INSPECTION TEST PLAN

FOR 11kV SWITCHGEAR PANEL

Sr.
Test Description Enclosure No.
No.

1) (a) The data of the equipment to be tested 1

(b) Test Equipments

(c) Test Format

2) The summary of test methods 2


Enclosure - 1

(a) Data of the Equipment to be tested


1.0 ELECTRICAL SPECIFICATIONS
Vacuum Circuit Breakers
Type VK
Service Voltage 11 kV
Rated Voltage 12 kV
Rated Frequency 50 Hz.
Rated Current Feeders 630 A
Incomer 2000 A

Rated Short Time Withstand Current 25 kA


Rated Short Circuit Duration 3 sec.
Rated Short Circuit Breaking Current 25 kA
Cubicles
Type PH
Service Voltage 11 kV
Rated Voltage 12 kV
Rated Frequency 50 Hz.
Rated Current Busbars 2000 A
Rated Current Circuits - Feeders 630 A
Incomers 2000 A

Rated Insulation Level :


- Power Frequency Withstand Voltage 28 kV / 1 min.
- Impulse Withstand Voltage 75 kV
Rated Short Time Withstand Current 25 kA
Rated Short Circuit Duration 3 sec.

2.0 MATERIALS OF CONSTRUCTION FOR THE PANEL


Part Material Thickness
Frame , Front Sheet Steel 3.0 mm
Base Plate Sheet Steel 3.0 mm
Rear doors, Others Sheet Steel 3.0 mm
Shutters Fiberglass Reinforced 4.0 mm
Plastic
3.0 SURFACE COATING Process Epoxy Powder Coating
Part name Paint Shade
Cubicle Frame - RAL 7032
Compartment Doors and Covers - RAL 7032
VCB Truck - RAL 7032
All other details will be as per the relevant project drawings for the 11 kV Switchgears.
Enclosure -1
(b) Test Instruments

1) High voltage test kit 0-28 kV

2) A.C. Current Injection kit

3) D.C. current injection kit

4) Test Bench with AC / DC supply

5) Millivolt meter

6) Continuity meter

7) Ammeter and voltmeter


Enclosure-1
(c.) Test Format

ROUTINE TEST CERTIFICATE


SWITCHBOARD TESTING

SALE NOTE NO. : TYPE OF PANEL :


CLIENT’S NAME : .
LAYOUT DRAWING No. : PANEL BOARD:
RATED VOLTAGE : SERVICE VOLTAGE :
RATED CURRENT OF BUSBAR:
RATED BREAKING CAPACITY OF THE BREAKER : AT
RATED AUXILIARY SUPPLY : CLOSING COIL: . A. C. / D.C. SHUNT TRIP A.C. / D.C.
SPRING CHARGING MOTOR A.C. / D.C. OTHER A.C./D.C.

Panel Panel Serial No. Breaker Serial No. Breaker Current Rating Max. Millivolt Drop Wiring Drawing No.
No. Value at 100A DC

ROUTINE TEST: FOLLOWING ROUTINE TESTS AS IEC-62271-100/200 HAVE BEEN


CONDUCTED.

1. OPERATION TEST ON SWITCHING DEVICE :


(i) 5 closing and 5 opening operations at 110% of rated supply voltage.
(ii) 5 closing operations at 85% and 5 opening operations at 70% of rated supply voltage.
(iii) 5 close - open operations at rated supply voltage with trip circuit energized by closing of the main contacts.
(iv) 5 closing and 5 opening operations by Mechanical ON / OFF Push Buttons.
2. CHECKING OF WIRING :
All electrical wiring, relays, meters, switches, indicating lamps and controls are checked and verified as per wiring
drawing requirements.
3. MECHANICAL OPERATIONS TEST :
Insertion and withdrawal of removable parts and interlocks between removable part and fixed portion is checked for
satisfactory operation.
4. DIELECTRIC TESTS :
(i) Power Frequency H.V. Test of the main circuit is carried out at 28kV for one minute on the Panel duly assembled
(ii) Power Frequency voltage test on auxiliary and control circuit is carried out at 2kV for one minute.

REMARKS:

Tested by Date :
Engineer Incharge Date :
Enclosure - 2

Summary of Test Methods

LIST OF ROUTINE TESTS TO BE CONDUCTED ON


11 kV INDOOR VCB PANEL

Acceptance
OPERATION TEST ON CIRCUIT BREAKER (ELECTRICAL & Verifica
1. Criteria as per
MECHANICAL) : tion
IEC

Insertion and withdrawal of removable parts and interlocks


between removable parts. All operation
a) VCBs shall be drawn out to test position and then inserted back should be possible
to the service position and the interlocks as per clause 7.101 of normally.
IEC 62271-100 shall be verified.

b) i) 5 Closing and 5 opening operations at 110% of rated


supply voltage.

ii) 5 Closing operations at 85% and 5 opening operations at


70% of rated supply voltage. All operation
should be possible
iii) 5 Close - Open operations at rated supply voltage with trip normally.
circuit energized by closing of the main contacts.

iv) 5 Closing and 5 opening operations by Mechanical ON /


OFF Push Buttons

2. CHECKING OF WIRING :

All electrical wiring, relays meters, switches, indicating lamps Should operate as
and controls as per wiring drawing requirements. per schematic.

3. MECHANICAL OPERATIONS TEST :

Insertion and withdrawal of removable parts and interlocks


between removable parts. All operation
VCBs shall be drawn out to test position and then inserted back should be possible
to the service position and the interlocks as per clause 7.101 of normally.
IEC 62271-100 shall be verified.

4. DIELECTRIC TESTS (HV CIRCUIT):


Power frequency HV test of the Main circuit at basic As per IEC-62271-
Insulation Level-28kV for One minute on the panel as per 100/200 (The
below sequence. Magar value to be noted before & after. equipment is
1. 22.4 kV (i.e., 80% of 28kV for repeat test as per IEC) considered to have
was applied to top main circuit of all panels with breaker passed the Power
open and the cable side of main circuit was earthed to Frequency Voltage
check dielectric strength of open contact of vacuum withstand tests if
interrupter. The breakers inside the panels passed the there are no
test disruptive discharge
2. 22.4 kV (i.e., 80% of 28kV for repeat test as per IEC)
was applied to R-phase and Y&B phases were earthed
with breaker closed to check insulation between R phase
& main enclosure (which is at earth potential)
3. 22.4 kV (i.e., 80% of 28kV for repeat test as per IEC)
was applied to Y-phase and R&B phases were earthed
with breaker closed to check insulation between Y phase
& main enclosure (which is at earth potential)
4. 22.4 kV (i.e., 80% of 28kV for repeat test as per IEC)
was applied to B-phase and R&Y phases were earthed
with breaker closed to check insulation between B phase
& main enclosure (which is at earth potential)
Magger value before and after test.

Testing Equipment details :- HV Test kit : Range :-0-40KV


AC,Serial No. 11/05/132(A), Moon Light Electronics, 2)
Serial no.000502, model no.ACU, Allied Electrical
Industries
5. DIELECTRIC TESTS (CONTROL CIRCUIT):
Power frequency voltage test on auxiliary and control circuit As per IEC-62271-
as per below method. 100/200
1. Applied 2KV for one minute between control circuit wire
shorted together and LV compartment earth part.
6. PRIMARY CURRENT INJECTION:
Operation test on the CTs, meters etc. will be done by
primary current injection. The current source shall be
connected to the cable terminals in the panel. The
operation of meters shall be checked. All trip circuit
continuity will be checked.
Testing Equipment details: - Range:-600A, Model No.D.CU,
Serial No. 000501. Allied Electrical Industries.
6. CONTACT RESISTANCE TEST:
The VBC contact resistance value to be measured by
applying 100A current to R, Y, B phases with testing kit.
Testing Equipment details: - Model No.CRM 100B, Serial
No. 2301.02x628. Scope T&M Pvt. LTD.
7. VISUAL INSPECTION (LV COMPARTMENT):
Verify protection Relay model number As per approved
relay list and BOM,
Verify Quantities of Meter, Test plug, Main protection relay, As per Door layout
Switches, lamps. and BOM,
Verify Control Switches operation & MCB As per Door layout
and BOM,
8. VISUAL INSPECTION (HV COMPARTMENT):
Verify VCB rating As per approved
Drawings
Verify Busbar Size. As per approved
Drawings
Verify CT/VT specification. As per approved
Drawings