D E
1545 1545
9T12-07-150 All dimensions to be confirmed on site.
A B C D E F G H 1. All dimensions are in millimeters unless
indicated otherwise.
T12-10-200 2. All dimensions to be confirmed an site.
23950 9T12-05-150 3. All structural drawings must be read in
9T12-03-150 conjunction with all the other relevant
1430 4270 4730 3090 4730 4270 1430 drawings from other consulting disciplines,
9T12-04-150
any discrepancies found should be
T12-10-200
1710
500
500
9T12-05-150 communicated immediately.
9T12-06-150
T12-11-200
C1 C1 C1 C1 4. Foundations shall generally be taken down
9T12-04-150 1000 mm below existing ground level and all
1 BEAM 01 (230X450) BEAM 01 (230X450) 1
3000
excavations to be approved first by the
T12-11-200
C2 C2
T12-11-200 engineer before concrete blinding is laid
BEAM 02 (230X450)
5. Weak Pockets of bearing strata to be dug out
and filled with Grade 15 all in concrete mix.
17T10-14-200 T
17T10-14-200 T
1000 1000 Approval by Engineer.
14T10-01-2per rib bott. T12-11-200 7. All Structural Concrete to be Tested for
9T12-08-150
3190
3190
Compressive Strength by an Approved
150
9T12-09-150 8. Concrete to receive full time curing preferably
6T10-10 2top, 4bott 6T10-10
surface curing or equal and approved by the
2top, 4bott 2top, 4bott
Engineer.
E
345
345
9T12-07-150 9. Concrete Mixes:
C1 BEAM 03 (230X450) C1 · Mass concrete to have a minimum
C1
T12-10-200 works cube strength of 15N/mm² at
BEAM 01 (230X450) BEAM 01 (230X450)
28 days with 40 mm Maximum
E
aggregate size.
1365
1365
· Reinforced concrete to have a minimum
works cube strength of 25 N/mm² at 28
20T10-11-2per rib bott. C2 C2 20T10-11-2per rib bott. days with 20 mm maximum Aggregate
2T16 T12-11-200 9T12-05-150
BEAM 05 (230X450) BEAM 05 (230X450) size.
800
800
4. Reinforcement
Staircase 9T12-06-150 9T12-04-150
350
C2 C1 · T....denotes High yield bars to be round
12500
12500
C1 R8@200 c/c
(See details)
3000
2 BEAM 06 (230X450) 1200 BEAM 06 (230X450) 2 9T12-02-150 9T12-06-150 and ribbed bars to B.S.4461.
5300
4T10-05-2per rib bott.
BEAM 10 (230X450)
BEAM 11 (230X450)
BEAM 12 (230X450)
BEAM 12 (230X450)
BEAM 11 (230X450)
BEAM 10 (230X450)
BEAM 09 (230X450)
5. Minimum cover to all steel in
1000 Section thru
24T10-14-200 T
24T10-14-200 T
T12-11-200 foundations,ground beams and stub
1000 Half Landing Beam columns to be 40 mm unless shown
9T12-08-150 9T12-07-150
T12-10-200
otherwise.
4500
4500
6. Block Work: All load bearing block walls to be
12T10-13 12T10-13 9T12-09-150 constructed from solid block of 5.0N/mm
9T12-01-150
4top, 8bott 4top, 8bott min.with B.S 5628 Part 1 Structural use of
D D 9T12-02-150
Unreinforced Masonry. Mortar to conform to
Mortar designation (III) of Table 1 BS 5628
450
Part 1.
6T10-08 6T10-08 7. Joints: Movement joints to be a maximum
F
BEAM 04 (230X450)
C1 C1 C2 C1 C2 C1 C1 8. Beams Dimensions should be as
22T10-14-200 T
22T10-14-200 T
C1 ROOF BEAM LEVEL ROOF BEAM LEVEL
documented in the general Arrangements'
350
350
F
1800
1800
18T10-07-2per rib bott. 18T10-07-2per rib bott. details.
3 9. All steels laid and fixed will be inspected and
approved by the Project Engineer, Design
Engineer and Local Government
4 BEAM 08 (230X450) BEAM 08 (230X450) 4 Supervision/Technical Team before concrete
casting commences.
C1 C1 C1 C1
4T16-01 4T20-01
STAIRCASE PLAN VIEW 10. Concrete Cover to Center Top steel is 50mm
and 40mm to Bottom Center Steel.
1430 4270 730 4000 3090 4000 730 4270 1430 11. Concrete For Beams to be of 30-35N/mm²
Compressive Strength and 20mm
3000
3000
T10 Top
16R8-02
16R8-02
23950 01 01 01 01 Aggregates.
1200
2650
2650
12. All Structural Concrete to be Tested for
BRC MESH BS No 142 300 BRC MESH BS No 142 Compressive Strength by Central Materials
75
T10-2per rib top & bott.
230
230
.Laboratory.
A B C D E F G H 13. Concrete to receive full time 28DAYS' curing
preferably surface curing or equal and
01 01 01 01 approved by the Engineer.
150 300 150 300 150 300 150 300 150 300 150 300 150 300 150 300
150
1000
1000
T10-2per rib bot 230 230 FLOOR 14. Shuttering striking off to commence only after
SECOND
225MM THICK RC 1st & 2nd FLOOR MAXSPAN SLAB DETAILS SECTION F-F thru FLOOR SLAB SECTION E-E thru FLOOR SLAB
approval by the Project Engineer,Design
Engineer and the Local Government
225
225
Supervision/Technical Team.
SECOND FLOOR 15. Solid Slab is 150mm Thick Unless Shown
SUSPENDED SLAB CONSTRUCTION NOTES T10-2per rib bott
BRC MESH BS No 142 otherwise.
300 300 16. Structural steel to be of grade 43C to BS
75
1. 75mm thick concrete toping 4360
17. Welding to be metal arc process in
2. 150mm thick masxpans accordance with BS5135 and BS4570 as
225
225
3. A142 BRC mesh in concrete toping appropriate.
175
T10 Bott T10-200c/c Top 1 18. All fillet welds shall be 6mm minimum and
continuous on all sides by welders approved
4T16-01 4T20-01
SECTION D-D thru FLOOR SLAB 19.
to BS 4872 Part 1.
All load bearing block walls are to be
A B C D E F G H constructed from solid blocks of 5.0 N/mm²
23950 minimum characteristic strength complying
3000
3000
75mm Kicker 01 01 01 01 with BS 5628, Part 1, 1978; Structural Use of
15R8-02
15R8-02
100
1430 4270 730 4000 3090 4000 730 4270 1430 Unreinforced Masonry.
2550
2550
Site Dim. (min 1000mm)
20. Mortar to conform to designation [III] of table
230
230
1, BS 5628, Part 1.
X-R8-03-150
21. Provide masonry anchors every 2 courses
500
500
using mild steel hoop iron to BS 1243. 1978
C1 C1 C1 C1 01 01 01 01
1000
1000
150
member
1 1 Starter Bars
230 230 Member description Cover max concrete
F2 F2 C2 C2 F2 F2 agg size grade
X X
T12-01-150
(See Column
B
F2 F2 Foundation minimum to any steel 50mm 20mm C25
Schedule)
225
225
FIRST FLOOR FIRST FLOOR Column minimum to links 30mm 20mm C30
a a Beam minimum to links 30mm 20mm C25
A A T12-01-150 Slab minimum to any steel 30mm 20mm C25
01
B B
3190
3190
T12-01 Ring beam minimum to links 30mm 20mm C25
H
Column minimum to any steel 30mm 20mm C30
A
225
225
50mm
50
Stair case minimum to any steel 30mm 20mm C25
Blinding in A Mass conc 30mm C20
Concrete
345
345
C1 C1 C1 C1
TYPICAL DETAILS Column Base F1, F2, F4 REVISIONS.
(See Table 1) (See Table 1)
3000
3000
F2 F2 01 01 01 01
15R8-02
15R8-02
1365
1365
2550
2550
Date Description
230
230
F3 F3
C2 C2 DIMENSION REINFORCEMENT
FOOTING
NUMBER
F4 F4 A B H a Direction
800
800
01 01 01 01
1000
1000
C2 C2
12500
12500
Y
F2 F2 F1 6 1000 1000 350 385 6T12-150 6T12-150
F2 16 1800 1800 350 785 11T12-150 11T12-150
GROUND FLOOR GROUND FLOOR Engineer:
F3 2 2000 3400 450 NA 13T12-150 22T12-150
BEAM 11 (230X450)
618
100
100
Table 1
4500
4500
3400
PROPOSED THREE STOREY
75mm Kicker 75mm Kicker
F1 F1 100mm Concrete Slab 100mm Concrete Slab RESIDENTIAL APARTMENT BLOCK
100
F2 F2 F2 F2 F2 F2
3 3 ON PLOT 24-26, CHRISTINE AWERI
100
C1 C1 C2 C1 C1 C2 C1 C1 1000mm Gauge DPM 1000mm Gauge DPM RD, KAKOOGE A, LIRA MUNICIPALITY
25
25
1800
X-R8-03-150
X-R8-03-150
Eng. PATRICK AGONA
150
Site dim.
hardcore or similar hardcore or similar P.O. BOX 29614,KLA
F1 F1 F1 F1 (See Column (See Column
4 4 approved material approved material Schedule) Schedule)
618
C1 C1 C1 C1 Architect: .
503 1934 02 503
230 230 230 230 2x 13T12-01-150 (Top & Bottom)
Title:
FIRST & SECOND FLOOR RC. DETAILS
450
T12-01 02
200mm C20 mass 200mm C20 mass RC. STAIRCASE DETAILS
Concrete Concrete 2000 FOUNDATION LAYOUT AND DETAILS
690 690 50mm
200
Blinding in 3400
50
A B C D E F G H Section A-A Through Section B-B Through COLUMN BASE F3 Concrete