Abstract: A new Test Bench for speed governors has been developed and successfully tested in a
simulation laboratory and in a Hydro-Québec hydroelectric powerhouse. Equipped with a Real-Time
Simulator, the RT-LAB BERTA Test Bench makes it possible to cause the speed governor and turbine to
react as though they are operating in an islanded power system, while remaining connected to the main
grid. This ensures that the generating unit under test actually contributes to the stability of the whole
power system. On-site testing has demonstrated that previous speed governor settings which were
thought to be very stable were in fact generating undesirable power oscillations. Through the use of the
proposed Test Bench, more accurate settings can be made on-site without the need to conduct laborious
analyses.
Keywords: Speed Governor, Islanded Operation, Frequency Stability, Power System Stability, Speed
Regulation, Frequency Regulation, Test Bench, Real-Time Simulation.
Figure 2 : PID speed governor block diagram 3. MAIN PRINCIPLES TO CONSIDER WHEN
ADJUSTING A SPEED GOVERNOR
Test E1 shows that the system is well stabilized with the
appropriate integral gain Ki = 0.105. However, Test E2 shows Following the basic concept discussed in the preceding
that using a value Ki = 0.25 will destabilize the isolated section, basic principles can be derived that must be observed
system. when optimizing speed governor parameters.
2.2 Operating in Multi-machine Power System The first principle to follow when setting the speed governor
The simulation of a similar disturbance on a multi-machine of a synchronous generator is that the speed governor must be
power system model of an actual large power system (Figure set to ensure operating stability in an islanded power system,
3) illustrates the validity of this basic concept. This explains regardless of its actual operating mode, as demonstrated in
why, although rarely operating in an islanded power system, the preceding section.
A second important principle dictates that the speed
governor must avoid contributing to natural electro-
mechanical power oscillations. This typically occurs when
the control gains of the speed governors, mainly the
derivative gains, are too high or when the speed or electric
power signals attacking the speed governor control unit are
not properly filtered. The small oscillations of these two
signals in the frequency range between 0.4 Hz and 3 Hz,
characterizing synchronous operation in a multi-generator
system, reverberate on the displacement of the turbine gates
and generate destabilizing mechanical power oscillations.
Here are other principles to follow:
Each generating unit must contribute to regulating the
speed of the power system;
PSS behavior must not interfere with the speed governor Figure 4: Illustration of how RT-LAB BERTA is setup for
and conversely; onsite testing; configured with Physical Hardware-in-
Settings must be made as quickly as possible to the-Loop
minimize frequency deviations during a load variation, The current (2) and voltage (3) signals are captured on the
without compromising the operating stability in an secondary windings of the voltage and current transformers
islanded power system; of the generator.
Regulating action must not place excessive demand on
power chain components of the gate or valve Once captured, the signals are converted into voltage signals
servomotors. For instance, a high gain in the mechanical proportional to real values. These signals are within the ±15
amplification chain can cause intolerable vibrations in Volt range and are therefore compatible with the AD
the servomotors’ oil piping and compromise the security converters.
of the facility.
The frequency error signal, synthesized by the islanded Real-
Time Simulator or generated by a definite step or sinusoidal
function, is converted into alternating voltage (4) oscillating
4. HARDWARE-IN-THE-LOOP TEST BENCH at the simulated controlled frequency. It is then injected into
DESCRIPTION the appropriate input port of the speed governor.
4.1 Test Bench Setup with Physical Hardware-in-the-
Loop
The Real-Time Simulator incorporated into the RT-LAB 4.2 Test Bench Hardware Components
BERTA Test Bench enables high-fidelity testing and The proposed Test Bench’s equipment is designed to be
simulation to be conducted with physical Hardware-in-the- compact and portable, and includes:
Loop (HIL). Figure 4 illustrates how an actual RT-LAB
BERTA Test Bench is deployed for onsite testing; including Voltage and current sensors to adapt high-current and
how it will interface with physical hardware including a high-voltage signals to signals in the range of ± 15V;
physical Speed Governor under test, a physical Turbine under AD and DA input/output boards;
test, a physical generator synchronized to the real power grid, Standard PC computer with Intel Dual-Core processor
and physical Current & Voltage Transformers. for real-time computing;
3-way switch (2 for input, 1 for output) for connection
The electric power generated by the synchronous generator is between the generator output voltage, Test Bench output
controlled by the speed governor. This governor controls the and the input port of speed governor;
opening of the wicket gate, while the turbine generates the A laptop computer to control the Test Bench and signal
mechanical power driving the generator which transforms monitoring;
mechanical power into electric power. An additional flat screen;
The proposed Test Bench receives signals from the generator An emergency UPS power supply;
and from the speed governor. It also injects signals into the Two robust carrying cases;
speed governor to verify and optimize the speed governor Required cables and accessories.
parameters as if the synchronous machine were connected to
an islanded power system.
4.3 Test Bench Software Components
The signal for the gate servomotor stroke (1) is usually The basic software consists of the following:
available in the speed governor cabinet or can be captured
with a suitable meter. RT-LAB Real-Time simulation platform;
OPAL-RT TestDrive user interface (developed with
LabVIEW) to control and monitor the Test Bench;
BERTA Speed Regulator Test Software including the 5.2 PID Controller
following modules: The proposed Test Bench is also equipped with a PID
Digital calculators for frequency and electric power; controller that can be used instead of the speed governor’s
Modules to estimate the speed and mechanical actual PID controller. The output signal of this controller
power; replaces the output signal of the actual controller and directly
Real-Time Simulator of islanded power system drives the servomotor chain.
operation, including a power stabilizer simulation
5.3 Power System Stabilizer Simulation Function
function;
The proposed Test Bench also permits monitoring of Power
Adjustable PID controller;
System Stabilizer (PSS) behavior during a power system
Signal generator for speed errors;
frequency disturbance, enabling the engineer to determine
Signal converter for speed errors into AC modulated whether the PSS and the speed governor contribute together
voltage; to the system stability or react against each other.
Speed governor and turbine adjustable linear models
for comparison with real values. This topic has been emphasized by P. Kundur as a factor
“BERTA_Alert”: Continuous monitoring module, influencing inter-area modes of oscillations: “Speed-
including an automatic signal recording launcher governing systems normally do not have a very significant
following a frequency variation in the power system; effect on inter-area oscillations. However, if they are not
properly tuned, they may decrease damping of the
Test Bench optional modules include: oscillations significantly” (“Power System Stability and
Control”, P. Kundur, page 822)
“BERTA_Training”: Training and test preparation
module, including a simple power system model ready
for real-time simulation;
“BERTA_Ident”: Command (.m) and modeling (.mdl)
MATLAB files to facilitate off-line estimation of the
turbine and speed governor models.
The Real-Time Simulator enables the operator to quickly and But the opposite is also true. Figure 5 illustrates interesting
accurately set speed governor parameters, thereby ensuring cases where the PSS badly interferes with the speed
the frequency stability of the unit when operated in an governor. The simulated disturbance is a sudden load
islanded power system, and improving its contribution to increase that will decelerate all synchronous machines. Test
power system stability when it is synchronized with a large E11b, where the stabilizers are switched off, illustrates the
power system. increasing instability of a multi-machine power system at
natural power frequency of around 1 Hz. However, the
The Real-Time Simulator generates a speed error signal frequency signal envelope perfectly follows the islanded
corresponding to the behavior of the generator in an islanded system frequency curve. As shown by Test E61, the islanded
power system. Injecting this signal into the speed governor system behavior is stable, which means that the speed
while the unit is generating power in the system sets up a governor is correctly set. But simulating the PSS in cases
closed loop simulating the operation of an islanded system, E11, E41 and E51 shows a deteriorated stability in islanded
even though the AC generator is actually synchronized to a mode of operation. This means that the low frequency
multi-machine power grid. behavior of the PSS reacts against the speed governor. The
proposed Test Bench therefore allows for on-site validation
The speed error signal is added to the actual frequency signal
of PSS settings in case of generation or load rejection.
so that the governor will still react to an actual system
frequency variation. An AC generator outputs a 10 V AC
signal corresponding to the simulated frequency that will 6. ON-SITE TESTS & RESULTS
replace the original voltage signal. Conducting on-site tests at a powerhouse has traditionally
been a very costly endeavor since it requires the generator
under test to be taken offline. Extensive advanced planning
and coordination with the utility's operations centre is
required to schedule testing and typically all testing must be
completed in just a few hours. The result has been that only a
limited number of tests could be performed, producing results
that were not always accurate.
Using the proposed Test Bench, more extensive testing of a
greater number of speed governor settings can be performed
in a shorter period of time without compromising the stability
of the whole power system.
This is demonstrated through on-site tests performed in a
Hydro-Québec hydroelectric powerhouse in November 2008.
The set-up is as shown in Figure 4.
The simulated disturbance is a sudden 5% load increase. The
islanded frequency signal is used to modulate the generated
60Hz voltage signal that is injected into the speed governor Figure 7: Two different sets of PID gains.
voltage input port. Gate servomotors variation
The following figures clearly show that settings from Test20
(actual settings) are acceptable, but do not provide a very
good system damping. Settings from Test60 show a better
damping, though a greater initial speed decrease. Many other
tests were performed using different settings and load
variation steps. Hydro-Québec experts will eventually select
the best settings according to their operating philosophy.
More than 60 tests were performed within only a few hours.
This was achieved due to the very easy operation of the RT-
LAB BERTA Test Bench.
REFERENCES
Schleif, F.R. and Wilbor, A.B. (1966). The Coordination of
Hydraulic Turbine Governors for Power System Operation,
IEEE Transactions on Energy Conversion, USA
P. Kundur (1994). Power System Stability and Control,
Electrical Power Research Institute (EPRI), McGraw-Hill
International, USA
Figure 11: Rear view of the RT-LAB BERTA real-time
computer showing the I/O connection with the speed
governor during on-site testing by Hydro-Québec
powerhouse, November 2008