Elevator debugging(b)

In addition to commissioning manual on "Fault diagnosis and countermeasures," In addition, we add


some common troubleshooting guide.
1, 2-storey floor elevator hoistway self-learning how to accomplish?
Field Description: elevator hoistway complete self-learning, you can make high-speed operation, but
after re-power, NICE3000 appear E35, can not be run at high speed.
Problem Cause: The elevator tool only two layers, wells and self-learning is a floor leveling began. So
after making the hoistway self-learning, the resulting leveling flapper pulses F4-05 to 0. The system in
the case of each power pulse will be on the floor, efficacy and found flapper pulse number is 0 prompts
E35.
Remedy: Lift out the bottom, from the gate area, and then re-hoistway self-learning can be.
2, synchronous motor-pumped self-learning at E35
Field Description: elevator hoistway self-learning after each to two flat layers flapper, immediately
report E35 tips.
Cause of the problem: NICE3000 synchronous machine in addition to PG card (MCTC-PG-B), the
connection between the two (via CN6) is the system records the rotary encoder pulse basis, but not A
corresponds to the PGA; B corresponding to the PGB can, The installation of the way with the unit.
Hence, the control system of the hoistway self-learning process, the first two flat layers flapper arrives,
the number of pulses within the system records is 0 or a negative value if prompted immediately E35.
Remedy: Adjust PG card to CN6 wiring. A maintenance operation, see F4-03, and lift up the
recognition, the number of pulses increases; downward, the pulse number is reduced.
Appendix: E35 produces all the reasons
Before the start: 1, F4-01's current floor data with F6-01 lift the bottom data inconsistencies. 2, under
a forced deceleration invalid. 3, F0-00 = 0, the open-loop mode. If the overhaul, the next button is
always valid or opening, closing and will not enter button has been effective self-learning operation.
Operation: 1, a test switch is not in the service position. 2, if the F9-02 within the time set by running
the same direction, door zone signal is not received, the elevator will be reported E35. This parameter
setting is less than 3S, this function is invalid, not detected. If you have long floor hoistway self-
learning, should F9-02 parameter set to less than 3S, self-learning is complete, then changed to 45S.
3, floor height less than 500mm. 4, since the end of the study currently inconsistent with the top floors.
3, the synchronous machine parking brake, the elevator slip car

Field Description:

Live in synchronous machine debugging process and found that each parking brake at the same time,
the car has slipped car feel.

Cause of the problem: synchronous and asynchronous machine machine parking brake moments are
different. The same time is not enough torque to maintain. Because synchronous machine without
transmission damping, at the moment if you do not brake extension torque at zero speed maintenance
time, it is easy to slip.

Remedy: The F8-11 = 0.2 seconds Default parameters, the scene changed to 0.4 seconds.
4, the lift is E38 tips

Field Description: The elevator car door zone does not start at E38 fault, open the door. Check fault
information records and found that failure rate has reached the rated speed, the current is more than
the rated current.
Cause of the problem: the elevator door zone starts, the brake is not fully open, set in F1-13 encoder
detects code disc is not received within the time signal, and during this time the speed command and
drive the elevator reached the rated current has been issued values.
Remedy: Check the brake power is normal; checking brake contactor loop control of all auxiliary point
whether there is an exception. Check the encoder used correctly. Increased brake detection switch to
detect open judgment, if the detected fault is not passed immediately reported E37.