Вы находитесь на странице: 1из 12

Applied Thermal Engineering 54 (2013) 190e201

Contents lists available at SciVerse ScienceDirect

Applied Thermal Engineering


journal homepage: www.elsevier.com/locate/apthermeng

Effects of solar shading devices on energy requirements of standalone


office buildings for Italian climates
Laura Bellia, Francesco De Falco, Francesco Minichiello*
DII, University of Naples Federico II, Naples, Italy

h i g h l i g h t s

< Solar shading devices on a building reduce annual energy requests of the systems.
< The energy saving has been evaluated for an office building in Italian climates.
< These savings have been evaluated considering heating, cooling and lighting systems.
< In warm summer climates (Palermo), the highest saving has been obtained (about 20%).
< Building and shading device characteristics influence the energy savings.

a r t i c l e i n f o a b s t r a c t

Article history: In Europe, the building energy demand is about 40% of the total energy requirement. In order to obtain
Received 22 October 2012 significant energy saving in this sector, the European Energy Performance Building Directive (EPBD)
Accepted 19 January 2013 2002/91/CE and the EPBD Recast (Directive 2010/31/UE) promote the use of passive strategies for
Available online 9 February 2013
buildings, which improve indoor thermal conditions above all in summer and so allow the reduction of
size and energy requirements of air conditioning systems.
Keywords:
This paper analyzes the influence of external solar shading devices on the energy requirements of
Building
a typical air-conditioned office building for Italian climates. A type of office building widespread in
Office
Solar shading
Europe has been considered. The energy saving related to the solar shading refers only to summer air
Louver conditioning, but the evaluation has been carried out for the entire year, by using a building energy
Overhang simulation code. The energy demand of the main technical systems (heating, cooling and lighting) and
Energy saving the energy saving related to the use of solar shading devices have been evaluated, as a function of the
Dynamic simulation most significant parameters, such as the climate, the geometrical characteristics of the shadings and the
Italian climates building, the thermal transmittance of the building envelope and the building orientation. The solar
shading devices have shown the highest energy efficiency for warm summer climates: for example, the
global annual energy saving related to the use of suitable shading devices has been evaluated between 8%
for Milan (the coldest climate) and 20% (for Palermo, the warmest one).
Ó 2013 Elsevier Ltd. All rights reserved.

1. Introduction Performance Building Directive (EPBD) 2002/91/CE [5] and the


EPBD Recast (Directive 2010/31/UE) [6] promote the use of passive
With reference to the total final energy requirement, 29% de- strategies for buildings, which improve indoor thermal conditions
pends on the household sector [1,2]. In particular, as regards above all in summer and so allow the reduction of size and energy
Europe, the building energy demand is about 40% of the global requirements of air conditioning systems [7,8]. This allows also
energy requirement. In order to obtain significant energy saving in a useful reduction of peaks for summer electric energy demand [9].
this sector, several strategies have been proposed related to air Among the various passive strategies proposed for opaque [9,10]
conditioning systems [3,4]. On the other hand, the European Energy and transparent [11,12] building envelope, the use of suitable
shading devices for building transparent components is note-
worthy. Nowadays, this solution is still more useful, as the “shift
* Corresponding author. DII, University of Naples Federico II, Napoli, P. le Tecchio
toward better insulated building envelopes, reduced air-infiltration
80, 80125 Italy. Tel.: þ39 081 2538665; fax: þ39 081 2390364. rates . is leading to indoor spaces that are more sensitive to solar
E-mail addresses: minichie@unina.it, francesco.minichiello@unina.it (F. Minichiello). gain” [13].

1359-4311/$ e see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.applthermaleng.2013.01.039
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 191

The main function of a shading system is the protection of the climates: Palermo is the hottest among them, Milan the coldest,
building transparent envelope from solar radiation in summer while Rome is characterized by an intermediate climate. The energy
conditions, so preventing overheating by blocking the access of requirements of the main technical systems (heating, cooling and
unwanted energy flow into the building. In fact, although several lighting) have been evaluated. The influence of various parameters
factors contribute to summer heat gain (e.g., electrical equipment, on the energy saving related to the use of suitable solar shadings
occupants, lights, etc.), in hot climates a significant fraction derives (overhangs on the south facade and louvers on the eastewest fa-
from solar heat gain entering through the fenestration areas. cades) has been analyzed. The most important examined parame-
Among the several shading solutions for limiting this thermal load, ters are: geometrical characteristics of shadings and building,
intercepting the solar radiation before it reaches the glazed area, thermal transmittance of the building envelope, type of lighting
through the use of external shading devices, is the most effective control system and building orientation.
one [14,15]. It is noteworthy that “fenestration products fully The aim of this paper is to provide simplified criteria for engi-
shaded from the outside reduce solar heat gain by as much as neers and architects in order to: a) establish if the use of external
80%” [16]. solar shading devices for standalone office buildings is suitable or
Palmero-Marrero and Oliveira [17] investigated the effects of not, in terms of energy requirements, for various Italian climates
louver shading devices applied to a building for different climates (but this evaluation is applicable also to other similar climates); b)
(Mexico, Cairo, Lisbon, Madrid, London), assessing their impact on in the case of energetic suitability, quantify obtainable energy
indoor thermal conditions and energy demand compared to saving and optimize the geometry and positioning of the shading
a building without shading devices. devices, as a function of various parameters. The analysis has been
Tzempelikos and Athienitis [18] evaluated the effects of shading carried out considering above all the end user electric energy
device characteristics, shading control and glazing area on cooling (neither the primary energy, nor the CO2 equivalent emissions);
and lighting energy needs for a building located in Montreal; an only a simplified evaluation of the full life cycle energy consump-
exterior roller blade has been considered as shading device. tion related to the production of shading devices has been also
Datta [19] analyzed the influence of fixed horizontal louver reported.
shading devices on thermal performance of a building for Italian
climates, considering a simple 2-zone building with high external 2. Case study
wall U-value (1.691 W m2 K1); the study was focused on a louver
shading device applied to the south-facing window. In Fig. 1, the modeled office building is shown, while the main
Overhang application on electrochromic windows and the characteristics of the complex building-systems and boundary
related energy saving for commercial buildings in USA are analyzed design conditions are reported in Table 1. The air conditioning
by Lee and Tavil [20], while in Ref. [21] thermotropic glass with
active dimming control for solar shading is investigated.
Florides et al. [22] show that the cooling load reduction related
to the use of window shading is about 8e9% for modern houses in
Cipro.
David et al. [23] analyze the thermal effects and the visual ef-
ficiency of solar shades, proposing simple indices to consider both
these aspects.
In Ref. [15], an experimental configuration of external shading
devices applied to apartment houses in South Korea is presented;
daylight aspects and energy savings for heating and cooling are
evaluated, by using also an energy simulation program.
Abu-Zour et al. [24] propose a new design of solar collector in-
tegrated into solar louvers.
Anyway, few research investigations have been carried out to
evaluate the energy performances of solar shading devices applied
to buildings for Italian climates [19]; moreover, in the energy
analysis on building shading devices, the energy request of the
lighting system has been rarely considered [18], as well as a com-
plete building instead of a single-zone building.
Hence, in this paper, an extended analysis on energy saving
related to external solar shading devices for Italian climates is
presented. The investigation has been carried out by using Ener-
gyPlus, an accurate building energy simulation program [25];
EnergyPlus is an energy and thermal load simulation program
which can help the user to size appropriate HVAC equipment,
improve energy performance of buildings and related systems,
develop life cycling cost analyses, etc. It is noteworthy that shading
models used by EnergyPlus have been validated by means of
experimental investigation [13,26]. The approach based on building
performance simulation has been conveniently used in several
research works related to the building energy efficiency [27,28].
Three different Italian climates (cities of Palermo, Rome and
Milan) and a typical air-conditioned office building have been
analyzed for both winter and summer. The above mentioned lo-
calities have been chosen as representative of typical Italian Fig. 1. The simulated office building: volumetric scheme and plan of the typical floor.
192 L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201

system of the building is characterized by fan-coils connected to an


electric water chiller/heat pump; the values of global heating COP
and cooling EER are reported in Table 1.
The choice of the optimal shading device for a given window
depends above all on the orientation of the facade and on the
apparent path of the sun. Therefore, in Fig. 2 the modeled solar
shadings applied to the examined building are shown, i.e. over-
hangs on the south facade and louvers on the eastewest facades,
coherently with the practice and the indications from scientific
literature [16,30]. The main characteristics of the selected shading
devices are reported in Table 2. As regards the louver configuration
and, in particular, the slat angle of 25 (Fig. 2 and Table 2), they have
been chosen on the basis of a carried-out energy optimization, as
reported in Section 3.8.
It can be also noted that this paper refers to Mediterranean
climates, so the optimal energy solutions are different from those of
Central-Northern Europe, whose cold climates usually require high
solar gains in winter and, thus, not fixed shading devices for
buildings (or no shading).
In Fig. 3, typical applications of external solar shading devices in
Italy are shown.

3. Results

Several parameters have been varied for the case study, in order
to better analyze the effects of solar shading devices on the building
energy requirements, as regards heating, cooling and lighting sys-
tems; unless otherwise specified, the values of the most important
parameters are those reported in Tables 1 and 2. It can be noted that
because the short sides of the examined building are eastewest
oriented (except for the Section 3.8), their fenestration area is lit-
tle compared to the long sides, therefore the influence of the lou-
vers on the energy requirements is much minor compared to the
overhangs (on long south side).
Moreover, it can be noted that the use of the solar shadings leads
to energy saving only for the cooling system, while it leads to an
increase in energy requirements for both heating and lighting
systems (because less solar radiation, useful for daylighting and
Fig. 2. The considered solar shading devices: louvers and overhangs.

Table 1
Main characteristics of the analyzed building, systems and climates.

Width (NeS direction) 12.8 m Length 32.3 m


Height 10.5 m Plan area and volume 413.4m2e4341.1 m3
Surface to volume ratio 0.28 m1 Infiltration airflow rate 0.5 ACH
Window to wall ratio (WWR) for each facade 30% (unless otherwise specified) Window height 1.5 m
Window area South exposure: 100 m2 East exposure: 23 m2 West exposure: 16 m2
North exposure: 100 m2
TSUMMER-SET-POINT 26  C Glass g-value 0.70
UGLAZING 2.7 W m2 K1 TWINTER-SET-POINT 20  C
UFRAME 3.6 W m2 K1 Uwall 0.58 W m2 K1
UROOF 1.0 W m2 K1 UBASEMENT FLOOR 0.90 W m2 K1
Occupancy level 0.111 persons/m2 Occupancy scheduling From 9:00 a.m. to 18 p.m.,
5 days/week
Illuminance level on work plane Office: 400 lx atrium and corridors: Thermal load related to the office 20 W/m2
100 lx toilets: 200 lx electrical equipment
Metabolic rate 0.9 met/person Clothing thermal resistance 1 clo for winter, 0.5 clo for
summer
Cooling SEER (fan-coils þ water chiller) 2.8 (Milan) Heating SCOP (fan-coils þ 2.8 (Milan)
2.7 (Rome) heat pump) 3.0 (Rome)
2.6 (Palermo) 3.2 (Palermo)
Note: HVAC systems only operate with building occupancy
Weather data from Italian Climatic data collection “Gianni De Giorgio” [29]
Location Milan (Linate) Latitude 45.43 , Rome (Fiumicino) Latitude 41.80 , Palermo (Punta Raisi)
Longitude 9.28 Longitude 12.23 Latitude 38.18 , Longitude
13.10
Cooling degree-days (base 10  C) 1771 2174 3082
Heating degree-days (base 18  C) 2454 1514 744
Maximum monthly global horizontal radiation (average daily total) 5539 Wh m2 (July) 6121 Wh m2 (July) 6714 Wh m2 (July)
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 193

Table 2
Characterization of selected shading devices.

Overhang Louver

Orientation South Orientation East, west


Projection 1.0 m (unless otherwise specified) Blades of the louver 4 (unless otherwise specified)
Vertical offset from top of window 0.0 m Vertical offset from top of window 0.0 m
Horizontal window overlap 0.0 m Horizontal window overlap 0.0 m
Note: the geometrical parameters reported in this table are also shown in Fig. 2. Blade depth 0.7 m
Angle 25
Vertical spacing 0.3 m
Distance from window 0.3 m
Material of the selected shading devices (for both overhangs and louvers): aluminium.
Thermal conductivity ¼ 221.0 W/mK; specific heat ¼ 896 J/kg K; density ¼ 2740 kg/m3; solar reflectance ¼ 0.61; infrared emittance: 0.25.

winter heating, enters the building when solar shadings are For Palermo climate (Fig. 4A), the best energy performances
adopted). Therefore, the best energy solution for the building have been obtained for overhangs with depth of 1.0 m e savings of
minimizes the overall annual energy demand. about 20% in terms of total electric energy for heating, cooling and
A preliminary analysis has been carried out showing that in lighting (as regards heating and cooling, the electric energy is that
winter, for Italian climates, the thermal energy picking-up is suit- required by all the equipment of the HVAC system, i.e. fan-coils,
able for the analyzed office building. For instance, with reference to electric chiller/heat pump, pumps, etc.). The saving drops to 16%
the hottest locality (Palermo), we have verified that in the period when adopting a 0.5 m or 1.5 m overhang.
from 1 December to 31 March (identified as conventional winter Similar results have been obtained (Fig. 3B and C) for Rome
period by the Italian rules for the climatic zone of Palermo) cooling (savings between 9% and 15%) and Milan (1e8%).
is required only in 117 h, i.e. about 4% of the total hours (2904 h). For all the climates investigated, 1.0 m overhangs represent the
best solution in terms of energy demand reduction for the exam-
3.1. Influence of the overhang depth ined building, but it should be noted that the optimal overhang
depth depends on the window height (1.5 m in the reference case).
Energy requirements of the examined building were calculated, The influence of the geometrical characteristics of the shadings
adopting the overhang typologies reported in Table 2, for Palermo, (louvers) on the eastewest facades is examined in a successive
Rome and Milan climates. Moreover, the energy demands for each section.
type of overhang and climate were compared to those related to the Even though this paper refers to the end user electric energy,
reference building with no shading devices. The overhang depth also a simplified analysis has been carried out on the full life cycle
has been fixed to 0.5 m, 1.0 m and 1.5 m, a variation similar to that energy consumption in the production of shading devices. The
reported in Ref. [30]. The results are reported in Fig. 4. “cradle-to-gate” approach (instead of the “cradle-to-site” one) has

Fig. 3. Typical applications of external solar shading devices.


194 L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201

Fig. 4. Influence of the overhang depth on the annual energy requests for Palermo (A), Rome (B) and Milan (C).
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 195

Fig. 5. Influence of the climatic conditions on the annual energy requests for shaded building and no-shaded one.

been used, so neglecting the energy related to transport from fac- material), and the embodied energy value of 200 MJ/kg has been
tory gate to construction site [31]. With reference to the case of used for the aluminium production. The results show that the
1.0 m overhangs, the global mass of the overhangs and louvers has primary energy saved by using the solar shading devices equalizes
been evaluated (about 470 kg, considering extruded aluminium as the embodied energy by 3 years for the most irradiated locality

Fig. 6. Influence of the building height on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo (A) and Milan (B).
196 L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201

(Palermo) and by 5 years for the less irradiated one (Milan). The warmest climate in summer, 15% reduction for Rome (intermediate
actual value (0.46) of the thermal to electrical conversion efficiency climate), and 8% for Milan (the coldest of the considered climates).
for Italy has been considered. Obviously, if extruded recycled alu- It can be noted that only for Milan, the chiller (cooling) energy
minium is used, much minor embodied energy value has to be requirements are similar or lower than the heating ones.
considered (about 17 MJ/kg), and therefore the above cited time It is also noticeable that, for the considered climates, the per-
period is significantly minor. Finally, it is noteworthy taking into centage energy savings related only to the cooling system are be-
account that aluminium is a recyclable material. tween 26% and 29%.
In the following analyses, only the end user electric energy
saving has been considered. 3.3. Influence of the building height

3.2. Influence of the climate In Fig. 6, results relative to the same building, but with 11
instead of 3 floors, are shown, in order to verify if the percentage
The influence of the different Italian climates has been evaluated energy saving connected to the solar shadings depends also on the
considering three typical localities of Southern, Central and height of the building. This possible dependence is negligible. In
Northern Italy, i.e. Palermo, Rome and Milan. As expected, the en- fact, comparing the results for Palermo (Fig. 6A), the energy saving
ergy saving potential related to the shading system is greater in values are 17%, 22% and 17% (for 0.5 m, 1.0 and 1.5 m overhangs),
climates characterized by warmer summer, because the cooling very similar to 16%, 20% and 16% obtained for the building of 3
energy requirements are higher compared to the other considered floors (Fig. 4A). Also for Milan (7%, 8% and 1% versus 6%, 8% and 1%,
climates. With reference to Fig. 5, 1.0 m overhangs allow 20% i.e. Fig. 6B versus Fig. 4B), the dependence of the percentage energy
reduction of total energy demand for Palermo, which has the savings on the number of building floors is negligible.

Fig. 7. Influence of the building external wall thermal insulation on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo (A) and Milan (B).
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 197

3.4. Influence of the building thermal insulation For colder climate of Milan, the global energy savings are 3% for
the uninsulated building and 16% for the well insulated building
The examined building is now considered for two different (Fig. 7B). It can be noted that for Milan, in the case of uninsulated
conditions of thermal insulation: no thermal insulation (U-values: building, the energy saving related to the use of solar shadings is
1.5 W m2 K1 for flat roof and ground floor, 2.1 W m2 K1 for negligible, because the cold winter climate leads to heating energy
external wall) and high thermal insulation (U-values: requirements significantly higher than the summer cooling
0.15 W m2 K1 for flat roof and ground floor, 0.25 W m2 K1 for ones. This result is coherent with those of other previous research
external wall). For each insulation level, the effects of the shading papers [19].
systems on building energy demand are investigated, for both So, the level of thermal insulation of the building envelope plays
Palermo and Milan climates (Fig. 7). a significant role on the total energy requirements, both in warm
For Palermo climate (Fig. 7A), the considered shading system and cold climates. In the case of cold climate and very low level of
allows a 14% energy saving for the uninsulated building and a 24% building insulation, the solar shadings are not useful.
saving for the well insulated building. It can be also noted that the
insulated building envelope leads to a relevant increase in cooling 3.5. Influence of the external wall thermal mass
energy demand compared to the uninsulated building (69% with no
shading system, 59% with shading system). The cooling energy The results reported in Fig. 8 for Palermo and Milan show that
demand represents the highest energy requirement for this warm the influence of the external wall thermal mass on the energy
climate, leading to a relevant increase in global energy demand saving related to the use of solar shadings is negligible (external
(39% and 29%). wall internal heat capacity: 134.8 kJ m2 K1 for high thermal mass,

Fig. 8. Influence of the building thermal mass on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo (A) and Milan (B).
198 L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201

Fig. 9. Influence of the building window to wall ratio (WWR) on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo (A) and Milan (B).

12.8 kJ m2 K1 for low thermal mass). In fact, for Palermo (Milan) 3.6. Influence of the window to wall ratio
this energy saving is about 20% (8%) independently of the level of
the external wall thermal mass (see Fig. 4 versus Fig. 8). In case of In the previous sections, a typical window to wall ratio
high thermal mass, a future investigation considering also suitable (WWR ¼ 30%) has been considered for the examined building
night ventilation (not present in this case study) could be useful. [18,32] (WWR represents, for each facade, the ratio between the

Fig. 10. Schemes of the lighting control system: two steps (A), linear with off (B).
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 199

window area and the total area of the wall). In this section, the this increase; this conclusion is coherent with that obtained by
influence of WWR of the building on the energy saving related to other researchers [32].
the use of solar shadings has been investigated for Palermo and
Milan (Fig. 9). The following main considerations can be drawn: 3.7. Influence of the lighting control system

 In case of WWR ¼ 60%, higher percentage energy savings can In this section, the influence of the lighting control system on the
be obtained by using solar shadings compared to the case of energy saving related to the use of solar shadings has been inves-
WWR ¼ 30% (for Palermo these saving rises from 20% to 28%, tigated for Palermo and Milan. The following types of lighting control
for Milan from 8% to 15%); system have been considered: one step, two steps, linear with off
 In case of WWR ¼ 60%, energy saving slightly increases when (the schemes of the second and the third type are shown in Fig. 10).
using 1.5 m overhangs instead of 1.0 m overhangs, because the The results reported in Fig. 11 show that the energy saving related to
height of the windows of the new building (WWR ¼ 60%) is the use of solar shadings is almost independent of the type of lighting
major compared to the reference building (WWR ¼ 30%) and, control system: in fact, these savings are about 20% for Palermo and
thus, overhangs with higher depth work slightly better; 8% for Milan, independently of the selected lighting control system.
 As expected, passing from WWR ¼ 30% to WWR ¼ 60%, the Besides, in Fig. 11 it can be seen that the linear control system leads to
global energy requirements increase, above all for Palermo significant energy savings for lighting compared to the case of one
(25% adopting shading devices, 38% without shading devices); step control system (37e42%), even if the savings are minor when the
 Both for Palermo and Milan, the global energy requirements of overall energy demand is considered (8e9%).
the building with WWR ¼ 30% without shadings are about It is also noticeable that, passing from a building with one step
equal to those of the building with WWR ¼ 60% and the lighting control system and no shadings (the worst case) to the
shadings. This result not only confirms that highly glazed same building with linear lighting control system and 1.0 m over-
building require more energy, but also shows that the use of hangs (the best solution), significant global energy savings are
suitable shading devices can eliminate or significantly reduce obtained (26% and 15% for Palermo and Milan).

Fig. 11. Influence of the lighting control system on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo (A) and Milan (B).
200 L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201

Fig. 12. Influence of the building orientation on the annual energy requests in the cases of shaded building and no-shaded one, for Palermo and Milan.

3.8. Influence of the orientation of the building shading devices for standalone office buildings are suitable or not,
in terms of energy requirements, for a given Italian climate (but this
The same building has been analyzed, but with the long sides evaluation is applicable also to other similar climates); b) in the
oriented toward east and west (instead of south and north). In this case of energetic suitability, quantify obtainable energy saving and
case, instead of overhangs, the shading system more suitable for the optimize the geometry and positioning of the shading devices, as
long sides is represented by a louver unit with 10 blades, height a function of the main parameters. The analysis has been carried
equal to 0.15 m and inclination of 25 (this configuration has been out considering above all the end user electric energy.
chosen on the basis of a carried-out energy optimization). On the The following principal conclusions can be highlighted (with
contrary, the short side oriented toward south is better shaded by reference to the use of suitable overhangs on south-facing facades
means of overhangs instead of louvers; no shading device has been and louvers on the east and west facing facades, unless otherwise
considered for north side. specified):
In Fig. 12 the results relative to this building are reported for
Palermo and Milan. The following main considerations can be - The energy savings are higher when choosing overhangs with
drawn: depth of 1.0 m e but this depth is strictly correlated to the
height of the windows;
- The use of shadings for Milan is even negative e the global - In the optimal case (overhangs with depth of 1.0 m), the global
energy requirements increase of 9%, due above all to the sig- energy saving is equal to about 20% for Palermo (the hottest
nificant rising in the lighting energy demand (133%); climate), 15% for Rome (intermediate climate) and 8% for Milan
- For Palermo only little global energy savings (5%) are obtained (the coldest one), and this confirms that shadings are prefer-
e in fact, the reduction of the energy requirement for cooling is able in warm climates;
significant (31%), but also the increase in lighting energy de- - For Palermo, the considered shading system allows a 14% en-
mand is relevant (189%); ergy saving for an uninsulated building and a 24% saving for
- As expected, the energy behavior of this building is worse a highly insulated building. For colder climate of Milan, these
compared to the reference typical building with long sides saving values are 3% and 16%. This shows that for cold winter
oriented toward south and north (for example, as regards the climates, in the case of uninsulated building, the energy saving
case of the building without shading, a 10% increase in global related to the use of solar shadings is negligible, because the
energy requirements has been obtained for Palermo, 6% for heating energy requirements are significantly higher than the
Milan). summer cooling ones (on which solar shadings have a positive
influence);
4. Conclusions - The window to wall ratio WWR of the building influences
significantly the energy saving related to the use of solar
This paper analyses the influence of solar shading devices on the shadings (for example, in the case of WWR ¼ 60%, compared to
energy requirements of a typical standalone office building, for the case of WWR ¼ 30%, the global energy requirements
three Italian climates. Energy performances achievable by applying increase, above all for Palermo, and higher percentage energy
external solar shading to an air-conditioned building have been savings can be obtained by using solar shading e for Palermo
evaluated for both winter and summer, by means of a suitable this saving rises from 20% to 28%, for Milan from 8% to 15%);
building energy simulation code, EnergyPlus. The energy re- moreover, the global energy requirements of the building with
quirements for heating, cooling and lighting have been analyzed, as WWR ¼ 30% without shadings are about equal to those of the
a function of the main boundary conditions. building with WWR ¼ 60% and the shadings. This result shows
The aim of this paper is to provide simplified criteria for engi- that the use of suitable shading devices can eliminate or sig-
neers and architects in order to: a) establish if external solar nificantly reduce the increase of energy demand typical of
L. Bellia et al. / Applied Thermal Engineering 54 (2013) 190e201 201

highly glazed building; this conclusion is coherent with that [5] European Parliament, EPBD e Energy Performance of Buildings Directive.
Directive 2002/91/EC of the European Parliament and of the Council of the
obtained by other researchers [32];
European Union, European Parliament, 2002.
- The global energy saving connected with the use of shadings is [6] European Parliament, EPBD Recast e Energy Performance of Buildings
almost independent of the type of lighting control system; Directive. Directive 2010/31/EU of the European Parliament and of the Council
- Negligible influence on the global energy saving connected of the European Union, European Parliament, 2010.
[7] G.H. dos Santos, N. Mendes, Numerical analysis of passive cooling using
with the use of shadings is related to the height of the exam- a porous sandy roof, Appl. Therm. Eng. 51 (2013) 25e31.
ined building and the external wall thermal mass; [8] M. Kayfeci, A. Kecebas, E. Gedik, Determination of optimum insulation
- When the long sides of the building are oriented toward east thickness of external walls with two different methods in cooling applications,
Appl. Therm. Eng. 50 (2013) 217e224.
and west instead of north and south, the energy behavior of the [9] A. Synnefa, M. Santamouris, I. Livada, A study of the thermal performance of
building worsens (for example, as regards the case of the reflective coatings for the urban environment, Sol. Energy 80 (2006) 968e981.
building without shading, a 10% increase in global energy re- [10] F. Ascione, L. Bellia, P. Mazzei, F. Minichiello, Solar gain and building envelope:
the surface factor, Build. Res. Inform. 38 (2) (2010) 187e205.
quirements has been obtained for Palermo, 6% for Milan), and [11] T. Inoue, Solar shading and daylighting by means of autonomous responsive
the use of shadings for Milan is even negative (the global en- dimming glass: practical application, Energy Build. 35 (2003) 463e471.
ergy requirements increase of 9%), while for Palermo only little [12] P.A.B. James, A.S. Bahaj, Smart glazing solutions to glare and solar gain: a ‘sick
building’ case study, Energy Build. 37 (2005) 1058e1067.
global energy savings (5%) are obtained.
[13] B.A. Lomanowski, J.L. Wright, Modeling fenestration with shading devices in
building energy simulation: a practical approach, in: Proceedings of Building
Finally, these further general conclusions can be derived: Simulation 2009, Glasgow, Scotland, July 27e30, 2009, pp. 976e983.
[14] E. Gratia, A. De Herde, The most efficient position of shading devices in
a double-skin façade, Energy Build. 39 (2007) 364e373.
- The long sides of the building have to be oriented toward north [15] G. Kim, H.S. Lima, T.S. Limb, L. Schaeferc, J.T. Kim, Comparative advantage of
and south, if possible; an exterior shading device in thermal performance for residential buildings,
- The depth of the overhangs (on the south side) depends also on Energy Build. 46 (2012) 105e111.
[16] ASHRAE, 2009 ASHRAE Handbook e Fundamentals, Chapter 15 (Fenestration),
the window height (for example, the depth of 1 m is suitable ASHRAE (American Society of Heating, Refrigeration and Air-Conditioning
for window height of 1.5 m, but the optimal depth should be Engineers), Atlanta, 2009.
increased for higher windows). [17] A.I. Palmero-Marrero, A.C. Oliveira, Effect of louver shading devices on
building energy requirements, Appl. Energy 87 (2010) 2040e2049.
[18] A. Tzempelikos, A.K. Athienitis, The impact of shading design and control on
A useful further research will be focused on the evaluation of building cooling and lighting demand, Sol. Energy 81 (2007) 369e382.
a suitable relationship between climatic characteristics and energy [19] G. Datta, Effect of fixed horizontal louver shading devices on thermal
performance of building by TRNSYS simulation, Renew. Energy 23 (2001)
convenience in using solar shading devices on buildings. 497e507.
[20] E.S. Lee, A. Tavil, Energy and visual comfort performance of electrochromic
Nomenclature windows with overhangs, Build. Environ. 42 (2007) 2439e2449.
[21] T. Inoue, M. Ichinose, N. Ichikawa, Thermotropic glass with active dimming
control for solar shading and daylighting, Energy Build. 40 (2008) 385e393.
T temperature,  C [22] G.A. Florides, S.A. Kalogirou, S.A. Tassau, L.C. Wrobel, Modeling of the
U unitary thermal transmittance, W m2 K1 modern houses of Cyprus and energy consumption analysis, Energy 25 (2000)
915e937.
[23] M. David, M. Donn, F. Garde, A. Lenoir, Assessment of the thermal and visual
Acronyms efficiency of solar shades, Build. Environ. 46 (2011) 1489e1496.
[24] A.M. Abu-Zour, S.B. Riffat, M. Gillott, New design of solar collector integrated
MI referred to Milan, e
into solar louvres for efficient heat transfer, Appl. Therm. Eng. 26 (2006)
PA referred to Palermo, e 1876e1882.
RM referred to Rome, e [25] D.B. Crawley, L.K. Lawrie, C.O. Pedersen, R.J. Liesen, D.E. Fisher, R.K. Strand,
SCOP mean winter seasonal energy efficiency ratio, e R.D. Taylor, R.C. Winkelmann, W.F. Buhl, Y.J. Huang, A.E. Erdem, ENERGYPLUS,
a new-generation building energy simulation program, in: Proceedings of
SEER mean summer seasonal energy efficiency ratio, e Building Simulation ’99, vol. 1, 1999, pp. 81e88.
WWR window to wall ratio, e [26] P.G. Loutzenhiser, H. Manz, S. Carl, H. Simmler, G.M. Maxwell, Empirical val-
idation of solar gain models for a glazing unit with exterior and interior blind
assemblies, Energy Build. 40 (2008) 330e340.
References [27] F.R. Mazarrón, J. Cid-Falceto, I. Cañas, An assessment of using ground thermal
inertia as passive thermal technique in the wine industry around the world,
[1] International Energy Agency, Worldwide Trends in Energy Use and Efficiency, Appl. Therm. Eng. 33e34 (2012) 54e61.
Authoring Institution: International Energy Agency (IEA), Head of Communica- [28] M.R. Hall, K.B. Najim, C.J. Hopfe, Transient thermal behaviour of crumb
tion and Information Office, Paris, France, 2008 (last access: December 2012), rubber-modified concrete and implications for thermal response and energy
http://www.iea.org/publications/freepublications/publication/Indicators_2008- efficiency in buildings, Appl. Therm. Eng. 33e34 (2012) 77e85.
1.pdf. [29] Last access: December 2012. Authoring institution: USA Department of energy
[2] M.J. Suarez, C. Sanjuan, A.J. Gutierrez, J. Pistono, E. Blanco, Energy evaluation of an (DOE), apps1.eere.energy.gov/buildings/energyplus/weatherdata_sources.cfm.
horizontal open joint ventilated facade, Appl. Therm. Eng. 37 (2012) 302e313. [30] A.I. Palmero-Marrero, A.C. Oliveira, Evaluation of a solar thermal system using
[3] A. Capozzoli, P. Mazzei, F. Minichiello, D. Palma, Hybrid HVAC systems with building louvre shading devices, Sol. Energy 80 (5) (2006) 545e554.
chemical dehumidification for supermarket applications, Appl. Therm. Eng. 26 [31] G.P. Hammon, C.I. Jones, Embodied energy and carbon in construction ma-
(2006) 795e805. terials, Proc. Inst. Civ. Eng. Energy 161 (2) (2008) 87e98.
[4] F. Ascione, L. Bellia, A. Capozzoli, F. Minichiello, Energy saving strategies in air- [32] H. Poirazis, A. Blomsterberg, M. Wall, Energy simulation for glazed office
conditioning for museums, Appl. Therm. Eng. 29 (2009) 676e686. buildings in Sweden, Energy Build. 40 (2008) 1161e1170.

Вам также может понравиться