Elevator debugging(b)
Field Description:
Live in synchronous machine debugging process and found that each parking brake at the same time,
the car has slipped car feel.
Cause of the problem: synchronous and asynchronous machine machine parking brake moments are
different. The same time is not enough torque to maintain. Because synchronous machine without
transmission damping, at the moment if you do not brake extension torque at zero speed maintenance
time, it is easy to slip.
Remedy: The F8-11 = 0.2 seconds Default parameters, the scene changed to 0.4 seconds.
4, the lift is E38 tips
Field Description: The elevator car door zone does not start at E38 fault, open the door. Check fault
information records and found that failure rate has reached the rated speed, the current is more than
the rated current.
Cause of the problem: the elevator door zone starts, the brake is not fully open, set in F1-13 encoder
detects code disc is not received within the time signal, and during this time the speed command and
drive the elevator reached the rated current has been issued values.
Remedy: Check the brake power is normal; checking brake contactor loop control of all auxiliary point
whether there is an exception. Check the encoder used correctly. Increased brake detection switch to
detect open judgment, if the detected fault is not passed immediately reported E37.