KUHSE OPERATIONAL INSTRUCTION TA81NX0-E

Genset Automatic Control Unit June 2002


for start-stop of emergency power gensets
Type: KEA 081 - NSTR Replaces : December 2001

CONTROLS ON ALARM 6

AUTOM. DEVICE LOCKED ALARM 7

START INDICATION ALARM 8

OVERCRANK / TROUBLE ALARM 9

ALARM 1 ALARM 10

ALARM 2 ALARM 11

ALARM 3 ALARM 12

ALARM 4 ALARM 13

ALARM 5 ALARM 14

LED ALARM
OFF MANUAL AUTO TEST START
TEST OFF

APPLICATION OF AUTOMATIC CONTROL UNIT

The automatic control unit KEA 081-NSTR is The functions of the output relays and of the rele-
applied in emergency power supply installations. vant parameters are programmable by means of a
Difference to the type KEA 071-NSTR is that this Laptop. The KEA unit is provided with an optical
module does not need a relay unit (RZ) because fibre conductor (OFC) interface, by which an
18 output relays (max. 1 amp., 35 V GS) are inte- automation control system (a protocol converter
grated. The unit may be applied to 12 - or 24 volt might be required), a fault signal extension or a
supply voltage, the voltage range is selected by an remote monitoring system (TELEMON) may be
internal switch. For monitoring of the installation connected.
and of the genset 14 external fault signal indica- The automatic unit contains following soft-
tions, and 4 internal fault signals each, initiated ware:
from mains- and generator voltage sensor, are − mains failure detection,
provided. − activation of start pre-conditions,
A measuring accessory MZ 081 is required in − starting-up of engine on start release,
order to measure the mains- and generator volt- − change-over from mains to generator supply,
age. This measuring accessory (the connecting − frequency control on island operation mode,
cable is not included) belongs to the scope of de- − genset monitoring and protection,
livery. The mains- and generator voltage is meas-
− detection of re-established mains voltage,
ured in 3-phase mode. It is monitored for:
− change-over to mains supply,
− under- and over voltage,
− running-out and shutdown of the genset,
− under- and over frequency,
− battery voltage sensor.
− asymmetry.

Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39


Telephone +49 (0) 4171 798-0, FAX +49 (0) 4171 798-117, http://www.kuhse.de
TA81NX0-E - 2 / 10 - 06/2002

WARNING HINTS
⇒ This unit must be applied only for the purpose mentioned under 'APPLICATION'.
⇒ Installation and commissioning must be carried out by sufficiently qualified staff only.
⇒ Applicable regulations, especially the VDE rules, are to be observed.
⇒ The unit's programming must be carried out in a way to except absolutely hazards against per-
sons and things.

Table of Contents

Design page 3 Overspeed page 8


Battery under voltage page 8
Operation- and indication elements page 3
Fault signals 13 and 14 page 8
Operation and functions page 3 Mains C.B. tripped page 8
Selector OFF page 4 Generator C.B. tripped page 8
Selector MANUAL page 4 Engine does not stop page 9
Selector AUTOMATIC page 4 Internal signals of the
Selector TEST page 5 Voltage Sensors page 9
Push button START page 5
Software page 9
Push button LED TEST page 5
Starting sequence page 9
Push button ALARM OFF page 6
Operate- / shut-down solenoid /
Operational- and fault signals page 6 gas magnetic valve page 9
Controls on page 6 Run-up detection page 9
Automatic device locked page 6 Frequency control on emergency
Start indication page 6 power mode page 10
Overcrank / engine trouble page 6 Emergency stop / Emergency off page 10
Mimic Diagram / Voltage Sensors page 6 Technical data page 10
Fault signal indications page 7 Purchase order numbers page 10

Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39


Telephone +49 (0) 4171 798-0, FAX +49 (0) 4171 798-117, http://www.kuhse.de
TA81NX0-E - 3 / 10 - 06/2002

DESIGN

The automatic control unit is provided for installa- Modem can be connected. By this the following
tion into the switchboard front door. Protection settings are enabled (input is password-protected):
degree IP 44 is attained at installed status. The − coding of the fault signal indications for
fault signal indications are marked by inter- o warning or shutdown,
changeable text labels. The measuring accessory o NC- or NO circuits,
MZ 081 is fitted with a snap-on fastening for DIN o delayed or un-delayed monitoring,
EN 50 022 rail. It is provided for installation on o generator C.B. tripping /not tripping,
the mounting plate and fulfils the protection de- − programming of the response values of voltage
gree IP 00. It is connected to the automatic unit by and frequency sensors, of timers and other
means of a multi-core cable and serves for mains- function blocks,
and generator voltage monitoring. − indication of the actual status of the external
The automatic unit is fitted with an optical fi- signal contacts, of actual values of voltages,
bre conductor (OFC) interface, by which a PC or frequencies, timers and the engine speed.

OPERATION- AND INDICATION ELEMENTS

LEDs for LEDs for alarm indications


basic functions according to customers order

LEDs for mains voltage


and frequency
CONTROLS ON ALARM 6

AUTOM. DEVICE LOCKED ALARM 7


LEDs for generator
LEDs for alarm START INDICATION ALARM 8 voltage and frequency
signals
OVERCRANK / TROUBLE ALARM 9

according to
ALARM 1 ALARM 10
Push button Mains ON
customers order
ALARM 2

ALARM 3
ALARM 11

ALARM 12
Push button Gen. ON
ALARM 4 ALARM 13

ALARM 5 ALARM 14 Push button Mains OFF


Push button Gen. OFF

Signal: gen. C.B. is ON


Signal: mains C.B. is
LED ALARM
OFF MANUAL AUTO TEST START
TEST OFF

ON

Push button selector Push buttons

OPERATION AND FUNCTION

All indicating and operating elements are ar- an input (e.g. by connecting a key-operated con-
ranged clearly visible on the automatic unit front trol switch); so an unintentional or unacceptable
plate. The operation modes are to be selected by change of a decided selection can be avoided. By
means of four push-buttons with integrated LEDs, means of the push-button selector, the following
showing the actual selected position. The push- modes of operation are to be selected.
button selector may be electrically locked-out by
TA81NX0-E - 4 / 10 - 06/2002

PUSH BUTTON SELECTOR: OFF

On connecting the automatic control unit to bat- − Shut-down of genset (if running),
tery voltage, this operational mode will be pre- − Switching-off of all indicated fault signals, ex-
selected automatically (Reset Function), to pre- cept fault indications 13 and 14, as long as the
vent the genset from starting unintentionally. On corresponding alarm contact is active,
switching-over from any other operational mode − Reset of automatic unit, in case the external
to position OFF, following will be initiated: EMERGENCY STOP contact is not active.

PUSH BUTTON SELECTOR: MANUAL

On selecting this operational mode, a relay, which Changing back to mains supply takes place by
is configured for the function AUXILIARY DRIVES means of the push button MAINS ON. On pressing
ON is energized at once. The LED START INDICA- the push button GEN. OFF, the generator C.B. is
TION shows flashing light. In case the start can be disconnected indeed, but the mains C.B. does not
enabled, a reply signal is required (e.g. gas leak- close accordingly. Connection of the mains C.B.
age tested, exhaust gas flap open, pre-lubrication has to be made manually.
pressure attained). The blinking LED START IN- Similarly the mains C.B. is not automatically
DICATION changes (on engine stand-still) to connected in case a fault signal (e.g. GENERATOR
steady light. In case no starting release is required, OVER CURRENT) appears during generator opera-
the input must be permanently connected to L[-] tion, which disconnects the generator.
potential. Now the engine may be started-up by Pressing the ON push buttons is non-effective
pressing the push-button START. in case the voltage of the selected system (mains
By means of the mimic diagram arranged push or generator) is not within its pre-set limit values
button MAINS OFF (O) the mains C.B. may be dis- or in case the phase sequence is incorrect.
connected, even on engine standstill. By means of The remote start command does not effect an
the push button MAINS ON (I) it may be connected automatic generator circuit breaker closing. To
again. stop the genset, the push-button selector is to be
Provided, the generator voltage and frequency set to position OFF (no remote start command
are within their rated value limits, then by means alive) to position AUTOMATIC.
of the push-buttons MAINS OFF respectively GEN.
ON, change-over to genset operation may take
place.

PUSH BUTTON SELECTOR: AUTOMATIC

In case of faultless mains voltage the mains (e.g. gas leakage checked, exhaust gas flap
voltage supply is connected and the genset is on opened, pre-lubrication pressure attained), a reply
standby mode. The mains voltage is permanently signal for the start release must take place. The
measured and monitored. As soon as the pro- blinking LED START INDICATION changes
grammed limit values of voltage or frequency are thereby (on engine standstill) to steady light. Pro-
no longer kept, the condition will be indicated by vided no starting release is required, the input
means of the corresponding mimic diagram ar- must be permanently connected to negative poten-
ranged LEDs (f<, f> U<, U>). After running-out tial [L-].
of a programmable time lag the genset will be If the genset should not start, even after com-
started-up. The automatic unit may be pro- plete cranking sequence program has elapsed, the
grammed in a manner either to initiate always a fault signal OVERCRANK/ENGINE TROUBLE will
starting-up in case of mains failure, or starting-up occur and the automatic unit will be locked-out.
takes place only in case of a simultaneous remote When the generating set, after running-up, has
start command is given. This function enables an reached nominal voltage and frequency, the mains
additional start interlock. circuit breaker will be disconnected and after a
At the automatic start procedure first of all a time lag (about 2 sec., programmable) the genera-
relay is energized which performs the function tor circuit breaker is closed. After mains voltage
AUXILIARY DRIVES ON (relay must be pro- re-establishing a delay time starts running-down
grammed). The LED START INDICATION shows (reconnection delay period) before the generator
blinking light. In case the start can be released C.B. is disconnected and after elapsed change-
TA81NX0-E - 5 / 10 - 06/2002

over delay the mains C.B. is connected again. To Additionally to the start initiation by mains failure
prevent the engine from a heat increase, the genset the genset start can be initiated also by means of
will run unloaded for an adjusted idle run time two remote start commands in this push button se-
(cooling-down period), and then will be shut- lector position:
down. − start along with change-over,
The automatic unit may be programmed in a − start without change-over.
manner to initiate the start and change-over to
generator operation also in case the mains circuit At a remote start along with change-over to
breaker is tripped by a disturbance (for generator operation, the genset is started-up simi-
switchboards according to VDE 107). The genset lar to mains failure mode. Also change-back is
is started-up automatically in that case and takes similar to mains re-establishing. The input start
over the emergency power supply. The mains without change-over is provided for e.g. sprin-
C.B. tripping is indicated by a fault signal. The kler installations. In case the genset is started-up
fault signal MAINS C.B. TRIPPED must be deleted via this input, only the starting program is running
to enable mains reconnection operation. In case of down, no change-over takes place. If now a mains
faultless mains voltage the automatic unit changes failure should occur, however a change-over to
back to mains supply after the reconnection delay emergency power supply takes place.
period has elapsed.

PUSH BUTTON SELECTOR: TRIAL / TEST

On selecting this operational mode, a relay, which connected, or by means of the push buttons GEN.
is configured for the function AUXILIARY DRIVES OFF (O) or MAINS ON (I) the generator can be dis-
ON is energized. The LED START INDICATION connected.
shows flashing light. In case the start can be en- If during test operation mode a mains failure
abled (conditions similar to selector switch posi- occurs or a remote start with change-over com-
tion MANUAL), the blinking LED START INDICA- mand is given, change-over to generator operation
TION changes to steady light. The starting pro- take place. Now a manual generator circuit
gram is initiated after start release. breaker disconnection is impossible.
Provided, the generator voltage and frequency To stop the genset, the push-button selector is
are within their rated value limits, then by means to be set to position OFF or (no remote start com-
of the mimic diagram located push-buttons GEN. mand alive) to position AUTOMATIC.
ON (I) or MAINS OFF (O) the generator can be

PUSH BUTTON: START

In case operational mode MANUAL is selected, the In case the diesel engine requires pre-glowing, ar-
starter motor can be energized and the engine can rangements for this must be realized externally.
be cranked by pressing the push-button START. When another operational mode is selected or
If the automatic unit's program is programmed for when generator set is running, the push-button is
gas engine, this program sequence will run. not active.

PUSH BUTTON: LAMPS TEST / LED TEST

The operative readiness of all LEDs of the auto- an actual alarm signal. To include in this test other
matic control unit can be checked by means of signal lights, assembled in switchboard panels, a
this push-button, without initiating or suppressing relay can be programmed to this function.

PUSH BUTTON: ALARM OFF

By a pulse of this push-button, the audible signal ble LED signal may be switched-off by pressing
caused by a fault signal, will be silenced. After the push-button once again.
having eliminated the source of trouble, the visi-
TA81NX0-E - 6 / 10 - 06/2002

OPERATIONAL- AND FAULT SIGNAL INDICATIONS

Above the push button selector there are, arranged The following indications are provided as a basic
on the left side in two verticals, LEDs for indicat- fitting:
ing important relevant operating and fault events.

CONTROLS ON

After starting-up of the genset, this green LED tion is switched-off, as soon as the shut-down
signal indicates activating of monitoring circuits, procedure is beginning.
which are depending on genset's run. The indica-

AUTOMATIC UNIT LOCKED

This indication shows, that an external EMER- To reset the control unit, the push-button selector
GENCY STOP push-button has been pressed or that has to be set to position OFF(RESET). Prior to this,
a faulty condition has caused the genset to shut- the reason for trouble has to be eliminated, or the
down. The red LED indicates, that the automatic EMERGENCY STOP push-button has to be
control unit as well as the genset is locked-out for unlocked.
any further starting attempt.

START INDICATION

This signal is lighting, if there is a starting de- DICATION is flashing. On enable signal, the LED
mand, processed by the automatic control unit at changes to steady light.
AUTOMATIC mode or if the operational mode The indication is switched-off automatically,
MANUAL or TEST is selected. As long as there is as soon as the genset's actual speed on running-up
no enable signal for starting, the LED START IN- exceeds the firing speed. Now, it is not possible,
to actuate the starter motor, not even manually.

OVERCRANK / ENGINE TROUBLE

This signal is switched-on, in case shut-down command emitted by the automatic


− the genset has not started, even after the com- control unit (with signal AUTOMATIC UNIT
plete start sequence program has elapsed (si- LOCKED),
multaneously with signal AUTOMATIC UNIT − the genset is still running even after complete
LOCKED), stop time has elapsed (without signal AUTO-
− the genset came to a standstill without any MATIC UNIT LOCKED).

MIMIC DIAGRAM / VOLTAGE SENSOR

The mimic diagram symbolizes the mains incom- and delay times can be classified. Four red and
ing, the generator, mains- and generator circuit two green LEDs each are provided for the mains-
breaker and the bus bar. Push-buttons are assem- and generator voltage monitoring. These LEDs
bled for: indicate, whether the voltages are within their
− MAINS ON (I), nominal ranges or whether and which deviations
− MAINS OFF (O), are present.
− GENERATOR ON (I), These LEDs, of first line below the mains- re-
− GENERATOR OFF (O). spectively generator symbol (from left to right),
are indicating:
The position of the mains- respectively generator − under frequency (<f),
circuit breaker is indicated by green LEDs, ar- − voltage / frequency within nominal range,
ranged below the corresponding push-buttons.
− over frequency (>f).
Functions of the voltage sensors, switching points
TA81NX0-E - 7 / 10 - 06/2002

The second LED line of LEDs indicates: When voltage or frequency values have recovered
− under voltage / incorrect phase sequence(<U), to pre-determined limits, the red LED goes out at
− voltage / frequency within nominal range, once and a delay release time starts running down.
− over voltage (>U). The green LEDs are flushing during this period
and will change to steady light, when the delay
The signal "Undervoltage" is also presented in time has elapsed. Internally, now the voltage sys-
case the measuring voltage of the generator is tem is recognized as "within nominal limits".
connected with a left turning rotating field or, in The LEDs of the generator voltage sensor are
case the voltage shows a voltage vector asymme- out of order in case the operational mode OFF is
try. selected, or in case no starting command is alive
The monitoring criteria of the mains-and gen- during operational mode AUTOMATIC. The LEDs
erator voltage sensor may by classified in such a of the mains voltage sensor are always active.
manner that:
− the sensor is non-effective, LED indication along with fault signal
− the corresponding LED operates as a static When programmed for fault alarm signals in case
indication for the voltage sensor output, of deviation from nominal voltage or frequency
− or the voltage sensor output is connected to an values, the alarm will be activated only after drop-
internal fault alarm. out time lag has elapsed. The green LEDs extin-
guish and the corresponding red LED is actuated
Static LED indication only as a normal fault indication, i.e. it is flashing, the
The corresponding red LED is alight, when an en- horn sounds. This signal is, similar to all other
abled monitoring detects a deviation from nomi- fault indications, included into the common alarm
nal value. During drop-out time lag, the mimic signal.
diagram arranged green LEDs remain lighted, un-
til the delay time has elapsed. The function will be
processed now internally.

FAULT SIGNALS

The basic configuration of the automatic control The eight signals, which are internally used to
unit include the possibility of processing 24 single monitor the mains- and generator voltage, are:
fault signals, by which 4 each are provided for the − mains under- and over voltage,
mains- and generator voltage monitoring and 14 − mains under- and over frequency,
are freely applicable by the user. The fault signals − generator under- and over voltage,
are basically divided into three groups: − generator under- and over frequency.
− The operation depending fault signals (e.g.
LOW OIL PRESSURE) are just released for If, during automatic mode the generator is discon-
monitoring with a time lag after running-up of nected by means of a fault signal, the engine is
the genset, noticeable by the LED signal CON- stopped after elapsed running-out period and the
TROLS ON.
automatic unit is locked-out.
− The operation independent fault signals (e.g. Coming-up of a fault signal is indicated by
BATTERY UNDERVOLTAGE) are permanently blinking LEDs. Simultaneously the audible signal
active, except the selector switch is set to po- is activated (for the pre-set duration). By means of
sition OFF. a pulse given by the push button ALARM OFF (or
automatically after running-out of the pre-set
− The fault signals 13 and 14 are selector
time) the audible signal is silenced, along with a
switch - and operation independent. They
change of the blinking indication into steady light.
are applied for indications (e.g. LEAKAGE),
Several warning alarms which could occur in se-
which have to be permanently signalled, even
quence, would repeatedly release the audible
on selector switch position OFF. The horn is
alarm; each alarm is indicated by the correspond-
not energized in position OFF, but the fault
ing blinking LEDs as well.
signals are included into the common alarms.
In case of warning alarms, another pulse by push
These fault signals are acting similar to nor-
button ALARM OFF will cancel the visible signal,
mal fault signals on having set the selector
provided the matter of alarm has been eliminated.
switch to any operational position (but not
OFF).
TA81NX0-E - 8 / 10 - 06/2002

In case of signals, which lead to a shut-down of having eliminated the faulty condition (for exam-
generator set, any subsequent operation is locked ple, unlocking of an external EMERGENCY STOP
out by the automatic control unit. This condition push-button), the push-button selector has to be
is shown by the signal AUTOMATIC DEVICE set to position OFF. Now it is possible, to select
LOCKED. To reset the automatic control unit, after again an operational mode.

OVERSPEED

For overspeed monitoring either the internal gen- overspeed alarm, this fault signal causes always a
erator frequency or the frequency of a separate genset shut-down, even in case all fault signals are
speed sensor (pick-up or tacho generator) may be configured for warning only (e.g. on sprinkler sys-
used. Provided a fault signal is programmed for tems).

BATTERY UNDERVOLTAGE

An internal sensor may be classified for battery 081 has to be connected to another source than the
voltage monitoring. To monitor this signal prop- monitored.
erly, the voltage supply for automatic unit KEA

FAULT SIGNALS 13 AND 14

These two signals may be delayed from contract OFF, however without audible signal. Criteria,
closing 0 up to 240 sec., i.e. the alarm contact which have to be always signalled, can be moni-
must be active for the programmed time delay to tored by this (e.g. tank filling level, leakage warn-
initiate a fault signal. Furthermore these two fault ing).
signals are also active on selector switch position

INTERNAL SIGNAL: MAINS C.B. TRIPPED

The mains circuit breaker can be monitored emergency power supply during operational mode
against automatic tripping (e.g. by installed over TEST. The fault signal is internally triggered in
current tripping devices). In case this fault signal case no position indication signal (mains C.B. is
is provided (necessary to fulfil the VDE 107 rule), ON) takes place after running-out of the mains
starting-up takes place on push button selector po- C.B. closing pulse.
sition AUTOMATIC respectively a change-over to

INTERNAL SIGNAL: GENERATOR C.B. TRIPPED

The generator circuit breaker can be monitored grammed for the assigned fault signal. The fault
against automatic tripping (e.g. on installed over signal is internally triggered in case no position
current tripping device). Therefore a valid fault indication signal (Generator C.B. is ON) takes
signal number must be programmed (see Service place after running-out of the generator closing
Instruction) for this function. Additionally the pulse.
function "warning/shut-down" must be pro-

INTERNAL SIGNAL: ENGINE DOES NOT STOP (ENGINE TROUBLE)

If, after running-out of the stopping period, the By this an alarm is initiated in case the stopping
"Running" signal of the engine is still active, the device of the engine (e.g. defective stopping sole-
fault signal OVERCRANK / TROUBLE is triggered. noid, faulty gas magnetic valve) is out of work.
TA81NX0-E - 9 / 10 - 06/2002

INTERNAL SIGNALS OF VOLTAGE SENSORS

The frequency - and voltage deviations of the sounds and the relevant common alarm is acti-
mains and generator may be indicated as fault vated.
signals. Provided the function is programmed as A fault signal does not effect the voltage sen-
fault signal, the indication on variant voltage takes sor output. If, e.g. the fault signal GEN UNDER
place as late as the dropping delay has running- FREQUENCY was active as warning signal, but the
out. The green LEDs are extinguished then and frequency is correct again, the fault signal remains
the corresponding red LED is illuminated as a active but for the internal control action of the
normal fault signal, i.e. it is blinking. The horn automatic unit the generator voltage is considered
as "correct".

STARTING SEQUENCE

The following parameters are provided for the − speed detection by pick-up,
start/stop sequence: − RUNNING signal by charging dynamo D+,
− start delay, − RUNNING signal by generator voltage,
− cranking time, − pick-up-, tacho generator frequency on nomi-
− time lag between STARTER ON and IGNITION nal speed,
ON, − starter speed, drop value,
− time lag between IGNITION ON and GAS − firing speed, drop value,
VALVE OPEN, − nominal speed, drop value.
− break time,
In case of using diesel engines, fitted with pre-
− delay time CONTROLS ON,
glowing device, an external pre-glow push-button
− mains recovery delay,
must be provided, operative on operational mode
− cooling-down period, MANUAL. For an automatic start sequence, the
− stopping time, pre-glowing time (start delay) can be pro-
− number of cranking attempts, grammed.
− speed detection by tacho generator,

FREQUENCY CONTROL ON EMERGENCY POWER SUPPLY MODE

During emergency power supply mode, the fre- The automatic unit emits adjusting pulses to the
quency can be regulated to a nominal value, inde- speed control device in case the frequency is not
pendent of the genset load. Therefore, the engine within classified limit values. There is a break be-
must be equipped with a speed control device or tween two pulses, which enables the engine to
with an electronic governor, fitted with control carry out the speed adjusting command.
input.

EMERGENCY STOP / EMERGENCY OFF (EXTERNAL)

Only one short pulse is needed to initiate the − output for the start pre-conditions switched-
EMERGENCY STOP procedure. Independent of ac- off,
tual operational mode, the following functions − locking-out of the automatic control unit for
will be activated: any further starting attempt (indication:
− tripping of generator C.B., AUTOMATIC DEVICE LOCKED).
− shut-down of genset,
TA81NX0-E - 10 / 10 - 06/2002

TECHNICAL DATA

DESIGN − Nominal voltage 231 / 400 volts,


− KEA unit for flush mounting adjusting range 138 - 276 volts.
− Dimensions (WxHxD): 260 x 170 x 90 mm − Nominal voltage 3 x 400 volts,
− Weight approx. 2.2 kg adjusting range 240 - 480 volts.
− Protection degree (installed): IP 44 − Wrong rotating field causes indication <U
− Ambient temperature: − Generator frequency 50 or 60 Hz,
− Storage -20 °C ... +80 °C adjustable 40 to 70 Hz, contin. (<0.1 Hz)
− Operation 0 °C ... +55 °C − Input for battery voltage sensor
− Standards/Regulations: DIN EN 50 178
INPUTS, OUTPUTS, INTERFACE
MEASURING ACCESSORY − 14 terminals for fault signal contacts, option-
− Dimensions (WxHxD): 225 x 70 x 40 mm ally NO/NC circuits,
− Weight approx. 1 kg − internal fault signals each of mains and gen-
− Protection degree: IP 00 erator voltage: 2 x voltage, 2 x frequency
− 18 outgoing relays, thereof 14 for program-
POWER SUPPLY ming, max. contact rating 35 V DC, 1 amp.
− 12 V or 24 V DC +/- 15 %, changeable − Optical fibre conductor (OFC) interface for
− Range of function ability: 9 V - 35 V DC coupling to PC for adjusting jobs, to an
automation control system by additional hard-
ANALOGUE INPUTS and software, to a fault signal extension or to
Mains and generator voltage sensor, adjustable in a remote monitoring system (TELEMON).
1-volt-steps
− Nominal voltage 3 x 100 volts,
adjusting range 60 - 120 volts.

Purchase order numbers: 2A81N X 0


Mains- / Gen. voltage
3 x 100 V 3 x 100 V 1
3 x 100 V 231/400 V 2 Example: Automatic control unit for emergency power
3 x 100 V 3 x 400 V 3 installations, mains- and generator volt. 231 / 400 V
231/400 V 3 x 100 V 4 ⇒ purchase order no.: 2A81N50
231/400 V 231/400 V 5
231/400 V 3 x 400 V 6
3 x 400 V 3 x 100 V 7
3 x 400 V 231/400 V 8
3 x 400 V 3 x 400 V 9