General-Purpose AC Drive
Version 0.1
Dated 14th OCT, 2013
CONTENTS
1.1 Designation
MD310 X X.X X
Mark Built-in Braking Unit
MD310 series AC drive
B Yes
1.2 Nameplate
Nameplate
Manufacturer
Suzhou Inovance Technology Co.,Ltd.
Ver0.1 Page 1 of 53
1.3 General Specifications
MD310 MD310 MD310 MD310 MD310 MD310 MD310 MD310 MD310 MD310
Drive Model
T0.4B T0.7B T1.5B T2.2B T3.7B T5.5B T7.5B T11B T15B T18.5B
Frame Size 1 2 3 4 5
Rated Input Voltage Three-phase 380 to 440 VAC,-15% to 20% (323 to 528 VAC)
Drive Input
Rated Input Current(A) 1.9 3.4 5.0 5.8 10.5 14.6 20.5 26.0 35.0 38.5
Applicable [kW] 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
Motor [HP] 0.5 1 2 3 5 7.5 10 15 20 25
Output Current, [A] 1.5 2.1 3.8 5.1 9.0 13.0 17.0 25.0 32.0 37
Drive Output
Power Capacity, [kVA] 1.0 1.5 3.0 4.0 5.9 8.9 11.0 17.0 21.0 24.0
Overload Capacity☆ 120% for 1 hour & 150% for 60 Sec &180% for 2 Sec
Max. Output Frequency 300 Hz for SVC control, 600Hz for V/F control
Recommended [kW] ≥0.15 ≥0.15 ≥0.15 ≥0.25 ≥0.30 ≥0.40 ≥0.50 ≥0.80 ≥1.00 ≥1.30
Braking Resistor [Ω] ≥300 ≥300 ≥220 ≥200 ≥130 ≥90 ≥65 ≥43 ≥32 ≥25
W W
A A For models above 7.5 kW, the fan
is installed on the top of the AC
drive.
FE
FE D/
D/ FE REW
D/
FE REW LO REW
D/RE CA
MD
RU L
LO W N/ER
CA R
RU L
N/ER
MD 31
R
31 0
0
FEW/RED
B B H1
H H
D
D
Ver0.1 Page 2 of 53
CHAPTER 2 WIRING
MD310
power supply S V
T W
OP +24V
J7 COM
+24V
J5 AO1
DI1 Analog output
I V GND (No function assigned)
DI2
DI3 GND
485-
DI4 RS485
485+
DI5
FM
COM Open collector 1
(High-speed pulse output)
+10V COM Multi-function
open-collector output
AI1 DO1
Analog inputs
Open collector 2
(Frequency sources) AI2 J4 (Running state)
GND I2 V2 CME
T/C
Interface for the external keypad J1
T/B Multi-function relay output
Extension card interface J3 (Fault output)
T/A
MD310
power supply S V
T W
OP +24V
J7
COM
+24V
FWD J5 AO1
DI1 Analog output
I V GND (No function assigned)
FJOG DI2
RESET DI3 GND
Ver0.1 Page 3 of 53
Wiring Of Single-Phase 220 VAC (Keypad Control, F6-00 = 0)
MCCB
L1 (-) P(+) BR U
Single-phase 220 V
power Supply
MD310
L2 V
W
OP +24V
J7
COM
+24V
J5 AO1
DI1 Analog output
I V GND (No function assigned)
DI2
DI3 GND
485-
DI4 RS485
485+
DI5
FM
COM Open collector 1
(High-speed pulse output)
+10V COM Multi-function
open-collector output
AI1 DO1
Analog inputs
Open collector 2
(Frequency sources) AI2 J4 (Running state)
GND I2 V2 CME
T/C
Interface for the external keypad J1
T/B Multi-function relay output
Extension card interface J3 (Fault output)
T/A
MCCB
L1 (-) P(+) BR U
Single-phase 220 V
power Supply
MD310
L2 V
W
OP +24V
J7
COM
+24V
FWD J5 AO1
DI1 Analog output
I V GND (No function assigned)
FJOG DI2
RESET DI3 GND
Ver0.1 Page 4 of 53
2.2 Terminals
R, S, T Three-phase power supply input terminals Connect to the three-phase AC power supply
P(+), (-) Positive and negative terminals of DC bus Common DC bus input point
P(+), BR Connecting terminals of braking resistor Connect to a braking resistor
U, V, W Output terminals Connect to a three-phase motor.
L1, L2 Single-phase power supply input terminals Connect to the single-phase 220 VAC power supply.
P(+), (-) Positive and negative terminals of DC bus Common DC bus input point.
Ver0.1 Page 5 of 53
Terminals Of Control Circuit
Provide +10 VDC power supply externally. Usually, it provides power supply
+10V-GND +10 VDC power supply to the external potentiometer with resistance range of 1 to 5 kΩ.
Maximum output current: 10 mA
Provide +24 VDC power supply externally. Usually, it provides power supply
+24V-COM +24 VDC power supply to DI/DO terminals and external sensors.
Maximum output current: 200 mA
Connect to +24 VDC by default. When DI1 to DI5 need to be driven by the
OP Input terminal of external power supply external signal, OP needs to be connected to the external power supply and
be disconnected from +24 VDC.
AI1-GND Analog input 1 AI1 input voltage range: 0 to 10 VDC
AI2 input range: 0 to 10 VDC or 4 to 20 mA
AI2-GND Analog input 2 Impedance: 22 kΩ
DI1-COM Digital input 1
DI2-COM Digital input 2 Optical coupling isolation, compatible with dual-polarity input
Impedance: 2.4 kΩ.
DI3-COM Digital input 3 Input voltage range: 9 to 30 VDC
DI4-COM Digital input 4
Besides features of DI1 to DI4, it can be used for high-speed pulse input.
DI5-COM High-speed pulse input
Maximum input frequency: 20 kHz.
Voltage or current output, determined by jumper J5 on the control board.
AO1-GND Analog output 1 Output voltage range: 0 to 10 VDC.
Output current range: 0 to 20 mA.
Ver0.1 Page 6 of 53
CHAPTER 3 EASY SETUP
Fr equency
F0-08
[x.xHz]
F0-18
F0-17 F6-09 F6-08 [x.xSec]
Fr equency [x.xSec] [x.x% ] [x.x% ]
F6-11 [ x.xHz]:Default 0.0Hz
output
DC injection braking 2 frequency threshold
command F6-04
[x.xSec]
Time
0
ON
DI 1 For war d
OFF
ON
IGBT's Active
OFF
100%
F6-06 [ x.xSec]: F6-13 [ x%]: F6-14 [ x.xSec]:
DC injection braking 1 active time(if F6-00=0) DC injjection braking 2 level DC injection braking 2 active time
Pre-excitation active time (if F6-00=2)
DC Injection/
40%
Pr e-excitation F6-05 [ x%]: F6-12 [ x.xSec] (Default: 0.0Sec)
DC injection braking 1 level (if F6-00=0) DC injection braking 2 delay time
20%
Pre-excitation level (if F6-00=2)
0%
100%
0%
t1 t2 t3 t4 t5 t6 t8 t9
Stages
t7
Ver0.1 Page 7 of 53
Timing Diagram Description
F6-04
F6-09
F6-09
-After the delay time set in F6-12, the IGBT becomes active again -----
Ver0.1 Page 8 of 53
3.2 Step By Step Setup
Setup Flowchart
RUN!
Check motor rotation and machine travelling direction Refer to User Manual
Ver0.1 Page 9 of 53
Step 1: Get Familiar With Keypad
Overview
Indicators
LED display
Increment key
Programming key
Indicators
TUNE/TC : ON indicates torque control mode, blinking slowly indicates auto-tuning state, blinking quickly indicates fault state.
REMOTE : It indicates whether the AC drive is operated by means of keypad, terminals or communication.
OFF indicates keypad control, ON indicates terminal control, and blinking indicates communication control.
, OFF indicates the stop state, ON (green) indicates the running state, and ON (red) indicates the faulty state.
LED Display
The 5-digit LED display is able to display the frequency reference, output frequency, monitoring data and fault codes.
Ver0.1 Page 10 of 53
Keys On Keypad
Confirm Enter the menu interfaces level by level, and confirm the parameter setting.
Shift Select the displayed parameters in turn in the stop or running state, and select the digit to be
modified when modifying parameters.
Stop/Reset Stop the AC drive when it is in the running state and perform the reset operation when it is in
the faulty state. The functions of this key are restricted by F7-02.
Multifunction Perform function switchover (such as quick switchover of command source or direction)
according to the setting of F7-01.
Ver0.1 Page 11 of 53
Keypad Operation
F0
U0
AC
…
A2
A1
FP F0 27
…
PRG ENTER ENTER ENTER ENTER
F1 F0 02 2
50.00 F0 F0 F0 01 0 F0 02
U0 F0 27 2 save the value
PRG PRG PRG
AC
…
… F0 02
A2
A1
FP
…
F1 PRG
F0
F0 to FP Standard function code group Compatible with MD380 series function codes
Ver0.1 Page 12 of 53
Step 2: Set Motor Parameters
Ver0.1 Page 13 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F0-07 Frequency source 5-digit
selection - - - 0 0 N.A 00
0:X + Y
1: X – Y
2: Max. (X, Y)
3: Min. (X, Y)
F0-07
X &Y
Unit’s digit
Ver0.1 Page 14 of 53
Step 6: Select Operation Mode
DI
FWD Enable
DI DI
REV Two-wire mode 1 Two-wire mode 2 Direction
DI DI
COM COM
FWD Run
DI DI
Enable Stop
Three-wire mode 1 Three-wire mode 2 DI
DI
REV Direction
DI DI
COM COM
Ver0.1 Page 15 of 53
Step 7: Set Start Mode And Stop Mode
Ver0.1 Page 16 of 53
Step 9: Set DI And DO If Needed
DI Setting
Function Parameter Name Setting Range Unit Default Commission
code
F4-00 DI1 function selection 0: No function 1
N.A
1: Forward RUN (FWD) FWD
F4-01 DI2 function selection 2: Reverse RUN (REV) 4
3: Three-wire control N.A
FJOG
4: Forward JOG (FJOG)
F4-02 DI3 function selection 9
5: Reverse JOG (RJOG) N.A
RESET
6: Terminal UP
F4-03 DI4 function selection 7: Terminal DOWN 12
8: Coast to stop N.A Multi-reference
9: Fault reset (RESET) terminal 1
F4-04 DI5 function selection 10: RUN pause
11: External fault normally open (NO) input
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
15: Multi-reference terminal 4
16: Terminal 1 for acceleration/deceleration
time selection
17: Terminal 2 for acceleration/deceleration
time selection
18: Frequency source switchover
19: UP and DOWN setting clear (terminal,
keypad)
20: Command source switchover terminal 1
21: Acceleration/Deceleration prohibited
22: PID pause
23: PLC status reset
24: Swing pause
25: Counter input
26: Counter reset
27: Length count input
28: Length reset
29: Torque control prohibited 13
30: Pulse input (enabled only for DI5) N.A Multi-reference
31: Reserved terminal 2
32: Immediate DC injection braking
33: External fault normally closed (NC) input
34: Frequency modification forbidden
35: PID action direction reverse
36: External STOP terminal 1
37: Command source switchover terminal 2
38: PID integral pause
39: Switchover between
main frequency source X and preset
frequency
40: Switchover between auxiliary frequency
source Y and preset frequency
41: Motor selection terminal 1
42: Motor selection terminal 2
43: PID parameter switchover
44: User-defined fault 1
45: User-defined fault 2
46: Speed control/Torque control switchover
47: Emergency stop
48: External STOP terminal 2
49: Deceleration DC injection braking
50: Clear the current running time
Ver0.1 Page 17 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F4-10 DI filter time 0.000 to 1.000 s 0.010
F4-35 DI1 delay 0.0 to 3600.0
s 0.0
Ver0.1 Page 18 of 53
DO Setting
Function Parameter Name Setting Range Unit Default Commission
code
F5-00 FM terminal output 0: Pulse output (FMP)
mode N.A 0
1: Switch signal output (FMR)
F5-01 FMR function 0: No output
(open-collector output 1: AC drive running
terminal) selection 2: Fault output (stop)
3: Frequency-level detection FDT1 output
4: Frequency reached 0
N.A
5: Zero-speed running (no output at stop) No output
6: Motor overload pre-warning
7: AC drive overload pre-warning
8: Set count value reached
9: Designated count value reached
F5-02 Relay function
(T/A-T/B-T/C) selection 10: Length reached
11: PLC cycle completed
12: Accumulative running time reached
13: Frequency limited 2
14: Torque limited N.A
Fault output
15: Ready for RUN
16: Reserved
17: Frequency upper limit reached
18: Frequency lower limit reached (no output at
F5-03 Extension card relay stop)
function (P/A-P/B-P/C) 19: Undervoltage state output
selection 20: Communication setting
21: Reserved
22: Reserved 0
N.A
23: Zero-speed running 2 (having output at No output
stop)
24: Accumulative power-on time reached
25: Frequency level detection FDT2 output
26: Frequency 1 reached
F5-04 DO1 function selection 27: Frequency 2 reached
(open-collector output 28: Current 1 reached
terminal) 29: Current 2 reached
30: Timing duration reached 1
31: AI1 input limit exceeded N.A AC drive
32: Load becoming 0 running
33: Reverse running
34: Zero current state
35: Module temperature reached
36:Software current limit exceeded
F5-05 Extension card DO2 37: Frequency lower limit reached (having
function selection output at stop)
38: Alarm output 4
39: Motor overheat warning N.A Frequency
40: Current running time reached reached
41: Fault output (no output at undervoltage)
Ver0.1 Page 19 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F5-22 DO active mode 7-segment
0 0 0 0 0 N.A 00000
selection
Ver0.1 Page 20 of 53
Step 12: Set DC Injection Braking/ Pre-Excitation If Needed
Ver0.1 Page 21 of 53
CHAPTER 4 TROUBLESHOOTING
Err02 Overcurrent 1. The output circuit is short circuited. 1: Eliminate short circuit.
during 2. The acceleration time is too short. 2: Increase the acceleration time.
acceleration
3. Manual torque boost or V/F curve is not 3: Adjust the manual torque boost or V/F curve.
appropriate. 4: Check that the power supply is normal.
4. The power supply is too low. 5: Select rotational speed tracking restart or start the
5. The startup operation is performed on the rotating motor after it stops.
motor. 6: Remove the added load.
6. A sudden load is added during acceleration. 7: Select a drive of higher power class.
7. The AC drive model is of too small power class.
Err03 Overcurrent 1. The output circuit is short circuited. 1: Eliminate short circuit.
during 2. The deceleration time is too short. 2: Increase the deceleration time.
deceleration
3. The power supply is too low. 3: Check the power supply, and ensure it is normal.
4. A sudden load is added during deceleration. 4: Remove the added load.
5. The braking resistor is not installed. 5: Install the braking resistor.
Err04 Overcurrent at 1. The output circuit is short circuited. 1: Eliminate short circuit.
constant speed 2. The power supply is too low. 2: Adjust power supply to normal range.
3. A sudden load is added during operation. 3: Remove the added load.
4. The AC drive model is of too small power class. 4: Select a drive of higher power class.
☆: Voltage thresholds
Voltage Class DC Bus Overvoltage DC Bus Undervoltage Braking Unit Operation Level
Single-phase 220 V 400V 200V 381V
Three-phase 220 V 400V 200V 381V
Three-phase 380 V 810V 350V 700V
Ver0.1 Page 22 of 53
Display Fault Name Possible Causes Solutions
Err08 Control power The input voltage exceeds the allowed range. Adjust the input voltage to within the allowed range.
fault
Err10 Drive overload 1. The load is too heavy or the rotor is locked. 1: Reduce the load, or check the motor, or check the
2. The drive is of too small power class. machine whether it is locking the rotor.
2: Select a drive of higher power class.
Err12 Power input 1. The three-phase power supply is abnormal. 1: Check the power supply.
phase loss 2. The drive board is faulty. 2 to 4: Seek for maintenance.
3. The lightening protection board is faulty.
4. The control board is faulty.
Err13 Power output 1. The cable between drive and motor is faulty. 1: Check the cable.
phase loss 2. The drive's three-phase output is unbalanced 2: Check the motor windings.
when the motor is running. 3 to 4: Seek for maintenance.
3. The drive board is faulty
4. The IGBT is faulty.
Err14 IGBT overheat 1. The ambient temperature is too high. 1: Reduce the ambient temperature.
2. The air filter is blocked. 2: Clean the air filter.
3. The cooling fan is damaged. 3 to 5: Seek for maintenance.
4. The thermal sensor of IGBT is damaged.
5.The IGBT is damaged.
Err15 External 1. External fault signal is input via DI. Reset the fault.
equipment fault 2. External fault signal is input via VDI.
Err16 Communication 1. The host computer is abnormal. 1: Check cabling of the host computer.
fault 2. The communication cable is faulty. 2: Check the communication cabling.
3. The extension card type set in F0-28 is incorrect. 3: Set F0-28 correctly.
4. The communication parameters in group FD are 3: Set the communication parameters properly.
set improperly.
Err18 Current The drive board is faulty. Replace the drive board.
detection fault
Err19 Motor tuning 1. Motor parameters are wrong. 1. Check motor parameters F1-00 to F1-05.
fault 2. Motor tuning overtime. 2. Check the wiring between drive and motor.
Err21 EEPROM The EEPROM chip is damaged. Replace the main control board.
read-write fault
Err23 Short circuit to The motor is short-circuited to ground. Replace the cables or motor.
ground
Err26 Accumulative The accumulative running time reaches the setting of Clear the record by performing parameter initialization
running time F8-17. (set FP-01 to 2).
reached
Err27 User-defined 1. The user-defined fault 1 signal is input via DI. Reset the fault.
fault 1 2. User-defined fault 1 signal is input via VDI.
Ver0.1 Page 23 of 53
Display Fault Name Possible Causes Solutions
Err28 User-defined 1. The user-defined fault 2 signal is input via DI Reset the fault.
fault 2 2. The user-defined fault 2 signal is input via VDI.
Err29 Accumulative The accumulative power-on time reaches the setting Clear the record by performing parameter initialization
power-on time of F8-16. (set FP-01 to 2).
reached
Err30 Off load fault Offload when it’s running. Check the connection between motor and load.
Err31 PID feedback The PID feedback is lower than FA-26. Check the PID feedback signal or set FA-26 to a
lost during proper value.
running
Err40 Quick current 1. The load is too heavy or the rotor is locked. 1: Reduce the load, or check the motor, or check the
limit 2. The drive is of too small power class. machine whether it is locking the rotor.
2: Select a drive of higher power class.
Err41 Motor The current motor is switched over via a terminal Switch over the motor only after the AC drive stops.
switchover fault during running of the AC drive.
during running
Ver0.1 Page 24 of 53
4.2 Common Symptoms And Diagnostics
There is no display at 1. There is no power supply or the power supply is 1: Check the power supply.
power-on. too low. 2 to 5: Seek for maintenance.
2. The switching power supply on the drive board is 6: Re-connect the 4-core and 28-core flat cables, or
faulty. seek for maintenance.
3. The rectifier bridge is damaged.
4. The buffer resistor of the drive is damaged.
5. The control board or the keypad is faulty.
6. The cable between the control board and the drive
board or keypad breaks.
"HC" is displayed at 1. The cable between the drive board and the control 1: Re-connect the 4-core and 28-core flat cables, or
power-on. board is in poor contact. seek for maintenance.
2. The control board is damaged. 2: Seek for maintenance.
3. The motor winding or the motor cable is 3: Check the motor or replace it, and check the motor
short-circuited to the ground. cable.
4. The power supply is too low. 4. Check the power supply according to charpter1.3.
The display is normal upon 1. The cooling fan is damaged or the rotor is locked. 1: Replace cooling fan, or check the machine whether
power-on, but "HC" is 2. A certain terminal is short-circuited. it is locking the rotor.
displayed after after 2: Eliminate short circuit.
startup and the motor
stops immediately.
Err14 is reported 1. The carrier frequency is set too high. 1: Reduce F0-15.
frequently. 2. The cooling fan is damaged, or the air filter is 2: Replace the fan and clean the air filter.
blocked. 3: Seek for maintenance.
3. Components (thermal coupler or others) inside the
drive are damaged.
The motor does not rotate 1. The motor or motor cable is damaged. 1: Check the motor, or check the cable between the
after the AC drive outputs 2. The motor parameters are set improperly. drive and the motor.
a non-zero reference. 2: Check and re-set motor parameters.
3. The cable between the drive board and the control
board is in poor contact. 3: Re-connect the 4-core and 28-core flat cables, or
4. The drive board is faulty. seek for maintenance.
5. The rotor is locked. 4: Seek for maintenance.
5: Check the machine whether it is locking the rotor.
The DI terminals are 1. The DI parameters are set incorrectly. 1: Check and reset DI parameters in group F4.
disabled. 2. The input signal is incorrect. 2: Check the input signals, or check the input cable.
3. The wire jumper between OP and +24V is in poor 3: Check the jumper between OP and +24 V.
contact. 4: Seek for maintenance.
4. The control board is faulty.
The drive reports 1. The motor parameters are set improperly. 1: Reset motor parameters.
overcurrent and 2. The acceleration/deceleration time is too small. 2: Set proper acceleration/deceleration time.
overvoltage frequently.
3. The load fluctuates. 3: Check the machine, or seek for maintenance.
Ver0.1 Page 25 of 53
CHAPTER 5 FUNCTION CODE TABLE
Ver0.1 Page 26 of 53
Group F1: Motor 1 Parameters
Function Parameter Name Setting Range Unit Default Commission
code
F1-00 Motor type 0: Common asynchronous motor N.A 0
1: Variable frequency asynchronous motor
F1-01 Rated motor power 0.1 to 7.5 kW Model
dependent
F1-02 Rated motor voltage 1 to 1000 V Model
dependent
F1-03 Rated motor current 0.01 to 655.35 A Model
dependent
F1-04 Rated motor frequency 0.01 to max frequency Hz Model
dependent
F1-05 Rated motor rotational 1 to 65535 RPM Model
speed dependent
F1-06 Stator resistance 0.001 to 65.535 Ω Model
(asynchronous motor) dependent
F1-07 Rotor resistance 0.001 to 65.535 Model
Ω
dependent
F1-08 Leakage inductive 0.01 to 655.35 Model
mH
reactance dependent
F1-09 Mutual inductive 0.1 to 6553.5 Model
mH
reactance dependent
F1-10 No-load current 0.01 to F1-03 Model
(asynchronous motor) A
dependent
F1-37 Auto-tuning selection 0: No auto-tuning
1: Static auto-tuning N.A 0
2: Complete dynamic auto-tuning
Ver0.1 Page 27 of 53
Group F3: V/F Control
Function Parameter Name Setting Range Unit Default Commission
code
F3-00 V/F curve setting 0 to 9 N.A 0
F3-01 Torque boost 0.0 to 30.0 % Model
dependent
F3-02 Cut-off frequency of 0.00 to maximum output frequency Hz 50.00
torque boost
F3-03 Multi-point V/F 0.00 to F3-05 Hz 0.00
frequency 1 (F1)
F3-04 Multi-point V/F voltage 0.0 to 100.0 %
1 (V1) 0.0
F3-05 Multi-point V/F F3-03 to F3-07 Hz
frequency 2 (F2) 0.00
F3-06 Multi-point V/F voltage 0.0 to 100.0 % 0.0
2 (V2)
F3-07 Multi-point V/F F3-05 to rated motor frequency (F1-04) Hz 0.00
frequency 3 (F3)
F3-08 Multi-point V/F voltage 0.0 to 100.0 % 0.0
3 (V3)
F3-09 V/F slip compensation 0 to 200.0 % 0.0
gain
F3-10 V/F over-excitation 0 to 200 %
gain 64
F3-11 V/F oscillation 0 to100 % Model
suppression gain dependent
F3-13 Voltage source for V/F 0 to 8
separation N.A 0
F3-14 Voltage digital setting 0 to rated motor voltage
for V/F separation V 0
Ver0.1 Page 28 of 53
Group F4: Input Terminals
Function Parameter Name Setting Range Unit Default Commission
code
F4-00 DI1 function selection 0 to 59 N.A 1
F4-01 DI2 function selection 0 to 59 N.A 4
F4-02 DI3 function selection 0 to 59 N.A 9
F4-03 DI4 function selection 0 to 59 N.A 12
F4-04 DI5 function selection 0 to 59 N.A 13
F4-05 DI6 function selection 0 to 59 N.A 0
F4-06 DI7 function selection 0 to 59 N.A 0
F4-07 DI8 function selection 0 to 59 N.A 0
F4-08 DI9 function selection 0 to 59 N.A 0
F4-09 DI10 function selection 0 to 59 N.A 0
F4-10 DI filter time 0.000 to 1.000 s 0.010
F4-11 Terminal wiring mode 0: Two-wire mode 1
selection 1: Two-wire mode 2 N.A 0
2: Three-wire mode 1
3: Three-wire mode 2
F4-12 Terminal UP/DOWN 0.01 to 65.535 Hz/s 1.00
rate
F4-13 AI curve 1 minimum 0.00 to F4-15 V
input 0.00
F4-14 Corresponding setting -100.0 to100.0
of AI curve1 minimum % 0.0
input
F4-15 AI curve 1 maximum F4-13 to 10.00 V 10.00
input
F4-16 Corresponding setting -100.0 to 100.0
of AI curve1 maximum % 100.0
input
F4-17 AI1 filter time 0.00 to 10.00 s 0.10
F4-18 AI curve 2 minimum 0.00 to F4-20 V 0.00
input
F4-19 Corresponding setting -100.0 to 100.0
of AI curve2 minimum % 0.0
input
F4-20 AI curve 2 maximum F4-18 to 10.00 V 10.00
input
F4-21 Corresponding setting -100.0 to 100.0
of AI curve2 maximum % 100.0
input
F4-22 AI2 filter time 0.00 to 10.00 s 0.10
F4-23 AI curve 3 minimum 0.00 to F4-25 V 0.00
input
F4-24 Corresponding setting -100.0 to100.0
of AI curve3 minimum % 0.0
input
F4-25 AI curve 3 maximum F4-23 to 10.00 V 10.00
input
F4-26 Corresponding setting -100.0 to 100.0
of AI curve3 maximum % 100.0
input
F4-27 AI3 filter time 0.00 to10.00 s 0.10
F4-28 Pulse minimum input 0.00 to F4-30 kHz 0.00
F4-29 Corresponding setting -100.0 to100.0
of pulse minimum % 0.0
input
F4-30 Pulse maximum input F4-28 to 50.00 kHz 50.00
Ver0.1 Page 29 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F4-31 Corresponding setting -100.0 to 100.0
of pulse maximum % 100.0
input
F4-32 Pulse filter time 0.00 to10.00 s 0.10
F4-33 AI curve selection 111 to 555 N.A 321
F4-34 Setting for AI less than 000 to 111 N.A 000
minimum input
F4-35 DI1 delay time 0.0 to 3600.0 s 0.0
F4-36 DI2 delay time 0.0 to 3600.0 s 0.0
F4-37 DI3 delay time 0.0 to 3600.0 s 0.0
F4-38 DI active mode 00000 to 11111 N.A
selection 1 00000
F4-39 DI active mode 00000 to 11111 N.A 00000
selection 2
Ver0.1 Page 30 of 53
Group F6: Start/Stop Control
Function Parameter Name Setting Range Unit Default Commission
code
F6-00 Start mode 0: Direct start N.A 0
2: Pre-excited start (asynchronous motor)
F6-03 Startup frequency 0.00 to 10.00 Hz 0.00
F6-04 Startup frequency 0.0 to 100.0 s 0.0
active time
F6-05 DC injection braking 1 0 to 100
level/ % 0
Pre-excitation level
F6-06 DC Injection Braking 1 0.0 to 100.0
active time/ s 0.0
Pre-excitation active
time
F6-07 Acceleration/ 0: Linear mode
Deceleration mode 1: S-curve mode A N.A 0
2: S-curve mode B
F6-08 Time proportion of 0.0 to (100.0 minus F6-09)
S-curve starting % 30.0
segment
F6-09 Time proportion of 0.0 to (100.0 minus F6-08)
S-curve ending % 30.0
segment
F6-10 Stop mode 0: Decelerate to stop N.A 0
1: Coast to stop
F6-11 DC Injection Braking 2 0.00 to maximum frequency Hz 0.00
frequency threshold
F6-12 DC Injection Braking 2 0.0 to 36.0 s
delay time 0.0
F6-13 DC Injection Braking 2 0 to 100 %
level 0
F6-14 DC Injection Braking 2 0.0 to 36.0 s 0.0
active time
F6-15 Brake use ratio 0 to 100 % 100
Ver0.1 Page 31 of 53
Group F8: Auxiliary Functions
Function Parameter Name Setting Range Unit Default Commission
code
F8-00 JOG running 0.00 to maximum frequency Hz 2.00
frequency
F8-01 JOG acceleration time 0.0 to 6500.0 s 20.0
F8-02 JOG deceleration time 0.0 to 6500.0 s 20.0
F8-03 Acceleration time 2 0.0 to 6500.0 s Model
dependent
F8-04 Deceleration time 2 0.0 to 6500.0 s Model
dependent
F8-05 Acceleration time 3 0.0 to 6500.0 s Model
dependent
F8-06 Deceleration time 3 0.0 to 6500.0 s Model
dependent
F8-07 Acceleration time 4 0.0 to 500.0 s Model
dependent
F8-08 Deceleration time 4 0.0 to 6500.0 s Model
dependent
F8-09 Jump frequency 1 0.00 to maximum frequency Hz 0.00
F8-10 Jump frequency 2 0.00 to maximum frequency Hz 0.00
F8-11 Frequency jump 0.00 to maximum frequency Hz 0.00
amplitude
F8-12 Forward/Reverse 0.0 to 3000.0
rotation dead-zone s 0.0
time
F8-13 Reverse control 0: Enabled N.A
1: Disabled 0
F8-14 Running mode when 0: Run at frequency lower limit
frequency reference 1: Stop N.A 0
lower than frequency 2: Run at zero speed
lower limit
F8-15 Droop control 0.00 to 10.00 Hz 0.00
F8-16 Accumulative 0 to 65000
power-on time h 0
threshold
F8-17 Accumulative running 0 to 65000 h
time threshold 0
F8-18 Startup protection 0: No N.A 0
1: Yes
F8-19 Frequency detection 0.00 to maximum frequency Hz 50.00
value (FDT1)
F8-20 Frequency detection 0.0 to 100.0 (FDT1 level)
hysteresis % 5.0
(FDT1hysteresis )
F8-21 Detection range of 0.00 to 100 (maximum frequency) %
frequency reached 0.0
F8-22 Jump frequency during 0: Disabled
acceleration/decelerati 1: Enabled N.A 0
on
F8-25 Frequency switchover 0.00 to maximum frequency
point between
acceleration time 1 Hz 0.00
and acceleration time
2
F8-26 Frequency switchover 0.00 to maximum frequency
point between
deceleration time 1 Hz 0.00
and deceleration time
2
F8-27 Terminal JOG priority 0: Disabled N.A 0
1: Enabled
F8-28 Frequency detection 0.00 to maximum frequency N.A
value (FDT2) 50.00
Ver0.1 Page 32 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F8-29 Frequency detection 0.0 to 100.0 (FDT2 level)
hysteresis (FDT2 % 5.0
hysteresis )
F8-30 Any frequency 0.00 to maximum frequency
reaching detection Hz 50.00
value 1
F8-31 Any frequency 0.0 to 100.0 (maximum frequency)
reaching detection % 0.0
amplitude 1
F8-32 Any frequency 0.00 to maximum frequency
reaching detection Hz 50.00
value 2
F8-33 Any frequency 0.0 to 100.0 (maximum frequency)
reaching detection % 0.0
amplitude 2
F8-34 Zero current detection 0.0 to 300.0 % 5.0
level (rated motor current as 100%)
F8-35 Zero current detection 0.01 to 600.00 s
delay 0.10
F8-36 Output overcurrent 0.0 (no detection) %
threshold 0.1 to 300.0 (rated motor current) 200.0
F8-37 Output overcurrent 0.00 to 600.00 s 0.00
detection delay time
F8-38 Any current reaching 1 0.0 to 300.0 (rated motor current) % 100.0
F8-39 Any current reaching 1 0.0 to 300.0 (rated motor current) %
amplitude 0.0
F8-40 Any current reaching 2 0.0 to 300.0 (rated motor current) % 100.0
F8-41 Any current reaching 2 0.0 to 300.0 (rated motor current) % 0.0
amplitude
F8-42 Timing function 0: Disabled N.A 0
1: Enabled
F8-43 Timing duration source 0 to 3 N.A 0
F8-44 Timing duration 0.0 to 6500.0 min 0.0
F8-45 AI1 input voltage lower -11.00 to F8-46 V
limit 3.10
F8-46 AI1 input voltage F8-45 to 11.00 V
upper limit 6.80
F8-47 Module temperature 0 to 100 ℃ 75
threshold
F8-48 Cooling fan control 0: Fan working during running N.A 0
1: Fan working continuously
F8-49 Wakeup frequency Dormant frequency (F8-51) to maximum Hz 0.00
frequency (F0-10)
F8-50 Wakeup delay time 0.0 to 6500.0 s 0.0
F8-51 Dormant frequency 0.00 to wakeup frequency (F8-49) Hz 0.00
F8-52 Dormant delay time 0.0 to 6500.0 s 0.0
F8-53 Current running time 0.0 to 6500.0 min 0.0
reached
Ver0.1 Page 33 of 53
Group F9: Fault And Protection
Function Parameter Name Setting Range Unit Default Commission
code
F9-00 Motor overload 0: Disabled N.A 1
protection selection 1: Enabled
F9-01 Motor overload 0.20 to 10.00 N.A 1.00
protection gain
F9-02 Motor overload 50 to 100 % 80
warning coefficient
F9-03 Overvoltage stall gain 0 to 100 N.A 0
F9-04 Overvoltage stall 120 to 150 % 130
protective voltage
F9-05 Overcurrent stall gain 0 to 100 N.A 20
F9-06 Overcurrent stall 100 to 200 %
protective current 150
F9-07 Short-circuit to ground 0: Disabled N.A
upon power-on 1: Enabled 1
F9-09 Fault auto reset times 0 to 20 N.A 0
F9-10 DO action during fault 0: Not act N.A 0
auto reset 1: Act
F9-11 Time interval of fault 0.1 to 100.0 s
auto reset 1.0
F9-12 Input phase loss 0: Disabled N.A
protection selection 1: Enabled 0
F9-13 Output phase loss 0: Disabled N.A 1
protection selection 1: Enabled
F9-14 1st fault type 0 to 51 N.A -
F9-15 2nd fault type 0 to 51 N.A -
F9-16 3rd (latest) fault type 0 to 51 N.A -
F9-17 Frequency upon 3rd -
fault - -
F9-18 Current upon 3rd fault - - -
F9-19 Bus voltage upon 3rd - - -
fault
F9-20 DI status upon 3rd - - -
fault
F9-21 Output terminal status -
upon 3rd fault - -
F9-22 AC drive status upon -
3rd fault - -
F9-23 Power-on time upon -
- -
3rd fault
F9-24 Running time upon 3rd -
- -
fault
F9-27 Frequency upon 2nd - - -
fault
F9-28 Current upon 2nd fault - - -
F9-29 Bus voltage upon 2nd -
- -
fault
F9-30 DI status upon 2nd -
- -
fault
F9-31 Output terminal status - - -
upon 2nd fault
F9-32 Frequency upon 2nd - - -
fault
F9-33 Current upon 2nd fault - - -
F9-34 Bus voltage upon 2nd -
- -
fault
F9-37 DI status upon 1st fault - - -
F9-38 Output terminal status -
upon 1st fault - -
Ver0.1 Page 34 of 53
Function Parameter Name Setting Range Unit Default Commission
code
F9-39 Frequency upon 1st -
- -
fault
F9-40 Current upon 1st fault - - -
F9-41 Bus voltage upon 3rd -
fault - -
F9-42 DI status upon 1st fault - - -
F9-43 Output terminal status - - -
upon 1st fault
F9-44 Frequency upon 1st - - -
fault
F9-47 Fault protection action 00000 to 22222 N.A 0000
selection 1
F9-48 Fault protection action 00000 to 11111 N.A 0000
selection 2
F9-49 Fault protection action 00000 to 22222 N.A 0000
selection 3
F9-54 Frequency selection 0 to 4
for continuing to run N.A 0
upon fault
F9-55 Backup frequency 0.0 to 100.0 (maximum frequency) Hz
upon abnormality 100.0
F9-59 Action selection at 0: Invalid
instantaneous power 1: Decelerate N.A 0
failure 2: Decelerate to stop
F9-60 Action pause judging 80.0 to 100.0
voltage at %
instantaneous power 90.0
failure
F9-61 Voltage rally judging 0.00 to 100.00
time at instantaneous s 0.50
power failure
F9-62 Action judging voltage 60.0 to 100.0 (standard bus voltage)
at instantaneous % 80.0
power failure
F9-63 Protection upon load 0: Disabled N.A 0
becoming 0 1: Enabled
Ver0.1 Page 35 of 53
Group FA: Process Control And PID Function
Function Parameter Name Setting Range Unit Default Commission
code
FA-00 PID setting source 0 to 6 N.A 0
FA-01 PID digital setting 0.0 to 100.0 % 50.0
FA-02 PID feedback source 0 to 8 N.A 0
FA-03 PID action direction 0: Forward action N.A 0
1: Reverse action
FA-04 PID setting feedback 0 to 65535 N.A 1000
range
FA-05 Proportional gain Kp1 0.0 to 100.0 N.A 20.0
FA-06 Integral time Ti1 0.01 to 10.00 s 2.00
FA-07 Differential time Td1 0.00 to 10.000 s 0.000
FA-08 Cut-off frequency of 0.00 to maximum frequency Hz 2.00
PID reverse rotation
FA-09 PID deviation limit 0.0 to 100.0 % 0.0
FA-10 PID differential limit 0.00 to 100.00 % 0.10
FA-11 PID setting change 0.00 to 650.00 s 0.00
time
FA-12 PID feedback filter 0.00 to 60.00 s 0.00
time
FA-13 PID output filter time 0.00 to 60.00 s 0.00
FA-14 Reserved - - -
FA-15 Proportional gain Kp2 0.0 to 100.0 N.A 20.0
FA-16 Integral time Ti2 0.01 to 10.00 s 2.00
FA-17 Differential time Td2 0.000 to 10.000 s 0.000
FA-18 PID parameter 0 to 2 N.A 0
switchover condition
FA-19 PID parameter 0.0 to FA-20 % 20.0
switchover deviation 1
FA-20 PID parameter FA-19 to 100.0 % 80.0
switchover deviation 2
FA-21 PID initial value 0.0 to 100.0 % 0.0
FA-22 PID initial value 0.00 to 650.00 s 0.00
holding time
FA-23 Maximum deviation 0.00 to 100.00
between two PID % 1.00
outputs in forward
direction
FA-24 Maximum deviation 0.00 to 100.00
between two PID % 1.00
outputs in reverse
direction
FA-25 PID integral property 00 to 11 N.A 00
FA-26 Detection value of PID 0.0: Not judging feedback loss % 0.0
feedback loss 0.1 to 100.0
FA-27 Detection time of PID 0.0 to 20.0 s 0.0
feedback loss
FA-28 PID operation at stop 0: No PID operation at stop N.A
1: PID operation at stop 0
Ver0.1 Page 36 of 53
Group FB: Swing Frequency, Fixed Length And Count
Function Parameter Name Setting Range Unit Default Commission
code
FB-00 Swing frequency 0: Relative to the central frequency
N.A 0
setting mode 1: Relative to the maximum frequency
FB-01 Swing frequency 0.0 to 100.0
% 0.0
amplitude
FB-02 Jump frequency 0.0 to 50.0 % 0.0
amplitude
FB-03 Swing frequency cycle 0.0 to 3000.0 s 10.0
FB-04 Triangular wave rising 0.0 to 100.0
% 50.0
time coefficient
FB-05 Set length 0 to 65535 m 1000
FB-06 Actual length 0 to 65535 m 0
FB-07 Number of pulses per 0.1 to 6553.5
N.A 100.0
meter
FB-08 Set count value 1 to 65535 N.A 1000
FB-09 Designated count 1 to 65535
value N.A 1000
Ver0.1 Page 37 of 53
Group FC: Multi-Reference And Simple PLC Function
Function Parameter Name Setting Range Unit Default Commission
code
FC-00 Reference 0 -100.0 to 100.0 % 0.0
FC-01 Reference 1 -100.0 to 100.0 % 0.0
FC-02 Reference 2 -100.0 to 100.0 % 0.0
FC-03 Reference 3 -100.0 to 100.0 % 0.0
FC-04 Reference 4 -100.0 to 100.0 % 0.0
FC-05 Reference 5 -100.0 to 100.0 % 0.0
FC-06 Reference 6 -100.0 to 100.0 % 0.0
FC-07 Reference 7 -100.0 to 100.0 % 0.0
FC-08 Reference 8 -100.0 to 100.0 % 0.0
FC-09 Reference 9 -100.0 to 100.0 % 0.0
FC-10 Reference 10 -100.0 to 100.0 % 0.0
FC-11 Reference 11 -100.0 to 100.0 % 0.0
FC-12 Reference 12 -100.0 to 100.0 % 0.0
FC-13 Reference 13 -100.0 to 100.0 % 0.0
FC-14 Reference 14 -100.0 to 100.0 % 0.0
FC-15 Reference 15 -100.0 to 100.0 % 0.0
FC-16 Simple PLC running 0 to 2
mode N.A 0
FC-17 Simple PLC retentive 00 to 11
selection N.A 00
FC-18 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 0
FC-19 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 0
FC-20 Running time of simple 0.0 to 6553.5
PLC reference 1 s or h 0.0
FC-21 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 1
FC-22 Running time of simple 0.0 to 6553.5 s or h 0.0
PLC reference 2
FC-23 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 2
FC-24 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 3
FC-25 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 3
FC-26 Running time of simple 0.0 to 6553.5
PLC reference 4 s or h 0.0
FC-27 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 4
FC-28 Running time of simple 0.0 to 6553.5 s or h 0.0
PLC reference 5
FC-29 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 5
FC-30 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 6
Ver0.1 Page 38 of 53
Function Parameter Name Setting Range Unit Default Commission
code
FC-31 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 6
FC-32 Running time of simple 0.0 to 6553.5 s or h 0.0
PLC reference 7
FC-33 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 7
FC-34 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 8
FC-35 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 8
FC-36 Running time of simple 0.0 to 6553.5
PLC reference 9 s or h 0.0
FC-37 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 9
FC-38 Running time of simple 0.0 to 6553.5 s or h 0.0
PLC reference 10
FC-39 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 10
FC-40 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 11
FC-41 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 11
FC-42 Running time of simple 0.0 to 6553.5
PLC reference 12 s or h 0.0
FC-43 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 12
FC-44 Running time of simple 0.0 to 6553.5 s or h 0.0
PLC reference 13
FC-45 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 13
FC-46 Running time of simple 0.0 to 6553.5
s or h 0.0
PLC reference 14
FC-47 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 14
FC-48 Running time of simple 0.0 to 6553.5
PLC reference 15 s or h 0.0
FC-49 Acceleration/decelerati 0 to 3
on time of simple PLC N.A 0
reference 15
FC-50 Time unit of simple 0: s (second); N.A 0
PLC running 1: h (hour)
FC-51 Reference 0 source 0 to 6 N.A 0
Ver0.1 Page 39 of 53
Group FD: Communication
Function Parameter Name Setting Range Unit Default Commission
code
FD-00 Baud rate 0000 to 9999 N.A 6005
FD-01 Data format 0 to 3 N.A 0
FD-02 Local address 0: Broadcast address;
1 to 247 N.A 1
FD-03 Response delay 0 to 20 ms 2
FD-04 Communication 0.0 (invalid); s 0.0
timeout 0.1 to 60.0
FD-05 Modbus protocol 00 to 11 N.A 00
selection
FD-06 Current unit in 0: 0.01
communication 1: 0.1 A 0
Ver0.1 Page 40 of 53
Group FE: User-Defined Function Code
Function Parameter Name Setting Range Unit Default Commission
code
FE-00 User-defined function F0-00 to FP-xx,
code 0 - F0-00
A1-00 to Ax-xx,
FE-01 User-defined function U0-xx to U0-xx
code 1 - F0-02
FE-02 User-defined function
code 2 - F0-03
FE-03 User-defined function
code 3 - F0-07
FE-04 User-defined function
code 4 - F0-08
FE-05 User-defined function
code 5 - F0-17
FE-06 User-defined function
code 6 - F0-18
FE-07 User-defined function
code 7 - F3-00
FE-08 User-defined function
code 8 - F3-01
FE-09 User-defined function
code 9 - F4-00
FE-10 User-defined function
code 10 - F4-01
FE-11 User-defined function
code 11 - F4-02
FE-12 User-defined function
code 12 - F5-04
FE-13 User-defined function
code 13 - F5-07
FE-14 User-defined function
code 14 - F6-00
FE-15 User-defined function
code 15 - F6-10
FE-16 User-defined function
code 16 - F0-00
FE-17 User-defined function
code 17 - F0-00
FE-18 User-defined function
code 18 - F0-00
FE-19 User-defined function
code 19 - F0-00
FE-20 User-defined function
code 20 - F0-00
FE-21 User-defined function
code 21 - F0-00
FE-22 User-defined function
code 22 - F0-00
FE-23 User-defined function
code 23 - F0-00
FE-24 User-defined function
code 24 F0-00
FE-25 User-defined function
code 25 - F0-00
FE-26 User-defined function
code 26 - F0-00
FE-27 User-defined function
code 27 - F0-00
FE-28 User-defined function
code 28 - F0-00
Ver0.1 Page 41 of 53
Function Parameter Name Setting Range Unit Default Commission
code
FE-29 User-defined function
code 29 - F0-00
Ver0.1 Page 42 of 53
Group A1: Virtual DI/DO
Function Parameter Name Setting Range Unit Default Commission
code
A1-00 VDI1 function selection 0 to 59 N.A 0
A1-01 VDI2 function selection 0 to 59 N.A 0
A1-02 VDI3 function selection 0 to 59 N.A 0
A1-03 VDI4 function selection 0 to 59 N.A 0
A1-04 VDI5 function selection 0 to 59 N.A 0
A1-05 VDI state setting mode 00000 to 11111 N.A 00000
A1-06 VDI state selection 00000 to 11111 N.A 00000
A1-07 Function selection for 0 to 59
N.A 0
AI1 used as DI
A1-08 Function selection for 0 to 59 N.A 0
AI2 used as DI
A1-09 Function selection for 0 to 59 N.A 0
AI3 used as DI
A1-10 State selection for AI 000 to 111 N.A 000
used as DI
A1-11 VDO1 function 0 to 41 N.A 0
selection
A1-12 VDO2 function 0 to 41
selection N.A 0
A1-13 VDO3 function 0 to 41.
selection N.A 0
A1-14 VDO4 function 0 to 41
N.A 0
selection
A1-15 VDO5 function 0 to 41
N.A 0
selection
A1-16 VDO1 output delay 0.0 to 3600.0 s 0.0
A1-17 VDO2 output delay 0.0 to 3600.0 s 0.0
A1-18 VDO3 output delay 0.0 to 3600.0 s 0.0
A1-19 VDO4 output delay 0.0 to 3600.0 s 0.0
A1-20 VDO5 output delay 0.0 to 3600.0 s 0.0
A1-21 VDO state selection 00000 to 11111 N.A 00000
Ver0.1 Page 43 of 53
Group A2: Motor 2 Parameters
Function Parameter Name Setting Range Unit Default Commission
code
A2-00 Motor type selection 0: Common asynchronous motor
N.A 0
1: Variable frequency asynchronous motor
A2-01 Rated motor power 0.1 to 30.0 Model
kW dependent
A2-02 Rated motor voltage 1 to 1000 Model
V dependent
A2-03 Rated motor current 0.01 to 655.35 Model
A dependent
A2-04 Rated motor frequency 0.01 to maximum frequency Model
Hz dependent
A2-05 Rated motor rotational 1 to 65535 Model
speed RPM dependent
A2-06 Stator resistance 0.001 to 65.535 Model
Ω dependent
A2-07 Rotor resistance 0.001 to 65.535 Model
Ω dependent
A2-08 Leakage inductive 0.01 to 655.35 Model
reactance mH dependent
A2-09 Mutual inductive 0.1 to 6553.5 Model
reactance mH dependent
A2-10 No-load current 0.01 to A2-03 Model
A dependent
A2-37 Auto-tuning selection 0: No auto-tuning
1: Static auto-tuning N.A 0
2: Complete auto-tuning
A2-38 Speed loop 0 to 100
N.A 30
proportional gain 1
A2-39 Speed loop integral 0.01 to 10.00
s 0.50
time 1
A2-40 Switchover frequency 0.00 to A2-43
Hz 5.00
1
A2-41 Speed loop 0 to 100
N.A 15
proportional gain 2
A2-42 Speed loop integral 0.01 to 10.00
s 1.00
time 2
A2-43 Switchover frequency A2-40 to maximum output frequency
Hz 10.00
2
A2-44 Vector control slip gain 50 to 200 % 100
A2-45 Time constant of 0.000 to 0.100 s 0.000
speed loop filter
A2-46 Vector control 0 to 200 N.A 64
over-excitation gain
A2-47 Torque upper limit 0 to 7
source in speed N.A 0
control mode
A2-48 Digital setting of torque 0.0 to 200.0
upper limit in speed % 150.0
control mode
A2-51 Excitation adjustment 0 to 20000
N.A 2000
proportional gain
A2-52 Excitation adjustment 0 to 20000
N.A 1300
integral gain
A2-53 Torque adjustment 0 to 20000
N.A 2000
proportional gain
A2-54 Torque adjustment 0 to 20000
N.A 1300
integral gain
Ver0.1 Page 44 of 53
Function Parameter Name Setting Range Unit Default Commission
code
A2-61 Motor 2 control mode 0: Sensorless vector control (SVC ) N.A 0
2: Voltage/Frequency (V/F) control
A2-62 Motor 2 0: Same as motor 1
acceleration/decelerati 1: Acceleration/Deceleration time 1
on time 2: Acceleration/Deceleration time 2 N.A 0
3: Acceleration/Deceleration time 3
4: Acceleration/Deceleration time 4
A2-63 Motor 2 torque boost 0.0: Fixed torque boost, Model
% dependent
0.1 to 30
A2-65 Motor 2 oscillation 0 to 100 N.A Model
suppression gain dependent
Ver0.1 Page 45 of 53
Group A3: Motor 3 Parameters
Function Parameter Name Setting Range Unit Default Commission
code
A3- 00 Motor type selection 0: Common asynchronous motor
N.A 0
1: Variable frequency asynchronous motor
A3- 01 Rated motor power 0.1 to 30.0 Model
kW dependent
A3- 02 Rated motor voltage 1 to 1000 Model
V dependent
A3- 03 Rated motor current 0.01 to 655.35 Model
A dependent
A3- 04 Rated motor frequency 0.01 to maximum frequency Model
Hz dependent
A3- 05 Rated motor rotational 1 to 65535 Model
speed RPM dependent
A3- 06 Stator resistance 0.001 to 65.535 Model
Ω dependent
A3- 07 Rotor resistance 0.001 to 65.535 Model
Ω dependent
A3- 08 Leakage inductive 0.01 to 655.35 Model
reactance mH dependent
A3- 09 Mutual inductive 0.1 to 6553.5 Model
reactance mH dependent
A3- 10 No-load current 0.01 to A3- 03 Model
A dependent
A3- 37 Auto-tuning selection 0: No auto-tuning
1: Static auto-tuning N.A 0
2: Complete auto-tuning
A3- 38 Speed loop 0 to 100
N.A 30
proportional gain 1
A3- 39 Speed loop integral 0.01 to 10.00
s 0.50
time 1
A3- 40 Switchover frequency 0.00 to A3- 43
Hz 5.00
1
A3- 41 Speed loop 0 to 100
N.A 15
proportional gain 2
A3- 42 Speed loop integral 0.01 to 10.00
s 1.00
time 2
A3- 43 Switchover frequency A3- 40 to maximum output frequency
Hz 10.00
2
A3- 44 Vector control slip gain 50 to 200 % 100
A3- 45 Time constant of 0.000 to 0.100 s 0.000
speed loop filter
A3- 46 Vector control 0 to 200 N.A 64
over-excitation gain
A3- 47 Torque upper limit 0 to 7
source in speed N.A 0
control mode
A3- 48 Digital setting of torque 0.0 to 200.0
upper limit in speed % 150.0
control mode
A3- 51 Excitation adjustment 0 to 20000
N.A 2000
proportional gain
A3- 52 Excitation adjustment 0 to 20000
N.A 1300
integral gain
A3- 53 Torque adjustment 0 to 20000
N.A 2000
proportional gain
A3- 54 Torque adjustment 0 to 20000
N.A 1300
integral gain
Ver0.1 Page 46 of 53
Function Parameter Name Setting Range Unit Default Commission
code
A3- 61 Motor 2 control mode 0: Sensorless vector control (SVC ) N.A 0
2: Voltage/Frequency (V/F) control
A3- 62 Motor 2 0: Same as motor 1
acceleration/decelerati 1: Acceleration/Deceleration time 1
on time 2: Acceleration/Deceleration time 2 N.A 0
3: Acceleration/Deceleration time 3
4: Acceleration/Deceleration time 4
A3- 63 Motor 2 torque boost 0.0: Fixed torque boost, Model
% dependent
0.1 to 30
A3- 65 Motor 2 oscillation 0 to 100 N.A Model
suppression gain dependent
Ver0.1 Page 47 of 53
Group A4: Motor 4 Parameters
Function Parameter Name Setting Range Unit Default Commission
code
A4- 00 Motor type selection 0: Common asynchronous motor
N.A 0
1: Variable frequency asynchronous motor
A4- 01 Rated motor power 0.1 to 30.0 Model
kW dependent
A4- 02 Rated motor voltage 1 to 1000 Model
V dependent
A4- 03 Rated motor current 0.01 to 655.35 Model
A dependent
A4- 04 Rated motor frequency 0.01 to maximum frequency Model
Hz dependent
A4- 05 Rated motor rotational 1 to 65535 Model
speed RPM dependent
A4- 06 Stator resistance 0.001 to 65.535 Model
Ω dependent
A4- 07 Rotor resistance 0.001 to 65.535 Model
Ω dependent
A4- 08 Leakage inductive 0.01 to 655.35 Model
reactance mH dependent
A4- 09 Mutual inductive 0.1 to 6553.5 Model
reactance mH dependent
A4- 10 No-load current 0.01 to A4- 03 Model
A dependent
A4- 37 Auto-tuning selection 0: No auto-tuning
1: Static auto-tuning N.A 0
2: Complete auto-tuning
A4- 38 Speed loop 0 to 100
N.A 30
proportional gain 1
A4- 39 Speed loop integral 0.01 to 10.00
s 0.50
time 1
A4- 40 Switchover frequency 0.00 to A4- 43
Hz 5.00
1
A4- 41 Speed loop 0 to 100
N.A 15
proportional gain 2
A4- 42 Speed loop integral 0.01 to 10.00
s 1.00
time 2
A4- 43 Switchover frequency A4- 40 to maximum output frequency
Hz 10.00
2
A4- 44 Vector control slip gain 50 to 200 % 100
A4- 45 Time constant of 0.000 to 0.100 s 0.000
speed loop filter
A4- 46 Vector control 0 to 200 N.A 64
over-excitation gain
A4- 47 Torque upper limit 0 to 7
source in speed N.A 0
control mode
A4- 48 Digital setting of torque 0.0 to 200.0
upper limit in speed % 150.0
control mode
A4- 51 Excitation adjustment 0 to 20000
N.A 2000
proportional gain
A4- 52 Excitation adjustment 0 to 20000
N.A 1300
integral gain
A4- 53 Torque adjustment 0 to 20000
N.A 2000
proportional gain
A4- 54 Torque adjustment 0 to 20000
N.A 1300
integral gain
Ver0.1 Page 48 of 53
Function Parameter Name Setting Range Unit Default Commission
code
A4- 61 Motor 2 control mode 0: Sensorless vector control (SVC ) N.A 0
2: Voltage/Frequency (V/F) control
A4- 62 Motor 2 0: Same as motor 1
acceleration/decelerati 1: Acceleration/Deceleration time 1
on time 2: Acceleration/Deceleration time 2 N.A 0
3: Acceleration/Deceleration time 3
4: Acceleration/Deceleration time 4
A4- 63 Motor 2 torque boost 0.0: Fixed torque boost, Model
% dependent
0.1 to 30
A4- 65 Motor 2 oscillation 0 to 100 N.A Model
suppression gain dependent
Ver0.1 Page 49 of 53
Group A6: AI Curve Setting
Function Parameter Name Setting Range Unit Default Commission
code
A6-00 AI curve 4 minimum -10.00 to A6-02
V 0.00
input
A6-01 Corresponding setting -100.0 to 100.0
of AI curve 4 minimum % 0.0
input
A6-02 AI curve 4 inflexion 1 A6-00 to A6-04
input V 3.00
A6-03 Corresponding setting -100.0 to 100.0
of AI curve 4 inflexion % 30.0
1 input
A6-04 AI curve 4 inflexion 1 A6-02 to A6-06 V 6.00
input
A6-05 Corresponding setting -100.0 to 100.0
of AI curve 4 inflexion % 60.0
1 input
A6-06 AI curve 4 maximum A6-06 to 10.00
V 10.00
input
A6-07 Corresponding setting -100.0 to 100.0
of AI curve 4 maximum % 100.0
input
A6-08 AI curve 5 minimum -10.00 to A6-10
input V 0.00
A6-09 Corresponding setting -100.0 to 100.0
of AI curve 5 minimum % 0.0
input
A6-10 AI curve 5 inflexion 1 A6-08 to A6-12 V 3.00
input
A6-11 Corresponding setting -100.0 to 100.0
of AI curve 5 inflexion % 30.0
1 input
A6-12 AI curve 5 inflexion 1 A6-10 to A6-14
V 6.00
input
A6-13 Corresponding setting -100.0 to 100.0
of AI curve 5 inflexion % 60.0
1 input
A6-14 AI curve 5 maximum A6-14 to 10.00
input V 10.00
A6-15 Corresponding setting -100.0 to 100.0
of AI curve 5 maximum % 100.0
input
A6-24 Jump point of AI1 input -100.0 to 100.0 % 0.0
corresponding setting
A6-25 Jump amplitude of AI1 0.0 to 100.0
input corresponding % 0.5
setting
A6-26 Jump point of AI2 input -100.0 to +100.0
corresponding setting % 0.0
A6-27 Jump amplitude of AI2 0.0 to 100.0
input corresponding % 0.5
setting
A6-28 Jump point of AI3 input -100.0 to +100.0 % 0.0
corresponding setting
A6-29 Jump amplitude of AI3 0.0 to 100.0
input corresponding % 0.5
setting
Ver0.1 Page 50 of 53
Group AC: AI/AO Correction
Function Parameter Name Setting Range Unit Default Commission
code
AC-00 AI1 measured voltage 0.500 to 4.000 Factory
V
1 corrected
AC-01 AI1 displayed voltage 0.500 to 4.000 Factory
V
1 corrected
AC-02 AI1 measured voltage 6.000 to 9.999 V Factory
2 corrected
AC-03 AI1 displayed voltage 6.000 to 9.999 V Factory
2 corrected
AC-04 AI2 measured voltage 0.500 to 4.000 Factory-corre
1 V cted
AC-05 AI2 displayed voltage 0.500 to 4.000 Factory-corre
1 V cted
AC-06 AI2 measured voltage 6.000 to 9.999 Factory-corre
2 V cted
AC-07 AI2 displayed voltage 6.000 to 9.999 Factory-corre
2 V cted
AC-08 AI3 measured voltage -9.999 to 10.000 Factory-corre
1 V cted
AC-09 AI3 displayed voltage -9.999 to 10.000 Factory-corre
1 V cted
AC-10 AI3 measured voltage -9.999 to 10.000 Factory-corre
2 V cted
AC-11 AI3 displayed voltage -9.999 to 10.000 Factory-corre
2 V cted
AC-12 AO1 target voltage 1 0.500 to 4.000 Factory
V
corrected
AC-13 AO1 measured voltage 0.500 to 4.000 Factory
1 V
corrected
AC-14 AO1 target voltage 2 6.000 to 9.999 Factory
V
corrected
AC-15 AO1 measured voltage 6.000 to 9.999 Factory
2 V
corrected
AC-16 AO2 target voltage 1 0.500 to 4.000 Factory
V
corrected
AC-17 AO2 measured voltage 0.500 to 4.000 Factory
1 V
corrected
AC-18 AO2 target voltage 2 6.000 to 9.999 Factory
V
corrected
AC-19 AO2 measured voltage 6.000 to 9.999 Factory
2 V
corrected
Ver0.1 Page 51 of 53
5.2 Monitoring Function Codes
Group U0: Monitoring
Function Parameter Name Setting Range Unit Default Commission
code
U0-00 Running frequency - Hz -
U0-01 Reference frequency - Hz -
U0-02 Bus voltage - V -
U0-03 Output voltage - V -
U0-04 Output current - A -
U0-05 Output power - kW -
U0-06 Output torque - % -
U0-07 DI state - N.A -
U0-08 DO state - N.A -
U0-09 AI1 voltage - V -
U0-10 AI2 voltage - V -
U0-11 AI3 voltage - V -
U0-12 Count value - N.A -
U0-13 Length value - N.A -
U0-14 Load speed - N.A -
U0-15 PID setting - N.A -
U0-16 PID feedback - N.A -
U0-17 PLC stage - N.A -
U0-18 Input pulse frequency - kHz -
U0-19 Feedback speed - Hz -
U0-20 Remaining running -
time Min -
U0-21 AI1 voltage before -
correction V -
U0-22 AI2 voltage before -
correction V -
U0-23 AI3 voltage before -
correction V -
U0-24 Linear speed - m/Min -
U0-25 Accumulative -
Min -
power-on time
U0-26 Accumulative running -
Min -
time
U0-27 Pulse input frequency - Hz -
U0-28 Communication setting -
value % -
U0-29 Reserved - - -
U0-30 Main frequency X - Hz -
U0-31 Auxiliary frequency Y - Hz -
U0-32 Viewing any register -
N.A -
address value
Ver0.1 Page 52 of 53
Function Parameter Name Setting Range Unit Default Commission
code
U0-34 Motor temperature - C -
U0-35 Target torque - % -
U0-37 Power factor angle - ° -
U0-41 DI state visual display - N.A -
U0-42 DO state visual display - N.A -
U0-43 DI function state visual - N.A -
display 1
U0-44 DI function state visual - N.A -
display 2
U0-59 Current frequency - % -
reference
U0-60 Current running - % -
frequency
U0-61 AC drive state - N.A -
Ver0.1 Page 53 of 53