Академический Документы
Профессиональный Документы
Культура Документы
2
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Ducts Insulations
The need for duct insulation is influenced by
(1) Duct location, whether indoors or outdoors.
(2) The effect of heat loss or gain on equipment size and operating cost.
(3) The need to prevent condensation on low-temperature ducts.
(4) The need to control temperature change in long duct lengths.
(5) The need to control noise with interior duct lining.
Figure 1
3
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Duct insulations include semi rigid boards and flexible blanket types,
composed of organic and inorganic materials in fibrous, cellular, or
bonded particle forms. Insulations for exterior surfaces may have attached
vapor barriers or facings, or vapor barriers may be applied separately.
When applied to the duct interior as a liner, insulation both insulates
thermally and absorbs sound. Duct liner insulations have sound-permeable
coatings or other treatment on the side facing the airstream to withstand air
velocities without deterioration.
Fibrous glass ducts are available in preformed round ducts or in board
form for fabrication of rectangular ductwork. Round and rectangular ducts
have a minimum density of about 48 kg/m3, with a thermal conductivity of
0.033 W/(m·K) at 24°C mean temperature.
Round ducts with a diameter of up to about 760 mm and boards in various
thicknesses and sizes are used to form required sizes of rectangular ducts.
The maximum recommended velocity is 10 m/s, although tests at
velocities exceeding 50 m/s show no fiber erosion. Primary use is for low-
pressure systems tested at 1.5 times the recommended static pressure.
Maximum recommended air temperature is 120°C. A complete system
provides greater decibel attenuation than is usually provided by standard
duct liners, with greater reduction in airborne equipment noise and
crosstalk. Higher design velocities are also possible.
Heating Ducts
The effect of duct insulation on residential heating system equipment
size can be marginal. However, insulation can reduce operating costs
significantly, depending on unit costs for heating and the extent of duct
exposed to outside conditions. In addition, duct insulation maintains the
supply air temperature, which may keep the air entering the conditioned
space within a more comfortable range.
Vapor retarders are not required on exterior insulation of ducts used for
heating alone, but they must be provided for ducts used for alternate
heating and cooling.
4
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Cooling Ducts
Insulation can reduce operating costs and cooling equipment size
significantly. The advantage of adequate insulation is especially
significant in areas with high dry-bulb and dew-point temperatures.
Ducts for summer air conditioning are insulated with the same materials as
heating ducts. Ducts in any unconditioned space should be insulated and
have vapor retarders to prevent condensation.
Joints and laps in the vapor retarder must be sealed. Flexible closed cell
insulation does not always need a supplemental vapor retarder, but care
must be taken to form vapor-tight seams at joints.
5
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Lower equipment costs. Duct insulation can reduce space conditioning
loads and, and in some cases, allows for the installation of smaller, less
costly heating and cooling equipment.
6
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
7
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Figure 1 A
Figure 1 B
Use Figure 13A to determine U-factors for insulated and uninsulated
ducts. Lauvray (1978) has shown the effects of (1) compressing insulation
8
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
wrapped externally on sheet metal ducts and (2) insulated flexible ducts
with air-porous liners. For a 50 mm thick, 12 kg/m3 fibrous glass blanket
compressed 50% during installation, the heat transfer rate increases
approximately 20% (see Figure 1A). Pervious flexible duct liners also
influence heat transfer significantly (see Figure 1B). At 12.7 m/s, the
pervious liner U-factor is 1.87 W/(m2 ·K); for an impervious liner, U =
1.08 W/(m2·K).
Figure 1 A,B shows heat transfer coefficients for insulated and uninsulated
ducts. Note that when internal insulation is used, the external duct
dimensions must be increased to compensate. Also, the roughness factor
for internal duct lining may differ significantly from the ‘‘standard’’
roughness of 0.0003. In calling out duct sizes, it is common practice to
present the net free duct size and add the internal insulation thickness to it,
i.e., 24 _ 12 in _ 1 in AL. In some applications code requirements for
indoor air quality may prohibit the use of internal duct insulation.
Example 1.
A 20 m length of 600 mm by 900 mm uninsulated sheet metal duct, freely
suspended, conveys heated air through a space maintained above freezing
at 5°C. Based on heat loss calculations for the heated zone, 8100 L/s of
standard air [cp = 1.006 kJ/(kg·K)] at a supply air temperature of 50°C is
required. The duct is connected directly to the heated zone. Determine the
temperature of the air entering the duct and the duct heat loss.
9
Air Conditioning Equipment Technology
Mr. Dastan Zrar Ghafoor Chapter 1
Example 2.
Same as Example 1, except the duct is insulated externally with 50 mm
thick fibrous glass with a density of 12 kg/m3. The insulation is wrapped
with 0% compression.
10