Академический Документы
Профессиональный Документы
Культура Документы
1. Introduction
The hangar is made of steel elements which form the basic structural system. It covers a
span of 30 m in both directions with a total area of 900m2 and is open in the front. At
the back there is two storey partitioned spaces to be used for different functions with a
total floor area of about 300 m2.
There are the usual prevalent forces of dead, live, wind and seismic action effects to be
considered for design. But here due to the short limited height of the structure, its
weight, and orientation; seismic action is small and not governing. The governing lateral
force was found to be wind according to designed sizes and geometry of the structure.
But the remaining three actions are considered with the necessary partial safety factors
and combinations assumed to cover all possible scenarios and come up with a safe
design.
We have used steel grade Fe 430 with characteristic yield strength of 255 N/mm2 for all
members of structural steel. Concrete class C-25 and steel grade S-300 is used for the
foundation, foundation columns, and slab on ground.
The ground slab of the hanger is designed to be fully supported on the underlying soil.
Here it is considered to have no structural connection with the steel structure. Thus,
reinforced concrete is considered to be the best possible option.
The hangar is fully open on one side and therefore it needs a special structure as its
lateral force resisting system. Therefore, the lateral force resisting system consists of
the three side structural walls with cross bracings and connected with each other by
means of a diaphragm at the roof level. The bracings are released for compression
forces in the model, since are considered ineffective in compression. This is so because
these elements are long and slender and will buckle and become ineffective by small
compressive load if subjected. The roof peripherals are totally braced along with one
additional bay to create the diaphragm structure for distribution of lateral forces.
3. Structural Analysis
3.1 Loading
Dead load, all dead loads meaning structure dead load, roof sheet, wall cladding and
dead load on mezannine floor are considered for design.
Here the analysis was set to consider the self weight of the structure with the
appropriate safety factor.
Roof sheet, is 4mm thick EGA 500 fixed on purlins. And hence the loads are set to be
distributed action on the purlins.
Live load, we have considered live action effects of 2kN/m2 on the mezannine floors.
Further 0.25kN/m2 load is considered on roof for construction and maintenance.
Wind load
As stated earlier the governing lateral action effect is wind load over seismic action.
Following is the analysis for wind load.
Pitch Angle
α= tan -1 (1.5/15)
= 5.71o
The roof type is Duo pitch
Altitude > 2000m
Temperature= 20oc
Pressure calculation
External pressure
The wind pressure acting on the external surface of structure We shall be
obtained from
𝑊𝑒 = 𝑞𝑟𝑒𝑓 ∗ 𝐶𝑒 (𝑍𝑒 ) ∗ 𝐶𝑝𝑒 …………..EBCS1, 1995
Art 3.5.2
Internal pressure
The wind pressure acting on internal surface of structure Wi shall be obtained from
𝑊𝑖 = 𝑞𝑟𝑒𝑓 ∗ 𝐶𝑒 (𝑍𝑖 ) ∗ 𝐶𝑝𝑖
𝜌 = 𝑎𝑖𝑟 𝑑𝑒𝑛𝑠𝑖𝑡𝑦
The variation of air density with altitude is given in table 3.1 of EBSC 1, 1995
For our site which is at altitude of >2000m above sea level, the value of
ρ =0.94Kg/m3
𝑣𝑟𝑒𝑓 2 = 𝐶𝑑𝑖𝑟 ∗ 𝑐𝑡𝑒𝑚𝑝 ∗ 𝐶𝑎𝑙𝑡 ∗ 𝑣𝑟𝑒𝑓0
= 1 ∗ 1 ∗ 1 ∗ 22 𝑚⁄𝑠 = 22 𝑚⁄𝑠
1 2
𝑞𝑟𝑒𝑓 = ∗ 0.94 ∗ 22 𝑚⁄𝑠 = 227.48 𝑁⁄𝑚2
2
Terrain category
Addis Ababa is an urban municipality. Hence, it is a terrain category IV and the
related parameters are
KT=0.24, Zo (m) =1, Zmin (m) = 16 ……….EBSC1, 1995 Art
3.8.3
Roughness coefficient
𝑍
𝐶𝑟(𝑧) = 𝐾𝑇 ∗ ln(𝑍0) For Zmin < Z < 200m
= 0.6654
Topography coefficient Ct =1 (topographically unaffected)
The topography coefficient Ct(Z) accounts for the increase of mean wind speed
due to abrupt changes in topography, such as isolated hills, escarpments. But in
our case it is assumed that the location is topography unaffected.
Ct = 1 for ∅ < 0.05 ……..EBCS1, 1995 Art
3.8.4
Exposure coefficient
7𝐾𝑇
𝐶𝑒(𝑍𝑒) = 𝐶𝑟 2 (𝑧) ∗ 𝐶𝑡 2 (𝑧) ∗ [1 + 𝐶𝑟(𝑧)∗𝐶𝑡(𝑧)] …...EBCS1, 1995 Art 3.8.5
7∗0.24
𝐶𝑒(𝑍𝑒) = 0.66542 ∗ 12 ∗ [1 + 0.6654∗1] = 1.56
Using the area A of the zones external pressure coefficient, Cpe is calculated from the
tables as follows
Cpe= Cpe,1 , A≤ 1 m2
Positive and negative values (coefficients) are calculated by interpolation using the
pitch angle α= 5.71o
When θ= 0o
Pitch F G H I J
angle (α)
Cpe,10 Cpe,10 Cpe,10 Cpe,10 Cpe,10
5o -1.7 -1.2 -0.6 -0.3 -0.3
15o -0.9 -0.8 -0.3 -0.4 -1
Zone F G H I J
Zone F G H I
Area(m2) 11.025 20.475 252 585
Pitch Angle F G H I
Cpe,10 Cpe,10 Cpe,10 Cpe,10
5o -1.6 -1.3 -0.7 -0.5
For θ=90o
We = q ref ∗ Ce (Ze ) ∗ Cpe
= 0.355Cpe
Or
= 0.355 ∗ −0.5 = −0.1775 KN⁄m2
Net pressure
The net wind pressure across an element is the difference of the pressures on each
surface taking due account of their signs.
𝑊𝑛𝑒𝑡 = 𝑊𝑒 − 𝑊𝑖
𝐶𝐴𝑆𝐸 1 ∶ 𝑊𝑛𝑒𝑡 = 𝑊𝑒 − 𝑊𝑖 = (−0.5822 − 0.284) KN⁄m2 = −0.866 KN⁄m2
A=(e/5)*9=3.6*9=32.4m2, B=(e-A)*9=14.4*9=129.6m2,
C=(30-e)*9=12*9=108m2, D=E=30*9=270m2
External pressure coefficients (Cpe) can be found from Table A.1 - EBCS 1/95 as below
d/h = 30/9 = 3.33
Zone A B C D E
d/h Cpe, 10 Cpe, 10 Cpe, 10 Cpe, 10 Cpe, 10
<= 1 -1 -0.8 -0.5 0.8 -0.3
3.33 -1 -0.8 -0.5 0.6446 -0.3
>= 4 -1 -0.8 -0.5 0.6 -0.3
Cpi = -0.5
Cpi = -0.5
Cpi = -0.5
Cpi = 0.8
reasonable design. And hence in accordance the procedure for analysis of Euro
code, since both second order analysis and global imperfections are considered,
there is no need to check for individual members for stability. Here only
symmetric sway is considered and hence torsional effects are not considered.
h. Design
Using the analysis output and the European code, 2005 we have designed/
capacity check for the elements.
From the results of failed sections we tried to come up with better and economic
design by adjusting, reanalyzing and designing again until all members are safe
for the possible loads.
Section class: considering the worst possible condition of stress distribution, which is
full compression, all sections are class I. This is so because the provided thickness of the
elements is large enough to allow plastic moment resistance to develop creating plastic
hinges with sufficient rotational capacity and no local buckling. This in turn allows for
plastic global analysis to be carried out which results in the most efficient design.
The sections are proportions to resist the main action effects which are axial and
flexural loads. These may be in different combination as axial only for truss elements,
only tensile axial load for bracings, flexure only for some beams and combination of
flexure and axial force for purlins, columns and beam columns.
This is also visible in the euro code which considers only interactions of flexure and
axial forces and neglects shear and torsion. Here again, the maximum torsion and shear
loads are way lesser than the capacity of the sections proportioned and hence it is safe
to assume, the requirements are always satisfied and further don’t affect the capacity of
the section for the overall capacity.
Φ=0.5(1+α(λ-0.2)+ λ2)
k , y = (Afy/Ncr)0.5, Ncr=π2EI/L2=195.6kN
5.4 Columns
Capacity check for Buckling
Design loads, when flexure is predominant
Moment, Major axis 27.0kNm
Minor axis 0.0kNm
Axial load -43.61kN, compression
Calculate the buckling reduction factor
χ=1/( Φ+( Φ2- λ2)0.5)
Φ=0.5(1+α(λ-0.2)+ λ2)
k , y = (Afy/Ncr)0.5, Ncr=π2EI/L2=830kN
The adjoining members are much stiffer than that of the member under analysis. Thus,
β=1
The adjoining members are much stiffer than that of the member under analysis.
Thus, β=1
As a result the effective length is 1m.
Slenderness ratio; λ=le/i
λ = 2.14/0.0311=68.8
The limiting slenderness ratio; λp = 𝜋(𝐸/𝑓𝑦)1/2 fy=275MPa for t≤ 4mm
λp = π*(210/0.275)0.5 λp=86.8
The adjoining members are much stiffer than that of the member under analysis.
Thus, β=1
As a result the effective length is 1m.
Slenderness ratio; λ=le/i
λ = 2/0.0311=64.3
λp = π*(210/0.275)0.5 λp=86.6
The normalized slenderness ratio; λ= λ/ λp
λ= 64.3/86.8=0.74
The corresponding reduction factor from table 6.2 and fig 6.4 K=0.85
𝑁𝑠𝑑 93.65∗1000
<1 <1 0.34 < 1 ……….ok
K∗A∗fy 0.85∗1216∗275
7. Bracing Design
7.1 Wall Bracing Member
Analysis outputs and section properties:
Nsd= 63.72 KN length= 5.8m
Ixx=Iyy= 9.14*10-6 m4 section= 80*80*3mm
λ = 5.8/0.0311=184.12
The limiting slenderness ratio; λp = 𝜋(𝐸/𝑓𝑦)1/2 fy=275MPa for t≤ 4mm
λp = π*(210/0.275)0.5 λp=86.6
The normalized slenderness ratio; λ= λ/ λp
λ= 184.12/86.8=2.12
The corresponding reduction factor from table 6.2 and fig 6.4 K=0.2
𝑁𝑠𝑑 63.72∗1000
<1 <1 1.25 ≃ 1 ……….ok
K∗A∗fy 0.2∗924∗275
The adjoining members are much stiffer than that of the member under analysis. Thus,
β=1
λ= 148/86.8=1.7
The corresponding reduction factor from table 6.2 and fig 6.4 K=0.3
𝑁𝑠𝑑 93.65∗1000
<1 <1 0.933 < 1 ……….ok
K∗A∗fy 0.3∗1216∗275
8. Connections
8.1 Beam to column connections
Wall beam to column
Design in puts from the analysis; use bolt type 5.6 with a diameter 12mm such that fyb=
300MPa and fub= 500MPa
Vsd= 13.4KN
Shear capacity of a bolt Veff=0.6fyAveff/γ
Veff= 0.6*300*(𝜋 ∗ 62 )/1.1 = 18.5KN
Vsd/Veff=0.72<1……..ok
Mezzanine beam to column
Design in puts from the analysis; use bolt type 5.6 with a diameter 14mm such that fyb=
300MPa and fub= 500MPa
Vsd= 23.82KN
Shear capacity of a bolt Veff=0.6fyAveff/γ
Veff= 0.6*300*(𝜋 ∗ 72 )/1.1 = 25.2KN
Vsd/Veff=0.94<1……..ok
The ground floor is fully rested on the underlying soil and is not connected to the frame
structure at all. And hence minimum reinforcement provided is sufficient.
As,min=ρminb.d=(0.5/(300)) x 1000 x 120=200mm2. Provide φ8c/c200mm.
10. Design for base plate, foundation column and concrete footing
10.1 Base plate
For design of footings it is safe to consider envelope action effects to reduce the
probability of failure and hence,
Moment, Major axis 27.0kNm
Minor axis 15.0kNm
Axial load -149.12kN, compression
Using concrete grade C25MPa and steel grade S300,
yd =P/A +Myy c/I+Mzz c/I
10.3 Footing
Moment, Major axis 27.0kNm
Minor axis 15.0kNm
Axial load -149.12kN, compression
The existing soil condition at the design area is not given. Following this footing is
merely a proper design but carried out to make the design complete. With this in mind
say the allowable soil stress is all=250kpa,
Carrying out the design considering allowable soil stress, wide beam shear, punching
shear and developed bending stress
The footing shall be
Square 120cm x 120cm and a thickness of 25cm with φ12c/c300mm mesh at the
bottom.