Вы находитесь на странице: 1из 2

FUNCTION_BLOCK OPERATE

TITLE = 'OperationMessage'{
S7_tasklist:='OB32';
S7_m_c:='true';
S7_alarm_ui := '1' //1=PCS7-Message dialog; 0=Standard message dialog
}
AUTHOR : ATEAM
NAME : OPERATE
FAMILY : ATEAM
VERSION : '1.0'
VAR_INPUT
MSG_EVID{ // Attributes for Alarm-Properties
S7_visible:='false'; // Alarms are transferred to WinCC
S7_link:='false';
S7_param:='false';
S7_server:='alarm_archiv';
S7_a_type:='alarm_8p'
}:DWORD:=0;
SIG_1 : BOOL; // Internal Alarm Event Tag
SIG_2 : BOOL; // Internal Alarm Event Tag
SIG_3 : BOOL; // Internal Alarm Event Tag
SIG_4 : BOOL; // Internal Alarm Event Tag
SIG_5 : BOOL; // Internal Alarm Event Tag
SIG_6 : BOOL; // Internal Alarm Event Tag
SIG_7 : BOOL; // Internal Alarm Event Tag
SIG_8 : BOOL; // Internal Alarm Event Tag
BA_EN{ //Batch busy enable
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='false' //Parameter do not supports O&M
} : BOOL := 0;
OCCUPIED{ //Batch busy ID
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='false' //Parameter do not supports O&M
} : BOOL := 0;
BA_ID{ //Consequtive batch number
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='false' //Parameter do not supports O&M
} : DWORD;
BA_NA{ //Batch name (charge name)
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='false' //Parameter do not supports O&M
} : STRING[32] :='';
STEP_NO{ //Batch step number
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='false' //Parameter do not supports O&M
} : DWORD;
szText1{
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='true' //Parameter supports O&M
} : STRING[32] :=''; //user text
szText2{
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='true' //Parameter supports O&M
} : STRING[32] :=''; //user text
szText3{
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='true' //Parameter supports O&M
} : STRING[32] :=''; //user text
szText4{
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='true' //Parameter supports O&M
} : STRING[32] :=''; //user text
szText5{
S7_visible:='true'; //Parameter visible in CFC chart
S7_m_c:='true' //Parameter supports O&M
} : STRING[32] :=''; //user text
END_VAR
VAR_OUTPUT
MSG_STATUS :WORD;
MSG_ERROR : BOOL;
MSG_DONE : BOOL;
MSG_ACK_STATE : WORD;
END_VAR
VAR_IN_OUT
// user-specific associated message values of ALARM_8P
AUX_PR05 {S7_visible := 'false'} : ANY; //Associated value 5
AUX_PR06 {S7_visible := 'false'} : ANY; //Associated value 6
AUX_PR07 {S7_visible := 'false'} : ANY; //Associated value 7
AUX_PR08 {S7_visible := 'false'} : ANY; //Associated value 8
AUX_PR09 {S7_visible := 'false'} : ANY; //Associated value 9
AUX_PR10 {S7_visible := 'false'} : ANY; //Associated value 10
END_VAR
VAR
ALARM_8P_1:SFB35; //Multi instance call of ALARM_8P block
iERROR : INT; //used for return value of sfc call
dwFILL_ZERO :DWORD; //used for SFC "FILL"
abyBA_NA : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte batch name
abyText1 : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte Text4
abyText2 : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte Text5
abyText3 : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte Text6
abyText4 : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte Text7
abyText5 : ARRAY [1..32] OF BYTE := 16(0); //intern array of byte Text8
wSTEP_NO :DWORD; //intern Batch step number
dwBA_ID :DWORD; //intern Batch ID
END_VAR

BEGIN
wSTEP_NO := STEP_NO;
dwBA_ID := BA_ID;
dwFILL_ZERO := 0;
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyBA_NA); //reset complete memory
iERROR := BLKMOV(SRCBLK:=BA_NA,DSTBLK:= abyBA_NA); //copy used characters of string
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyText1); //fill complete memory
iERROR := BLKMOV(SRCBLK:=szText1,DSTBLK:= abyText1); //fill complete memory
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyText2); //fill complete memory
iERROR := BLKMOV(SRCBLK:=szText2,DSTBLK:= abyText2); //fill complete memory
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyText3); //fill complete memory
iERROR := BLKMOV(SRCBLK:=szText3,DSTBLK:= abyText3); //fill complete memory
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyText4); //fill complete memory
iERROR := BLKMOV(SRCBLK:=szText4,DSTBLK:= abyText4); //fill complete memory
iERROR := FILL(BVAL:=dwFILL_ZERO,BLK:= abyText5); //fill complete memory
iERROR := BLKMOV(SRCBLK:=szText5,DSTBLK:= abyText5); //fill complete memory
//ALARM_8P Call with parameters
//Call of instance address EEEE für ID is needed
ALARM_8P_1(EV_ID:=MSG_EVID,ID:=16#EEEE,
SIG_1:=SIG_1,
SIG_2:=SIG_2,
SIG_3:=SIG_3,
SIG_4:=SIG_4,
SIG_5:=SIG_5,
SIG_6:=SIG_6,
SIG_7:=SIG_7,
SIG_8:=SIG_8,
SD_1:=abyBA_NA,
SD_2:=wSTEP_NO,
SD_3:=dwBA_ID,
SD_4:=abyText1,
SD_5:=abyText2,
SD_6:=abyText3,
SD_7:=abyText4,
SD_8:=abyText5,
SD_9:=AUX_PR09,
SD_10:=AUX_PR10
);
MSG_STATUS := ALARM_8P_1.STATUS;
MSG_ERROR := ALARM_8P_1.ERROR;
MSG_DONE := ALARM_8P_1.DONE;
MSG_ACK_STATE := ALARM_8P_1.ACK_STATE;
END_FUNCTION_BLOCK