Project: Rating Program: LTC v1_157.

idd
Unit Tag: Software Version: YW 16.04
Engineer: Date: 11/25/16 10:54:03
Customer:

STANDARD SOUND REPORT

Warnings / Errors
WARNING Last data line is partload operating limit with pre-rotation vanes (1).

Page 1 of 3
Project: Rating Program: LTC v1_157.idd
Unit Tag: Software Version: YW 16.04
Engineer: Date: 11/25/16 10:54:03
Customer:
Unit Specifications
Model YK6D6SQ65EIH Gear Code XA
Rated Net Capacity (Tons) 400.0 Specified Net Capacity (Tons) 400.0
NPLV.IP (kW/Ton.R) 0.3325 Refrigerant Type/Charge (lb) R134A/1023
Full Load (kW/Ton.R) 0.5882 A-Weighted SPL (dBA) 79.5
Input Power (kW) 235.3 Max Motor Load (kW) 230.0
Voltage / Hz (Input) 415 / 50.0 Oil Cooler Refrig clr
Condenser Gas Inlet Type Baffle
Job FLA (Amps) 373 OptiSound Control Y
Isolation Valve Y
LRA (Amps) 2366 Variable Orifice VALVE:2
Min Circuit Ampacity 467 Starter Type VSD w/o Filter
LVD0292W**K***04GZ-
Max Circuit Breaker Amps 800 Starter Model 68A

Evaporator Condenser
Fluid Water* Water*
Tube MTI No. 321* 260* / 260
Passes 2* 2*
Fouling Factor (hr-ft²-°F/Btu) 0.000100* 0.000250*
Entering Fluid Temp (°F) 53.60 89.60*
Leaving Fluid Temp (°F) 44.60* 96.80
Fluid Flow (gpm) 1063 1548
Fluid Pressure Drop (ft) 10.8 13.6
(*) Designates User Specified Input
Chiller Sound Pressure Levels (Standard)
Octave Band Center Frequency, Hz
Percent A-Weighted
Load (dBA)
63 125 250 500 1000 2000 4000 8000
100 75.0 75.0 75.0 74.0 74.0 74.0 73.0 70.0 80

90 75.0 74.5 73.5 72.0 72.5 73.0 71.5 67.5 78

80 75.0 74.5 72.5 71.0 72.0 72.5 71.0 66.0 78


70 75.0 73.5 71.5 69.5 70.0 71.0 69.5 64.0 77

60 75.0 73.0 70.0 68.0 68.0 69.5 68.0 62.0 75

50 75.0 73.0 70.0 68.0 68.0 69.0 68.0 62.0 75


40 75.0 73.5 71.5 70.0 70.0 70.5 69.5 64.5 76

30 75.0 74.5 74.0 73.0 73.0 73.0 72.0 68.5 79

20 75.0 75.0 75.5 74.5 74.5 74.5 73.5 71.0 80

15 75.0 75.0 75.5 74.5 74.5 74.5 73.5 71.0 80


The octave and A-weighted sound pressure levels are the levels expected to be obtained if measurements are performed
in accordance with AHRI Standard 575-08, Method of Measuring Machinery Sound Within Equipment Rooms.
Tolerances: The sound levels of identical unit selections can vary due to manufacturing tolerances and test repeatability.
Variations of ±3 dBA on the A-weighted levels and ±5 dB on the octave band levels are possible.
Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-
Heating Packages Using Vapor Compression Cycle Certification Program, which is based on

Page 2 of 3
AHRI Standard 550/590 (IP) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.
Compliant with ASHRAE 90.1 - 2004.
Compliant with ASHRAE 90.1 - 2007.
Compliant with ASHRAE 90.1 - 2010.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant
Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.75-EG1.
Auxiliary components included in total KW - oil pump & heater, chiller controls.

Page 3 of 3