also

The Clean Agent Extinguishing system shall be installed by the specialist contractor in
accordance with NFPA2001 and Local Authority having jurisdiction. The installation shall be
carried out in a well-coordinated manner approved by the Site Engineer.

310.007 FIRE BLANKETS

One 180cm x 120cm fire blanket shall be installed within every kitchen and pantry, as shown
on the drawings and as required by the Local AHJ. The fire blanket shall be of woven glass
fibre and as per the requirements of local authority having jurisdiction. The blanket shall be
installed in a wall mounted PVC container.

5148212/D3028/Rev 0 S60/15 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

310.008 SPARES AND TOOLS

The Contractor shall provide spare sprinklers (along with suitable wrenches) of all types
used on the project. The number of spare sprinklers shall be as per LPC/NFPA but in any
case they shall not be less than 25 of each type. The sprinklers and wrenches shall be kept
in a suitable cabinet (with breakable glass door) mounted in the basement pump room or as
designated by the building landlord.

310.010 FIRE HOSE REELS:

Type: General requirements.


Application: First aid fire fighting by building occupants.
Manufacturer and reference: As defined in the manufacturers and suppliers list, or
approved equivalent
Mounting
Swinging arm.
Hose - Comply with BS 3169.
Provide each reel with smooth bore non-kink rubber hose.
Hose diameter: 25mm
Hose length (m) 30m
Ensure hose is rated for distribution pressures.

Terminate with an outlet nozzle of type approved by local authority having jurisdiction.
The hose reels shall be connected to the wet riser system and the connection shall include
site adjustable pressure reducing valves.

Direct acting pressure reducing valves shall be installed for all hose reels to ensure that the
operating pressure at the hose reel is between 4.0 Bar and 5.0 Bar at design flow rates in
accordance with the requirements and regulations of the local authority having jurisdiction.

Refer to the pipework schematic drawings for location of PRVs, however, the Contractor
shall provide all PRV's necessary to ensure pressure within the stated range at the hose
reel. The pressure reducing valves shall be site adjustable, approved by local authority
having jurisdiction be UL listed and FM approved where possible.

Hose reel operating instructions shall be clearly marked on the hose reel. The instructions
shall be installed in a prominent position facing the operator.

310.010A FIRE HOSE REELS:

Type: A - (Ref Type 1).


Application: Architectural Cabinet type.

Cabinet type hose reels shall be suitable for recessed fitting and be of the automatic
swinging type mounted 1.5m from floor level and provided with a lockshield pattern local
isolating valve. The Contractor shall coordinate the installation with the Main Contractor
to ensure the architectural door and associated finishes do not impeded the operation of
the hosereel and access to the valves and extinguishers where these are also installed.

310.010B FIRE HOSE REELS:

Type: B (Ref: Type 2).


Application: Concealed type.

Concealed automatic swinging type hose reels shall be installed within a steel cabinet
concealed within the wall or similar. The cabinet shall be of stainless steel construction,
or to suit the requirements of the Architect. The cabinet shall have two doors, one for the
hosereel and the other for the landing valve, flat hose (where installed) and extinguishers.

5148212/D3028/Rev 0 S60/16 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

310.010C FIRE HOSE REELS:

Type: C - (Ref: Type 3).


Application: Surface type.

Surface automatic swinging type hose reels shall be similar to type 2 but shall be
mounted within a galvanised steel cabinet painted red. The cabinet shall have two doors,
one for the hose reel and the other for the landing valve, flat hose (where installed) and
extinguishers.

310.021 FIRE PUMP SET:

Type: General requirements.


Application: Applicable to all fire fighting pump set serving the combined wet riser,
sprinkler and fire hose reels.
Manufacturer and reference: As defined in the manufacturers and suppliers list. Or
approved equivalent
Duty: As Pump Schedule given in the Mechanical Equipment Schedules. The
scheduled fire pump duty is at the pumps rated differential head. The fire pump shall
deliver not less than 150% of the rated capacity at a pressure of not less than 65% of
the rated head. The shutoff head shall not exceed 140% of the rated head.

Components:

The pump shall be a horizontal split case (or vertical mounted split case), double-suction,
bronze-fitted, centrifugal pump mounted on a common base plate with the pump driver
complete with coupling and coupling guard. The pump shall have a common horizontal
centreline between the suction and discharge connections.

The Contractor shall supply and install the following components as a minimum: -

All components and ancillaries recommended by NFPA 20;


UL Listed/FM Approved Duty and standby pumps;
UL Listed/FM Approved Jockey pump;
Integral wiring and control panel;
Interconnecting pipework, valves and fittings;
Anti-vibration mountings.

The Contractor shall supply and install packaged electric pumps, electric jockey pumps and
backup fire pumps, either packaged diesel set or generator driven electrical pumps. All
pumps shall be installed on prepared concrete bases at the location shown on the drawings.

The pump sets shall completely conform to NFPA requirements and have UL listing/FM
approval for the specific pump, driver and controller proposed by the Contractor and to the
requirements and regulations of the local authority having jurisdiction.

The controllers shall completely conform to NFPA requirements for the specific pump model
proposed by the Contractor and to the requirements and regulations of the local authority
having jurisdiction.

Engines and electric motors shall be rated for continuous operation at 50°C. All motors shall
be NEMA drip-proof. The diesel engine, where provided, shall be water-cooled (weir tank
type).

The fire protection pumps (electric and diesel) shall be horizontal type. The motor and
engine shall be rated in accordance with NFPA 20. One number UL Listed/FM Approved
vertical multi-stage type jockey pump shall be provided.

5148212/D3028/Rev 0 S60/17 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

The duty of all fire protection pumps shall be as per Fire Protection System Specialist
Contractor's design to meet the requirements of sprinkler installation as per latest NFPA 13
and NFPA 14, subject to Engineer's to the requirements and regulations of the local authority
having jurisdiction.

The fire protection pumps shall be suitable for a working pressure as defined in the Schedule
of Pumps or at least 17.0 bar (whichever is higher).

The components and operating procedure for controllers detailed herein indicate the basic
requirements of the fire protection system. However, the entire operation of the fire pump
sets and wet riser system shall be in full compliance with NFPA and to the requirements and
regulations of the local authority having jurisdiction.

Full dry run protection shall be provided to the fire pumps in the form of a dedicated float
switch (one per compartment) that shall cause the pumps to shut down in the event of a low
water level in the tank. The switch shall be provided with a spare set of volt free contacts for
monitoring by the BMS system.

310.021A FIRE PUMP SET:

Type: A - Electric fire pump (Ref: FFP-B3-01).


Application: Electric fire pump.

Components:

The electric motor for the fire pump shall be a standard NEMA design B, open drip proof,
1.15 service factor, squirrel cage induction motor with grease lubricated ball bearings.
The locked rotor current shall not exceed the values specified in NFPA 20. The motor
shall be wound for 400 volts 3-phase 50Hz operation with operating speed motor as
required by the fire pump.

The controller shall be UL listed and FM approved for fire pump service and shall meet or
exceed all the requirements of the latest edition of NFPA 20, the National Electric Code
(NFPA 70) and the requirements and regulations of the local authority having jurisdiction.
The controller shall be of the combined manual and automatic type.

Enclosures shall be minimum 1.5mm gauge sheet steel protected to NFPA and the
requirements of the local authority having jurisdiction and be fitted with lockable access
door and finished in high quality stove enamel.

The controller shall contain but not be limited to the following components:
-Isolating switch
Circuit breaker, of appropriate size & rating
Motor starter, for automatic & manual starting
Power on LED light, start & stop push buttons
Contacts for remote indication of "Pump Run, "Loss of Power," and Phase
Reversal"
0-600 PSI pressure switch with adjustable settings
Control relays & control circuit transformer
Running period timer set for 10 min. (may be deleted)
Remote start relay
Emergency run handle with mechanical latch
Automatic transfer switch for transfer to an alternate power source,
assembled as part of controller.
Low suction pressure alarm & shutdown panel with automatic (manual)
reset
Extra auxiliary contacts
Remote alarm panel, visual & audible

5148212/D3028/Rev 0 S60/18 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Built-in alarm panel


Sequential start

The following equipment shall be mounted on the enclosure door:

1 - Isolator handle
1 - Stop/reset push button
2 - Supply health indicating lights

Volt free normally closed contacts shall be provided to signal the following conditions to
the main fire alarm panel:

Pump on demand
Fault on controller

OPERATION

As defined within NFPA 20 and associated sections of the NFPA and to the requirements
and regulations of the local authority having jurisdiction.

System shall be suitable for following power supply:

Voltage : 400
Phase : 3
Frequency : 50 Hertz

310.021B FIRE PUMP SET:


Type: B - Diesel fire pump (Ref: FPP-x-xx).
Application: Diesel fire pump.

Components:

The diesel engine driver shall be UL listed & FM approved for fire pump service & shall
meet or exceed all the requirements of NFPA 20 and the requirements and regulations of
the local authority having jurisdiction. The engine shall have a motor rating equal to or
greater than the maximum BHP requirement of the fire pump when operating at any point
on its performance curve. The operating rated speed of the engine shall be equal to the
pump's rated speed.

The engine shall be equipped with the following standard features: -

Governor to regulate engine speed within 10%


Over speed shutdown device with manual reset
Battery contactors
Alternator or generator for battery recharging
Heat exchanger cooling system
Engine oil heater
Raw water cooling line as per NFPA 20
Battery rack and cables
Flexible exhaust connector
Instrument panel with tachometer, oil pressure gauge, temperature gauge,
and hour meter
Duel set batteries
Junction box with numbered terminals to correspond with terminals in
controller
Fuel tank
Exhaust silencer

5148212/D3028/Rev 0 S60/19 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

The unit shall be arranged for automatic and manual starting, with 24-volt battery system.

The engine controller shall be UL listed and FM approved for fire pump service and shall
meet or exceed all the requirements of the latest edition of NFPA 20 and the
requirements and regulations of the local authority having jurisdiction. The controller shall
provide complete automatic and manual operation of the diesel engine.

Enclosures shall be minimum 1.5mm gauge sheet steel protected to NFPA and the
requirements of the local authority having jurisdiction and be fitted with lockable access
door and finished in high quality stove enamel.

The following equipment shall be mounted within the enclosure:

Fully mechanically interlocked on load AC isolating switch to prevent access door being
opened when switch is in 'on' position.

Standard features shall include the following items:

Duel Battery chargers


Selector switch
Remote start
AC power failure start
Sequential start
0-600 PSI pressure switch
Weekly automatic test start
Pressure recorder

Visual signals with common alarm for each of the following conditions:

Low oil pressure


High water temperature
Failure to start
Over speed shutdown
Battery 1 & 2 failure
Automatic cranking cycle with 6 cranking attempts alternating between
both battery sets.

Separate terminals to signal the following conditions:

Engine running
Selector switch mis-set
Trouble on engine or controller

Additional visual & audible alarms in controller:

Low fuel level


Low pump house temperature
Low suction pressure (switch by others)
Reservoir low

Additional remote contacts to signal the following conditions:

Failure to start
Low oil pressure
High water temp
Over speed
Battery 1 failure
Battery 2 failure

5148212/D3028/Rev 0 S60/20 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

AC or charger failure

Remote alarm panel with" power on light" & visual & audible indication of:

Engine running
Engine trouble
Selector switch mis-set
Additional contacts for added alarms

ALARM CONTACTS:

Remote volt free normally closed contacts shall be provided to signal the following
conditions to the Main Fire Alarm Panel:

Pump on demand
Fault on controller

OPERATION

As defined within NFPA 20 and associated sections of the NFPA and to the requirements
and regulations of the local authority having jurisdiction.

System shall be suitable for following power supply:


Voltage : 220
Phase : 1
Frequency : 50 Hertz

310.021C FIRE PUMP SET:

Type: C - Jockey pump (Ref:FJP-B3-01).


Application: Jockey pump.

Components:

This unit shall be designed to operate on NFPA installations and to local authority having
jurisdiction regulations.

Enclosures shall be reinforced polycarbonate and fitted with access cover secured by
captive screws. Protection shall comply with IP65.

The following equipment shall be mounted on the enclosure door:


1 - Isolator operating handle

System shall be suitable for

Voltage : 400
Phase : 3
Frequency : 50 Hertz

Volt free normally closed contacts shall be provided to signal the following conditions to
the main fire alarm panel:

Pump on demand
Fault on controller.

For wet riser pumpset the 'pump on demand' indication shall be annunciated after a time
delay of approximately 15 seconds (delay period to be adjustable).

5148212/D3028/Rev 0 S60/21 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

310.021D FIRE PUMP SET:

Type: D - Electric pump backed by generator (Ref: FFP-B3-02).


Application: Electric pump backed by generator.

Components:

This pump set including driver, controller and operation shall be identical to the main
electric driven pump but shall be supplied with power from the building generator.

OPERATION

As defined within NFPA 20 and associated sections of the NFPA and to the requirements
and regulations of the local authority having jurisdiction.

System shall be suitable for following power supply:

Voltage : 400
Phase : 3
Frequency : 50 Hertz

310.022 FACTORY PERFORMANCE TEST:

PUMP: The pump shall be hydrostatically tested to twice the working pressure of the system
but in no case less than 17 bar (250 psi). Each unit shall also be given a complete
performance test. A certified performance curve shall be supplied to the Engineer for
approval.

CONTROLLER: All controllers shall be completely tested before shipment from the factory.
Full test results and test data shall be issue to the Engineer for approval.

310.022 SYSTEM PERFORMANCE TEST:

A system performance (field acceptance) test shall be conducted upon completion of the fire
pump installation. The test shall be conducted as recommended in NFPA 20 in the presence
of the Engineer and the local authority having jurisdiction. A system (field) performance
characteristic curve shall be produced and compared for verification to the factory
performance curve.

310.040 FLOW SWITCH:

Type UL listed.
Application: Install a flow switch in the common discharge manifold and wire into the
control panel.

310.055 CLEAN AGENT FIRE SUPPRESSION SYSTEM:

Type: A Clean agent fire suppression system (Ref:FSCP-CA).


Application: Main LV rooms and Main GSM Room, MMP and as indicated in the
drawings. In all areas where clean agent extinguishing systems are specified, the
system shall be designed and installed to protect the ceiling and floor voids also.
Manufacturer and reference: As defined in the manufacturers and suppliers list, or
approved equivalent.

System Requirements

The Clean Agent Extinguishing System shall be installed by the specialist Contractor in
accordance with NFPA2001 and approvals of the local authority having jurisdiction. The
installation shall be carried out in a well coordinated manner approved by the Engineer. A

5148212/D3028/Rev 0 S60/22 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

dedicated pressure relief and smoke clearance ventilation system shall be installed as part of
this installation and the Contractor shall coordinate all works with the Building Services
Contractor. The extract fan duties are indicative only and the specialist contractor shall
design and install the extract ventilation in accordance with fire extinguishing system used
and to the requirements and regulations of the local authority having jurisdiction. The
ventilation system shall be provided to facilitate extract of the room after operation of the
clean agent system. The ventilation system shall operate in accordance with specification
section W60.

Scope

Contractor shall install independent clean agent extinguishing system with automatic
detection and control for each area mentioned in the specification and drawings. The
cylinders with manifold shall be housed in an adjacent mechanical plantroom where possible
or within the respective rooms being protected. This is on the basis the latter does not
contravene or compromise the requirements and regulations of the relevant statutory
authority, i.e. ADDC (E), Etisalat/du etc. The work shall be carried out by a specialist
Contractor and shall include all design, engineering, labour, materials, equipment and
services necessary and required, to complete and test the suppression system including
approval of shop drawings from the local authority having jurisdiction.

Acceptable Clean Agents:

INERGEN
Argonite
NOVEC 1230
Or approved equivalent that complies with the requirements and regulations of the
local authority having jurisdiction.

Type: A - Inergen System

System Description and Operation

The system described in this specification is generally based on INERGEN. However,


subject to specific technical differences with alternative agents the requirements below shall
apply to the alternative.

The system shall be an INERGEN total flooding gaseous, clean agent, fire
suppression system designed to provide a uniform concentration within the protected
area.
The amount of INERGEN to be provided shall be the amount required to obtain a
uniform (minimum) concentration as required by the Design Manual for ten (10)
minutes. Take into consideration such factors as un-

additional dampers), and any other feature of the facility that could affect
concentration. The design concentration shall be 51% by volume at 70°F.
Coincidence Zone Smoke Detection the INERGEN system shall be automatically
actuated by cross-zoned detection circuits. Smoke detectors shall be ionization
detectors and photoelectric with compatibility listings for use with the control unit.
Smoke detectors shall be installed to meet BS.6266. The detectors shall be alternated
throughout the protected area with the system requiring two (2) detectors in alarm prior
to automatic INERGEN release.
The system shall be complete in all aspects. It shall include all mechanical and
electrical installation, detection and control equipment, agent storage containers
(including standby), INERGEN discharge nozzles, pipe and fittings, manual release
and abort station, audible and visual alarm devices, auxiliary devices and control,
shutdowns, caution / advisory signs, functional checkout and testing and all other
components necessary for a functional INERGEN clean agent fire suppression
system.

5148212/D3028/Rev 0 S60/23 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Auxiliary components as below shall be included.

1) Double action manual releasing stations shall be provided at each exit of the protected
area and shall, when activated, immediately release the INERGEN agent and cause
all audible/visual alarms to activate. In addition, activation of the manual releasing
stations shall cause immediate shutdown of air and power circuits.

2) Abort stations shall be provided at each exit of the protected area and shall, when
operated, interrupt the discharge of INERGEN agent and emergency power-off
functions. The abort stations shall be momentary devices (dead-man) requiring
constant pressure to maintain contact closure. Note: Manual Releasing Station
activation shall override any abort station. Abort station operation shall be per IRI and
FM guidelines.

3) Graphic annunciator (optional) shall be provided at the control panel location. The
graphic annunciator shall be provided by the equipment manufacturer in an approved
NEMA enclosure with keyed face plate. The graphic annunciator shall display the
entire INERGEN protected area and shall indicate each smoke detector and its
proximity. Smoke detectors, when activated, will individually annunciate at the graphic
annunciator as follows:

Ceiling Detector : Red LED


Subfloor Detector : Amber LED

Automatic Operation of each protected area shall be as follows:

1) Actuation of the first zone within the system shall:

a)
b) Energise an alarm bell and visual indicator to evacuate the protected area.
c) Generate one set of auxiliary contacts which can perform system functions such as:
i. Operate door Holder / closure on access doors
ii. Transmit a signal to a fire alarm system.
iii. Shutdown HVAC equipment

2) Actuation of the 2nd Zone within the system shall:

a) -
b) Energise an alarm horn/strobe device.
c) Shutdown the HVAC System and / or close dampers in supply and return ducts,
release door holders etc.,
d) Start Time - delay sequence (adjustable 0-60 sec)

3) After completion of the time-delay sequence, the INERGEN System shall discharge and
the following shall occur.

a) Illuminate an Extinguishant discharge lamp on the Control Panel.


b) Energise a Visual indicator outside the hazard area in which the discharge
occurred.

4) The control panel will provide voltage free contacts to allow the following signals to be
repeated to the Main Fire Alarm Panel and the BMS system:

a) Common fire
b) Common fault
c) INERGEN discharged.

5148212/D3028/Rev 0 S60/24 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

System Material and Equipment Requirements

The INERGEN System materials and equipment shall be standard products of latest design
and suitable to perform the functions intended.

Provide minimum two (2) inspections during the first year of service. Inspection shall be
made at maximum 6 months intervals commencing when the system is first placed in to
normal service.

The main contractor shall be responsible for sealing and securing the protected spaces
against agent loss and / or leakage during the 10 min

The System shall be capable of being actuated by manual discharge devices located at each
hazard exit. The manual discharge station shall be of the electrical actuation type and shall
be supervised at the main control panel.

All electrical enclosures, raceways and conduits shall be employed in accordance with
applicable codes and intended use and contain only those electrical circuits associated with
the fire detection and control system and shall not contain any circuit that is unrelated to the
system.

Unless specifically provided otherwise in each case, all conductors shall be enclosed in steel
conduit, rigid or thin wall as conditions dictate.

Any conduit or raceway exposed to weather or other similar conditions shall be properly
sealed and installed to prevent damage. Provisions for draining and/or drying shall be
employed.

NEMA rating and/or electrically hazardous classifications shall be observed and any
equipment or materials installed must meet or exceed the requirements of service.

Any wiring shall be of the proper size to conduct the circuit current but shall not be smaller
than #18 AWG unless otherwise specified for a given purpose. Wire that has scrapes, nicks,
gouges or crushed insulation shall not be used. The use of aluminium wire is strictly
prohibited.

Splicing of circuits shall be kept to a minimum and are only to be found in an electrical device
suited for the purpose.

Wire spliced together shall have the same colour insulation.

Wire splices shall be made with appropriate devices suited for the purpose.

All wire terminations shall be made with crimp terminals unless the device at the termination
is designed for bare wire terminations.

All electrical circuits shall be numerically tagged with suitable devices at the terminating point
and/or splice. All circuit numbers shall correspond with the installation drawings.

The use of coloured wires is encouraged but not required unless dictated by state or local
authorities.

White coloured wire shall be used exclusively for the identification of the neutral conductor of
an alternating current circuit.

Green coloured wire shall be used exclusively for the identification of the earth ground
conductor of an AC or DC circuit.

5148212/D3028/Rev 0 S60/25 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

All control systems shall be UL Listed or FM approved and is utilized with listed or approved
compatible operating devices and shall be capable of the following features:

1. Ground fault indication


2. Supervised detection circuit(s)
3. Supervised alarm circuit(s)
4. Supervised release circuit(s)
5. Supervised manual pull circuit (if applicable)
6. Supervised primary power circuit
7. Alarm overrides trouble logic
8. Battery standby
9. Front panel indicating lamps (LEDs)
10. Key lock steel enclosure
11. Programmable time delay
12. Programmable detection logic
13. Prioritized trouble logic
14. Microprocessor based logic
15. History buffer

System Components

INERGEN Storage Cylinders

Cylinder assemblies shall be of steel construction with a standard paint finish. Each cylinder
shall be equipped with a pressure seat-
exceeds 40 cylinders, a second pilot valve shall be provided and used for cylinder activation.
Each valve shall be constructed of forged brass and shall attach to the cylinder providing a
leak tight seal. Each valve shall also include a safety pressure relief device, which provides
relief at 270 bar per CGA test methods. Gas shall be stored at 200 bar.

Filling of the cylinder assembly shall be by an authorized INERGEN systems distributor in


conjunction with a factory authorized INERGEN agent filling station. Initial filling and

and shall not require replacement components for normal service. Refilling shall be
available within 24 hours.

Cylinder Bracket

Each cylinder assembly shall be furnished with a hexagon shaped bracket that allows the
cylinder to be secured into position using fixing links. This facilitates the ease of installation
and removal of the cylinders.

Cylinder brackets shall be approved for use with the INEGEN system.

Valve Actuators

Electric valve actuators shall be of brass construction and stackable design with swivel
connections to allow removal of actuators for maintenance or testing.

Operation of actuators shall not require replacement of components. NO ELECTRO-


EXPLOSIVE DEVICES may be used to actuate the valve assembly.

Electric actuators shall be the magnetic latch, continuous duty type for 24 VDC operation.

5148212/D3028/Rev 0 S60/26 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Actuation devices shall be approved for use with the INEGEN system.

Discharge Hose/Check Valve

When manifolding, all cylinder assemblies shall include a flexible discharge hose and check
valve for connection to the manifold inlet.

All hose/check valves shall be approved for use with the INERGEN valve.

Discharge Nozzles

Discharge nozzles shall be of two-piece construction and sized to provide flow rates in
accordance with system design flow calculations.

A nozzle inlet orifice plate shall be included. The orifice size shall be determined by a
computerized flow calculation program.

Orifice(s) shall be machined in the nozzle body to provide a horizontal discharge pattern
based upon the approved coverage arrangements.

Nozzles shall be stamped marked with the orifice code / size. The nozzles shall be threaded
directly to the discharge piping without the use of special adapters.

Orifice Union/Nipple Assemblies (High Pressure Systems Only)

An orifice unit shall be included in the manifold to reduce pressure in the downstream pipe
network.

Orifice unit assemblies shall be rated at 2000 lb. Class minimum

Orifice unit assemblies shall be approved for use with the INERGEN system.

Orifice union/nipple assemblies shall be permanently marked with the manufacturer's orifice
code. The orifice union/nipple shall be threaded directly to the manifold piping without the
use of special adapters.

Inergen Entrance Warning Signs

INERGEN entrance warning signs shall be provided and displayed at each entrance to the
protected area.

Inergen Manual Release Warning Signs

INERGEN manual release warning signs shall be provided and displayed next to each
extinguishant release unit.

Directional Valves

Where two or more hazard enclosures are to be protected from a single bank of cylinders,
directional valves shall be used to divert the gas from the manifold to the appropriate area.
Directional valves shall be used in conjunction with nitrogen pilot cylinders with one being
used per area protected.

Nitrogen pilot cylinder(s) shall be actuated, either electrically, pneumatically and/or manually
- the nitrogen being piped to pneumatically operate the appropriate directional valve and the
required number of cylinder valves. Pilot check valves shall be incorporated into the nitrogen
actuation line to prevent unwanted cylinders from discharging into the given risk. In order to
prevent inadvertent discharges of the remaining cylinders due to minor leakage past any

5148212/D3028/Rev 0 S60/27 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

check valves, bleed/vent valves shall be fitted in the pilot line upstream of these check
valves.

Pilot cylinder valves are to have integral pressure gauge, fill connection, solenoid, low
pressure switch and manual release lever.

Pressure Gauge

Each cylinder shall be fitted with a dial faced type pressure gauge, with a range from 0 to
250 bar.

High Pressure Manifolds

Each of the cylinders shall be interconnected with a galvanized steel manifold. The manifold
shall be supplied by the main system equipment manufacturer and tested at works by the
manufacturer to a pressure of at least 320 bar. Standard sections of manifold shall be
interconnected by high pressure fittings with ISO 228 threaded pipe connections, with a ring
seal joint. High pressure fittings (90 Deg elbows and tees) shall be brass construction with
ISO 228 left or right hand threaded connections. Manifold interconnecting pipes) shall be
brass construction with ISO 228 left or right hand threaded connections.

Manifold interconnecting pipes and fittings should be supplied by the main equipment
manufacturer as part of the ISO approved system.

Each branch connection from the manifold to a vessel shall be fitted with a non-return
assembly. The main NRV body is to be manufactured from CZ121 brass. The NRV is to be a
piston type with neoprene seal and rated for a test pressure of 320 bar.

The Specialist Subcontractor shall be responsible for ensuring that there is adequate space
for installing and maintaining the Clean Agent Extinguishant Storage Cylinder banks.

Piping

requirements, NFPA 2001 approved piping standards and guidelines for Clean Agent
extinguishant used. All distribution piping shall be installed by qualified individuals using
good, accepted practices and quality workmanship procedures. All piping shall be adequately
supported and anchored at all directional changes and nozzles locations.

System piping shall be of non-combustible materials having physical and chemical


characteristics such that its integrity under stress can be predicted with reliability.

As a minimum, piping materials shall be black steel pipe conforming to ASTM A-53A
ERW or ASTM A-106A seamless.

Under no conditions shall ordinary cast iron pipe, steel pipe conforming to ASTM A-
120 or ASTM A-53/A-120 be used.

Piping joints shall be suitable for the design conditions and shall be selected with
consideration of joint tightness and mechanical strength.

As a minimum, fittings beyond the orifice union/nipple shall be black, 300 lb. class
fittings conforming to ANSI B-16.3. Ordinary cast iron fittings shall not be used.
Distribution piping downstream of the orifice union must be a minimum of Schedule
40.

The system manifold up to the orifice union/nipple must be constructed of Schedule 80


piping and 2000 lb. or 3000 lb. forged steel fittings.

5148212/D3028/Rev 0 S60/28 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

All piping shall comply with NFPA 2001.

Piping shall be installed in accordance with good commercial practice to the


appropriate codes, securely supported with UL Listed hangers and arranged with
close attention to the design layout since deviations may alter the design flow
performance as calculated.

Piping shall be bracketed within 12" (300 mm) of all discharge nozzles.

All piping shall be reamed, blown clear and swabbed with appropriate solvent to
remove mill varnish and cutting oils before assembly.

Multi-outlet fittings other than tees shall not be permitted.

Assembly of all joints shall conform to the appropriate standards. Threaded pipe joints
shall utilize Teflon tape applied to the male threads only.

Pipe Fittings

All pipe fittings shall be suitable for the selected pipe work. The fittings shall be of forged
steel in accordance with BS 3799.

All fittings shall meet the pressure requirement of the extinguishant used in the system in
accordance with NFPA 2001.

The piping system shall be securely supported with clamps, brackets, etc., against thrust
forces, vibration and damage. Proper sleeves with sealing shall be provided wherever a pipe
crosses a wall or obstruction.

High Pressure Systems

A) For closed sections of pipe, fittings shall be as follows

Upto and including 40 mm in diameter


Forged steel, screwed, complying with BS.3799 or forged steel, butt weld, complying
with Grade WPA or Grade WPB of BS.1640 : Part 3 or forged steel, socket weld,
complying with BS.3799.

Above 40 mm
Forged steel, socket weld, complying with BS 3799.

Note: With due regard to the pressure ratings, stainless steel compression couplings in
accordance with BS.4368 may be used where tubes in accordance with BS.3605 are
to be used.

B) For open ended pipe, fittings shall be as follows.

Upto and including 20 mm in diameter


Forged steel, screwed, complying with Grade WPA or Grade WPB of BS.3799.

Above 20 mm upto and including 40 mm in diameter


Forged steel, screwed, complying with Grade WPA or Grade WPB of BS.3799.

Above 40 mm
Forged steel, screwed, complying with Grade WPA or Grade WPB of BS.3799.

5148212/D3028/Rev 0 S60/29 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Discharge Nozzles

INERGEN clean agent fire suppression system shall discharge from specially designed
Nozzles with discharge characteristics to suit the application. These shall be strategically
located to flood the entire area with uniform concentration of 51% (minimum) within the
specified time limit after initiation of actuation device.

The nozzles shall be designed to provide proper agent quantity and distribution. The
discharge nozzle shall be of Aluminium / Brass / Stainless Steel corrosion resistant metal.

Discharge nozzles shall be of two-piece construction and sized to provide flow rates in
accordance with system design flow calculations.

A nozzle inlet orifice plate shall be included. The orifice size shall be determined by a
computerized flow calculation program.

Orifice(s) shall be machined in the nozzle body to provide a horizontal discharge


pattern based upon the approved coverage arrangements.

Nozzles shall be stamped marked with the orifice code / size. The nozzles shall be
threaded directly to the discharge piping without the use of special adapters.

Smoke Detectors

Smoke Detectors shall operate on ionisation principle and shall be activated by the presence
of combustion products. Detectors shall have a nominal sensitivity to conform to the
requirements of BS 5446, part 1.

Smoke Detector shall be plug-in type unit constituting two ionisation chambers, amplifier
switching circuit and LED indication. Out of the two ionisation chambers of the detector, one
chamber shall function for fire detection and the other as a reference to stabilise the detector
for changes in environmental temperature, humidity and pressure.

The amplifier switching circuit in the detector head, shall be solid state type and shall be
suitable for operation on 24 v D.C. supply. The LED indication on the detector shall light to
indicate the initiation of alarm immediately after detection of fire. It shall be possible to
connect a remote indicating lamp to the detector.

The smoke detector shall have terminals for connecting the same in circuit without any
soldering. It shall be possible to secure the detector in the base to prevent unauthorised
tampering in the system.

Alarm Sounders

The INERGEN Alarm Sounders shall be rated for 24 V DC and shall produce a distinctive
tone sound having an output of minimum 95 db at one metre. The sounders shall be
finished in red and shall be suitable for mounting outdoor / indoor as per requirements of
local authority having jurisdiction.

Xenon Beacons

A red stand alone Xenon Beacon rated at 1J output shall be provided outside the protected
area for visual indication of immit Extinguishant discharge.

Door Release Units

The door release units shall be of solenoid operated and controlled by the fire suppression
system. It shall be of continuously operating duty to keep the door open. A manual release
switch shall be provided by the side of solenoid to enable doors to be closed without

5148212/D3028/Rev 0 S60/30 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

operating the fire alarm system. The holding force of door unit shall be 11 kg. The operating
voltage shall be 24 V DC.

Control Panel

A control panel shall be housed in sheet steel enclosure, and located at a suitable location
near the entrance to each of the protected areas. The control panel shall include switch input
for various detectors, pressure switches etc., relay outputs with either monitored contacts or
volt free contact or a combination. The panels shall be suitable for specified main voltages
of 50Hz power supply. The operating voltage of the panel shall be 24V DC which shall be
backed by a set of maintenance free batteries during a power failure. A Battery charger shall
be provided to keep the batteries charged all the time from the mains power supply. The
standby battery power shall be suitable to operate the panel for 24 Hours in quiescent mode
and for half hour in alarm mode to conform to the requirement of BS 5839 Part 1.

The following shall be provided as part of the panel.

Shielded manual release push button to override automatic / manual key lock off
condition.
Status indicator lights for visual indication of

Lamp Test Facility


Monitoring of wiring for open and short circuit condition with visual and audible
indication of system fault.
Main Supply healthy indication.
Alarm Silence push button.
Solid state field programmable time delay 0-60 seconds.

Abort Switch

A system hold-off button, non-latching type shall be provided which while depressed shall
interrupt the discharge sequence. Upon release of this unit, the discharge will proceed.

Wiring

Mineral Insulated Copper Covered Cables PVC Sheathed (MICC PVC)

All MICC Cables shall be of an approved type and shall be complete with PVC Sheath. The
end of the mineral insulated copper cables shall be protected from moisture by suitable seal
and insulation shall be thoroughly dry before sealing material is applied. Such sealing
material and any material used to insulate the conductors, shall have insulation and moisture
proofing properties, shall retain these properties throughout the range of temperature to
which the cable is subjected to in service. All terminations shall comply with BS 4081 / Part 1
or any additional amendments to this specification.

It shall be fastened to wall / cable trays at intervals recommended by the manufacturer with
the correct saddles, in accordance with table B2M of the IEE Regulations.

High temperature seals shall be used throughout and for temperature up to 185ºC shall
comprise of high temperature compound as recommended by Cable Manufacturer with fibre
glass disc and P.T.F.E. sleeving. Seals for temperature above 185ºC shall comprise of a
fused powder glass compound with porcelain bead sleeving.

Standard brass ring type compression glands shall be used at all terminations except for
flame proof installations and flush mounted accessories. The standard gland terminate in
factory made metal box or enclosure suitably tapped to accept the gland thread or
alternatively where a tapped hole is not practical, a ring type bush gland shall be used
secured with suitable brass bush and compression washer.

5148212/D3028/Rev 0 S60/31 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Standard glands for tapped entry units shall have a minimum of five full thread engagements.

Flameproof gland shall be used on fireproof installations, suitable for use with certified
enclosures in atmospheres containing groups 2 and 3 as defined in BS 229 in accordance

All terminations and bends shall be made with correct tool as recommended by the Cable
Manufacturer.

Earthing

To minimise the risk of electrostatic discharge, all pipe work shall be earthed. For this
purpose, PVC Cu yellow green cable of min 4 mm cross section shall be used.

Warning Signs

The Warning signs shall be as per local authority having jurisdiction and NFPA 2001
guidelines and be prominently displayed at and near the entrance of the protected area as
necessary.

System Inspection and Checkout

After the installation has been completed, the entire system shall be checked out, inspected
and functionally tested by qualified, trained personnel, in accordance with
recommended procedures and NFPA Standards.

All containers and distribution piping shall be checked for proper mounting and
installations.
All electrical wiring shall be tested for proper connection, continuity resistance to
ground.
The complete system shall be functionally tested in the presence of the owner or his
representative and all functions, including system and equipment interlocks, must be
operational at least five (5) days prior to the final acceptance tests.

- Each detector
procedures and test values recorded.
- All system and equipment interlocks, such as door release devices and audible and
visual devices, equipment shut downs, local and remote alarms, etc., shall function
as required and designed.

Training Requirements

Prior to final acceptance, the installing contractor shall provide operational training to the

Manual and Abort Functions, Fault Procedures, Auxiliary Functions and Emergency
Procedures.

Acceptance Tests

-
cedures to be
used to test the INERGEN system(s). The tests shall demonstrate that the operational
and installation requirements of this specification have been met. All tests shall be
conducted in the presence of the owner and shall not be conducted until the Test Plan
has been approved.
The tests shall demonstrate that the entire control system functions as designed and
intended. All circuits shall be tested for automatic actuation, Manual actuation, HVAC
and power shut downs, audible and visual alarm devices, manual over ride of abort

5148212/D3028/Rev 0 S60/32 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

functions and agent container pressure supervision. Supervision of all panel circuits,
including AC and battery power supplies, shall be tested and qualified.
A Room pressurisation test shall be conducted, in each protected space to determine
the presence of openings which would affect the INERGEN system concentration
levels. All testing shall be in accordance with NFPA 2001.
If room pressurisation testing indicates that openings exists which will result in and / or
loss of the INERGEN extinguishing agent, the Main Contractor shall be responsible for
adequately sealing all protected space(s) against agent loss or leakage. The
Specialist Subcontractor and the Main Contractor jointly shall inspect all work to
ascertain that the protected space(s) have been adequately and properly sealed. If
the room pressurisation test is not successful in accordance with these the Specialist
Subcontractor shall then direct the Main Contractor to determine and correct the cause
of the test failure. The Main Contractor shall conduct additional room pressurisation
tests, at no additional cost to the owner until a successful test is obtained. Copies of
successful test results shall be submitted to the owner for record.
Upon acceptance by the owner, the completed INERGEN system(s) shall be placed in
normal service.
The Specialist Subcontractor shall, where specified, allow and carry out Discharge
Test in line with the NFPA-2001.

Documentation for Clean Agent Extinguishing System

The documentation for the Clean Agent Extinguishing System shall include the following:

Technical details relating to the safety and use of Clean Agency Extinguishing
Systems
Component data sheets on each item in the system
Spare parts list
System sequence of operations

Guaranteed Total Recharge cost by zone during the warranty period.

Operation and Maintenance

Prior to final acceptance, the specialist subcontractor shall provide complete Operation and
Maintenance Instruction Manuals, four (4) copies to the owner. All aspects of system
operation and maintenance shall be detailed, including piping isometrics, wiring diagrams of
all circuits, a written description of the system design and sequence of operation, drawings(s)
illustrating control logic and equipment used in the system. Checklists and procedures for
emergency situations, trouble shooting techniques, maintenance operations and procedures
shall be included in the manual.

Spare Parts

The Specialist Subcontractor shall allow the spare parts according to the list of spares
recommended for 2 years trouble - free operating as per Contract, and hand over before
start of Commissioning on Site. The contractor is to include in tender option quotation for a
comprehensive service contract of the complete extinguishing system, which shall provide a
free gaseous fire suppression system refill of all discharged cylinders, under their cylinder
exchange system. The list of spares shall be submitted along with the tender.

Type: B Novec 1230 Clean Agent Fire Suppression System

System Description and Operation


The system shall be a new Total Flood Fire Suppression System using Novec 1230 fire
protection fluid designed to provide a uniform concentration within the protected area.
The system shall provide a Novec 1230 minimum design concentration of 4.2% by
volume for Class A hazards and a minimum of 5.85% by volume for Class B hazards in

5148212/D3028/Rev 0 S60/33 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

all areas and/or protected spaces, at the minimum anticipated temperature within the
protected area. System design shall not exceed 10% for normally occupied spaces,
adjusted for maximum space temperature anticipated, with provisions for room
evacuation before agent release.
The system shall be complete in all ways. It shall include a mechanical and electrical
installation, all detection and control equipment, agent storage containers, Novec 1230
agent, discharge nozzles, pipe and fittings, manual release and abort stations, audible
and visual alarm devices, auxiliary devices and controls, shutdowns, alarm interface,
advisory signs, functional checkout and testing, training and any other operations
necessary for a functional UL listed Clean Agent suppression system.
Provide two (2) inspections during the first year of service: Inspections shall be made at
6-month intervals commencing when the system is first placed into normal service.
The general contractor shall be responsible for sealing and securing the protected
spaces against agent loss and/or leakage during the 10-minute hold period.
F The system(s) shall be actuated by a combination of ionization and photoelectric
detectors installed for maximum area coverage of 250 sq. ft. (23.2 m) per detector, in
both the room, under floor and above ceiling protected spaces. If the airflow is one air
change per minute, photoelectric detectors only shall be installed for maximum area
coverage of 125 sq. ft. (11.6 m) per detector. (Ref. NFPA No. 72.)
Detectors shall be Cross-Zoned detection requiring two detectors to be in alarm before
release.
Automatic operation of each protected area shall be as follows:

1. Actuation of one (1) detector, within the system, shall:

a) Illuminate the ALARM lamp on the control panel face.

b) Energize an alarm bell.

c) Transfer auxiliary contacts, which can perform auxiliary system functions such as:
Operate door holder/closures on access doors; Transmit a signal to a fire alarm
system; Shutdown HVAC equipment.

d) Light an individual lamp on an optional annunciator.

2. Actuation of a 2nd detector, within the system, shall:

a) Illuminate the PRE-

b) Energize a pre-discharge horn/strobe device.

c) Shut down the HVAC system and/or close dampers.

d) Start time-delay sequence (not to exceed 60 seconds).

e) System abort sequence is enabled at this time.

f) Light an individual lamp on an optional annunciator.

3. After completion of the time-delay sequence, the SAPPHIRE Clean Agent system
shall discharge and the following shall occur:

a) Illuminate a SYSTEM FIRED lamp on the control panel face.

b) Shutdown of all power to high-voltage equipment.

c) Energize a visual indicator(s) outside the hazard in which the discharge occurred.

d) Energize a System Fired audible device. (Optional)

5148212/D3028/Rev 0 S60/34 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

4. The system shall be capable of being actuated by manual discharge devices located
at each hazard exit. Operation of a manual device shall duplicate the sequence
description above except that the time delay and abort functions shall be bypassed.
The manual discharge station shall be of the electrical actuation type and shall be
supervised at the main control panel.

System Material and Equipment Requirements

The Novec 1230 Clean Agent system materials and equipment shall be standard products of
the latest design and suitable to perform all functions intended. When one or more pieces of
equipment must perform the same function(s), they shall be duplicates produced by one
manufacturer.

All devices and equipment shall be U.L. Listed and/or FM approved.

Each system shall have its own supply of clean agent.

The system design can be modular, central storage, or a combination of both design criteria.

Systems shall be designed in accordance with the manufacturers guidelines.

Each supply shall be located within the hazard area, or as near as possible, to reduce the
amount of pipe and fittings required to install the system.

System Components

NOVEC 1230 Storage Cylinders


The clean agent shall be stored in Clean Agent storage tanks. Tanks shall be super-pressur-
ized with dry nitrogen to an operating pressure of 360 psi @ 70 °F (24.8 bar at 21 °C). Tanks
shall be of high-strength low alloy steel construction and conforming to NFPA 2001.

Each tank shall have a pressure gauge and low pressure switch (optional) to provide visual
and electrical supervision of the container pressure. The low-pressure switch shall be wired
to the control panel to provide audible and visual Trouble alarms in the event the container
pressure drops below 290 psi (20 bar). The pressure gauge shall be colour coded to provide
an easy, visual indication of container pressure. Tanks shall have a pressure relief provision
that automatically operates before the internal nominal pressure exceeds 730 psi (50 bar).

Cylinder Bracket
Each cylinder assembly shall be furnished with a hexagon shaped bracket that allows the
cylinder to be secured into position using fixing links. This facilitates the ease of installation
and removal of the cylinders.

Cylinder brackets shall be approved for use with the NOVEC 1230 clean agent system.

Valve Actuators
Tanks (master) shall be actuated by either a resettable electric actuator or by pneumatic
means from a nitrogen cartridge located in the releasing device. Explosive devices shall not
be permitted.

Discharge Nozzles
Engineered discharge nozzles shall be provided within the manufacturers guidelines to
distribute the Novec 1230 agent throughout the protected spaces. The nozzles shall be
designed to provide proper agent quantity and distribution. Nozzles shall be available in 1/2
in. through 2 in. pipe sizes. Each size shall be available in 180° and 360° distribution
patterns.

5148212/D3028/Rev 0 S60/35 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Piping
Distribution piping and fittings shall be installed in accordance with the manufacturers
requirements, NFPA 2001, and approved piping standards and guidelines. All distribution
piping shall be installed by qualified individuals using accepted practices and quality
procedures. All piping shall be adequately supported and anchored at all directional changes
and nozzle locations.

a) All piping shall be reamed, blown clear and swabbed with suitable solvents to remove
burrs, mill varnish and cutting oils before assembly.
b) All pipe threads shall be sealed with Teflon tape pipe sealant applied to the male thread
only.

Agent
The fire suppression agent shall be Novec 1230 Fire Protection Fluid manufactured by 3M
Company, St. Paul, MN or their approved supplier.

Agent shall not contain any Hydrofluorocarbons (HFC).

Control Panel
The control panel shall be an AUTOPULSE releasing panel.

The detection control system and its components shall be UL listed and FM approved for use
as a local fire alarm system with releasing device service.

The control system shall perform all functions necessary to operate the system detection,
actuation, and auxiliary functions.

The control system shall include battery standby power to support 24 hours in standby and 5
minutes in alarm.

The control system shall be microprocessor based, utilizing a distributed processing concept.
A single microprocessor failure shall not impact operation of additional modules in the
system.

The control system shall be capable of supporting Cross Zoned Detection.

The control system shall supply integrated 2.0 amp (minimum) power supply circuitry.

Each control system shall contain four (4) initiating circuits:

a) Each circuit shall be capable of Class A (Style D) or Class B (Style A) operation.

b) Each circuit shall be capable of operating up to fifteen (15) approved detectors or


thirty (30) detectors per system.

c) Each circuit shall be capable of monitoring contact devices configured for manual
release, manual alarm, system abort, trouble input or auxiliary (non-fire) input.

Each control system shall contain release circuits for activation of a fire suppression
system(s):

a) Each circuit shall be capable of Class B (Style Y) operation.

b) Each circuit shall be rated for a minimum of 1.5 amp @ 24 VDC.

Each control system shall contain two (2) indicating appliance circuits for annunciation:

a) Each circuit shall be capable of Class A (Style B) or Class B (Style Y) operation.

5148212/D3028/Rev 0 S60/36 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

b) Each circuit shall be rated for a minimum of 1.5 amp @ 24 VDC.

Each control system shall provide an auxiliary power supply rated for 2 amps @ 24 VDC.

Each control system shall provide two (2) SPST relays: one for common alarm and one for
common trouble. Four (4) additional programmable relays can be added to each control
system by adding a relay module.

Detectors
The detectors shall be spaced and installed in accordance with the manufacturers
specifications and the guidelines of NFPA 72.

The ionization detector shall be an Ansul model or equivalent.

The photoelectric detector shall be an Ansul model or equivalent.

Manual Release (Electric)


The electric manual release shall be a dual action device which provides a means of
manually discharging the suppression system when used in conjunction with the detection
system.

The manual release or manual pull station shall be a dual action device requiring two distinct
operations to initiate a system actuation.

Manual actuation shall bypass the time delay and abort functions and shall cause all release
and shutdown devices to operate in the same manner as if the system had operated
automatically.

Manual release shall be located at each exit from the protected hazard.

Abort Station
The optional abort station shall be the Dead Man type and shall be located next to each
manual release.

The abort station shall be supervised and shall indicate a trouble condition at the control
panel, if depressed, and no alarm condition exists.

Locking or Keyed abort stations shall not be permitted.

Audible and Visual Alarms


Alarm audible and visual signal devices shall operate from the control panel and shall consist
of alarm bell, alarm horn, and horn strobe devices

A strobe device shall be placed outside, and above, each exit door from the protected space.
Provide an advisory sign at each light location.

Caution and Advisory Signs


Signs shall be provided to comply with NFPA 2001 and the recommendations of the
equipment provider.

1. Entrance sign: (1) required at each entrance to a protected space.

2. Manual discharge sign: (1) required at each manual release station.

3. Flashing light sign: (1) required at each flashing light over each exit from a
protected space.

5148212/D3028/Rev 0 S60/37 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

System and Control Wiring


All system wiring shall be furnished and installed by the contractor.

All wiring shall be installed in electrical metallic tubing (EMT), or conduit, and must be
installed and kept separate from all other building wiring.

All system components shall be securely supported independent of the wiring. Runs of
conduit and wiring shall be straight, neatly arranged, properly supported, and installed
parallel and perpendicular to walls and partitions.

The sizes of the conductors shall be those specified by the manufacturer. Color-coded wire
shall be used. All wires shall be tagged at all junction points and shall be free from shorts,
earth connections (unless so noted on the system drawings), and crosses between
conductors. Final terminations between the control panel and the system field wiring shall be
made under the direct supervision of a factory-trained representative.

All wiring shall be installed by qualified individuals, in a neat and workmanlike manner, to
conform to the National Electrical Code, Article 725 and Article 760, except as otherwise
permitted for limited energy circuits, as described in NFPA 72. Wiring installation shall meet
all local, state, province, and/or country codes.

The complete system electrical installation and all auxiliary components shall be connected
to earth ground in accordance with the National Electrical Code.

System Inspection and Checkout


After the installation has been completed, the entire system shall be checked out, inspected

recommended procedures and NFPA Standards.

All containers and distribution piping shall be checked for proper mounting and
installations.
All electrical wiring shall be tested for proper connection, continuity resistance to ground.
The complete system shall be functionally tested in the presence of the owner or his
representative and all functions, including system and equipment interlocks, must be
operational at least five (5) days prior to the final acceptance tests .
-
procedures and test values recorded.
- All system and equipment interlocks, such as door release devices and audible and
visual devices, equipment shut downs, local and remote alarms, etc., shall function
as required and designed.

Training Requirements
Prior to final acceptance, the installing contractor shall provide operational training to the

Manual and Abort Functions, Fault Procedures, Auxiliary Functions and Emergency
Procedures.

Acceptance Tests
- operations manuals are submitted, the

test the Novec 1230 system(s). The tests shall demonstrate that the operational and
installation requirements of this specification have been met. All tests shall be
conducted in the presence of the owner and shall not be conducted until the Test Plan
has been approved.
The tests shall demonstrate that the entire control system functions as designed and
intended. All circuits shall be tested for automatic actuation, Manual actuation, HVAC
and power shut downs, audible and visual alarm devices, manual over ride of abort

5148212/D3028/Rev 0 S60/38 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

functions and agent container pressure supervision. Supervision of all panel circuits,
including AC and battery power supplies, shall be tested and qualified.
A Room pressurisation test shall be conducted, in each protected space to determine the
presence of openings which would affect the Novec 1230 system concentration levels.
All testing shall be in accordance with NFPA 2001.
If room pressurisation testing indicates that openings exists which will result in and / or
loss of the Novec 1230 extinguishing agent, the Main Contractor shall be responsible for
adequately sealing all protected space(s) against agent loss or leakage. The Specialist
Subcontractor and the Main Contractor jointly shall inspect all work to ascertain that the
protected space(s) have been adequately and properly sealed. If the room
pressurisation test is not successful in accordance with these the Specialist
Subcontractor shall then direct the Main Contractor to determine and correct the cause
of the test failure. The Main Contractor shall conduct additional room pressurisation
tests, at no additional cost to the owner until a successful test is obtained. Copies of
successful test results shall be submitted to the owner for record.
Upon acceptance by the owner, the completed Novec 1230 system(s) shall be placed in
normal service.
The Specialist Subcontractor shall, where specified, allow and carry out Discharge Test
in line with the NFPA-2001.

Documentation for Clean Agent Extinguishing System


The documentation for the Clean Agent Extinguishing System shall include the following:

Technical details relating to the safety and use of Clean Agency Extinguishing Systems
Component data sheets on each item in the system
Spare parts list
System sequence of operations

Guaranteed Total Recharge cost by zone during the warranty period.

Operation and Maintenance


Prior to final acceptance, the specialist subcontractor shall provide complete Operation and
Maintenance Instruction Manuals, four (4) copies to the owner. All aspects of system
operation and maintenance shall be detailed, including piping isometrics, wiring diagrams of
all circuits, a written description of the system design and sequence of operation, drawings(s)
illustrating control logic and equipment used in the system. Checklists and procedures for
emergency situations, trouble shooting techniques, maintenance operations and procedures
shall be included in the manual.

Spare Parts
The Specialist Subcontractor shall allow the spare parts according to the list of spares
recommended for 2 years trouble - free operating as per Contract, and hand over before
start of Commissioning on Site. The contractor is to include in tender option quotation for a
comprehensive service contract of the complete extinguishing system, which shall provide a
free gaseous fire suppression system refill of all discharged cylinders, under their cylinder
exchange system. The list of spares shall be submitted along with the tender.

310.065 WET CHEMICAL FIRE SUPPRESSION SYSTEM:

Application:
All kitchen extract canopies (except the canopies for dishwashers).
The system shall be conform to NFPA-17A, 96 and 72 listed by UL and tested to UL300.
The system shall be complete with:
Wet chemical cylinders.
Automatic and manual actuation.

5148212/D3028/Rev 0 S60/39 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Remote manual release.


Fusible links, stainless steel pipework, nozzles, valves etc.
Controller.
Interface with fire alarm system.
Solenoid operated gas shut-off valves.

310.075 DELUGE WATER SPRAY SYSTEM

Application: LPG storage tank area


The system shall conform to NFPA-54 and NFPA-58 and listed by UL. The specialist
contractor shall design the entire system for the fire protection of the LPG tank area as per
the requirements of NFPA and the local authority having jurisdiction and submit to the
Engineer for approval.

310.076 PREACTION AUTOMATIC SPRINKLER SYSTEM

Application: Lift machine rooms


The system shall conform to NFPA-13 and listed by UL. The specialist contractor shall
design the entire system for the fire protection of the lift machine rooms as per the
requirements of NFPA and the local authority having jurisdiction and submit to the Engineer
for approval.

The system shall be provided complete with automatic pre action solenoid valve, automatic
and closed sprinkler systems, piping and heat/smoke detection system, controls and
electrical wiring and all other accessories required to ensure a fully operational and reliable
system in accordance with the requirements of NFPA and the local Authority having
jurisdiction (AHJ). The preaction valve shall be UL listed and FM approved and shall have a
working pressure of 250 PSI. The spacing of the detection devices, including automatic
sprinklers used as detectors shall be in accordance with their listings and approved

The pre action system shall be provided with double interlocking devices with fail safe timer
to allow the lift sufficient time to reach its recalled floor and shall meet the requirements of
the NFPA and ASME and the local AHJ. The system shall be fully integrated with the fire
alarm system.

310.095 FOAM DELUGE SYSTEM

Type: A Foam Deluge System (Ref: FSCP-FO).


Application: Generator rooms and high hazard areas containing diesel fuel and as
indicated on the drawings.
Manufacturer and reference: As defined in the manufacturers and suppliers list. Or
approved equivalent.

System Description
The sprinkler system shall be an overhead deluge AFFF foam sprinkler system. The
system shall be designed to provide adequately proportioned foam water solution at listed
water flows past proportioning device. The system shall be installed in accordance with
NFPA 16, Standard for the Installation of Deluge Foam-Water Sprinkler and Foam-Water
Spray Systems, NFPA 11, Standard for Low Expansion Foam, NFPA 13, Standard for
Installation of Sprinkler Systems and occupancy standards pertaining to the system
installation.

Components:-

Deluge Valve
Deluge foam systems shall utilize a 90° pattern type of deluge valve. Deluge valve shall
employ a positive vent on the priming line to ensure that the deluge valve will not

5148212/D3028/Rev 0 S60/40 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

prematurely reset. Inlet and outlet connections of deluge valve can be flanged by flanged
or flanged by grooved, respectively. Deluge valve shall be UL listed and FM approved.
Deluge valve shall have a working pressure of 250 PSI. Valve trim shall be compatible and

Deluge Release System


Deluge valve shall utilize a UL listed and FM approved release system. One of the
following methods shall be incorporated in the release system:
a) Deluge systems utilizing hydraulic release of the deluge valve prime water
pressure shall employ a rate-of-rise release detector, fixed temperature release or
fire sprinkler in the release line piping. Rate-of-rise detector shall activate release
when a rise of temperature of 9°C (15°F) over the period of one minute is
experienced. Rate-of-rise release shall have a means of installing a 68°C (155°F)
fixed temperature release on the device. Rate-of-rise release shall be
automatically resetting. All devices used in the hydraulic release line shall be UL
listed and FM approved.

b) Deluge systems utilizing pneumatic pilot line release systems shall employ a rate-
of-rise release detector, fixed temperature release or fire sprinkler in the release
line piping. Rate-of-rise detector shall activate release when a rise of temperature
of 9°C (15°F) over the period of one minute is experienced. Rate-of-rise release
shall have a means of installing a 68°C (155°F) fixed temperature release on the
device. Rate-of-rise release shall be automatically resetting. All devices used in
the pneumatic release line shall be UL listed and FM approved.

c) Deluge systems utilizing electric release systems shall utilize a release control
panel and solenoid valve UL listed and FM approved for use with the Deluge
Valve. Detectors shall be compatible with release control panel.

Concentrate Controller (Proportioner)


Concentrate controller shall be a UL listed and FM approved device. Concentrate
controller shall be listed and approved with the foam concentrate to be proportioned and
the foam bladder tank. Concentrate controller shall be a brass, wafer type device. The
concentrate controller shall be listed with a nominal orifice plate size for the foam
concentrate to be proportioned.

Foam Bladder Tank


The foam bladder tank employed in low flow foam system shall be an ASME code pressure
vessel. Foam bladder tank utilized shall have been listed for use with the foam concentrate
and proportioning method utilized. Foam bladder tank bladder shall be constructed of
Buna-N rubber. Foam bladder tank shall adhere to the requirements set forth in NFPA 11,
The Standard for Low-Expansion Foam and NFPA 16, The Standard for the Installation of
Deluge Foam-Water Sprinkler Systems. Foam bladder tank shall be UL listed and FM
approved. Foam bladder tank to be a Vertical or Horizontal Foam Bladder Tank.

Concentrate Control Valve


Deluge valves that are utilized as concentrate control valves and are to be supplied by
AFFF or AR-AFFF shall utilize a 90° pattern type of deluge valve manufactured with a
corrosive resistant Halar coating. Concentrate control valve shall be externally resettable
by hydraulic means. Concentrate control valve shall employ a pressure operated relief
valve (PORV) on the priming line to release prime pressure from the top of the deluge
valve, PORV shall automatically reset and re-prime deluge valve once back pressure has
been removed. The inlet and outlet connections of deluge valve can be flanged by flanged,
flanged by grooved or threaded by threaded, respectively. Concentrate control deluge
valve shall have a working pressure of not less than 17 bar (250 PSI) unless listed for
higher pressures. Concentrate control valve shall be primed with an indicating control

line prior to the inline PORV. Concentrate control valve trim shall be compatible and

5148212/D3028/Rev 0 S60/41 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Foam Concentrate Piping


Foam concentrate piping shall be compatible with foam concentrate to be used. Foam
provider shall be consulted for acceptable materials of construction. Foam concentrate
piping shall be designed for the least equivalent feet of pipe run from bladder tank
discharge outlet to proportioning device and water supply to bladder tank. Excessive use
of elbows and tees shall be avoided. Foam concentrate piping shall be substantially
secured and restrained against movement, thrust and vibration. Foam concentrate piping
shall be protected from excessive heat and freezing temperatures. Foam concentrate
piping shall be installed with a fitting such as a grooved coupling or union to be readily
removed between proportioning assembly and concentrate control valve.

Foam Concentrate
Aqueous Film Forming Foam (AFFF) or Alcohol Resistant Aqueous Film Forming Foam
(AR-AFFF) shall be utilized. Water-soluble liquids shall be protected with Alcohol resistant
type foam concentrate. Foam concentrates shall be synthetic and stored in accordance

protection application imposed. Foam concentrates shall be listed and approved for the
discharge outlets utilized in the protection scheme. Foam concentrates shall be UL listed
and FM approved for use with Foam Proportioning System. Foam concentrates shall be
proportioned for a minimum 1% or 3% concentration in accordance with its listing.

Discharge Devices
Closed head sprinklers or nozzles that have been specifically tested and found suitable for
the discharge of low expansion synthetic foam/water solution shall be installed. Standard
sprinklers or closed head nozzles used for discharge outlets shall have been tested for
minimum densities or minimum pressures as foam/water solution discharge outlets.
Discharge devices shall be UL listed or FM approved for the application for which they are
used. Closed head sprinklers and closed head nozzles shall be UL listed or FM approved
for use with the foam and the flammable liquid being protected.

Alarm Pressure Switch


Water flow will activate an alarm by way of an alarm pressure switch. The alarm pressure
switch shall be compatible with system devices. Alarm pressure enclosure shall be UL
listed and FM approved for the application in which it is used. Alarm pressure switch shall
have the ability to be wired for Class A or Class B service. Alarm pressure switch shall be

System Overhead Piping


Overhead sprinkler piping shall be in accordance with materials deemed acceptable by
NFPA 13, The Standard for the Installation of Sprinkler Systems, NFPA 16, The Standard
for the Installation of Deluge Foam-Water Sprinkler Systems and all other applicable
building standards.

System Control Valve


Low Flow Foam system control valve shall consist of a listed indicating type of control
valve. Control valve shall be listed for use in fire protection systems. Control valve shall
be rated for system working water pressure but in no case shall be listed for pressure less
than 12bar (175 PSI).

Hangers and Supports


System piping shall be substantially supported from the building structure. The installation
of hangers and supports shall adhere to the requirements set forth in NFPA 13, The
Standard for the Installation of Sprinkler Systems. Materials used in the installation or
construction of hangers and supports shall be listed and approved for such application.
Hangers or supports not specifically listed for service shall be designed and bear the seal
of a professional engineer.

5148212/D3028/Rev 0 S60/42 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

Fire Department Connection


A system fire department connection shall be provided on the system riser in accordance
with NFPA 16, The Standard for Installation of Deluge Foam-Water Sprinkler Systems.
Fire department connection shall be of a brass body with an integral clapper assembly to
separate flow between inlets. Fire department connection shall be installed in an area
accessible for the first response unit; actual fire department location shall be installed and
located only after proper coordination with fire officials. Fire department connection shall
be UL listed and FM approved for fire protection use.

Underground Piping
Piping and fittings used for the installation of underground water mains shall be listed for
such service. Local water system requirements shall be adhered to. Compatible fittings
and connection methods shall be reviewed with the water department authority. The
standards of the AWWA and NFPA 24, The Standard for the Installation of Private Fire
Service Mains and Their Appurtenances shall be minimum installation guidelines.

Drains and Flushing Connections


System drains shall adhere to the requirements set forth in NFPA 13, The Standard for the
Installation of Sprinkler Systems. Flushing connections shall be provided where system
piping is subject to accumulation of sediments or where periodic flushing is required by the
local authority having jurisdiction. System auxiliary drains shall be installed so that the
drain valve is accessible and labelled as a sprinkler system drain. Drains shall terminate to
the exterior of the building where practical. Drains that do terminate to the exterior shall be
installed with a 45° elbow directed to a splash block or other permanent erosion limiting
material.

Riser Test Connections


A test connection shall be provided on the system riser with a downstream isolation valve
for the purpose of testing foam proportioning. System test header shall be of adequate
size for at least a mid-range flow of the proportioning system. System test header shall be
installed with a means of draining any trapped sections of discharge piping subject to
freezing.

System Supervision

the position of their normal operating condition. Others shall execute the termination of
supervisory switch wires. Supervisory switches shall be Potter Electrical Signal Company
Control Valve Supervisory Switch.

System Commissioning
Foam water sprinkler system shall be tested in accordance with NFPA 11, NFPA 13, NFPA
16 and all othe
officials and a representative of the installing contractor shall witness foam-proportioning
tests. Additional foam concentrate shall be provided for testing by the installing contractor.
The installing contractor shall provide maintenance and material safety data sheets
(MSDS) to the owner

320.000 WORKMANSHIP

320.005 GENRAL REQUIREMENTS

The entire fire protection system installation shall be a fully coordinated installation carried
out by the specialist Contractor completely in accordance with the latest NFPA11, NFPA13,
NFPA14, NFPA16, NPFA20 and NFPA2001 as well as to the satisfaction of the local
authority having jurisdiction. The installation shall also comply with relevant workmanship
clauses of section Y and shall be approved by the Engineer.

5148212/D3028/Rev 0 S60/43 of 44
The Pulse Mixed Use Project at Residential Particular Specification Part B
City Dubai South-Parcel 1&4 Section S60

320.006 OPERATION AND ATTENDANCE OF THE FIRE PROTECTION SYSTEM

The Building Services Contractor shall be responsible for deploying his trained operators to
operate and maintain the fire protection system up to the time of handing over the
installation.

320.007 RECORDS AND DOCUMENTATION

Comply with all documentation requirements of the general A Clauses. In addition for all the
fire protection systems submit Test and Inspection/approval records for all hose reels, fire
cabinets, landing valves, clean agent extinguishing systems and other such fire protection
systems deployed in the Building.

320.008 TRAINING AND INSTRUCTION TO THE OPERATOR

Conduct training for the operator's staff in a structured manner duly approved by the
Engineer.

320.010 INSTALLATION:

Install, test and commission all fire protection systems to requirements of NFPA and the local
authority having jurisdiction

320.020 FIXING:

Establish fixing details prior to ordering.


Fit nozzle retainer, hose guide and isolating valve at about 900mm above floor level where
hose reels are located at high level.

320.030 ISOLATION:

Fit isolating valve at each hose reel.

END OF SECTION

5148212/D3028/Rev 0 S60/44 of 44

Вам также может понравиться