IIT Kharagpur NPTEL Web Course
2 | P a g e
Keywords: Characterisation, analytical methods, standards
Characterisation of coal and petroleum fractions, as well as gaseous fuels is done by some
specific test methods and apparatus. Some major characterization techniques are mentioned in
this section. Some standards, such as ASTM (American Society for Testing and Materials), BS
(British Standard), IS (Indian standard) etc. are followed to determine the properties.
matter, ash and fixed carbon content in terms of weight percentage. In this method, a specific
amount of finely powdered coal (1 or 2 g) is heated in a petri-dish for one hour at 105 to 1100C,
sample is cooled and weighed. The weight loss is the external moisture content. The coal sample
is then taken in a silica crucible and heated at 9250C for 7 min, the sample is quickly cooled to
avoid the oxidation and then weighed. The weight loss is expressed as volatile matter content.
About 1 g of powdered coal is taken in a silica dish and heated in a muffle furnace at 400 to
4500C for 30 mins, and then one hr at 725±250C. The weight of the incinerated residue is the ash
content. The fixed carbon is obtained by subtracting the weights of moisture, volatile matter and
Caking index for coal is determined by taking sample of the uniform mixtures of sand and coal
of total 25 g in different weight ratios. The samples taken in crucibles are kept inside a muffle
furnace at approximately 9250C for 7 min. Then the crucibles are removed and allowed to cool.
The lump or cake is observed to form from the mixtures. The cakes are taken out carefully and
IIT Kharagpur NPTEL Web Course
3 | P a g e
500 g weight is placed on the cakes. The percentage of loose particles comes out from the cakes
are determined separately for each cake which gives a measure of the binding property of the
coal sample. The maximum whole number ratio of sand to coal in the 25 g mixture which
produces a cake after heating that can withstand a weight of 500 g without producing 5% loose
Swelling index is one of the important properties of coal. Coal is heated under specified
condition on flame in a crucible. The swollen mass is cooled and compared with a standard chart
where profiles with numbers (which indicates swelling index) are given. The numbers are in
increasing order from 0 to 9 with a 0.5 increment. The higher the number better is the caking and
swelling characteristics.
Calorific value of coal is determined by Bomb calorimeter. It is a thick walled steel cylindrical
vessel with lid which is called Bomb. Two electrodes are inserted through the lid which are in
contact with fuse and fuel sample of known weight. An oxygen inlet valve is provided with the
lid through which high pressure oxygen gas (at about 25 to 30 atm) is supplied. Entire
arrangement is held in a calorimeter containing known weight of water and a mechanical stirrer
is provided to stir the water for uniform heating. A Beckmann thermometer is also provided to
measure the change in temperature of water due to combustion of fuel. Fig 1. shows the
schematic of the apparatus. The gross calorific value is calculated by the following formula
C. V m m T T T /m
Where, m1 and m2 are mass of water in calorimeter and water equivalent of bomb calorimeter
T1 and T2 are final and initial temperature of water sample. Tc is temperature correction for
IIT Kharagpur NPTEL Web Course
4 | P a g e
The major property of coke is its strength and hardness. Among many tests to determine
strength and hardness of coke, Micum test is important. In mecum test, 50 kg of coke samples
are taken in a metallic cylindrical drum (Micum trommel) of 1 m length and 1 m diameter, and
the drum is rotated about its horizontal axis at 25 rpm speed for 4 min. Iron angles are provided
inside the drum wall. This rotation gives a combined effect of abrasion and shatter to coke
samples. The particle size distribution after the test is determined by sieve analysis and this gives
the account of brittleness of coke during its handling and use. Micum index or M80 denotes the
method (ASTM D-86). This is the method of non-fractionating atmospheric distillation of light
cuts such as, gasoline, kerosene etc. A specific amount of liquid fuel is taken in a standard round
bottom flask with the arrangement of condenser and thermometer device. Fig 1. shows the
standard set-up , consisting of a flask, condenser, collector and thermometer. The fuel is heated
IIT Kharagpur NPTEL Web Course
5 | P a g e
by an electric heater at a specified rate and some part of vapour flows to the condenser through
the side limb of the flask. Other part of the vapour gets condensed and flows down as liquid to
the flask which acts as reflux. The condensed vapour from condenser is collected in the collector.
The volume percent distilled is plotted against corresponding temperature which provides the
Flash point and fire point of a definite petroleum cut are measured in a standard apparatus.
Different fractions may be classified based on their flash point, such as, fractions below 230C
flash point are highly inflammable, dangerous, between 23 to 660C are moderately inflammable
and above 660C are termed as safe. Gasoline lies in the first category, kerosene in the second and
higher oils, such as fuel oil and gas oils fall in the third. Abel apparatus is used for the oils
having flash point below 500C and Pensky-Martens apparatus is used for the oils having flash
point above that temperature. Both these apparata are of closed cup type. A specified amount of
oil is heated in a definite rate in a closed cup. A provision is made to remove a shutter to escape
the fuel vapor and air mixture and an external flame is introduced to test the flash. The
IIT Kharagpur NPTEL Web Course
6 | P a g e
temperature of the oil is determined by a thermometer at the time of flash. That is the flash point
of the oil. Flash point of heavy oils such as lubricating oil, crude oil or residue can be obtained
Pour point and cloud point of oil is determined by putting the oil in a specified test tube, where
thermometer is inserted. The oil is cooled at specified rate and at short interval of time the oil is
tested by tilting the test tube to see whether the oil is totally freezed. The maximum temperature
where oil does not show any flow, that temperature is recorded and the reporting of pour point is
done by adding 2.80C or 50F to that. Before that freezing temperature comes, haziness on the top
of the surface of the oil appears and that temperature is the cloud point of the oil.
Smoke point of kerosene is determined in a standard apparatus (Fig. 3) where kerosene is poured
in a specified holder (B) with wick on its top. The wick is lit and the height of its flame is so
adjusted that it gives a flame with round top, without any shoot tail. The maximum flame height
is measured by a mirror scale (C) at the back of the flame in the instrument. An exhaust (D) is
provided at the top of the apparatus. A lid with glass cover (A) is used to cover the flame from
wind.
IIT Kharagpur NPTEL Web Course
7 | P a g e
Burning quality of kerosene is determined by its char value. A standard lamp with glass chimney
is used. Definite amount of kerosene is poured in the lamp and wick is lit. The lamp is allowed to
keep lit for continuously 24 hours. The flame heights, initially and finally, are measured by the
graduation on the chimney. The char deposit on the wick is scraped and weighed. The mg of char
per kilogram of kerosene burned is expressed as char value of that kerosene. The decrease in
standard apparatus in which normally carbon dioxide, carbon monoxide, oxygen and nitrogen
gas composition in volume percentages are reported. Sometimes, hydrogen, methane and
unsaturated hydrocarbons can also be quantified in this apparatus. The apparatus consists of a
graduated burette upto 100 divisions from bottom to top, an aspirator bottle, a series of pipettes
having necessary fittings and a three way stop-cock connecting the top of the burette to the gas
stream. Each pipette contains an adsorbent for removing one gas. The adsorbents used are caustic
potash solution, freshly prepared alkaline pyrogallol solution and cuprous chloride in ammonia
solution for removal of CO2, O2 and CO respectively. Unsaturated hydrocarbons can be removed
by using bromine solution. The measured gas sample is passed to the pipettes one by one, by
opening the stopcock and raising and lowering the aspirator bottle several times for ensure
proper adsorption of gases in the respective adsorbents. The decrease in volume from the initial
volume after passage through every pipette gives the account of volume percent of the respective
gas. Fig.4 shows the typical figure of Orsat apparatus, where A is the graduated glass tube and E,
D, C and B are the pipettes containing KOH, alkaline pyrogallol, bromine solution and
IIT Kharagpur NPTEL Web Course
8 | P a g e
ammoniacal cuprous chloride solutions respectively, F is the stopcock, G is aspirator bottle, H is
rubber tube.
The gross calorific value at constant pressure of a gaseous fuel is determined by Junkers
calorimeter. The method is based on heating a particular amount of water by the heat evolved by
burning of the gaseous fuel. The calorific value is calculated by the following formula
∗ ∗ ,
.
.
Where, w= weight of hot water collected in kg, V= observed gas volume in m3, T= temperature
rise of water in 0C, Cp, water= Specific heat of water in kCal/kg.K, and K=[(Pa+Pg-Pw) in mm
Hg/760 mm Hg]×273/(273+t), where, Pa and Pg are the atmospheric and gauge pressure of gas,
IIT Kharagpur NPTEL Web Course
9 | P a g e
Reference
1. McGraw Hill Encylopedia of Science & Technology, no. 4, 9th edition, McGraw Hill,
2002.
2. Fuels and combustion, S. Sarkar, 2nd edition, Orient Longman Ltd., 1990.
Company, 1987.